Honeywell L7224 User Manual

L7224 Series Oil Electronic
Aquastat® Controller
TECHNICIAN’S QUICK REFERENCE GUIDE
The following service procedure provides a quick overview for L7224 Series Controllers. For more information, refer to form 69-1384.

Adjusting Settings

To discourage unauthorized changing of Aquastat® settings, a procedure to enter the adjustment mode is required. To enter the adjustment mode, press the UP, DOWN, and I buttons simultaneously for three seconds. Press the I button until the feature requiring adjustment is displayed:
• HL—High Limit.
• LL—Low Limit.
• Ldf—Low Limit differential.
• F - C—°F or °C.
Then press the UP and/or DOWN buttons to move the set point to the desired value. After 60 seconds without any button inputs, the control will automatically return to the READ mode.
To use the L7224U in a cold start boiler application, disable the Low Limit function by pressing the UP arrow button, DOWN arrow button and I buttons simultaneously for three seconds. Then push the I button until LL is displayed. Then press the down arrow button until OFF is displayed.

Display

In the RUN mode, the Aquastat® will flash “bt” (boiler temp) followed by the temperature (i.e., 220), followed by °F or °C.
To read boiler settings, press the I key to read the parameter of interest. For example, press I (HL) High Limit is displayed, followed by a three-digit number, i.e., 220, followed by °F or °C.
69-1957—1
L7224 SERIES
Pressing the I button again will display the LL (Low Limit) followed by a three-digit number and the corresponding degree designator. See the table below for an explanation of display readout.
After approximately 60 seconds without any key presses, the display will enter a dim display mode. To return to the bright display mode, simply press and release any key.
Display
Text Description
bt
f c
Boiler Temperature
High LimitHL
Low LimitLL
High Limit DifferentialHdf
Low Limit DifferentialLdf
Local Thermostat Statustt
Enviracom Thermostat Statustte
Burner Statusbrn
Circulator Statuscir
Zone ControlZc
Zone RequestZr
Error Codeerr
Degrees Fahrenheit
Degrees Celsius
Shows
M22149
Table 1. LED Error Codes
Error Code Cause/Action
Err1 Sensor fault; check sensor. Err2 ECOM fault; check EnviraCOM. wiring. Err3 Hardware fault; replace control. Err4 B1 fault; check B1 wiring/voltage. Err5 Low Line; Check L1-L2, 110 Vac. Err6 Fuse; Check ECOM wires, Replace fuse. Err7 EEPROM, HL, LL, Hdf, Ldf, Reset to default values. Err8 Repeated B1 fault (voltage present at B1 when
output is turned off); check B1 wiring/voltage.
69-1957—1 2
Loading...
+ 2 hidden pages