Honeywell L7248A, L7248C, L7248 L Owner's Manual

L7224A,C; L7248A,C,L Oil Electronic
®
Aquastat
APPLICATION
The L7224A,C and L7248A,C,L replace the L8124A, L8124C, L7124A,C, L7148A and L8148A Controllers. The L7224A,C and L7248A,C,L series controls provide status and diagnostic information through an LED display combined with LED lights as well as EnviraCOM™ communications enabled thermostats and diagnostic tools to enhance the diagnostic process.
L7224/L7248 Aquastat Controllers are intended for use in residential-type applications.
IMPORTANT
Use of Outdoor Temperature Reset on a tank­less coil application requiring a Low Limit setting will result in reduced system effectiveness and efficiency.
®
Controllers provide electronic
Controllers
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
Electrical Ratings:
Voltage: 120 Vac, 60 Hz. Power: 7 VA maximum at 120 Vac plus external loads. Thermostat current: 100 mA nominal at 24 Vac. Burner Relay:
7.4 A at 120 Vac Full Load Amperage (FLA);
44.4 A inrush Locked Rotor Amperage (LRA); Less Ignition Load: 360 VA.
Circulator Relay:
7.4 A at 120 Vac FLA; 44.4 A inrush LRA. Zone Controller (ZC): 7.4 A at 120 Vac FLA;
44.4 A inrush LRA.
NOTE: All loads combined cannot exceed 2000 VA.
Environmental Ratings:
Temperature: -30 °F to +150 °F (-34 °C to +66 °C). Humidity: 0 to 95% relative humidity, noncondensing.
Approvals:
Underwriters Laboratories Inc. Component Recognized. Canadian Underwriters Laboratories Inc. Component
Recognized.
2012 DOE Compliance and Operation
Operation of this control may delay the burner operation while the residual heat is circulated out of the boiler.
NOTE: This operation may be different than earlier electronic Aquastat® revisions which did not implement thermal purge.
68-0281EFS-05
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
WARNING
M22147B
3/4
(75)
5-11/16
(145)
3/8
(10)
2-5/8 (67)
7-1/8 (181)
6-1/2 (166)
3-13/32 (86)
2x 1/4 (7) x 3/8 (9)
1/16 (2)
1-3/16
(30)
3-1/32
(77)
2-1/16 (53)
1-1/8 (29)
4-1/4 (109)
Accessories:
W8735Y1000 Wireless Outdoor Reset Kit W873ER1000 Wireless Outdoor Reset Module C7089R1013 Wireless Outdoor Temperature Sensor
(requires W8735ER1000)
W8735S1000 AquaReset™ Outdoor Reset Kit (includes
50022037-002 Outdoor Reset Module and C7089U1006 Outdoor Temperature Sensor)
W8735S1008 AquaReset™ Domestic Hot Water Kit
(includes 50022037-005 Domestic Hot Water Module
and 32003971-003 Sensor) W8735S3000 EnviraCOM™ Alarm Module C7089U1006 Outdoor Temperature Sensor (used with the
50022037-002) 32003971-003 Temperature Sensor (used with
50022037-005) Sensor (See Table 2). 14,000,485-016 1/4 in. (6.35 mm) diameter, 1-1/4 in.
(31.75 mm) long glass cartridge Fuse, 1A, Slow-Blow. 120650 Heat Conductive Compound. 121371AA Sensor Well Clamp.
Table 1. Wells for L7224A,C; L7248A,C,L Controllers.
Part
Number
Spud Size
in. (mm)
Insertion
in. (mm)
Insulation
in. (mm)
123869A 1/2 (12.7) NPT 3 (76.2) 1-1/2 (38.1) 123870A 3/4 (19.05) NPT 3 (76.2) 1-1/2 (38.1)
Table 2. Sensors for L7224A,C and
L7248A,C,L Controllers.
Part Number
Length in.
(mm) Application
50001464-001 12 (304.8) Well-mounted controls 50001464-003 24 (609.6) Flush-mounted controls 50001464-004 36 (914.4) 50001464-005 48 (1219.2)
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. The installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
5. Set High Limit, Low Limit and Low Limit Differential
to the settings recommended by the boiler OEM.
6. Record the maximum High Limit setting from the
replaced controller in the text box provided on the cover insert label.
7. Record the High Limit setting at time of installation
in the text box provided on the cover insert label.
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
Mounting
The L7224A,C and L7248A,C,L models are available in a well-mount, horizontal position, vertical position, or flush mounted remote from the well versions. Dimensions for the variety of mounting options are shown in Fig. 1. Note that each identity will have only a single mounting option.
Fig. 1. L7224A,C; L7248A,C,L mounting dimensions in inches (mm).
68-0281EFS—05 2
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
SENSOR WIRES
IMMERSION WELL CLAMP SCREW
IMMERSION WELL CLAMP
M16120
HEAT-CONDUCTIVE COMPOUND (OPTIONAL)
CONTROLLER CASE
BOILER
IMMERSION WELL
SENSOR
C1
B1
ZC
L2
LINE
C2
ZR
L1
B2
T
T3
2
1
THERMOSTAT
TERMINALS
ENVIRACOM
TM
TERMINALS
SENSOR HOLES
FUSE
M32186
SENSOR CONNECTOR
DISPLAY
IMPORTANT
Immersion well must fit sensing element and sensor must rest against bottom of well.
New Installation
Order well assemblies separately; see Table 1 and form no. 68-0040, Immersion Wells and Compression Fittings for Temperature Controllers. Boilers usually have tappings that allow the well to be mounted horizontally so boiler water of average temperature can circulate freely over the well.
1. Turn off all power and drain the boiler, if applicable.
2. If no tapping is provided, prepare properly sized and
threaded tapping near the top of the boiler.
3. Sparingly coat the well threads with pipe dope.
NOTE: Do not attempt to tighten by using the case
as a handle.
4. Install the well in the boiler tapping and tighten
securely.
5. Refill boiler and check for water leakage.
6. Loosen but do not remove the well clamp screw.
7. Fit the case into the well so the clamp on the case
slides over the flange on the well.
8. Securely tighten the clamp screw.
9. Insert the sensor element into the well until it bot-
toms. See Replacement Sensor Installation section for details. (If necessary, slightly bend the wire inside the case to hold the sensor against the bot­tom of the well.)
10. Turn power ON.
11. Set High Limit, Low Limit and Low Limit Differential
to the settings recommended by the boiler OEM. (See OPERATION section.) (See INSTALLATION steps 6 and 7.)
12. On L7248L models, adjust ELL option to match your
configuration (see OPERATION section, and Fig. 11 and 13).
IMPORTANT
Best thermal response is obtained with a well that snugly fits the sensor. Insert the sensor until it rests against the bottom of the well. Use a well of correct length and bend the wiring, if neces­sary, to hold the bulb against the bottom of the well.
If the well is not a snug fit on the sensor, use the heat-conductive compound (furnished with TRADELINE plastic bag of compound lengthwise and twist it gently. Then snip off end of bag and work the open end of the bag all the way into the well. Slowly pull out the bag while squeezing it firmly to distribute compound evenly in the well. Bend the wiring, if necessary, to hold the sensor against the bottom of the well and to hold outer end of the sensor in firm contact with the side of the well. See Fig. 2. Wipe excess compound from the outer end of the well.
®
models) as follows: Fold the
Fig. 2. Position of sensor in immersion well.
Flush-Mounted Aquastat Replacement
Turn off all power and remove the old control. Refer to the cover insert of the old control to identify and tag each external lead as it is disconnected. If the old well is unsuitable for the new installation, remove it and replace it with a suitable new well. If the old well is suitable, use it.
Well-Mounted Aquastat Replacement
Turn off all power and remove the old control. Refer to the cover insert of the old control to identify and tag each external lead as it is disconnected. If the old well is unsuitable for the new installation, remove it and proceed with instructions for new installation. If the old well is suitable, use it.
1. Loosen, but do not remove, the well clamp screw on
the side of the control case.
2. Position immersion well clamp snugly over the
flange of the adapter and tighten the clamp screw.
3. Insert the sensor into the well as shown in Fig. 2 or
3. (See Replacement Sensor Installation section for details.)
Fig. 3. Circuit board, showing sensor connection and
well holes for horizontal mount models.
3 68-0281EFS—05
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
WARNING
SENSOR WIRES
M22026
HEAT-CONDUCTIVE COMPOUND (OPTIONAL)
BOILER
IMMERSION WELL
SENSOR
C1
B1
ZC
L2
LINE
C2
ZR
L1
B2
T
T3
2
1
THERMOSTAT
TERMINALS
ENVIRACOM
TM
TERMINALS
DISPLAY
SENSOR CONNECTOR
SENSOR HOLES
FUSE
RELAYS
M32187
WIRING
Electrical Shock Hazard. Can cause serious injury or death.
Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage.
All wiring must comply with local electrical codes and ordinances. Do not exceed the specifications in the Application section when wiring this control. Use wire rated for 194 °F (90 °C) or higher.
Fig. 4. Replacement sensor installation.
Replacement Sensor Installation
Turn off all power and:
1. Carefully disconnect sensor from circuit board by
pulling gently on the connector.
2. Gently pull sensor from thermo well and through cir-
cuit board by pulling on leadwires.
3. Carefully align replacement sensor with hole in cir-
cuit board and guide through Aquastat case and into well. (See Fig. 5).
4. Make sure sensor is fully seated to bottom of well
(See Fig. 4). Use a small pencil to measure depth of sensor in well, if necessary.
5. Connect sensor to circuit board by pressing con-
nector on sensor unit into mating connector on cir­cuit board (See Fig. 5).
6. For remote sensors (flush-mounted Aquastat Con-
trollers) be sure to use 121571AA Clamp (see Accessories) to securely hold sensor in place.
IMPORTANT
The terminals on these Aquastat Controllers are approved for use with copper wire only.
Follow the appropriate wiring diagrams shown on the inside of the front cover of the L7224A,C; L7248A,C,L or in Fig. 8–13.
Refer to Fig. 6 for Connections for the optional Outdoor Reset Module and the Domestic Hot Water (DHW) module. In subsequent wiring diagrams these modules will be displayed with a dotted line signifying that they are optional.
ZR
L1
L2
C2
B2
C1
B1
ZC
Fig. 6. Wiring the Outdoor Reset Module and the
50022037-002 OUTDOOR RESET MODULE
T
3
T
2
1
LINE
1 2 3 OT OT
Domestic Hot Water Module.
C7089U1006 OUTDOOR SENSOR
50022037-005 DOMESTIC HOT WATER MODULE
1 2 3 TS TS
32003971-003 TEMPERATURE SENSOR
M29651
Fig. 5. Circuit board, showing sensor connection and
Fuse
The 1 Amp fuse located near the transformer is intended to protect the EnviraCOM circuit from incorrect wiring. The Aquastat will continue to function should the fuse blow or be removed though no EnviraCOM communication will be possible on the bus and Err 6 will be displayed. See Table 1 0 .
68-0281EFS—05 4
well holes for vertical mount models.
OPERATION
General
The L7224A,C and L7248A,C,L Oil Electronic Aquastat Controllers are primary safety limit-rated devices designed for use with oil fired boilers with line voltage burners and circulators. Many boilers do not include wiring or control compartments as part of the design, but are provided with an integral, replaceable, immersion well that is the mounting hardware for the Aquastat Controllers. Wiring to the other controls is done through flexible metal conduit.
For boilers that do include a remotely (flush) mounted control, the wiring may be completed with conduit or routed behind the boiler sheet metal.
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
A separate electromechanical high-limit is not required in a system that uses this control to meet Underwriters Laboratories Inc. requirements for oil-fired boiler assemblies, UL 726.
On the L7224 models, the High Limit, Low Limit, Low Limit Differential, and Anti Short-Cycle time can be adjusted to the setting recommended by the boiler OEM. On the L7248 models, the High Limit, and Anti Short-Cycle time are also adjustable, see “Adjusting Settings”.
The overall range of the High Limit is from 130 °F to 240 °F (54 °C to 116 °C). Select devices may have different ranges. Some models have limited ranges on the High Limit setpoint; this limited range is listed on the device label.
Some models also have a Low Limit and Low Limit Differential adjustment. The range of the Low Limit is from 110 °F to 220 °F (43 °C to 104 °C). Select devices may have different ranges.
The Zr setting can be set to DHW, Zoning, or for tankless coil applications depending on the L7224/L7248.
If a W8735S1000 AquaReset™ Outdoor Reset Module is installed, the reset curve can be set by entering the minimum outdoor temperature, minimum (boiler) temperature, and maximum outdoor temperature on the 3-digit display. The range of the minimum outdoor temperature is from -40 °F to 40 °F (-40 °C to 4.4 °C) and has a default setting of 0 °F (-18 °C). The range of the maximum outdoor temperature is from 30 °F to 70 °F (-1.1 °C to 21.1 °C) and has a default setting of 40 °F. The range of the minimum (water or boiler) temperature is from 80 °F to 180 °F (26.7 °C to 82.2 °C) and has a default setting of 130 °F. See the “Outdoor Reset Module” Installation Instructions (form number 69-2335) for more information on setting the boiler reset curve and all related parameters.
The L7224A,C and L7248A,C,L are designed for use with 24 Vac electronic and electromechanical thermostats or EnviraCOM™ enabled thermostats, and have screw-type terminals for easy field connection.
Adjusting Settings
To discourage unauthorized changing of Aquastat settings, a procedure to enter the ADJUSTMENT mode is required. To enter the ADJUSTMENT mode, press the UP, DOWN, and I buttons (Refer to Fig. 5) simultaneously for three seconds. Press the I button until the feature requiring adjustment is displayed:
Table 3. Adjustable Features.
Display Definition
HL_ High Limit. Hdf High Limit Differential. LL_ Low Limit. (L7224A, C) Ldf Low Limit Differential (L7224A, C) ELL External Low Limit (L7248L only) duu ZR input configured as external Domestic Hot
Water (DHW) request (ON/OFF) (L7224A,C/ L7248L)
ASC Anti Short-Cycle Timeout (seconds); “OFF” is
disabled.
otL* Outdoor Temperature Low (minimum)
parameter for the outdoor reset curve (°F or °C)
otH* Outdoor Temperature High (maximum)
parameter for outdoor reset curve (°F or °C)
btL* Boiler Temperature Low (minimum) parameter
for outdoor reset curve
bP* Boost Period (minutes). “OFF” is displayed if
Boost is inactive
bS* Boost step (°F or °C) shown only if Boost is
active (bP=ON)
UUS* Warm Weather Shutdown Temperature
(°F or °C)
tPL** Thermal Purging Limit Temperature (°F or °C),
“OFF” if disabled
tPt** Termal Purging Time Delay (minutes), shown
only if tPL is enabled PC Pump Cycling (ON / OFF) F-C Temperature units (°F or °C)
* Settings available for adjustment on the 3-digit display
only if the W8735S1000 AquaReset Outdoor Reset Module is installed.
**Settings available for adjustment only when the
W8735S1000 AquaReset Outdoor Reset Kit is NOT installed.
Then press the UP and/or DOWN buttons to move the set point to the desired value, to change between °F and °C, or to enable (On) or disable (Off) the External Low Limit. After 60 seconds without any button inputs, the control will automatically return to the RUN mode.
Display
In the RUN mode, the Aquastat will flash “bt” (boiler temp) followed by the temperature (i.e., 220), followed by °F or °C.
To read boiler settings, press the I key to read the parameter of interest. For example, press I and High Limit (HL) is displayed, followed by a three-digit number, i.e., 220, followed by °F or °C. Pressing the I button again (on L7224 models) will display the Low Limit (LL) followed by a three-digit number and the corresponding degree designator. See Display Readout, Table 4.
After approximately 60 seconds without any key presses, the display will enter a dim display mode. To return to the bright display mode, simply press any key.
5 68-0281EFS—05
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
LOW LIMIT SETTING
HIGH LIMIT SETTING
SWITCH BREAKS ON TEMPERATURE RISE. BURNER TURNS OFF. CIRCULATOR OPERATES ON A CALL FOR HEAT.
SWITCH MAKES ON TEMPERATURE FALL. BURNER OPERATES ON A CALL FOR HEAT.
WITH NO HEATING DEMAND, SWITCH BREAKS ON TEMPERATURE RISE.
SWITCH MAKES ON TEMPERATURE FALL, BURNER IS ON TO MAINTAIN MINIMUM WATER TEMPERATURE. CIRCULATOR IS OFF.
M23364
WHEN WATER REACHES LOW LIMIT SETTING, THE BURNER SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).
1
1
10ºF (6ºC) DIFFERENCE
L7224: 10°F (6°C) DIFFERENCE L7248: 15°F (8°C) DIFFERENCE
Table 4. Display readout definitions.
Text Description Display
Err Error Code (if one is present)
bT Boiler Temperature
High Limit
1
HL
HdF High Limit Differential
LL Low Limit (L7224 only)
Ldf Low Limit Differential (L7224 only)
tt Local Thermostat Status
ttE EnviraCOM Thermostat Status
brn B1 (Burner) output (ON or OFF)
Cir C1 (Circulator) output (ON or OFF)
ZC ZC (Zone Control) output (ON or OFF)
Zr ZR (Zone Request) Call for HEAT (ON or OFF)
ELL External Low Limit Enabled (L7248L only)
duu ZR Configured as Domestic Hot Water
Request (L7224, L7248L only)
ASC Anti Short-Cycle Timeout
bSP
Boiler Set-Point
dhc
DHW Module Connected
ot
Outdoor Temperature
otL
Outdoor Temperature Low
otH
Outdoor Temperature High
btL
Boiler Temperature Low
bP
Boost Period
bS
Boost Step
UUS
Warm Weather Shutdown Temperature
1
Display shows local setting; not the setting as modified by an
external enviracom control.
2
Settings are viewable only if the outdoor reset module and out-
door temperature sensor are installed and functioning properly.
3
Settings are viewable only if the domestic hot water module
and sensor are installed and functioning properly.
Operation
The L7224 and L7248 models can be in any of four operational states: Normal, High Limit, Low Limit and Error. The controller moves back and forth from High Limit to Normal to Low Limit state as part of normal operation. Only devices having High Limit settings are restricted to the High Limit and Normal states. However, the controller will enter the Error state when there is an abnormal condition. The operating states are:
1. Normal: Boiler temperature went below the High
Limit setting (minus the Differential) and has not exceeded the High Limit setting; or, the boiler temperature went above the Low Limit setting and
68-0281EFS—05 6
2
3
2
2
2
2
(YES or NO)
2
2
             
        
2

has not gone below the Low Limit setting (minus the Differential); or, ZR input is not powered with 120 Vac (only L7248L with ELL set On).
2. High Limit: Boiler temperature went above the High
Limit setting and has not dropped below the High Limit setting (minus the Differential).
3. Low Limit: Boiler temperature went below the Low
Limit setting (minus the Low Limit Differential) and has not gone above the Low Limit setting; or, ZR input is powered with 120 Vac (only L7248L with ELL set On).
4. Error: The controller has detected an error condition
(e.g., open sensor) and has shut down the burner output. The ZC output is energized. The controller continues to monitor the system and automatically restarts if the error condition clears. Refer toTable 4.
The operating sequence for the L7224/L7248 is shown in Table 6–9.
High Limit Controller
The High Limit opens and turns off the burner when the water temperature reaches the setpoint. The High Limit automatically resets after the water temperature drops past the setpoint and through the Differential. The L7248 models have High Limit Differential presets of 15 °F (8 °C). The L7224 models have High Limit Differential presets of 10 °F (6 °C).
Low Limit and Circulator Controller
On a temperature rise, with the adjustable Differential at the default setting of 10 °F (6 °C), the burner circuit breaks and the circulator circuit makes (assuming no call for heat is present) at the Low Limit setpoint. On a temperature drop of 10 °F (6 °C) below the Low Limit setpoint, the burner circuit makes and the circulator circuit breaks. See Fig. 7.
Fig. 7. Setpoints and differentials.
Anti Short-Cycle Feature
The Anti Short-Cycle feature allows for field selection of a delay time between burner cycles. Should a call for heat occur following the end of the previous heat cycle and before the Anti Short-Cycle delay time is expired, the circulator will be allowed to run, but the burner will be held off until the time has elapsed. The range of the Anti Short­Cycle time is from OFF to five minutes.
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
NOTE: This feature is blocked if a Domestic Hot
Water demand occurs. Domestic Hot Water demands are serviced immediately, without any delay.
NOTE: When the Aquastat is connected to the oil
primary and/or thermostat via the EnviraCOM bus, the Anti Short-Cycle time does not apply to recycle events such as loss of airflow or flame. It applies only to loss of demand.
ZR-Domestic Hot Water (DHW) Request
The ZR terminal can be selected to service an indirect water heater heat request. This parameter is set via the 3 digit display (see Adjusting Settings section of this document). A heat request via the ZR terminal will have priority over all other features such as the Anti Short­Cycle feature or those enabled by the Outdoor Reset Module (See form #69-2335 for more information).
Frost Protection
The Frost Protection function protects the boiler and potentially the boiler plumbing from possible damage which may occur should the water in the system begin to freeze. The Frost Protection feature is enabled only in the L7248 (cold start models). The feature default setting is enabled (ON), but can be disabled using the 3-digit display. See “Adjusting Settings” on page 5.
When the Boiler temperature drops to the Frost Protection Limit temperature (fixed 40 °F), the burner is forced on. The Circulator and ZC outputs remain in the same state as before the Frost Protection function was enabled. They can be either ON or OFF during the Frost Protection cycle.
Table 5. Thermal Purge Settings.
Parameter name Minimum value Maximum Value Default
Boiler temperature drop Not adjustable Not adjustable 10 °F
Thermal purge temperature limit 120 °F (or OFF) 160 °F 140 °F (L7248)
Thermal purge temperature rate of drop Not adjustable Not adjustable 5 °F/minute
Thermal purge time delay 1 minute 10 minutes 2 minutes
When the Boiler temperature reaches the Frost Protection Limit temperature plus a fixed 10 °F differential, the burner is turned off unless requested to stay on due to a different demand.
Thermal Purge Operation
The intent of thermal purge is to insure usable residual heat in the boiler is circulated until it is sufficiently depleted from the system before the burner is allowed to fire. To that end, on a call for heat, the burner is held off while the circulator runs until the boiler temperature drops to the thermal purge temperature or a time delay is exceeded. Both of these parameters are adjustable. When the boiler temperature reaches the thermal purge temperature, the burner is allowed to fire. Thermal purge is only applied to cold start Aquastat models (L7248) and will not interfere with domestic hot water call for heat or boilers equipped with Honeywell outdoor reset accessories. For warm start models where a Low Limit must be set, thermal purge is not applied.
In addition to the thermal purge temperature and thermal purge time delay parameters, two other conditions release the Aquastat from thermal purge in order to maintain comfort in the space:
• The boiler temperature has dropped 10 °F from the beginning of the thermal purge.
• Boiler temperature is cooling at a rate greater than 5 °F/minute while the circulator is running.
The thermal purge feature applies to single zone as well as multi-zone applications.
Thermal Purge Settings
Some thermal purge parameters are configurable using the 3 digit display. See “Adjusting Settings” on page 5. Thermal purge may be disabled by setting the thermal purge temperature limit to "OFF".
Thermal Purge and Domestic Hot Water
The thermal purge feature is automatically disabled whenever there is a call for domestic hot water from the Zr terminal to ensure hot water is available in a timely manner. See “ZR-Domestic Hot Water (DHW) Request” on page 7.
Pump Cycling
The Pump Cycling feature exercises the system pump for 15 seconds after a non-adjustable five day period of no boiler activity. The Pump Cycling feature default setting is enabled (ON) but can be disabled (OFF) using the 3-digit display. See “Adjusting Settings” on page 5.
CHECKOUT
Put the system into operation and observe at least one complete cycle to make sure that the controller operates properly. See TROUBLESHOOTING section to use LED to assist in determining system operation.
TROUBLESHOOTING
When attempting to diagnose system performance, reference to the LED display can help to identify specific areas not working properly. The LED display will scroll Err, followed by a digit (1-8). Refer to Table 10 and 11 for a description of each error and suggested actions.
7 68-0281EFS—05
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
LINE VOLTAGE INDIRECT
LINE
TANK AQUASTAT
L2
T
T3
2
1
INDIRECT TANK CIRCULATOR
M32023
2
50022037-002 OUTDOOR RESET MODULE
1 2 3 OT OT
C7089U OUTDOOR SENSOR
SENSOR
LINE
VOLTAGE
CIRCULATOR
LINE
VOLTAGE
OIL BURNER
RELAY
1
2
Fig. 8. L7224A,C; L7248L single heat zone with indirect water tank and circulators. Optional Outdoor Reset
L1
(HOT)
L1
(HOT)
1
OUTDOOR RESET MODULE IS OPTIONAL.
FOR BEST PERFORMANCE SET DUU=”ON”.
L2
ZR
L1
L2
C2
B2
C1
B1
ZC
Module.
68-0281EFS—05 8
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
Table 6. L7224/L7248 Controller Operating Sequence.
Action System Response
Thermostat calls for heat. Circulator starts when water temperature is above Low Limit setting (if
Boiler temperature exceeds the High Limit. Burner is turned off. Burner restarts when the water temperature
applicable) or above the Thermal Purge Temperature Limit (tPL) if Thermal Purge is enabled. Boiler temperature is checked. Burner starts when water temperature is below High Limit setting minus the differential or at or below the Thermal Purge Temperature Limit (tPL) for cold start boilers if the Thermal Purge Temperature Limit is enabled. If tPL is enabled, the burner may also start if the boiler temperature is cooling at 10 ºF or greater per minute or the Thermal Purge Time Delay (tPt) has expired. If Anti Short-Cycle Time is enabled, the burner does not start until the set Anti Short-Cycle Time between cycles expires after the previous call for heat was satisfied.
drops below the High Limit setting minus the Differential. If Thermal Purge is enabled, the burner is turned on when either the Thermal Purge Temperature Limit is reached, the Thermal Purge Time Delay has expired or the boiler temperature cooling rate exceeds 10 ºF/
minute. Thermostat is satisfied. Circulator and burner turn off. Boiler temperature drops below the Low Limit
setting minus the differential (if applicable).
Error condition 1-5.
Burner is turned on, Circulator is turned off. Burner stops when the
water temperature exceeds the Low Limit setting. Power to Zc is
removed.
If an error condition is detected, all outputs except ZC are shut down.
Burner is off. Control continues to function and restarts when error is
corrected.
During the error check sequence, the system checks for drift in the
sensor and corrosion in the connections. Error condition 6. EnviraCOM communication is not available. Error condition 7. The control has reset the High Limit, Low Limit and Differential setting to
Error condition 8. If the error condition is detected, all outputs except ZC are shut down.
a default setting and will continue to run at those settings.
Performance of the system will be degraded.
Burner is off. Control continues to function and restarts when all three
user keys have been pressed longer than 60 seconds. Error condition 9*. System continues to run with no outdoor reset functionality Error condition 10*. System continues to run with outdoor reset parameters enabled as
programmed. Error cleared automatically. Error condition 11*. System continues to run with boiler temp set to High Limit.
* Error condition only available when the Outdoor Reset Module is installed.
Table 7. L7224/L7248 Controller Operating Sequence with multiple zones connected through the ZR terminal.
Action System Response
Zone Request (ZR) terminal is connected to L1 (Zone calls for heat).
Boiler temperature exceeds the High Limit. Burner is turned off. Burner restarts when the water temperature
Zone Request input is de-energized (Zones are satisfied).
Boiler temperature drops below the Low Limit setting minus the differential (if applicable).
Boiler temperature is checked. Burner starts when water temperature
is below High Limit setting or at or below the Thermal Purge
Temperature Limit (tPL) for cold start boilers if the Thermal Purge
Temperature Limit is enabled. If tPL is enabled, the burner may also
start if the boiler temperature is cooling at 10 ºF or greater per minute
or the Thermal Purge Time Delay (tPt) has expired. Anti Short-Cycle
Time is applied, see Table 6.
drops below the High Limit setting minus the Differential. If Thermal
Purge is enabled, the burner is turned on when either the Thermal
Purge Temperature Limit is reached, the Thermal Purge Time Delay
has expired or the boiler temperature cooling rate exceeds 10 ºF/
minute.
Burner turns off.
Burner turns on and Zone Control is de-energized. Burner turns off
and Zone Control is re-energized when the water temperature
exceeds the Low Limit setting.
9 68-0281EFS—05
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
.
Table 8. Controller Operating Sequence with External Low Limit device connected trough the ZR terminal.
Action System Response
Zone Request (ZR) terminal is connected to L1 (External Low Limit call for heat).
Boiler temperature exceeds the High Limit. Burner is turned off. Burner restarts when the water temperature
Zone Request input is de-energized (External Low Limit is satisfied).
Boiler temperature is checked. Burner starts when water temperature
is below High Limit setting. Circulator turns off.
drops below the High Limit setting minus the Differential.
Burner is turned off.
Table 9. L7224 Controller Operating Sequence with Domestic Hot Water connected trough the ZR terminal.
Action System Response
Zone Request (ZR) terminal is connected to L1 (Domestic Hot Water calls for heat).
Boiler temperature exceeds the High Limit. Burner is turned off. Burner restarts when the water temperature
Zone Request input is de-energized (Domestic Hot Water is satisfied).
Boiler temperature is checked. Burner starts when water temperature
is below High Limit setting.
drops below the High Limit setting minus the Differential.
Burner is turned off.
Table 10. LED Error Codes.
Aquastat
Error Code Cause/Action
EnviraCOM
Alarm
Err1 Aquastat sensor fault; check water sensor. 18 Err2 ECOM fault; check EnviraCOM™ wiring. 18 Err3 Excessive electrical noise or frequency out of range. Hardware fault; replace controller. 18, 58 Err4 B1 fault; check B1 wiring/voltage. 64 Err5 Low Line; check L1-L2, 110 Vac. 59
a
Err6
Warning: Fuse; check ECOM wires, replace fuse. 92
Err7 Warning: EEPROM, HL, LL, Hdf, Ldf; reset to default values. N/A
b
Err 8 Err9
Err 10
Err 11
a
Warnings are generated to enunciate the system is not operating optimally, but the Aquastat is still operating and maintaining boiler temperature. In the instance where an Outdoor Reset Module is used, the warnings may indicate a reset curve setting error one or more features is not running optimally, and the Aquastat is reverting to default settings or has stopped running the Outdoor Reset algorithms. The warnings are cleared when the issue(s) is resolved.
b
To clear Err 8 condition, depress and hold all three user keys simultaneously for 60 seconds. Err 8 condition clears and display returns to normal. Err 8 condition is designed to catch welded relays on the Aquastat and will normally only occur near end of life for the control. If Err 8 condition has occurred early in the controls life, be sure to check for voltage feedback to B1 when B1 should be off and check current draw on b terminal to be sure oil burner is not draw­ing excessive current. Err 8 condition will keep repeating if B1 fault is not cleared.
Repeated B1 fault (voltage present at B1 when output is turned off); check B1 wiring/voltage. 25
a
Warning: Outdoor Reset System failure; communication to Outdoor Reset Module lost, Outdoor Reset Module failure, multiple outdoor temperature sensors detected on the bus, or outdoor temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.
a
Warning: Boost Failure; Boost Mode active at least once per cycle for the last 60 consecutive cycles. Check Outdoor Reset curve settings.
a
DHW Module/Sensor failure; communication to DHW Module lost, DHW Module failure, or temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.
50, 53, 149
150
146, 147, 148
Table 11. Troubleshooting Guide
System
Condition
Boiler is cold, house is cold.
Diagnostic
Condition Check Action
Display is OFF. 120 Vac System power. Turn system power on. Display is ON. 24 Vac T-T No 24 V; replace control.
24 V present; disconnect thermostat, short T-T.
120 Vac at B1-B2 If no, replace control.
Refer to Err on display.
68-0281EFS—05 10
Boiler starts, check wiring and thermostat.
If yes, check burner and wiring.
System
M27115
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
2
C1
B1
ZC
L2
LINE
C2
ZR
L1
B2
T
T3
2
1
SENSOR
LINE
VOLTAGE
CIRCULATOR
LINE
VOLTAGE
OIL BURNER
RELAY
2
LOW VOLTAGE THERMOSTAT
L7224
3
L1 (HOT)
L2
1
2
1
4
5
6
ZONE 2 LOW VOLTAGE THERMOSTAT
R845A RELAY ZONE 2
ZONE 2
CIRCULATOR
TO ADDITIONAL R845A RELAYS FOR OTHER ZONES
Condition
Boiler is hot, house is cold.
Boiler is hot, no hot potable water.
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
Table 11. Troubleshooting Guide
Diagnostic
Condition Check Action
Display is ON. 120 Vac at C1-C2 120 Vac at C1-C2, check wiring to pump.
Boiler below the Low Limit temperature, wait for boiler to go above Low Limit temperature.
Boiler above LL? If yes, check for 120 Vac between ZC and L2.
ELL setting (L7248L only) Set ELL to Off for multizone system (see Fig.
Boiler above LL? If yes, check 120 Vac at ZR-L2 (only L7248L with ELL set On)
Display is ON. Boiler Demand signal from the
water heater (either 120 Vac at ZR-L2, or 0 Vac on T-T; depends on installation and “duu” setting)
“duu” setting Set duu to ON if 120 Vac water heater
Check DHW Module and DHW Sensor
Wiring OK, is pump running?
If not, replace the pump.
If pump is running, check for trapped air or
closed zone valves.
If no 120 Vac, replace control.
If yes, check zone relays, circulators and
wiring.
11).
Set ELL to On for External Low Limit (see
Fig. 13).
If no 120 Vac, check C1-C2 (see above).
If yes, check the External Low Limit control.
24 Vac on T-T (or 0 Vac on ZR-L2), check
wiring to water heater
Wiring OK, check the water heater
demand is connected to ZR
Set duu to OFF if open/closed water heater
demand is connected to T-T
DHW Module not properly connected and/or
DHW Sensor improperly positioned
Fig. 9. L7224A,C multizone system with circulator connections.
11 68-0281EFS—05
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
M32025
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
OPTIONAL FEATURE ON SELECT MODELS.
REFER TO DEVICE LABEL FOR WIRE COLOR CODE.
1
2
3
C1
B1
ZC
L2
LINE
C2
ZR
L1
B2
T
T
3
3
3
2
2
2
1
1
1
SENSOR
LINE
VOLTAGE
CIRCULATOR
L7224
3
4
3
3
5
BURNER MOTOR
IGNITOR
VALV E
BURNER MOTOR
IGNITOR
VALV E
CAD CELL
JUNCTION BOX
TO REMOTE ALARM CIRCUIT
ENVIRACOM™ TERMINAL
TH9421C
R7184
LIMIT
L1
L2
2
CAD CELL
T
T
3
2
1
L1 (HOT)
L2
1
LEGEND SCREW TERMINAL 1/4 IN. (6 MM) QUICK CONNECT TERMINAL
SOLDERLESS WIRE CONNECTION
VALVE IS OPTIONAL ON SPECIFIED MODELS.
ENVIRACOM™ TERMINAL 3 IS ALSO THE FIRST THERMOSTAT TERMINAL.
OPTIONAL OUTDOOR RESET MODULE AND OUTDOOR SENSOR.
DUU MUST BE SET TO “ON” ON THE AQUASTAT.
4
5
6
1 2 3 OT OT
C7089U1006 OUTDOOR SENSOR
6
50022037-002 OUTDOOR RESET MODULE
7
INDIRECT TANK CIRCULATOR
LINE VOLTAGE INDIRECT TANK AQUASTAT
L2
7
Fig. 10. L7224A,C single zone system with circulator and indirect water tank with EnviraCOM™ thermostat.
68-0281EFS—05 12
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
M29655
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
2
3
L1 (HOT)
L2
1
2
1
4
5
6
ZONE 2
LOW VOLTAGE
THERMOSTAT
R845A RELAY ZONE 2
ZONE 2
CIRCULATOR
TO ADDITIONAL R845A RELAYS FOR OTHER ZONES
C1
B1
ZC
L2
LINE
C2
ZR
L1
B2
T
T 3
2
1
SENSOR
LINE
VOLTAGE
CIRCULATOR
LINE
VOLTAGE
OIL BURNER
RELAY
2
LOW VOLTAGE THERMOSTAT
L7248L
ELL=OFF
OPTIONAL OUTDOOR RESET MODULE AND OUTDOOR SENSOR.
ENVIRACOM TERMINALS.
OPTIONAL DOMESTIC HOT WATER MODULE AND TEMPERATURE SENSOR.
3
4
5
1 2 3 OT OT
C7089U1006 OUTDOOR SENSOR
50022037-002 OUTDOOR RESET MODULE
1 2 3 TS TS
50022037-005 DOMESTIC HOT WATER MODULE
32003971-003 TEMPERATURE SENSOR
4
ENVIRACOM TERMINALS
3
5
Fig. 11. L7248L multizone system with circulator connections.
13 68-0281EFS—05
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
M32024
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
OPTIONAL FEATURE ON SELECT MODELS.
REFER TO DEVICE LABEL FOR WIRE COLOR CODE.
VALVE IS OPTIONAL ON SPECIFIED MODELS.
ENVIRACOM™ TERMINAL 3 IS ALSO THE FIRST THERMOSTAT TERMINAL.
1
2
3
C1
B1
ZC
L2
LINE
C2
ZR
L1
B2
T
T
3
2
1
SENSOR
LINE
VOLTAGE
CIRCULATOR
L7224
3
4
3
3
5
BURNER MOTOR
IGNITOR
VALV E
BURNER MOTOR
IGNITOR
VALV E
CAD CELL
JUNCTION BOX
TO REMOTE ALARM CIRCUIT
ENVIRACOM™ TERMINAL
R7184
LIMIT
L1
L2
2
CAD CELL
T
T
3
2
1
L1 (HOT)
L2
1
LEGEND SCREW TERMINAL 1/4 IN. (6 MM) QUICK CONNECT TERMINAL
SOLDERLESS WIRE CONNECTION
OPTIONAL OUTDOOR RESET MODULE AND OUTDOOR SENSOR.
OPTIONAL DOMESTIC HOT WATER MODULE.
WIRE ONLY THE ENVIRACOM TERMINALS (1, 2, 3) ON OIL PRIMARY IF CONNECTING TO REMOTE DIAGNOSTICS, OTHERWISE CONNECT A JUMPER BETWEEN THE TT TERMINALS.
ZONE PANEL TERMINALS MAY HAVE DIFFERENT LABEL. CHECK PANEL MANUFACTURER SPECIFICATIONS FOR WIRING INSTRUCTIONS.
6
7
8
1 2 3 TS TS
32003971-003 TEMPERATURE SENSOR
7
50022037-002 DOMESTIC HOT WATER MODULE
9
MULTI-ZONE RELAY PANEL
T T
4
5
1 2 3 OT OT
C7089U OUTDOOR SENSOR
6
50022037-002 OUTDOOR RESET MODULE
8
9
applications).
Fig. 12. L7224/L7248 multizone system with Outdoor Reset and Domestic Hot Water Modules (indirect tank
68-0281EFS—05 14
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
M27113
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.
2
W
L1 (HOT)L2
1
B
R
C1
B1
ZC
L2
LINE
C2
ZR
L1
B2
T
T3
2
1
SENSOR
LINE
VOLTAGE
CIRCULATOR
LINE
VOLTAGE
OIL BURNER
RELAY
2
LOW VOLTAGE THERMOSTAT
L7248L
ELL=ON
L6006 LOW LIMIT CONTROLLER
Fig. 13. L7248L External Low Limit connections.
15 68-0281EFS—05
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS
Automation and Control Solutions
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com
® U.S. Registered Trademark © 2012 Honeywell International Inc. 68-0281EFS—05 M.S. Rev. 03-12 Printed in United States
Loading...
+ 36 hidden pages