Aquastat
sensing in a UL limit-rated controller with a single
sensing probe. The L7224U controls the circulator, oil
burner and boiler temperature.
The L7224U is “Outdoor Temperature Reset” ready,
which is enabled when connected to the 50022037-002
Outdoor Reset Module. (option 1)
Additionally, the L7224U provides adjustable short cycle.
The L7224U replaces the L8124A, L8124C, L7124U,
L7148A, L7248A,C, L7224A,C, and L8148A Controllers.
The Aquastat Controller is intended for use in residentialtype applications.
The L7224U provides status and diagnostic information
through an LED display combined with LED lights as well
as EnviraCOM enabled thermostats and diagnostic tools
to enhance the diagnostic process.
Controller provides electronic temperature
Accessories (Ordered Separately):
50022037-002 AquaReset™ Outdoor Reset Module
C7089U1006 Outdoor Temperature Sensor (used with
the 50022037-002)
W8735S1000 (AquaReset™ Outdoor Reset Kit) includes
50022037-002 and C7089U1006)
50022037-005 Domestic Hot Water Module
32003971-003 Temperature Sensor (used with
50022037-005)
W8735S1008 AquaReset™ Domestic Hot Water Kit
(includes 50022037-005 and 32003971-003)
Sensor (See Table 2).
Sensor Well Clamp 121371AA.
14,000,485-016 1/4 in. (6.35 mm) diameter, 1-1/4 in.
(31.75 mm) length glass cartridge Fuse, 1 A,
Slow-Blow.
120650 Heat Conductive Compound.
Number
123869A 1/2 (12.7) NPT 3 (76.2)1-1/2 (38.1)
123870A 3/4 (19.05) NPT 3 (76.2)1-1/2 (38.1)
®
Controller
INSTALLATION INSTRUCTIONS
Table 1. Wells for L7224U Controller.
Part
Spud Size
in. (mm)
Insertion
in. (mm)
Insulation
in. (mm)
SPECIFICATIONS
Electrical Ratings:
Voltage: 120 Vac, 60 Hz.
Power: 7 VA maximum at 120 Vac plus external loads.
Thermostat current: 100 mA nominal at 24 Vac.
Burner Relay:
7.4 A at 120 Vac Full Load Amperage (FLA);
44.4 A inrush Locked Rotor Amperage (LRA);
Less Ignition Load: 360 VA.
Circulator Relay:
7.4 A at 120 Vac FLA; 44.4 A inrush LRA.
Zone Controller (ZC): 7.4 A at 120 Vac FLA;
44.4 A inrush LRA.
NOTE: All loads combined cannot exceed 2000 VA.
Environmental Ratings:
Temperature: -30° F to +150° F (-34° C to +66° C).
Humidity: 0 to 95% relative humidity, noncondensing.
Approvals:
Underwriters Laboratories Inc. Component Recognized.
Canadian Underwriters Laboratories Inc. Component
Recognized.
Table 2. Sensors for L7224U Controller.
Part Number
50001464-00112 (304.8) Well-mounted controls
50001464-00218 (457.2) Flush-mounted controls
50001464-00324 (609.6)
50001464-00436 (914.4)
50001464-00548 (1219.2)
Length in.
(mm)Application
Page 2
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
WARNING
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. The installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
5. Set High Limit, Low Limit and Differential to the settings recommended by the boiler OEM.
6. Record the maximum High Limit setting from the
replaced controller in the text box provided on the
cover insert label.
7. Record the High Limit setting at the time of installation in the text box provided on the cover insert
label.
3/4
(75)
7-1/8
(181)
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning
installation to prevent electrical shock or
equipment damage.
Mounting
The L7224U can be mounted in a well mount, horizontal
or vertical position, or flush mounted remote from the well.
IMPORTANT
Immersion well must fit sensing element and
sensor must rest against bottom of well.
New Installation
Order well assemblies separately; refer to Table 1 and
form no. 68-0040, Immersion Wells and Compression
Fittings for Temperature Controllers. Boilers usually have
tappings that allow the well to be mounted horizontally so
boiler water of average temperature can circulate freely
over the well. See Fig. 1 for mounting dimensions.
6-1/2
(166)
5-11/16
(145)
3/8
(10)
2-5/8 (67)
4-1/4 (109)
3-13/32 (86)
2x 1/4 (7) x 3/8 (9)
Fig. 1. L7224U mounting dimensions in inches (mm).
1. Turn off all power and drain the boiler.
2. If no tapping is provided, prepare properly sized and
threaded tapping near the top of the boiler.
3. Sparingly coat the well threads with pipe dope.
NOTE: Do not attempt to tighten by using the case as a
handle.
69-1720—032
3-1/32
(77)
1-3/16
(30)
1-1/8 (29)
1/16 (2)
4. Install the well in the boiler tapping and tighten
securely.
5. Refill boiler and check for water leakage.
6. Identify if installation requires vertical or horizontal
mounting.
7. Remove the well knockout, for either vertical or
horizontal mounting, by carefully prying the
knockout from the back of the case, using a
flat-bladed screw driver. Refer to Fig. 2.
2-1/16 (53)
M22147B
Page 3
KNOCKOUT FOR
HORIZONTAL
MOUNT
SCREWDRIVER
KNOCKOUT FOR
VERTICAL MOUNT
M22118
Fig. 2. Removing horizontal or vertical mounting
8. Loosen but do not remove the well clamp screw.
9. Fit the case into the well so the clamp on the case
slides over the flange on the well.
10. Securely tighten the clamp screw.
11. Insert the sensor element into the well until it
bottoms. (If necessary, slightly bend the wire inside
the case to hold the sensor against the bottom of
the well.)
12. Tur n powe r O N.
13. Set High Limit, Low Limit and Differentials to the
settings recommended by the boiler OEM. (See
OPERATION section, also refer to INSTALLATION
steps 6 and 7.)
IMPORTANT
Best thermal response is obtained with a well
that snugly fits the sensor. Insert the sensor until
it rests against the bottom of the well. Use a well
of correct length and bend the wiring, if necessary, to hold the bulb against the bottom of the
well.
If the well is not a snug fit on the sensor, use the
heat-conductive compound (furnished with
TRADELINE® models) as follows: Fold the
plastic bag of compound lengthwise and twist it
gently. Then snip off end of bag and work the
open end of the bag all the way into the well.
Slowly pull out the bag while squeezing it firmly
to distribute compound evenly in the well. Bend
the wiring, if necessary, to hold the sensor
against the bottom of the well and to hold outer
end of the sensor in firm contact with the side of
the well. See Fig. 3. Wipe excess compound
from the outer end of the well.
knockout.
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
SENSOR WIRES
CONTROLLER CASE
IMMERSION
WELL CLAMP
IMMERSION WELL
CLAMP SCREW
BOILER
IMMERSION
WELL
HEAT-CONDUCTIVE COMPOUND
(OPTIONAL)
SENSOR
M16120
Fig. 3. Position of sensor in immersion well.
Flush-Mounted Aquastat Replacement
Turn off all power and remove the old controller. Refer to
the cover insert of the old controller to identify and tag
each external lead as it is disconnected. If the old well is
unsuitable for the new installation, remove it and replace it
with a suitable new well. If the old well is suitable, use it.
See Fig. 1 and 4 for mounting tab location.
THERMOSTAT
TERMINALS
T
T3
2
1
TX
TT
ZR
L1
L2
C2
B2
C1
B1
ZC
FLUSH MOUNTING TAB (2)
Fig. 4. Location of L7224U flush-mounting tabs and
LINE
B1 ZC C1
LEDs.
ENVIRACOM
TERMINALS
TM
DISPLAY
LED's
CAPACITOR
SENSOR
CONNECTOR
RELAYS
TRANSFORMER
SENSOR HOLES
FUSE
RELAY
M22119A
369-1720—03
Page 4
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
WARNING
Well-Mounted Aquastat Replacement
Turn off all power and remove the old controller. Refer to
the cover insert of the old controller to identify and tag
each external lead as it is disconnected. If the old well is
unsuitable for the new installation, remove it and proceed
with instructions for new installation. If the old well is
suitable, use it.
1. Loosen, but do not remove, the well clamp screw on
the side of the controller case.
2. Position immersion well clamp snugly over the
flange of the adapter and tighten the clamp screw.
3. Insert the sensor into the well as shown in Fig. 5.
(If desired, distribute the heat-conductive compound in the tube prior to sensor insertion, as
described in New Installation.)
4. Make sure sensor is fully seated to bottom of well
(Fig. 5). Use a small pencil to measure depth of
sensor in well, if necessary.
SENSOR WIRES
BOILER
IMMERSION
WELL
HEAT-CONDUCTIVE COMPOUND
(OPTIONAL)
SENSOR
M22026
Fig. 5. Replacement sensor installation.
Replacement Sensor Installation
Turn off all power and carefully disconnect sensor from
circuit board by pulling gently on the connector.
1. Gently pull sensor from thermo well and through circuit board by pulling on leadwires.
2. Carefully align replacement sensor with hole in
circuit board and guide through Aquastat case and
into well. Refer to Fig. 5.
3. Make sure sensor is fully seated to bottom of well
(see Fig. 5). Use a small pencil to measure depth of
sensor in well, if necessary.
4. Connect sensor to circuit board by pressing
connector on sensor unit into mating connector on
circuit board (refer to Fig. 6).
5. For remote sensors (flush mounted Aquastat) be
sure to use the 121371AA clamp to securely hold
sensor in place. See Accessories.
WIRING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect power supply before making wiring
connections to prevent electrical shock or
equipment damage.
All wiring must comply with local electrical codes and
ordinances. Do not exceed the specifications in the
Application section when wiring this controller.
IMPORTANT
The terminals on these Aquastat Controllers are
approved for use with copper wire only.
Follow the appropriate wiring diagrams shown on the
inside of the front cover of the L7224U or in Fig. 9, 10, and
11.
Refer to Fig. 6 for Connections for the optional Outdoor
Reset Module and the Domestic Hot Water (DHW)
module. In subsequent wiring diagrams these modules
will be displayed with a dotted line signifying that they are
optional.
50022037-002
OUTDOOR
RESET MODULE
T
3
T
2
1
ZR
L1
L2
C2
B2
C1
B1
ZC
LINE
Fig. 6. Wiring the Outdoor Reset Module and the
Domestic Hot Water Module.
1 2 3 OT OT
C7089U1006
OUTDOOR
SENSOR
50022037-005
DOMESTIC HOT
WATER MODULE
1 2 3 TS TS
32003971-003
TEMPERATURE
SENSOR
M29651
OPERATION
General
The L7224U Oil Electronic Aquastat Controller is a
primary safety limit-rated device designed for use with oil
fired boilers with line voltage burners and circulators.
Many boilers do not include wiring or controller
compartments as part of the design, but are provided with
an integral, replaceable, immersion well that is the
mounting hardware for the Aquastat Controllers. Wiring to
the other controllers is done through flexible metal
conduit.
For boilers that do include a remotely (flush) mounted
controller, the wiring may be completed with conduit or
routed behind the boiler sheet metal.
A separate electromechanical High Limit is not required in
a system that uses this controller to meet Underwriters
Laboratories Inc. requirements for oil-fired boiler
assemblies, UL 726.
On the L7224U, the High Limit, High Limit Differential,
Low Limit, and Low Limit Differential and Anti-Short Cycle
time can be adjusted to the setting recommended by the
boiler OEM.
69-1720—034
Page 5
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
The overall range of the High Limit is from 130° F to
240° F (54° C to 116° C). Select devices may have
different ranges. Some models have limited ranges on the
High Limit setpoint; this limited range is listed on the
device label.
The range of the Low Limit is from 110° F to 220° F
(43° C to 104° C). Select devices may have different
ranges. The range of the Anti-Short Cycle time is from 10
seconds to five minutes.
If a 50022037-002 “Outdoor Reset Module” is installed,
the reset curve can be set by entering the minimum
outdoor temperature, minimum (water or boiler)
temperature, and maximum outdoor temperature on the
3-digit display. The range of the minimum outdoor
temperature is from -40°F to 40°F (-40°C to 4.4°C) and
has a default setting of 0°F (-18°C). The range of the
maximum outdoor temperature is from 30°F to 70°F (-1°C
to 21°C) and has a default setting of 40°F (4.4°C). The
range of the minimum (water or boiler) temperature is
from 80°F to 180°F (27°C to 82°C) and has a default
setting of 130°F (54°C). See the “Outdoor Reset Module”
Installation Instructions (form number 69-2335) for more
information on setting the boiler reset curve and all related
parameters.
The L7224U is designed for use with 24 Vac electronic
and electromechanical thermostats and EnviraCOM™
enabled thermostats, and have screw-type terminals for
easy field connection.
To replace a L8148A,C L7148A or L7248A,C controller,
the Low Limit function must be disabled; see Adjusting
Settings for directions.
Adjusting Settings
To discourage unauthorized changing of Aquastat
settings, a procedure to enter the ADJUSTMENT mode is
required. To enter the ADJUSTMENT mode, press the
UP, DOWN, and I buttons (refer to Fig. 9) simultaneously
for three seconds. Press the I button until the feature
requiring adjustment is displayed:
• HL_ — High Limit.
• Hdf — High Limit Differential.
• LL_ — Low Limit.
• Ldf — Low Limit Differential.
• duu — ZR input configured as external Domestic Hot
Water (DHW) request (ON/OFF)
• ASC — Anti Short-Cycle Timeout (seconds); “OFF” is
disabled.
• otL — Outdoor Temperature Low (minimum)
parameter for the outdoor reset curve (F or C)*
• otH — Outdoor Temperature High (maximum)
parameter for outdoor reset curve (F or C)*
• btL — Boiler Temperature Low (minimum) parameter
for outdoor reset curve*
• bP — Boost Period (minutes). “OFF” is displayed if
Boost is inactive*
• bS — Boost step (F or C) shown only if Boost is active
(bP=ON)*
• UUS — Warm Weather Shutdown Temperature (F or
C)*
• F-C — Temperature units (F or C)
* Settings available for adjustment on the 3-digit display
only if the AquaReset Outdoor Reset Module is installed.
Then press the UP and/or DOWN buttons to move the set
point to the desired value. After 60 seconds without any
button inputs, the controller will automatically return to the
RUN mode.
To use the L7224U in a cold start boiler application,
disable the Low Limit function by pressing the UP arrow
button, DOWN arrow button and I button simultaneously
for three seconds. Then push the I button until LL_ is
displayed. Then press the down arrow button until OFF is
displayed.
Display
In the RUN mode, the Aquastat will flash “bt” (boiler temp)
followed by the temperature (i.e., 220), followed by °F or
°C.
To read boiler settings, press the I key to read the
parameter of interest. For example, press I and HL (High
Limit) is displayed, followed by a three-digit number, i.e.,
220, followed by °F or °C. Pressing the I button again will
display the LL (Low Limit) followed by a three-digit
number and the corresponding degree designator. See
Fig. 7 for explanation of display readout.
After approximately 60 seconds without any key presses,
the display will enter a dim display mode. To return to the
bright display mode, simply press and release any key.
569-1720—03
Page 6
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
Text
Err
bt
HL
HdF
LL
Ldf
tt
ttE
brn
Cir
ZC
Zr
ELL
duu
1
Description
Error Code (if one is present)
Boiler Temperature
High Limit
High Limit Differential
Low Limit (L7224 only)
Low Limit Differential (L7224 only)
Local Thermostat Status
EnviraCOM Thermostat Status
B1 (Burner) output (ON or OFF)
C1 (Circulator) output (ON or OFF)
ZC (Zone Control) output (ON or OFF)
ZR (Zone Request) Call for HEAT (ON or OFF)
External Low Limit Enabled (L7248L only)
ZR Configured as Domestic Hot Water
Request (L7224, L7248L only)
Anti Short-Cycle Timeout
ASC
2
Boiler Setpoint
bSP
3
dhc
DHW Module Connected (YES or NO)
2
ot
Outdoor Temperature
otL
2
Outdoor Temperature Low
otH
Outdoor Temperature High
2
2
btL
Boiler Temperature Low
bP
2
Boost Period
bS
2
Boost Step
2
Warm Weather Shutdown Temperature
UUS
°F
Units are displayed in degrees Fahrenheit
°C
Units are displayed in degrees Celsius
OFF
Input or Output is OFF
Input or Output is ON
On
1
DISPLAY SHOWS LOCAL SETTING; NOT THE SETTING
AS MODIFIED BY AN EXTERNAL ENVIRACOM CONTROL.
2
SETTINGS ARE VIEWABLE ONLY IF THE OUTDOOR
RESET MODULE AND OUTDOOR TEMPERATURE
SENSOR ARE INSTALLED AND FUNCTIONING PROPERLY.
3
SETTINGS ARE VIEWABLE ONLY IF THE DOMESTIC
HOT WATER MODULE AND SENSOR ARE INSTALLED
AND FUNCTIONING PROPERLY.
Fig. 7. Explanation of display readout.
*Settings viewable on the 3-digit display only if the
“Outdoor Reset Module” is installed.
Display
Shows
M29552
Operation
The L7224U can be in any of four operational states:
Normal, High Limit, Low Limit and Error. The controller
moves back and forth from High Limit to Normal to Low
Limit state as part of normal operation. The operating
states are:
1. Normal: Boiler temperature went below the High
Limit setting (minus the Differential) and has not
exceeded the High Limit setting; or, the boiler temperature went above the Low Limit setting and has
not gone below the Low Limit setting (minus the Differential).
2. High Limit: Boiler temperature went above the High
Limit setting and has not dropped below the High
Limit setting (minus the Differential).
3. Low Limit: Boiler temperature went below the Low
Limit setting (minus the Low Limit Differential) and
has not gone above the Low Limit setting.
4. Error: The controller has detected an error condition
(e.g., open sensor) and has shut down the burner
output. The Zone Control (ZC) output is energized.
The controller continues to monitor the system and
automatically restarts if the error condition clears.
Refer to Table 4–6.
The operating sequence for the L7224U is shown in Table
3.
High Limit Controller
The High Limit opens and turns off the burner when the
water temperature reaches the setpoint. The High Limit
automatically resets after the water temperature drops
past the setpoint and through the adjustable Differential.
Low Limit and Circulator Controller
On a temperature rise, the burner circuit breaks and the
circulator circuit makes (assuming no call for heat is
present) at the Low Limit setpoint. On a temperature drop
of 10° F (6° C) below the Low Limit setpoint (with the
adjustable Differential at the minimum setting of 10° F
(6° C)), the burner circuit makes and the circulator circuit
breaks. Refer to Fig. 7.
SWITCH BREAKS ON
TEMPERATURE RISE.
HIGH LIMIT
SETTING
LOW LIMIT
SETTING
WHEN WATER REACHES LOW LIMIT SETTING, THE BURNER SHUTS
1
OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).
10ºF (6ºC)
DIFFERENCE
10ºF (6ºC)
DIFFERENCE
Fig. 8. Setpoints and differentials.
BURNER TURNS OFF.
CIRCULATOR OPERATES
ON A CALL FOR HEAT.
SWITCH MAKES ON
TEMPERATURE FALL.
BURNER OPERATES ON A
CALL FOR HEAT.
WITH NO HEATING
DEMAND, SWITCH BREAKS
ON TEMPERATURE RISE.
SWITCH MAKES ON
TEMPERATURE FALL,
BURNER IS ON TO
MAINTAIN MINIMUM
WATER TEMPERATURE.
CIRCULATOR IS OFF.
M23365
1
69-1720—036
Page 7
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
A
NOTE: Setting the Low Limit above the High Limit less
the High Limit Differential is not allowed as
improper circulator and Zone Control functions
could result.
Anti Short-Cycle Feature
The Anti Short-Cycle feature allows for field selection of a
minimum delay time between burner cycles. Should a call
for heat occur following the end of the previous heat cycle
and before the Anti-Short Cycle delay time is expired, the
circulator will be allowed to run, but the burner will be held
off until the time has elapsed.
NOTE: The Anti Short-Cycle feature is blocked if DHW
demand occurs. DHW demands are serviced
immediately, without any delay.
NOTE: When the Aquastat is connected to the oil pri-
mary and/or thermostat via the EnviraCOM bus,
the Anti Short-Cycle time does not apply to recycle events such as loss of airflow or flame. It
applies only to loss of demand.
ZR-Domestic Hot Water (DHW) Request
The ZR terminal on the L7224U can be selected to
service an indirect water heater heat request. This
parameter is set via the 3 digit display (see Adjusting
Settings section of this document). A heat request via the
ZC terminal will have priority over all other features such
as the Anti-Short Cycle feature or those enabled by the
Outdoor Reset Module (See form69-2235 for more
information).
CHECKOUT
Put the system into operation and observe at least one
complete cycle to make sure that the controller operates
properly. See TROUBLESHOOTING section to use LED
to assist in determining system operation.
TROUBLESHOOTING
When attempting to diagnose system performance,
reference to the LED display can help to identify specific
areas not working properly. The LED display will scroll
Err, followed by a digit (1-8). Refer to Table 7 for a
description of each error and suggested actions and Table
8 for a troubleshooting guide.
Boiler
temperature
drops below
the Low Limit
setting minus
the
differential (if
applicable).
Error
conditions
1-5.
Error
condition 6.
Error
condition 7.
Error
condition 8.
Error
condition 9*.
Error
condition 10*.
Error
condition 11*.
* Error condition only available when the Outdoor Reset
Module is installed.
Circulator starts when water temperature is
above Low Limit setting (if applicable).
Boiler temperature is checked. Burner
starts when water temperature is below
High Limit setting.
If Anti-short Cycle Time is enabled, the
burner does not start until the set Antishort Cycle Time between cycles expires
after the previous call for heat was
satisfied.
Burner is turned off. Burner restarts when
the water temperature drops below the
High Limit setting minus the Differential.
Circulator and burner turn off.
Burner is turned on, Circulator is turned
off. Burner stops when the water
temperature exceeds the Low Limit
setting.
If an error condition is detected, all outputs
except ZC are shut down. Burner is off.
The controller continues to function and
restarts when error is corrected.
During the error check sequence, the
system checks for drift in the sensor and
corrosion in the connections.
EnviraCOM communication is not
available.
The controller has reset the High Limit,
Low Limit and Differential Setting to a
default setting and will continue to run at
those settings. Performance of the system
will be degraded.
If the error condition is detected, all
outputs except ZC are shut down. Burner
is off.The controller continues to function
and restarts when all three user keys have
been pressed longer than 60 seconds.
System continues to run with no outdoor
reset functionality
System continues to run with outdoor reset
parameters enabled as programmed.
Error cleared automatically.
System continues to run with boiler temp
set to High Limit.
Table 4. L7224 Controller Operating Sequence with
multiple zones connected through the ZR terminal
ActionSystem Response
Zone Request (ZR)
terminal is
connected to L1
(Zone calls for
heat).
Boiler temperature
exceeds the High
Limit.
Zone Request input
is de-energized
(Zones are
satisfied).
Boiler temperature
drops below the
Low Limit setting
minus the
differential (if
applicable).
Table 5. Controller Operating Sequence with External
Low Limit device connected trough the ZR terminal.
Boiler temperature is checked.
Burner starts when water
temperature is below High Limit
setting. Anti Short-Cycle Time is
applied, see Table 3.
Burner is turned off. Burner restarts
when the water temperature drops
below the High Limit setting minus
the Differential.
Burner turns off.
Burner turns on and Zone Control
is de-energized. Burner turns off
and Zone Control is re-energized
when the water temperature
exceeds the Low Limit setting.
ActionSystem Response
Zone Request (ZR)
terminal is
connected to L1
(External Low Limit
call for heat).
Boiler temperature
exceeds the High
Limit.
Zone Request input
is de-energized
(External Low Limit
is satisfied).
Table 6. L7224 Controller Operating Sequence with
Domestic Hot Water connected trough the ZR
Boiler temperature is checked.
Burner starts when water
temperature is below High Limit
setting. Circulator turns off.
Burner is turned off. Burner restarts
when the water temperature drops
below the High Limit setting minus
the Differential.
Burner is turned off.
terminal.
ActionSystem Response
Zone Request (ZR)
terminal is connected to
L1 (Domestic Hot Water
calls for heat).
Boiler temperature
exceeds the High Limit.
Zone Request input is
de-energized (Domestic
Hot Water is satisfied).
Boiler temperature is checked.
Burner starts when water
temperature is below High
Limit setting.
Burner is turned off. Burner
restarts when the water
temperature drops below the
High Limit setting minus the
Differential.
Burner is turned off.
69-1720—038
Page 9
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
WARNING
Table 7. LED Error Codes.
Aquastat
Error
CodeCause/Action
EnviraCOM
Alarm
Err1Aquastat sensor fault; check water sensor.18
Err2ECOM fault; check EnviraCOM™ wiring.18
Err3Excessive electrical noise or frequency out of range. Hardware fault; replace controller.18, 58
Err4B1 fault; check B1 wiring/voltage.64
Err5Low Line; check L1-L2, 110 Vac.59
a
Err6
Warning: Fuse; check ECOM wires, replace fuse.92
Err7Warning: EEPROM, HL, LL, Hdf, Ldf; reset to default values.N/A
b
Err 8
Err9
Err 10
Err 11
a
Warnings are generated to enunciate the system is not operating optimally, but the Aquastat is still operating and
maintaining boiler temperature. In the instance where an Outdoor Reset Module is used, the warnings may indicate a
reset curve setting error one or more features is not running optimally, and the Aquastat is reverting to default settings
or has stopped running the Outdoor Reset algorithms. The warnings are cleared when the issue(s) is resolved.
b
To clear Err 8 condition, depress and hold all three user keys simultaneously for 60 seconds. Err 8 condition clears
and display returns to normal. Err 8 condition is designed to catch welded relays on the Aquastat and will normally
only occur near end of life for the control. If Err 8 condition has occurred early in the controls life, be sure to check for
voltage feedback to B1 when B1 should be off and check current draw on b terminal to be sure burner is not drawing
excessive current. Err 8 condition will keep repeating if B1 fault is not cleared.
Repeated B1 fault (voltage present at B1 when output is turned off); check B1 wiring/voltage. 25
a
Warning: Outdoor Reset System failure; communication to Outdoor Reset Module lost,
Outdoor Reset Module failure, multiple outdoor temperature sensors detected on the bus, or
outdoor temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.
a
Warning: Boost Failure; Boost Mode active at least once per cycle for the last 60 consecutive
cycles. Check Outdoor Reset curve settings.
a
DHW Module/Sensor failure; communication to DHW Module lost, DHW Module failure, or
temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.
50, 53, 149
150
146, 147,
148
Electrical Shock Hazard.
Can cause severe injury or death.
All circuits must have a common disconnect to
prevent the possibility of electrical shock.
969-1720—03
Page 10
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
Table 8. Troubleshooting Guidea.
System Condition Diagnostic Condition Check Action
Boiler is cold, house
is cold.
Boiler is hot, house
is cold.
Boiler is hot, no hot
potable water
a
Refer to Fig. 7 for Display and LED locations.
b
ZC LED ON indicates ZC terminal power is OFF.
c
ZC LED OFF indicates ZC terminal power is ON.
Display is OFF.120 Vac system power.Turn system power on.
Display is ON.
TT-LED is OFF.
Display is ON.
TT-LED is OFF.
Display is ON.
TT-LED is ON.
B1 LED is ON.
Display is ON.
TT-LED is ON.
Display is ON.
TT-LED is ON.
C1 LED is ON.
Display is ON.
TT-LED is ON.
C1 LED is OFF.
ZC LED is ON
Display is ON.
TT-LED is ON.
ZC LED is OFF
b
.
c
.
24 Vac T-T.No 24 V; replace controller.
24 V present; disconnect
thermostat, short T-T.
120 Vac at B1-B2.• If no, replace controller.
Boiler starts, check wiring and
thermostat.
• If yes, check burner and
wiring.
Refer to Err on display.—
120 Vac at C1-C2.• 120 Vac at C1-C2, check
Boiler below the Low Limit
temperature, wait for boiler to
go above Low Limit
temperature.
Boiler above LL? If yes, check
for 120 Vac between ZC and
L2.
wiring to pump.
• Wiring ok, is pump running?
If not, replace the pump.
• If pump is running, check for
trapped air or closed zone
valves.
—
• If no 120 Vac, replace
controller.
• If yes, check zone relays,
circulators and wiring.
•
69-1720—0310
Page 11
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
L1
(HOT)
LINE
VOLTAGE
CIRCULATOR
LINE
VOLTAGE
OIL BURNER
RELAY
TO ADDITIONAL R845A
RELAYS FOR OTHER ZONES
1
L2
LOW VOLTAGE
THERMOSTAT
L7248L
SENSOR
ZR
L1
L2
C2
B2
C1
B1
ZC
R845A RELAY ZONE 2
6
5
3
4
1
2
ZONE 2
2
LINE
T
T3
2
1
ZONE 2
CIRCULATOR
LOW VOLTAGE
THERMOSTAT
ENVIRACOM
3
TERMINALS
50022037-002 OUTDOOR
RESET MODULE
1 2 3 OT OT
C7089U OUTDOOR
SENSOR
4
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING
SCREW PROVIDED.
3
ENVIRACOM TERMINALS.
OPTIONAL OUTDOOR RESET MODULE AND OUTDOOR SENSOR SHOWN.
4
M29687
Fig. 10. L7224U multizone system with circulator connections.
1169-1720—03
Page 12
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
1
2
3
TH9421C
R7184
T
LIMIT
T
L1
3
L2
2
1
5
ENVIRACOM™
TERMINAL
TO REMOTE
ALARM
2
CIRCUIT
LEGENDSCREW TERMINAL1/4 IN. (6 MM) QUICK CONNECT TERMINAL
1
2
3
SOLDERLESS WIRE CONNECTION
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
OPTIONAL FEATURE ON SELECT MODELS.
REFER TO DEVICE LABEL FOR WIRE COLOR CODE.
BURNER
MOTOR
IGNITOR
VALV E
CAD
CELL
3
3
3
CAD
CELL
JUNCTION
BOX
BURNER
MOTOR
IGNITOR
VALV E
4
50022037-002
OUTDOOR
RESET MODULE
1 2 3 OT OT
L1
(HOT)
1
LINE
VOLTAGE
CIRCULATOR
6
C7089U
OUTDOOR
SENSOR
2
1
3
L2
L7224
T
T
3
2
SENSOR
ZR
L1
L2
C2
B2
C1
B1
ZC
4
VALVE IS OPTIONAL ON SPECIFIED MODELS.
5
ENVIRACOM™ TERMINAL 3 IS ALSO THE FIRST THERMOSTAT TERMINAL.
6
OPTIONAL OUTDOOR RESET MODULE AND OUTDOOR SENSOR.
1
LINE
M29686
Fig. 11. L7224U multizone system with circulator connections and EnviraCOM™ thermostat.
69-1720—0312
Page 13
MATERIAL SAFETY DATA SHEET
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
Section 1. Product And Company
Identification
Product Name: Heat Conductive Compound
MSDS ID: DS9021
Synonyms: MS1699
Product Use: Heat conductive material used to enhance
contact and heat transfer in temperature sensor
applications.
Manufacturer: Honeywell Inc.
1985 Douglas Drive North
Minneapolis, MN 55422.
Date Released: October 8, 1999
Customer Response Center: 800-328-5111
Emergency Telephone Information: 888-809-3787
NFPA Ratings:
Health 0; Flammability 1; Reactivity 0; Personal
Protection B
Section 2. Composition, Information on
Ingredients
IngredientCAS NumberPercentPELTVL
#2 Lithium Complex Grease (70%):
Mineral Oil64742-65-035-50
Mineral Oil64742-62-720-25
Lithium Hydrostearate/Sebacate
Complex
Zinc Alkyldithiophosphate68649-42-30-2——
Aluminum Paste (30%):
Aluminum, as Al7429-90-520-25
Aliphatic Petroleum Distillates8052-41-310-15
Stearic Acid57-11-41-2——
Aromatic Petroleum Distillates64742-95-61-2
Additional Information: Part No. 120650 (0.5 oz tube); Part No. 107408 (4 oz can); Part No. 197007 (5 gallon
container). May also contain minute amounts of lithium and molybdenum lubricant compounds.
68815-49-64-9——
3
5 mg/m
3
5 mg/m
15 mg/m
2900 mg/m
3
5 mg/m
5 mg/m
5 mg/m
3
10 mg/m
3
525 mg/m
5 mg/m
3
3
3
3
3
Section 3. Hazard Identification
Acute Health Effects:
Skin: Excessive contact may cause skin irritation and
dermatitis.
Eye: Direct contact with eye will cause irritation.
Inhalation: No adverse effects are expected.
Ingestion: Ingestion of product may cause nausea,
vomiting and diarrhea.
Chronic Health Effects:
Existing skin rash or dermatitis may be aggravated by
repeated contact.
OSHA Hazard Classifications: None.
Carcinogenicity: Not considered to be a carcinogen by
either OSHA, NTP, IARC, or ACGIH.
1369-1720—03
Page 14
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
Section 4. First Aid Measures
Eye Contact: Flush eyes with water for 15 minutes.
Remove any contact lenses and continue to flush.
Obtain medical attention if irritation develops and
persists.
Skin Contact: Remove excess with cloth or paper.
Wash thoroughly with mild soap and water. Obtain
medical attention if irritation develops and persists.
Ingestion: Contact physician or local poison control
center immediately.
Inhalation: Remove patient to fresh air and obtain
medical attention if symptoms develop.
Section 5. Fire Fighting Measures
Material Flash Point: > 383° F (195° C). Will burn if
exposed to flame.
Extinguishing Media: Carbon dioxide, dry chemical or
foam.
Special Fire Fighting Procedures: None.
Explosion Hazards: None. Aluminum powder can react
with water to release flammable hydrogen gas. In the
form of this product, this reaction is not expected.
Section 6. Accidental Release Measures
Scrape up and dispose of as solid waste in accordance
with state and federal regulations.
Section 7. Handling and Storage
Store in dry place. Keep container closed when not in
use.
Section 8. Exposure Controls and
Personal Protection
Ventilation: No special ventilation is required when
working with this product.
Respiratory Protection: None required.
Eye Protection: Not normally required. However, use
chemical safety goggles or faceshield if potential for
eye contact exists, especially if material is heated.
Hand/Clothing Protection: Not normally required.
Protective gloves and clothing are recommended, as
material is difficult to remove from skin and clothing.
Other Protective Equipment: None required.
Section 9. Physical and Chemical
Properties
Appearance/Odor: Aluminum color, semi-solid
material, pleasant odor.
Solubility in Water: Negligible.
Specific Gravity: 0.86.
Section 10. Stability and Reactivity
Stability: Stable.
Reactivity: Hazardous polymerization will not occur.
Incompatibilities: Strong oxidizing agents and
halogens.
Chemical Fate Information: Hydrocarbon components
will biodegrade in soil; relatively persistent in water.
Section 13. Disposal Consideration
Dispose of as solid waste in accordance with local,
state and federal regulations.
Section 14. Transportation Information
DOT Classification: Not classified as hazardous.
Section 15. Regulatory Information
SARA Title III Supplier Notification: Include in Section
311/312 inventory reports if amounts exceed 10,000
pounds. Aluminum compounds are subject to the
reporting requirements under Section 313 of
Emergency Planning and Community Right-To-Know
Act of 1986 (40 CFR 372). Ingredients listed in TSCA
Inventory.
Section 16. Other Information
This information is furnished without warranty,
expressed or implied, except that it is accurate to the
best of our knowledge.
69-1720—0314
Page 15
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
1569-1720—03
Page 16
L7224U OIL ELECTRONIC AQUASTAT® CONTROLLER
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée