Honeywell L7224U Installation Instructions Manual

69-1720-03
L7224U Oil Electronic Aquastat

APPLICATION

®
Aquastat sensing in a UL limit-rated controller with a single sensing probe. The L7224U controls the circulator, oil burner and boiler temperature.
The L7224U is “Outdoor Temperature Reset” ready, which is enabled when connected to the 50022037-002 Outdoor Reset Module. (option 1)
Additionally, the L7224U provides adjustable short cycle.
The L7224U replaces the L8124A, L8124C, L7124U, L7148A, L7248A,C, L7224A,C, and L8148A Controllers.
The Aquastat Controller is intended for use in residential­type applications.
The L7224U provides status and diagnostic information through an LED display combined with LED lights as well as EnviraCOM enabled thermostats and diagnostic tools to enhance the diagnostic process.
Controller provides electronic temperature
Accessories (Ordered Separately):
50022037-002 AquaReset™ Outdoor Reset Module C7089U1006 Outdoor Temperature Sensor (used with
the 50022037-002)
W8735S1000 (AquaReset™ Outdoor Reset Kit) includes
50022037-002 and C7089U1006) 50022037-005 Domestic Hot Water Module 32003971-003 Temperature Sensor (used with
50022037-005) W8735S1008 AquaReset™ Domestic Hot Water Kit
(includes 50022037-005 and 32003971-003) Sensor (See Table 2). Sensor Well Clamp 121371AA. 14,000,485-016 1/4 in. (6.35 mm) diameter, 1-1/4 in.
(31.75 mm) length glass cartridge Fuse, 1 A,
Slow-Blow. 120650 Heat Conductive Compound.
Number
123869A 1/2 (12.7) NPT 3 (76.2) 1-1/2 (38.1)
123870A 3/4 (19.05) NPT 3 (76.2) 1-1/2 (38.1)
®
Controller
INSTALLATION INSTRUCTIONS
Table 1. Wells for L7224U Controller.
Part
Spud Size
in. (mm)
Insertion
in. (mm)
Insulation
in. (mm)

SPECIFICATIONS

Electrical Ratings:
Voltage: 120 Vac, 60 Hz. Power: 7 VA maximum at 120 Vac plus external loads. Thermostat current: 100 mA nominal at 24 Vac. Burner Relay:
7.4 A at 120 Vac Full Load Amperage (FLA);
44.4 A inrush Locked Rotor Amperage (LRA); Less Ignition Load: 360 VA.
Circulator Relay:
7.4 A at 120 Vac FLA; 44.4 A inrush LRA. Zone Controller (ZC): 7.4 A at 120 Vac FLA;
44.4 A inrush LRA.
NOTE: All loads combined cannot exceed 2000 VA.
Environmental Ratings:
Temperature: -30° F to +150° F (-34° C to +66° C). Humidity: 0 to 95% relative humidity, noncondensing.
Approvals:
Underwriters Laboratories Inc. Component Recognized. Canadian Underwriters Laboratories Inc. Component
Recognized.
Table 2. Sensors for L7224U Controller.
Part Number
50001464-001 12 (304.8) Well-mounted controls
50001464-002 18 (457.2) Flush-mounted controls
50001464-003 24 (609.6)
50001464-004 36 (914.4)
50001464-005 48 (1219.2)
Length in.
(mm) Application
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
WARNING

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. The installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
5. Set High Limit, Low Limit and Differential to the set­tings recommended by the boiler OEM.
6. Record the maximum High Limit setting from the replaced controller in the text box provided on the cover insert label.
7. Record the High Limit setting at the time of installa­tion in the text box provided on the cover insert label.
3/4
(75)
7-1/8 (181)
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.

Mounting

The L7224U can be mounted in a well mount, horizontal or vertical position, or flush mounted remote from the well.
IMPORTANT
Immersion well must fit sensing element and sensor must rest against bottom of well.

New Installation

Order well assemblies separately; refer to Table 1 and form no. 68-0040, Immersion Wells and Compression Fittings for Temperature Controllers. Boilers usually have tappings that allow the well to be mounted horizontally so boiler water of average temperature can circulate freely over the well. See Fig. 1 for mounting dimensions.
6-1/2 (166)
5-11/16
(145)
3/8
(10)
2-5/8 (67)
4-1/4 (109)
3-13/32 (86)
2x 1/4 (7) x 3/8 (9)
Fig. 1. L7224U mounting dimensions in inches (mm).
1. Turn off all power and drain the boiler.
2. If no tapping is provided, prepare properly sized and
threaded tapping near the top of the boiler.
3. Sparingly coat the well threads with pipe dope.
NOTE: Do not attempt to tighten by using the case as a
handle.
69-1720—03 2
3-1/32
(77)
1-3/16
(30)
1-1/8 (29)
1/16 (2)
4. Install the well in the boiler tapping and tighten securely.
5. Refill boiler and check for water leakage.
6. Identify if installation requires vertical or horizontal
mounting.
7. Remove the well knockout, for either vertical or horizontal mounting, by carefully prying the knockout from the back of the case, using a flat-bladed screw driver. Refer to Fig. 2.
2-1/16 (53)
M22147B
KNOCKOUT FOR HORIZONTAL MOUNT
SCREWDRIVER
KNOCKOUT FOR VERTICAL MOUNT
M22118
Fig. 2. Removing horizontal or vertical mounting
8. Loosen but do not remove the well clamp screw.
9. Fit the case into the well so the clamp on the case
slides over the flange on the well.
10. Securely tighten the clamp screw.
11. Insert the sensor element into the well until it
bottoms. (If necessary, slightly bend the wire inside the case to hold the sensor against the bottom of the well.)
12. Tur n powe r O N.
13. Set High Limit, Low Limit and Differentials to the
settings recommended by the boiler OEM. (See OPERATION section, also refer to INSTALLATION steps 6 and 7.)
IMPORTANT
Best thermal response is obtained with a well that snugly fits the sensor. Insert the sensor until it rests against the bottom of the well. Use a well of correct length and bend the wiring, if neces­sary, to hold the bulb against the bottom of the well.
If the well is not a snug fit on the sensor, use the heat-conductive compound (furnished with TRADELINE® models) as follows: Fold the plastic bag of compound lengthwise and twist it gently. Then snip off end of bag and work the open end of the bag all the way into the well. Slowly pull out the bag while squeezing it firmly to distribute compound evenly in the well. Bend the wiring, if necessary, to hold the sensor against the bottom of the well and to hold outer end of the sensor in firm contact with the side of the well. See Fig. 3. Wipe excess compound from the outer end of the well.
knockout.
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
SENSOR WIRES
CONTROLLER CASE
IMMERSION WELL CLAMP
IMMERSION WELL CLAMP SCREW
BOILER
IMMERSION WELL
HEAT-CONDUCTIVE COMPOUND (OPTIONAL)
SENSOR
M16120
Fig. 3. Position of sensor in immersion well.

Flush-Mounted Aquastat Replacement

Turn off all power and remove the old controller. Refer to the cover insert of the old controller to identify and tag each external lead as it is disconnected. If the old well is unsuitable for the new installation, remove it and replace it with a suitable new well. If the old well is suitable, use it. See Fig. 1 and 4 for mounting tab location.
THERMOSTAT
TERMINALS
T
T3
2
1
TX TT
ZR
L1
L2
C2
B2
C1
B1
ZC
FLUSH MOUNTING TAB (2)
Fig. 4. Location of L7224U flush-mounting tabs and
LINE
B1 ZC C1
LEDs.
ENVIRACOM TERMINALS
TM
DISPLAY
LED's
CAPACITOR
SENSOR CONNECTOR
RELAYS
TRANSFORMER
SENSOR HOLES
FUSE
RELAY
M22119A
3 69-1720—03
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
WARNING

Well-Mounted Aquastat Replacement

Turn off all power and remove the old controller. Refer to the cover insert of the old controller to identify and tag each external lead as it is disconnected. If the old well is unsuitable for the new installation, remove it and proceed with instructions for new installation. If the old well is suitable, use it.
1. Loosen, but do not remove, the well clamp screw on the side of the controller case.
2. Position immersion well clamp snugly over the flange of the adapter and tighten the clamp screw.
3. Insert the sensor into the well as shown in Fig. 5. (If desired, distribute the heat-conductive com­pound in the tube prior to sensor insertion, as described in New Installation.)
4. Make sure sensor is fully seated to bottom of well (Fig. 5). Use a small pencil to measure depth of sensor in well, if necessary.
SENSOR WIRES
BOILER
IMMERSION WELL
HEAT-CONDUCTIVE COMPOUND (OPTIONAL)
SENSOR
M22026
Fig. 5. Replacement sensor installation.

Replacement Sensor Installation

Turn off all power and carefully disconnect sensor from circuit board by pulling gently on the connector.
1. Gently pull sensor from thermo well and through cir­cuit board by pulling on leadwires.
2. Carefully align replacement sensor with hole in circuit board and guide through Aquastat case and into well. Refer to Fig. 5.
3. Make sure sensor is fully seated to bottom of well (see Fig. 5). Use a small pencil to measure depth of sensor in well, if necessary.
4. Connect sensor to circuit board by pressing connector on sensor unit into mating connector on circuit board (refer to Fig. 6).
5. For remote sensors (flush mounted Aquastat) be sure to use the 121371AA clamp to securely hold sensor in place. See Accessories.

WIRING

Electrical Shock Hazard. Can cause serious injury or death.
Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage.
All wiring must comply with local electrical codes and ordinances. Do not exceed the specifications in the Application section when wiring this controller.
IMPORTANT
The terminals on these Aquastat Controllers are approved for use with copper wire only.
Follow the appropriate wiring diagrams shown on the inside of the front cover of the L7224U or in Fig. 9, 10, and
11.
Refer to Fig. 6 for Connections for the optional Outdoor Reset Module and the Domestic Hot Water (DHW) module. In subsequent wiring diagrams these modules will be displayed with a dotted line signifying that they are optional.
50022037-002 OUTDOOR RESET MODULE
T
3
T
2
1
ZR
L1
L2
C2
B2
C1
B1
ZC
LINE
Fig. 6. Wiring the Outdoor Reset Module and the
Domestic Hot Water Module.
1 2 3 OT OT
C7089U1006 OUTDOOR SENSOR
50022037-005 DOMESTIC HOT WATER MODULE
1 2 3 TS TS
32003971-003 TEMPERATURE SENSOR
M29651

OPERATION

General

The L7224U Oil Electronic Aquastat Controller is a primary safety limit-rated device designed for use with oil fired boilers with line voltage burners and circulators. Many boilers do not include wiring or controller compartments as part of the design, but are provided with an integral, replaceable, immersion well that is the mounting hardware for the Aquastat Controllers. Wiring to the other controllers is done through flexible metal conduit.
For boilers that do include a remotely (flush) mounted controller, the wiring may be completed with conduit or routed behind the boiler sheet metal.
A separate electromechanical High Limit is not required in a system that uses this controller to meet Underwriters Laboratories Inc. requirements for oil-fired boiler assemblies, UL 726.
On the L7224U, the High Limit, High Limit Differential, Low Limit, and Low Limit Differential and Anti-Short Cycle time can be adjusted to the setting recommended by the boiler OEM.
69-1720—03 4
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
The overall range of the High Limit is from 130° F to 240° F (54° C to 116° C). Select devices may have different ranges. Some models have limited ranges on the High Limit setpoint; this limited range is listed on the device label.
The range of the Low Limit is from 110° F to 220° F (43° C to 104° C). Select devices may have different ranges. The range of the Anti-Short Cycle time is from 10 seconds to five minutes.
If a 50022037-002 “Outdoor Reset Module” is installed, the reset curve can be set by entering the minimum outdoor temperature, minimum (water or boiler) temperature, and maximum outdoor temperature on the 3-digit display. The range of the minimum outdoor temperature is from -40°F to 40°F (-40°C to 4.4°C) and has a default setting of 0°F (-18°C). The range of the maximum outdoor temperature is from 30°F to 70°F (-1°C to 21°C) and has a default setting of 40°F (4.4°C). The range of the minimum (water or boiler) temperature is from 80°F to 180°F (27°C to 82°C) and has a default setting of 130°F (54°C). See the “Outdoor Reset Module” Installation Instructions (form number 69-2335) for more information on setting the boiler reset curve and all related parameters.
The L7224U is designed for use with 24 Vac electronic and electromechanical thermostats and EnviraCOM™ enabled thermostats, and have screw-type terminals for easy field connection.
To replace a L8148A,C L7148A or L7248A,C controller, the Low Limit function must be disabled; see Adjusting Settings for directions.

Adjusting Settings

To discourage unauthorized changing of Aquastat settings, a procedure to enter the ADJUSTMENT mode is required. To enter the ADJUSTMENT mode, press the UP, DOWN, and I buttons (refer to Fig. 9) simultaneously for three seconds. Press the I button until the feature requiring adjustment is displayed:
• HL_ — High Limit.
• Hdf — High Limit Differential.
• LL_ — Low Limit.
• Ldf — Low Limit Differential.
• duu — ZR input configured as external Domestic Hot Water (DHW) request (ON/OFF)
• ASC — Anti Short-Cycle Timeout (seconds); “OFF” is disabled.
• otL — Outdoor Temperature Low (minimum) parameter for the outdoor reset curve (F or C)*
• otH — Outdoor Temperature High (maximum) parameter for outdoor reset curve (F or C)*
• btL — Boiler Temperature Low (minimum) parameter for outdoor reset curve*
• bP — Boost Period (minutes). “OFF” is displayed if Boost is inactive*
• bS — Boost step (F or C) shown only if Boost is active (bP=ON)*
• UUS — Warm Weather Shutdown Temperature (F or C)*
• F-C — Temperature units (F or C)
* Settings available for adjustment on the 3-digit display
only if the AquaReset Outdoor Reset Module is installed.
Then press the UP and/or DOWN buttons to move the set point to the desired value. After 60 seconds without any button inputs, the controller will automatically return to the RUN mode.
To use the L7224U in a cold start boiler application, disable the Low Limit function by pressing the UP arrow button, DOWN arrow button and I button simultaneously for three seconds. Then push the I button until LL_ is displayed. Then press the down arrow button until OFF is displayed.

Display

In the RUN mode, the Aquastat will flash “bt” (boiler temp) followed by the temperature (i.e., 220), followed by °F or °C.
To read boiler settings, press the I key to read the parameter of interest. For example, press I and HL (High Limit) is displayed, followed by a three-digit number, i.e., 220, followed by °F or °C. Pressing the I button again will display the LL (Low Limit) followed by a three-digit number and the corresponding degree designator. See Fig. 7 for explanation of display readout.
After approximately 60 seconds without any key presses, the display will enter a dim display mode. To return to the bright display mode, simply press and release any key.
5 69-1720—03
Loading...
+ 11 hidden pages