Honeywell ML7421A, ML7421B SPECIFICATION DATA

ML7421A,B
Electric Linear Valve Actuators
GENERAL
These actuators enable modulating control in conjunction with controls providing an analog output. The direction of movement is reversible by means of an internal selector plug.
They operate Honeywell’s standard valves in heating, ventilation, and air conditioning (HVAC) applications.
SPECIFICATION DATA
FEATURES
Quick and easy installation
No separate linkage required
No adjustments
Force-limiting end switches
Manual operator
Synchronous motor
Corrosion-resistant design
Selectable 0...10 Vdc or 2...10 Vdc/
0...20 mA or 4...20 mA input signal
Position feedback signal
Direct or reverse-acting adjustable
Selectable stroke position on signal failure
Maintenance-free
SPECIFICATIONS
Temperature Limits
Ambient operating limits -10...+50 °C @ 5...95%rh Ambient storage limits -40...+70 °C @ 5...95%rh Medium valve temperature Max. +150 °C (220 °C with High-Temperature Kit)
Safety
Protection class III according to EN60730-1 Protection standard IP54 according to EN60529 Flame retardant housing V0 according to UL94, with metal cable gland
Noise level 45dB(A) Signals
Input range Y = 0(2)...10 Vdc, 0(4)...20 mA Input impedance for voltage R for mA R
Signal source output impedance Max. 1 k Output voltage range Position: 2...10 Vdc Output load Max. 1 mA
Wiring
Wiring terminals 1.5 mm2 Cable entry M20x1.5 and knock-out for PG11
Material
Cover ABS-FR Yoke and Base Aluminum diecast
Weight 2.0 kg Dimensions see Fig. 3 and Fig. 4
= 100 k
i
= 500
i
® U.S. Registered Trademark EN0B-0416GE51 R0409 Copyright © 2009 Honeywell Inc. All Rights Reserved.
ML7421A,B ELECTRIC LINEAR VALVE ACTUATORS
model number ML7421A3004 ML7421B3003
supply voltage
power consumption
signal input 0(2) Vdc
signal input 10 Vdc
stroke
run-time at 50 Hz
nominal stem force
Actuator stem retracted. Two-way valve: open, three-way valve port A - AB: closed
Actuator stem extended. Two-way valve: closed, three-way valve port A - AB: open
OPERATION
General
The drive of a synchronous motor is converted into linear motion of the actuator stem by using a worm gear transmission.
The actuator stem is connected with the valve stem by a button keyed retainer connection.
Via installed microswitches, the internal force sensor switches off the actuator precisely when the nominal stem force is reached.
If used as a replacement of an already-installed actuator M7421A,B, the following issue is to observe:
Permanent power supply (see section "Electrical Installation")
Manual Operation
The actuators are equipped with a manual operator used in case of power failure. Manual operation is possible only after the power supply has been switched off or disconnected.
To operate, push the manual operator knob down and turn clockwise to move the stem upward and counter-clockwise to move the stem downward. If the actuator returns to automatic control, the manual operator knob unlocks automatically.
24 Vac (+10%/-15%); 50/60 Hz
14 VA (50 Hz) / 16 VA (60 Hz)
20 mm 38 mm
1.9 min 3.5 min
1800 N
Input Signal Range
The range of the analog input signal Y (0...10 Vdc / 0...20 mA or 2...10 Vdc / 4...20 mA) can be selected by changing the position of jumper plug W2 (Fig. 1.). The factory set is at
0...10 Vdc.
Direction of Action
The direction of action (direct or reverse) can be selected by changing the position of jumper plug W3 (Fig. 1.). The factory set is: stem extends at increasing signal (direct acting).
NOTE: Jumper plugs W1, W2, W3, and W4 are accessible
after the cover has been removed. They are located on top side of the printed circuit board (see Fig. 2).
W4
W1
W3
W2
NOTE: Manual operation allows a very high closing force
capable of jamming the actuator spindle and exceeding the rating of the force switches, so that the motor cannot move. Therefore, after a manually close-off operation, it is necessary to release the spindle one turn by turning the manual operator knob, thus ensuring that the manual operator will automatically disengage on power resumption.
Fig. 1. Location of jumper plugs W1, W2, W3, W4
Electrical Installation
24 V and 24 V (see Fig. 3.) must be applied under all operating conditions.
Cable length/diameter for field mounting:
Max. 200 m / 1.5 mm2
Input Signal
The Vdc- or mA-input signal is selected by shifting jumper plug W4 (see Fig. 2). The factory setting of W4 is "Vdc". No external resistor for mA-input signal is necessary.
EN0B-0416GE51 R0409 2