Honeywell L7224 User Manual

L7224 Series Oil Electronic
Aquastat® Controller
TECHNICIAN’S QUICK REFERENCE GUIDE
The following service procedure provides a quick overview for L7224 Series Controllers. For more information, refer to form 69-1384.

Adjusting Settings

To discourage unauthorized changing of Aquastat® settings, a procedure to enter the adjustment mode is required. To enter the adjustment mode, press the UP, DOWN, and I buttons simultaneously for three seconds. Press the I button until the feature requiring adjustment is displayed:
• HL—High Limit.
• LL—Low Limit.
• Ldf—Low Limit differential.
• F - C—°F or °C.
Then press the UP and/or DOWN buttons to move the set point to the desired value. After 60 seconds without any button inputs, the control will automatically return to the READ mode.
To use the L7224U in a cold start boiler application, disable the Low Limit function by pressing the UP arrow button, DOWN arrow button and I buttons simultaneously for three seconds. Then push the I button until LL is displayed. Then press the down arrow button until OFF is displayed.

Display

In the RUN mode, the Aquastat® will flash “bt” (boiler temp) followed by the temperature (i.e., 220), followed by °F or °C.
To read boiler settings, press the I key to read the parameter of interest. For example, press I (HL) High Limit is displayed, followed by a three-digit number, i.e., 220, followed by °F or °C.
69-1957—1
L7224 SERIES
Pressing the I button again will display the LL (Low Limit) followed by a three-digit number and the corresponding degree designator. See the table below for an explanation of display readout.
After approximately 60 seconds without any key presses, the display will enter a dim display mode. To return to the bright display mode, simply press and release any key.
Display
Text Description
bt
f c
Boiler Temperature
High LimitHL
Low LimitLL
High Limit DifferentialHdf
Low Limit DifferentialLdf
Local Thermostat Statustt
Enviracom Thermostat Statustte
Burner Statusbrn
Circulator Statuscir
Zone ControlZc
Zone RequestZr
Error Codeerr
Degrees Fahrenheit
Degrees Celsius
Shows
M22149
Table 1. LED Error Codes
Error Code Cause/Action
Err1 Sensor fault; check sensor. Err2 ECOM fault; check EnviraCOM. wiring. Err3 Hardware fault; replace control. Err4 B1 fault; check B1 wiring/voltage. Err5 Low Line; Check L1-L2, 110 Vac. Err6 Fuse; Check ECOM wires, Replace fuse. Err7 EEPROM, HL, LL, Hdf, Ldf, Reset to default values. Err8 Repeated B1 fault (voltage present at B1 when
output is turned off); check B1 wiring/voltage.
69-1957—1 2
L7224 SERIES
Table 2. L7224 Controller Operating Sequence
Action System Response
Thermostat calls for heat.
Circulator starts when water temperature is above Low Limit setting (if applicable). Boiler temperature is checked. Burner starts when water temperature is below High Limit setting.
Boiler exceeds the High Limit.
Thermostat is
Burner is turned off. Burner restarts when the water temperature drops below the High Limit setting minus the differential.
Circulator and burner turn off.
satisfied. Error conditions
1-5.
Error conditions 6-7.
Error condition 8.If the error condition is detected, all outputs
If an error condition is detected, all outputs except ZC are shut down. Burner is off. Control continues to function and restarts when error is corrected. During the error check sequence, the system checks for drift in the sensor and corrosion in the connections.
If error condition 6 or 7 occurs, the control has reset the High Limit, Low Limit and Differential Setting to a default setting and will continue to run at those settings. Performance of the system will be degraded.
except ZC are shut down. Burner is off. Control continues to function and restarts when all three user keys have been pressed longer than 60 seconds.

Troubleshooting

When attempting to diagnose system performance, reference the LED display to help identify specific areas not working properly. The LED display will scroll “err”, followed by a digit (1-8). See Table 1 for a description of the error and suggested actions. See below for a troubleshooting guide.
Table 3. Troubleshooting Guide
System
Condition
Boiler is cold, house is cold
a
. Refer to Fig. 5 for Display and LED locations.
b
. ZC LED ON indicates ZC terminal power is OFF.
c
. ZC LED OFF indicates ZC terminal power is ON.
Diagnostic
Condition Check Action
Display is OFF 120 Vac system
Display is ON; TT-LED is OFF
Display is ON; TT-LED is OFF
power. 24 Vac T-T No 24V; replace
24V present; disconnect thermostat, short T-T
3 69-1957—1
a
.
Turn system power on.
control Boiler starts, check
wiring and thermostat
Table 3. Troubleshooting Guide
System
Condition
Boiler is cold, house is cold
Boiler is hot, house is cold
a
. Refer to Fig. 5 for Display and LED locations.
b
. ZC LED ON indicates ZC terminal power is OFF.
c
. ZC LED OFF indicates ZC terminal power is ON.
Diagnostic
Condition Check Action
Display is ON; TT-LED is ON B1 LED is ON
Display is ON; TT-LED is ON
Display is ON; TT-LED is ON
120 Vac at B1-B2• If no, replace control.
Refer to err on display
120 Vac at C1-C2• 120 Vac at C1-C2,
C1 LED is ON
Display is ON; TT-LED is ON C1 LED is OFF;
ZC LED is ON
Display is ON; TT-LED is ON ZC LED is
c
OFF
Boiler below the Low Limit temperature,
b
wait for boiler to go above Low Limit temperature.
Boiler above LL? If yes, check for 120 Vac between ZC and L2
a
.
If yes, check burner
and wiring
check wiring to pump
Wiring ok, is pump running? If not, replace the pump.
If pump is running, check for trapped air or closed zone valves.
If no 120 Vac, replace control.
If yes, check zone relays, circulators and wiring.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2006 Honeywell International Inc. 69-1957—1 Rev. 06-06
Loading...