Pneumatic Valve Actuators
2
4
3
MP953E &
MP953F
MP953C &
MP953D
POSITIONER
ON MP953E AND
MP953F ONLY
MINIMUM
CLEARANCE
1 2 3
4
OPERATION SIZE
NOMINAL DIA.
5 INCH
7-1/8 INCH
8 INCH
13 INCH
5-1/8 (130)
7-1/8 (181)
8-1/4 (210)
13-1/2 (343)
9-1/4 (235)
10-1/2 (267)
11-1/8 (283)
18-1/8 (460)
4-5/8 (117)
5-5/8 (143)
6-1/2 (165)
10 (254)
4-3/8 (111)
4-3/8 (111)
5-3/8 (137)
7-11/16 (195)
1
M13903
M
B
M
M18957
DIRECT
ACTING
MP953
VALVE
THERMOSTAT
MP953C,D Pneumatic Coil Valve Actuators
Pneumatic actuators provide proportional control of steam or hot
or cold liquids in HVAC systems by operating V5011, V5013, and
VGF valve assemblies. Replacement devices are available for older
Honeywell actuators.
• Rolling diaphragm for long life and low hysteresis.
• Easily attached to valve.
• Can be installed after piping valve.
• Slide lock feature permits simple engagement to valve stem.
• Direct- or reverse-action control.
• Does not include positive positioner.
Dimensions in inches (millimeters) Typical MP953C,D Operation
Pneumatic
Actuator Type: Valve
Fail Safe Mode: Spring Return
Air Connections: Dual barbed fitting for 5/32 in. O.D. and 1/4 in. O.D.
plastic tubing
Temperature Range: 0 F to 140 F (-18 C to +60 C)
Maximum Operating Pressure: 25 psi (172 kPa)
Humidity Range: 5 to 95% RH
Product Number Action
MP953C1000/U Direct Acting Low 2 psi to 7 psi 14 kPa to 48 kPa 3/4 in. 19 mm — —
MP953C1018/U Direct Acting Low 8 psi to 12 psi 55 kPa to 83 kPa 3/4 in. 19 mm — —
MP953C1026/U Direct Acting Low 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm — —
MP953C1067/U Direct Acting Medium 2 psi to 7 psi 14 kPa to 48 kPa 3/4 in. 19 mm — 311851-062 Stem
MP953C1075/U Direct Acting Medium 8 psi to 12 psi 55 kPa to 83 kPa 3/4 in. 19 mm — 311851-062 Stem
MP953C1083/U Direct Acting Medium 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm — 311851-062 Stem
MP953C1471/U Direct Acting High 2 psi to 7 psi 14 kPa to 48 kPa 1 1/2 in. 38 mm — 312466-605 Stem
MP953C1489/U Direct Acting High 4 psi to 11 psi 28 kPa to 76 kPa 1 1/2 in. 38 mm — 312466-605 Stem
MP953C1547/U Direct Acting Medium 3 psi to 15 psi 21 kPa to 104 kPa 1 1/2 in. 38 mm — —
MP953C1554/U Direct Acting High 2 psi to 7 psi 14 kPa to 48 kPa 3/4 in. 19 mm 13 in. diameter Actuator for
MP953C1562/U Direct Acting High 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm 13 in. diameter Actuator for
MP953D1107/U Reverse Acting Medium 8 psi to 13 psi 55 kPa to 90 kPa 3/4 in. 19 mm — —
MP953D1131/U Reverse Acting Medium 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm — —
MP953D1172/U Reverse Acting Medium 3 psi to 7 psi 21 kPa to 48 kPa 3/4 in. 19 mm — —
Actuator
Force
Spring Range Stroke
70-6910 707
Comments Includes(psi) (kPa) (inch) (mm)
2-1/2 in. and 3 in. valves
2-1/2 in. and 3 in. valves
Extension Assembly
Extension Assembly
Extension Assembly
Extension Assembly
Extension Assembly
14004697-001 Stem
Extension Assembly
14004697-001 Stem
Extension Assembly
Controls
Pneumatic Valve Actuators
2
4
3
MP953E &
MP953F
MP953C &
MP953D
POSITIONER
ON MP953E AND
MP953F ONLY
MINIMUM
CLEARANCE
1 2 3
4
OPERATION SIZE
NOMINAL DIA
5 INCH
7 1/8 INCH
8 INCH
13 INCH
5 1/8 (130)
7 1/8 (181)
8 1/4 (210)
13 1/2 (343)
9 1/4 (235)
10 1/2 (267)
11 1/8 (283)
18 1/8 (460)
4 5/8 (117)
5 5/8 (143)
6 1/2 (165)
10 (254)
4 3/8 (111)
4 3/8 (111)
5 3/8 (137)
7 11/16 (195)
1
M13903
M
B
M
M5445A
PILOT
MP953
DA
VALVE
THERMOSTAT
POSITIONER
MP953E,F Pneumatic Coil Valve Actuators
Pneumatic actuators provide proportional control of steam or hot
or cold liquids in HVAC systems by operating V5011, V5013, and
VGF valve assemblies. Replacement devices are available for older
Honeywell actuators.
• Rolling diaphragm for long life and low hysteresis.
• Easily attached to valve.
• Can be installed after piping valve.
• Slide lock feature permits simple engagement to valve stem.
• Direct- or reverse-action control.
• Integral positive positioner relay provides positive positioning under
varying load conditions.
Dimensions in inches (millimeters) Typical Piping for MP953E,F Pneumatic Valve Actuator Wiring
Actuator Type: Valve
Temperature Range: 0 F to 140 F (-18 C to +60 C)
Maximum Operating Pressure: 25 psi (172 kPa)
Humidity Range: 5 to 95% RH
Product Number Action
Actuator
Force
MP953E1285/U Direct Acting Medium 4 psi to 11 psi 28 kPa to 76 kPa 1 1/2 in. 38 mm Positive Positioner with 5 psi (35 kPa) range
MP953E1301/U Direct Acting Low 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm Positive Positioner with 3 psi range (21kPa)
MP953E1319/U Direct Acting Low 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm Positive Positioner with 5 psi range (35 kPa)
MP953E1327/U Direct Acting Low 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm Positive Positioner with 10 psi range (70 kPa)
MP953E1368/U Direct Acting Medium 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm 311851-062 Stem Extension Assembly and Positive
MP953E1376/U Direct Acting Medium 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm 311851-062 Stem Extension Assembly and Positive
MP953E1384/U Direct Acting Medium 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm 311851-062 Stem Extension Assembly and Positive
MP953E1400/U Direct Acting High 4 psi to 11 psi 28 kPa to 76 kPa 1 1/2 in. 38 mm 312466-605 Stem Extension Assembly and Positive
MP953E1418/U Direct Acting High 4 psi to 11 psi 28 kPa to 76 kPa 1 1/2 in. 38 mm 312466-605 Stem Extension Assembly and Positive
MP953E1435/U Direct Acting High 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm 14004697-001 Stem Extension Assembly and Positive
MP953E1443/U Direct Acting High 4 psi to 11 psi 28 kPa to 76 kPa 3/4 in. 19 mm Positive Positioner with 10 psi range and 14004697-
MP953F1093/U Reverse Acting Medium 8 psi to 13 psi 55 kPa to 90 kPa 3/4 in. 19 mm Positive Positioner with 3 psi range and EPDM
MP953F1101/U Reverse Acting Medium 8 psi to 13 psi 55 kPa to 90 kPa 3/4 in. 19 mm Positive Positioner with 5 psi range and EPDM
MP953F1119/U Reverse Acting Medium 8 psi to 13 psi 55 kPa to 90 kPa 3/4 in. 19 mm Positive Positioner with 10 psi range and EPDM
708 customer.honeywell.com 70-6910
Spring Range Stroke
Includes(psi) (kPa) (inch) (mm)
Positioner with 3 psi range
Positioner with 5 psi range
Positioner with 10 psi range
Positioner with 5 psi range
Positioner with 10 psi range
Positioner with 5 psi range (35 kPa)
001 Stem Extension Assembly
diaphragm
diaphragm
diaphragm