ISO 9001
35 and 70 lb-in. Non-Spring Return Direct Coupled Actuators
® |
® |
|
ML6161, ML7161 ML6174, ML7174
The 35 and 70 lb-in. Non-Spring Return Direct Coupled Actuators (DCA) are control motors that provide floating or proportioning control for valves and dampers. The proportioning motors accept a current or voltage signal from a controller to position the damper or valve at any chosen point between fully open and fully closed.
SPECIFICATIONS
Electrical Ratings:
Power Input: 24 Vac ±20%, 50/60 Hz.
|
|
|
Model |
Power Consumption |
|
|
|
|
θ |
ML6161A,B,C,D |
1.8 VA |
|
|
|
θ |
ML7161A |
4.8 VA |
|
|
|
θ |
ML6174A,B |
2.4 VA |
|
|
|
θ |
ML7174A |
5.4 VA |
|
|
|
Auxiliary Switch Ratings:
θElectrical selective NO or NC, not simultaneous.
θPilot Duty: 50 VA, 24 Vac.
θSwitch Differential: Three angular degree maximum.
Torque Ratings (at Rated Voltages): |
|
||
|
|
|
|
|
|
|
|
|
|
35 lb-in. DCA |
70 lb-in. DCA |
|
|
|
|
|
|
lb-in. (Nm) |
|
|
|
|
|
θ |
Running |
35 (4) |
70 (8) |
|
|
|
|
θ |
Breakaway |
35 (4) |
70 (8) |
|
|
|
|
θ |
Stall Minimum |
45 (5) |
70 (8) |
|
|
|
|
θ |
Stall Maximum |
70 (8) |
130 (14) |
|
|
|
|
Actuator Stroke:
θSelectable: 45°, 60°, and 90°.
θRotation: Clockwise (CW) and counter clockwise (CCW).
Device Weight:
θ 1.3 lb (0.58 kg).
Environmental Protection Ratings:
θNEMA1.
θIP54 (ML6161E, ML7161E, ML6174E, ML7174E only).
SPECIFICATION DATA
FEATURES
•45°, 60°, and 90° selectable stroke in either clockwise
(cw) or counterclockwise (ccw) directions.
•Magnetic coupling eliminates the need for mechanical stops.
•Two field-addable auxiliary switches.
•Auxiliary feedback potentiometer field-addable on select models.
•0° to 30° minimum position adjustment (cw or ccw direction) on all models.
•Manual declutch on select models.
•W7620 Terminal Unit Controller compatibility.
•Commercial Zone Damper in W7600 Commercial Zone System compatibility.
Actuator Timing for 90° Stroke:
|
|
|
|
|
|
At 50 Hz |
At 60 Hz |
|
|
|
|
θ |
90 Second Models |
108 sec |
90 sec |
|
|
|
|
θ |
Three-Minute Models |
216 sec |
180 sec |
|
|
|
|
θ |
Seven-Minute Models |
504 sec |
420 sec |
|
|
|
|
Mounting:
θMounts directly on 3/8 in. to 1/2 in. (10 to 13 mm) round or square shaft.
θMinimum Shaft Length Required: 1-3/4 in. (45 mm).
θActuator can be mounted with shaft in any position.
θSecured Using: Two 1/4 in. (6 mm) 28 NF Allen screws.
Actuator Minimum Design Life: |
|
||
|
|
|
|
|
|
35 lb-in. DCA |
70 lb-in. DCA |
|
|
|
|
θ |
Cycles |
50,000 |
40,000 |
|
|
|
|
θ |
Repositions |
1,500,000 |
1,500,000 |
|
|
|
|
Temperature Ratings:
θAmbient: 20°to 125°F (-18° to 50°C).
θDerated Timing to: -20°F (-29°C).
θShipping and Storage: -20° to 130°F (-29° to 54°C).
Humidity Ratings:
θ 5% to 95% RH noncondensing.
Noise Output:
θ 45 dBA at 1 meter maximum.
® U.S. Registered Trademark |
63-1146-1 |
Copyright © 1998 Honeywell Inc., Mpls. MN • All Rights Reserved |
35 AND 70 LB-IN NON-SPRING RETURN DIRECT COUPLED ACTUATORS
Models:
ML Motor Linkage
θ61 Floating Control
θ71 4-20 mA/2-10 Vdc Control
θ61 35 lb-in. (4 Nm), Non-Spring Return
θ714 70 lb-in. (8 Nm), Non-Spring Return
|
|
|
|
|
|
|
|
θ A |
Includes output for feedback |
||||||
|
|
|
|
|
|
|
|
|
|
|
potentiometer. |
||||
|
|
|
|
|
|
|
|
θ B |
Standard (includes minimum |
||||||
|
|
|
|
|
|
|
|
|
|
|
position setscrews) |
||||
|
|
|
|
|
|
|
|
θ C |
Includes output for feedback |
||||||
|
|
|
|
|
|
|
|
potentiometer and cover w/ |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
θ D |
conduit connections. |
||||||
|
|
|
|
|
|
|
|
Includes cover w/ conduit |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
connections. |
||||
|
|
|
|
|
|
|
|
θ E |
Standard with European |
||||||
|
|
|
|
|
|
|
|
|
|
|
ratings. |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
θ 1 |
Standard |
|||
|
|
|
|
|
|
|
|
|
|
|
θ 2 |
Includes declutch |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
function |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
ML |
|
|
|
|
|
|
|
|
|
|
|
|
|
XXX |
Varies by Model |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Dimensions:
CW
4-7/8
(123)
COM
CCW
11/16
(18)
3-3/8 (86)
M14227
TYPICAL SPECIFICATION
Non-spring return actuator shall be direct coupled type that requires neither crankarm nor linkage and be capable of direct mounting to a 3/8 inch or 1/2 inch diameter jackshaft. The actuator shall connect to the shaft using set screws. The actuator must provide floating or proportional control.
The actuator design must be for use in either clockwise or counterclockwise operation.
Actuators shall use a true synchronous ac stepper motor to drive the output hub. Run time shall be constant and independent of load, temperature and supply voltage (within product-family specifications). Overload protection shall be provided at all angles of rotation by a magnetic clutch mechanism that provides an absolute limit to the output torque without a physical link between the motor and the gear train.
Actuators shall have a minimum performance of 40,000 full-stroke powered cycles, and 1,500,000 repositions documented in the product data literature. Actuators shall be UL and CSA listed, manufactured under ISO 9001 International Quality Control Standards.
Feedback Potentiometer Ratings:
θElectrical Rating (200976A,C Potentiometer): 24 Vac, 50/60 Hz, 2.25W.
θResistance Output (Resistance Linear as Measured Between Terminals R-B):
θ0 ohms (at 0°, cw stroke).
θ250 ohms (at 45°, cw stroke).
θ333 ohms (at 60°, cw stroke).
θ500 ohms (at 90°, cw stroke).
Approvals:
θUnderwriter’s Laboratories Inc. Component Recognized:
File No. E4436; Guide No. XAPX2.
θMeets UL94-5V plenum requirements.
θCanadian Standards Association Certified (includes auxiliary switch).
Accessories:
θ200976A Auxiliary Potentiometer (0 to 500 ohm).
θ200976C Auxiliary Potentiometer (0 to 2000 ohm).
θ201052A Auxiliary Switch (one).
θ201052B Auxiliary Switch (two).
θ4074ENJ Bag Assembly—includes stop pin, shaft adapter, and two minimum position screws.
θ4074ENY Bag Assembly—includes stop pin and shaft adapter.
θ4074EVK Short Shaft Extender.
θ7640QW Metal Enclosure—for attaching conduit to actuator.
θT641 Floating Thermostat—for use with seven-minute models.
θT6984 Floating Thermostat—for use with 90-second and seven-minute models.
θT7984 Modulating Thermostat—for use with ML7174.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
|
Printed in U.S.A. on recycled |
www.honeywell.com |
XX63-1146XXXX—1 B.B. Rev. 5-98 |
paper containing at least 10% |
|
post-consumer2 paper fibers. |
/building/components/ |