Honeywell MM-3 User Manual

MM-3 MASTERTROL®
MINI-ZONE™-3
SCHEMATIC
The Mastertrol® Mini-Zone™ -3 Zone Control Panel, Model MM-3, controls up to 3 zones on any single stage heating and cooling system. Each zone is con­trolled by a thermostat which operates a motorized damper in the it’s zone duct to control the flow of conditioned air to the zone. (Up to 2 dampers may be wired to a single zone. When 3 or more dampers are required a Slave Damper Control Relay, Model SDCR, is required.)
The Zone 1 Thermostat requires a manual changeover subbase with “O” and “B” terminals. The “O” terminal must make with R when the subbase is switched to the COOL Mode. The “B” terminal must make with R when the subbase is switched to the HEA T Mode. When the Zone 1 Subbase in either the Heat or Cool Mode, any one of the 3 zone thermo­stats can call for the respective mode. The zone ther­mostat will energize it’s zone relay which activates the heating or cooling controls, opens it’s zone damper and close the dampers to the zones that are satisfied. When all z one thermostats are satisfied the heating or cooling will shut off and all zone dampers will return to their normal position. The normal posi­tion of the zone dampers is set by the OPEN/ CLOSED slide switch next to the motor terminals.
SYSTEM CONNEC­TIONS: The MM-3 Sys-
tem Terminals on the far left side of the panel are used to wire to the HVA C Unit. These terminals are isolated “dry” switching contacts similar to any typical thermostat. These terminals are wired to the HVA C Unit Terminals the same as any thermostat would when not using this zone control panel. The MM-3 connections used are typically the R-
HVAC UNIT CONNECTIONS
24 VOL T TRANSFORMER
FAN RELAY
W
HEAT RELAY
R
G
Y
C
G-Y-W terminals wired the the HVAC Unit Con­trol Center.
24 VOL T 40 VA TRANSFOMER MODEL PMT-40
COMPRESSOR RELAY IN OUTDOOR CONDENSING UNIT
HYDRO-AIR Systems - When using the MM-3 with a Hydro-Air System, one which uses a hot water coil in the air handler to provide heating in place of a furnace, the wiring is almost similar to that shown. In this application the Heat Relay shown may be a z one valve or circulator relay. The Fan must often be brought on with the call for Heat. To provide for this, jumper the Gh and G terminals on the MM-3.
OIL FURNACES - When using the MM-3 with an Oil Fired Furnace to provide heating the T and T termi­nals on the Oil Burner Primary Control must wire to the B and W wires.
NOTE: Once oper ational if the Oil Furnace continues to run when all zones are satis­fied, reverse the B and W wires on the MM-3.
IMPORTANT: When using the MM-3 as only a 2 Zone Panel, the Zone 3 Relay must remain plugged into its socket.
MASTERTROL MINI-ZONE -3 CONTROL PANEL
SYSTEM
C R
R
O
B
G
Gh
Y W
®
CHANGEOVER CONTROL
O1 G1
B1
2 1
THERMOSTAT
T6/Y
T5/R
T4/W
T6/Y
T5/R T4/W
T6/Y
T5/R T4/W
ZONE 3 THERMOSTAT
ZONE THERMOSTAT WIRING - The MM-3 can be used with several different single stage thermostats. The wiring shown is for the following recommended thermostats: Zone 1 Thermostat Zone 2 and 3 Thermostat TRT(-W) and MCRS(-W) TRT(-W)/T87F
/T87F and Q539A T8090T1003* T8090T1011* T8602C T8602D T8601C* T8603D*
*These thermostats may require additional wires. Refer to the wiring information included with the ther­mostat for complete information.
DAMPER MOTOR WIRING - This diagram shows Trol-A-Temps typical power open-power closed op­posed blade damper motors. Note the jumper wire required on the motor terminals 2 and 5. Round Spring Return Dampers can also be wired to the MM-3. When using the ARD-PC (D835), wire to the M1 and M6 terminals. When using the ARD-PO (D837), wire to the M1 and M4 terminals.
456Z
123X
ZONE 1 DAMPER MOTOR
456Z
123X
ZONE 2 DAMPER MOTOR
O
C ZONE 1
O C
ZONE 2
O C
ZONE 3
4/W
5/R
6/Y
DAMPER M6
M4
M1
M6
M4
M1
M6
M4
M1
G
ZONE 1 THERMOSTAT
AND SUBBASE
® U.S. Registered Trademark Copyright © 2000 Honeywell Inc. • All Rights Reserved
O
Y
R
B
W
4/W
5/R
6/Y
ZONE 2 THERMOSTAT
MODEL ARD-PC (POWER CLOSED)
ZONE 3 DAMPER MOTOR
M13558
69-1362
MM-3 MASTERTROLQD MINI-ZONETM-3
2
FAN
Kl
O-l
MM-3 RELAY INTERNAL WWNQ
ZONE 1 ZONE 2 ZONE 3
MM-3 DAMPER MOTOR INTERNAL WIRING
1 A A
W
Zone Relay
12
T 8 K3 K4
SYSTEM
W
12 12
T 8 4 8
c
I
MM-3 SYSTEM SCHEMATIC
T
W
K5
6
10
Damper Motor
TerminaJs
w
common CIomd open Common
Own
w
Closed
OP@n
Common Closed
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN
694362 G.H. 6-00
55408-0524
Home and Building Control
Honeywell Limited-Honeywell Limitbe
155 Gordon Baker Road North York, Ontario M2H 3N7
_ Printed in U.S.A. on recycled
paper containing at least 10%
w
post-consumer paper fibers.
www.honeywell.com
Loading...