Direct Coupled Damper Actuator—Spring Return
ML4125; ML8125
HVAC, Fast-Acting, Two-Position Actuators, 100 lb-in
The ML8125 Fast-Acting, Two-Position Actuators are spring return
direct coupled actuators (DCA) with an integral junction box for
on/off damper control.
• Integral spring return
• -40 C to 130 F (-40 C to 54 C) operating temperature range
• No audible noise during holding
• Electronic circuitry provides efficient operation while
eliminating the need for limit switches
• Ninety-five degree angle of rotation
• Die-cast aluminum housing. Housing design allows
flush mounting to damper
• Integral junction box with three conduit openings eliminates
need for separate wiring box
• Direct mounting to 3/8 or 1/2 in. round or square shaft
• Not intended for smoke control systems
Actuator Type: Damper
Rotational Stroke: 95 ±3 degrees
Fail Safe Mode: Spring Return
Torque Rating: 100 lb-in. (11.3 Nm)
Spring Return Torque: 100 lb-in. (11.3 Nm)
External Auxiliary Switches Available: Yes, 32003532-005
Number of Internal Auxiliary Switch: 0
Electrical Connections: Two color-coded leads
Electrical Connection Length: 16 in. (406 mm)
Environmental Rating: NEMA1
Frequency: 60 Hz
Mounting: Direct Coupled
Maximum Noise Rating, Holding (dBA @ 1m): 20 (no aud ble noise)
Maximum Noise Rating, Driving (dBA @ 1m): 65
Compatible Damper Shafts: 3/8 to 1/2 in. square or round
(10 to 13 mm square/round)
Shaft Adapter Type: Aluminum Hub, two set screws
Materials: Aluminum housing
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Ambient Temperature Range: -40 F to +130 F (-40 C to +55 C)
Storage Temperature Range: -40 F to 140 F (-40 C to +60 C)
Weight: 6 lb (2.72 kg)
Comments: Integral junction box with three 7/8 in. conduit openings
(fittings not included)
Approvals
Underwriters Laboratories, Inc: UL873, Plenum Rated
Canadian Underwriters Laboratories, Inc: cUL C22.2 No. 24-93
Commercial
Product Number
ML4125A1008/U Two position;
ML4125B1007/U Two position;
ML4125C1006/U Two position;
ML4125D1005/U Two position;
ML8125A1004/U Two position;
ML8125B1003/U Two position;
Control
Signal
SPST
SPST
SPST
SPST
SPST
SPST
Timing (seconds) Power Consumption
Maximum
Driving
@ 60 Hz
40 sec 25 sec 25 sec 0.16A, 15W 0.10A, 5W 120 Vac
40 sec 25 sec 25 sec 0.16A, 15W 0.10A, 5W 120 Vac
40 sec 25 sec 25 sec 0.12A, 18.6W 0.10A, 7W 230 Vac ±10% Mounting
40 sec 25 sec 25 sec 0.12A, 18.6W 0.10A, 7W 230 Vac ±10% Mounting
40 sec 25 sec 25 sec 15.6 VA 4 VA 24 Vac
40 sec 25 sec 25 sec 15.6 VA 4 VA 24 Vac
Nominal
Driving
@ 60 Hz
Maximum
Spring
Return (sec) Driving Holding
Supply
Voltage Includes
+10%, -15%
+10%, -15%
+20%, -10%
+20%, -10%
Ground
Screw
Ground
Screw
bracket
bracket
Mounting
bracket
Mounting
bracket
Spring
Return
Direction
CCW
CW
CCW
CW
CCW
CW
Components
70-6910 389