Honeywell L7148F1075 User Guide

Page 1
Electronic Aquastat® Controller
L7148F WITH QUICK CONNECTS
(SENSOR NOT INCLUDED)
L7148F WITH PLUG CONNECTIONS
(SENSOR NOT INCLUDED)
L7148F
PRODUCT DATA

FEATURES

• Available with quick connect or AMP® plug connections. T, TV and Z terminals are provided in a terminal block with screw connections.
• Vent damper plug optional.
• Separate high limit control not required.
• Software defined minimum/maximum limit settings.
• External 120 Vac to 24 Vac transformer, ordered separately, is field replaceable and upgradable.
• Patented limit rated 209659A,B,C Sensors are separately replaceable.
• Communications port for future field added advanced feature modules.
• Flush mounted to sheet metal rather than spud mounted to sensing well.
• 3/16 in. (5 mm) B1 quick connect and AMP plug connections meet ANSI miswiring requirements.
• UL353 Limit Controls approval for both U.S. and Canada.
• Meets UL 1998 Software Safety Standards.
• Diagnostic LED to assist in system troubleshooting.
The L7148F Electronic Aquastat® Controller is an immersion type hydronic controller that provides high limit protection and controls circulator, gas valve and optional vent damper equipment. The complete L7148F system requires a sensor, immersion well and transformer, all of which must be ordered separately. See Table 1 for sensor specifications.
An external 120 Vac to 24 Vac transformer is required to power the L7148F. For total external transformer VA requirements, add the 10 VA requirement for the control, gas valve load requirement (connections B1, B2), zone valve connection requirement (see zone valve specifications), vent damper requirement and VA requirement for any other equipment. Total low voltage load must not exceed 4A.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
Contents
General ............................................................................. 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Adjustment ....................................................................... 5
Operation .......................................................................... 5
Checkout .......................................................................... 11
Troubleshooting ................................................................ 11
68- 0189- 2
Page 2
L7148F ELECTRONIC AQUASTAT® CONTROLLER
(

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

Standard Models

Models:
L7148F Electronic Aquastat Controller with quick
connect terminals, with or without vent damper plug and communications port (for adding advanced feature modules).
L7148F Electronic Aquastat Controller with AMP plug
connections, with or without vent damper plug and communications port (for adding advanced feature modules). AMP connector on wiring board for transformer connection.
3/8
10) 4 (102)
4-11/16 (119)
7/16 (11)
4-1/2 (114)
1-3/16
(30)
6
(152)
1/2
(13)
1-5/8
(41)
(16)
M11500
5/8
High Limit Setpoint Range: 130°F to 240°F
(54°C to 116°C). (Select models may be different.)
Differential: Fixed 10°F (6°C). (Select models may
be different.)
Operating Voltage Range:
L1-L2 Line Voltage Power: Nominal, 120 Vac. R-C 24V Transformer Output: Nominal, 24 Vac.
Minimum/Maximum Ambient Temperature:
-30°F (-9°C) with 2.0A 24V load. 150°F (66°C) with 2.0A 24V load.
Operating Relative Humidity: 0 to 95% RH non-condensing.
Electrical Ratings (60 Hz only):
B1-B2: 2.0A at 24 Vac. C1-C2: Full Load 7.4A at 120 Vac; Locked Rotor,
44.4A at 120 Vac.
NOTE: Total Low Voltage load must not exceed 4.0A.
Case Dimensions: See Fig. 1.
ORDERING INFORMATION
Fig. 1. L7148F dimensions in in. (mm).
Mounting: Vestibule mount.
Approvals:
Underwriters Laboratories Inc. Component Recognized:
File No. MP466.
Canadian Underwriters Laboratories Inc. Component
Recognized: File No. MP466.
ANSI Miswiring: 3/16 in. (5 mm) B1 quick connect terminal
and AMP® plug connections meet ANSI Appliance Miswiring Standard.
Material Safety Data Sheets (MSDS): For more information
on heat-conductive compound, see form 69-0955.
Accessories:
107408 Heat Conductive Compound (4 oz. can). For more
information, see form 69-0955, Heat Conductive
Compound. 121371AA Sensor Retaining Clamp. 32002656-001 Sensor Retaining Spring.
Sensor: Sensor available separately. For leadwire lengths
available, see Table 1.
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0189—2 2
Page 3
L7148F ELECTRONIC AQUASTAT® CONTROLLER
Immersion Well: Available separately. Contact your
distributor or Honeywell sales representative to order, or refer to Accessories for Immersion Wells, Compression Fittings, and Element Holders, form 68-0040.
Table 1. Sensor Specifications.
Sensor Termination Lead Length Diameter Capsule Length Mounting Material
32004955-001 One 1/4 in. (6 mm) and one 3/16 in.
(5 mm) quick connect terminal.
32004955-002 18 in. (458 mm),
32004955-003 25 in. (610 mm),
32004955-004 36 in. (914 mm),
32004955-005 48 in. (1219
12 in. (304 mm), 18 gauge wire.
18 gauge wire
18 gauge wire.
18 gauge wire
mm), 18 gauge wire.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard. Can cause property damage, severe injury or death.
Use this product only in systems with a pressure relief valve.
WARNING
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before beginning wiring. Never apply a jumper across (or short) terminals B1 and B2. This will burn out the transformer.
Transfo rmer: Available separately with either quick connect
terminals or AMP plug connections. Contact your distributor or Honeywell sales representative to order.
3/8 in. (10 mm)
1-1/4 in. (32 mm)
Compression Thermal

Mounting

WARNING
Fire or Explosion Hazard. Can cause serious injury, death or property damage.
Sensor must be fully inserted to bottom of well.
IMPORTANT
Sensor and immersion well are not provided and must be purchased separately. Mounting screws must be obtained locally. See Table 1 for sensor specifications. The sensor is adaptable to existing immersion wells with a shell I.D. of 3/8 in. (10 mm). To order an immersion well, contact your distributor or Honeywell sales representative, or refer to Accessories for Immersion Wells, Compression Fittings, and Element Holders, form 68-0040.
In new and replacement applications, mount the Electronic Aquastat Controller on the vestibule away from heated surfaces. Use four no. 6 screws, obtained locally, to mount the control through the four mounting holes.
Mount the immersion well, purchased separately, where boiler water of average temperature can circulate freely around it.
To insert the immersion well into the boiler:
The L7148F is not designed for spud mounting to the sensing well.
1. Turn off all power and drain the boiler.
2. If no tapping is provided, prepare properly sized and
threaded tapping near the top of the boiler.
3. Coat the well threads sparingly with pipe dope, install
the well in the boiler tapping, and tighten securely.
4. Refill the boiler and check for water leakage.
plastic
3 68-0189—2
Page 4
L7148F ELECTRONIC AQUASTAT® CONTROLLER
R
4
IMPORTANT
• Sensor must be fully inserted to bottom of well.
• Remove all heat conductive compound from the well prior to sensor insertion.
5. Insert the sensor into the well. Make sure the sensor fits
securely against the bottom of the well.
To secure sensor and leadwire with mounting clamp (see Fig. 2.):
1. Loosen the draw nut and spread the jaws of the clamp.
2. Slide the jaws of the clamp over the mounting flange.
3. Adjust the sensor leadwire to fit through the groove in
the mounting clamp.
IMPORTANT
Do not overtighten the draw nut or a system shut-down could occur.
4. Tighten the draw nut so that the clamp is firmly attached
to the well and the leadwire is held securely in place.
5. Secure excess leadwire to prevent disconnection of
sensor or removal from the well.
BOTTOM OF WELL
MOUNTING FLANGE

Wiring

WARNING
Electrical shock hazard. Can cause serious injury, death or equipment damage.
Disconnect power supply before beginning wiring.
IMPORTANT
• An external transformer is required for operation. The user must size the transformer for the specific application.
• If L7148F is used to power zone valves, total low voltage (24V) load must not exceed 4A. Use a zoning panel such as the Honeywell R8889 when load exceeds these ratings.
All wiring must comply with local electrical codes and ordinances. Refer to the SPECIFICATIONS section when applying this control. For appropriate wiring diagrams, see Fig. 3 through 10.
For screw terminal connections:
1. Strip 1/16 in. of insulation from the
wire end.
2. Insert the wire under the terminal
screw and contact plate.
3. Using a standard, flat-headed
screwdriver, tighten the screw until the wire is firmly in contact with the screw and contact plate.
4. Tighten the screw an additional
one-half turn.
M1148
SENSO
SENSOR LEADWIRE
JAWS OF CLAMP
CLAMP
MOUNTING FLANGE
TIGHTEN SCREW AND DRAW NUT TO SECURE CLAMP
PLACE
JAWS OF
CLAMP OVER
M11483
Fig. 2. Secure sensor and leadwire with mounting
clamp or spring (see Accessories).
For quick connect terminal connections: Connect the quick connect to the appropriate terminal on the control. B1 and S1 are 3/16 in. (5 mm) quick connect terminals; all other terminals are 1/4 in. (6 mm).
For AMP plug connections: Connect the AMP plugs to the receptacles on the control. An AMP plug connection is shown in Fig. 8.
The L7148F and appropriately sized external transformer can power up to three Honeywell V8043 Zone Valves. Additional valves, in groups of three or less, require an additional transformer, or use Honeywell R8889 Zone Valve Panel. Follow the appropriate wiring diagrams when using zone valves. See Fig. 4, 5, 7, and 9.
On systems requiring a vent damper, the Honeywell vent damper can be connected directly to some L7148F Electronic Aquastat models (Fig. 9) or S8610 Spark Ignition Modules (Fig.8). With the vent damper plugged into the Electronic Aquastat Controller, a fuse in the Electronic Aquastat Controller blows when the thermostat first closes. Once the fuse is blown, the Electronic Aquastat Controller does not operate unless the vent damper is connected. With the vent damper plugged into the S8610, a fuse in the ignition module blows when first powered. Once the fuse is blown, the ignition module does not operate unless the vent damper is connected.
68-0189—2 4
Page 5
L7148F ELECTRONIC AQUASTAT® CONTROLLER
C
L
L

OPERATION

A system containing an L7148F Electronic Aquastat does not require a separate high limit controller. The L7148F can replace a Honeywell L4080 High-Limit Controller and an R8225 Transformer. The L7148F does not provide a low limit function. An external transformer, appropriately sized for the specific application; a sensor, and an immersion well are required for Aquastat¨ operation.
In the L7148F system without an advanced feature module, the circulator is on any time there is a thermostat call for heat. The addition of an advanced feature module may alter operation. The burner is also on during a thermostat call for heat unless the boiler water temperature exceeds the high limit setting.
The L7148F Electronic Aquastat has three states of operation:
2
L1 L2
1
IRCULATOR
DISCONNECT SWITCH
L7148F
CIRC
C2
L1
L2X L1X
4
G
C1
L2X
L1X
L2
3
R C
5
OPTIONAL VENT DAMPER PLUG
4
C
B2
B1
R
R
6
4
COM BURNER CONTRO 24V HOT
TO VALVE OR IGNITION CONTRO
normal, high-limit and reset: (The control moves back and forth between the normal and high-limit states, as needed.
HIGH LIMIT DIAL
However, the control only enters the reset state when there is an abnormal condition such as an internal error or shorted sensor.)
4
COM
DATA PORT
TO ADVANCED FEATURE MODULE
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
GROUND MUST BE AN EARTH GROUND CONNECTION. B1 AND S1 ARE 3/16 IN. QUICK CONNECT TERMINALS.
3
ALL OTHER TERMINALS ARE 1/4 IN. C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
4 5
FOR EXTERNAL TRANSFORMER VA REQUIREMENTS, REFER TO APPLICA TION SECTION.
6
R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS.
4
C
THERMOSTAT
STATUS
W
R
TO BOILER SENSOR
24VCOM
3
S1 S2
TO THERMOSTAT OR SWITCH CLOSURES FOR ZONES
M17967
1. Normal: The control enters the normal state when the
temperature of the boiler drops below the high limit setting minus 10°F (-12°C). The control exits the normal state and returns to the high limit state when the temperature of the boiler exceeds the high limit setting.
2. High limit: The control enters the high limit state when
the temperature of the boiler exceeds the high limit setting. The control exits the high limit state and returns to the normal state when the temperature of the boiler drops to the high limit setting minus 10°F (-12°C).
3. Reset: Detects an error condition such as an open
sensor and shuts down all outputs. The control continues to function and automatically restarts if the error condition is corrected.

High Limit

The high-limit switch shuts off the burner (B1, B2 output) when the boiler water temperature exceeds the high-limit setting. Because heating systems differ, the correct temperature setting for each system can vary. Follow the boiler manufacturer recommendations for the proper setting. Turn
Fig. 3. External connections for L7148F.
the HIGH-LIMIT dial on the control until the desired setting is directly below the indicator.

ADJUSTMENT

A manual adjustment potentiometer is used to set the high limit controller. At the maximum setpoint of 240°F (116°C), the calibration tolerance is plus 10°F (6°C) and minus 15°F (8°C). (Meets ASME and UL353 Standards).
(Select models available with other ranges.)
NOTE: Setpoint Range: 130°F (54°C) to 240°F (116°C).
Differential: Fixed at 10°F (6°C).

Sequence of Operations

The state of the burner and circulator outputs are dependent on the thermostat input mode (On/Off) and the current operation mode (High limit/Normal/Reset). See Table 2 Sequence of Operations.
NOTE: Table 2 applies only to the operation of the Electronic
Aquastat Controller without an advanced feature module. Advanced feature modules provide additional functions such as boiler temperature display and outdoor reset of high limit. Changes in output states and operation modes caused by these additional functions are not included.
5 68-0189—2
Page 6
L7148F ELECTRONIC AQUASTAT® CONTROLLER
.
L L
Table 2. Sequence of Operation
Operation
Thermostat
Mode Burner Circulator
Off Normal Off Off
Off High Limit Off Off
On Normal On On
On High Limit Off On
Either Reset Off Off
L2X
L2X
L1X
6
L1X
5
C
W
2
1 2
1
DISCONNECT SWITCH
L7148F
C2
L1
HIGH LIMIT DIAL
6
DATA PORT
TO ADVANCED FEATURE MODULE
6 6
G
C1
L2
COM
THERMOSTAT
STATUS
R C
4
OPTIONAL VENT DAMPER PLUG
6
C
B2
B1
R
R
7
5
S1 S2
R
TO BOILER SENSOR
COM BURNER CONTROL 24V HOT
TO V ALVE OR IGNITION CONTROL
V8043F
END SWITCH
TH-TR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
GROUND MUST BE AN EARTH GROUND CONNECTION. ADD JUMPER AS SHOWN.
3
FOR EXTERNAL TRANSFORMER VA REQUIREMENTS,
4
REFER TO APPLICATION SECTION.
5
B1 AND S1 ARE 3/16 INCH. QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1/4 INCH.
6
C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
7
R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS.
T87F ZONE 1
TH
TR
3
T87F ZONE 2
V8043F
END SWITCH
TH-TR
V8043F
END SWITCH
TH-TR
TH
TR
3
T87F ZONE 3
TH
TR
3
4
1
L2
M11475B
24VCOM
(HOT)
L1
Fig. 4. Wiring L7148F with multizone valves.
68-0189—2 6
Page 7
L7148F ELECTRONIC AQUASTAT® CONTROLLER
L
L7148F
T87F R845 RELAY
TT
4
C1
C2
COM
6
5
PUMP PUMP
2
4 4
G
L2X
L1X
L2
4
C
THERMOSTAT
STATUS
1
23
PUMP
DISCONNECT
SWITCH
L1
1
2
L7148F
L1
HIGH LIMIT DIAL
4
1
2 3
4 5
6
DATA PORT
TO ADVANCED FEATURE MODULE
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
GROUND MUST BE AN EARTH GROUND CONNECTION. B1 AND S1 ARE 3/16 INCH QUICK CONNECT TERMINALS. ALL OTHER
TERMINALS ARE 1/4 INCH. C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE. FOR EXTERNAL TRANSFORMER VA REQUIREMENTS, REFER TO
APPLICATION SECTION. R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR
USE WITH IGNITION CONTROLS.
TT
1
23
L2X L1X
W
3
24VCOM
T87F
R845
4
6
5
R C
5
OPTIONAL VENT DAMPER PLUG
4
C
B2 B1
R
R
6
3
S1 S2
R
TO BOILER SENSOR
TT
1
23
LOW VOLTAGE GAS VALVE (VR8300)
CIRCULATOR
TR
TH
T87F
THTR
4
M11477B
5
R845
6
R
W
C
4
L2X
L1X
C
4
R
3
B2
4
B1
R
6
C1
C2
L1
L2
2
G
4
S1
3
S2
1
24V
DATA
COM
4
Fig. 6. Wiring L7148F in multizone system
TO ADDITIONAL R845A RELAYS FOR OTHER ZONES
5
TR
THTR
TH
LOW VOLTAGE GAS VALVE (VR8300)
L1 (HOT)
1
1
L2
2
TO BOILER SENSOR
TO ADVANCED FEATURE MODULE
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
GROUND MUST BE AN EARTH GROUND CONNECTION.
3
B1 AND S1 ARE 3/16 INCH QUICK CONNECT TERMINALS. ALL OTHER TERMINALS ARE 1/4 INCH.
4
C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
5
FOR EXTERNAL TRANSFORMER VA REQUIREMENTS, REFER TO APPLICATION SECTION.
6
R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS.
R845A RELAY ZONE 1
6
5
4
3
1
2
CIRCULATOR ZONE 1
with R845 Switched Circulator.
24V THERMOSTAT
M11481B
Fig. 5. Wiring L7148F in a gas-fired, forced hot
water, tankless, zoned, pump system.
7 68-0189—2
Page 8
L7148F ELECTRONIC AQUASTAT® CONTROLLER
.
C
.
C
2
L1 L2
1
IRCULATOR
DISCONNECT SWITCH
L7148F
C2
L1
HIGH LIMIT DIAL
5
DATA PORT
TO ADVANCED FEATURE MODULE
5 5
G
C1
L2X
L1X
L2
COM
5
C
STATUS
THERMOSTAT
W
Fig. 7. Typical three-wire zone valve hookup diagram.
L2X
L1X
3
OPTIONAL VENT DAMPER PLUG
5
B2 B1
4
R
6
4
S1 S2
R
TO BOILER SENSOR
R C
C R
COM BURNER CONTROL 24V HOT
TO V ALVE OR IGNITION CONTROL
T87 ZONE 1
T87 ZONE2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
GROUND MUST BE AN EARTH GROUND CONNECTION. FOR EXTERNAL TRANSFORMER VA REQUIREMENTS,
3
REFER TO APPLICATION SECTION.
4
B1 AND S1 ARE 3/16 INCH. QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1/4 INCH.
C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
5
R IS A CONVENIENCE TERMINAL FOR 24V HOT
6
CONNECTION FOR USE WITH IGNITION CONTROLS.
3
2
1
T87 ZONE 3
3 2
1
3 2
1
120V
(HOT)
L1
L2
1
T87
ZONE 4
3 2
1
M17972
L2X
L2X
L1X
6
L1X
5
C
W
2
L1 L2
1
IRCULATOR
DISCONNECT SWITCH
L7148F
C2
L1
HIGH LIMIT DIAL
6
DATA PORT
TO ADVANCED FEATURE MODULE
6 6
G
C1
L2
COM
THERMOSTAT
STATUS
R C
4
OPTIONAL VENT DAMPER PLUG
6
C
B2 B1
R
R
6
5
S1 S2
R
TO BOILER SENSOR
24VCOM
S8610
MV MV/PV PV
THERMOSTAT
VENT DAMPER PLUG
GND (BURNER)
VR8304
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
GROUND MUST BE AN EARTH GROUND CONNECTION. B1 AND S1 ARE 3/16 INCH QUICK CONNECT TERMINALS
3
ALL OTHER TERMINALS ARE 1/4 INCH. C, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
4 5
FOR EXTERNAL TRANSFORMER VA REQUIREMENTS, REFER TO APPLICA TION SECTION.
R IS A CONVENIENCE TERMINAL FOR 24V HOT
6
CONNECTION FOR USE WITH IGNITION CONTROLS.
PV PV
MV MV
24V GND
24V TH-W
SPARK
M11478B
Fig. 8. Wiring L7148F with S8610 Intermittent Pilot Ignition Module with automatic
vent damper plug and Honeywell D892/D896/M892/M896 Vent Damper.
68-0189—2 8
Page 9
L7148F ELECTRONIC AQUASTAT® CONTROLLER
S8600
24V GND
DISCONNECT SWITCH
L1
1
L2
CIRCULATOR
24V
L2X L1X
8
R C
4
D892/D896/M892/M896
4
3
2
1
POLARIZED 4-PRONG MALE MOLEX PLUG AND 4-PRONG FEMALE MATING PLUG ON CABLE
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
REMOVE PLUG-IN THAT JUMPERS PINS 2 AND 3 WHEN USING VENT DAMPER. AFTER VENT DAMPER IS PLUGGED INTO L7148F, FUSE BLOWS WHEN THERMOSTAT FIRST
3
CLOSES. AFTER FUSE BLOWS, L7148F OPERATES ONLY WHEN VENT DAMPER IS CONNECTED.
4
SEE VENT DAMPER PRODUCT SPECIFICATIONS FOR INTERNAL SCHEMATICS.
5
S1 IS A 3/16 INCH QUICK CONNECT TERMINAL; S2 IS 1/4 INCH.
6
THIS DEVICE HAS AMP© PLUGS.
7
C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
8
FOR EXTERNAL TRANSFORMER VA REQUIREMENTS, REFER TO APPLICATION SECTION.
CABLE
L7148F
4
2
2
FUSE
3
3
5
1
6-PRONG FEMALE MOLEX RECEPTACLE IN L7148F AND 5-PRONG MALE MOLEX PLUG ON CABLE
6
C1
C2
L1
L2
HIGH LIMIT DIAL
7
COM
DATA PORT
STATUS
TO ADVANCED FEATURE MODULE
7
G
L2X
L1X
HIGH LIMIT CONTACTS
7
C
THERMOSTAT
W
6
7 7
B2 B1
R
3
5
S1 S2
R
TO BOILER SENSOR
24VCOM
THERMOSTAT
C R
6
M11480B
Fig. 9. Wiring L7148F with AMP plug connections and internal plug directly to
D892/D896/M892/M896 Vent Damper in hydronic intermittent pilot system.
9 68-0189—2
Page 10
L7148F ELECTRONIC AQUASTAT® CONTROLLER
V
C
L7148F
R
W
C
6
L2X
L1X
C
6
R
TO
ALVE OR
IGNITION
ONTROL
7
6
5
6
B1
6
B2
R
C1
C2
L1
L2
G
S1
S2
24V
DATA
COM
3
5
L1 (HOT)
1
L2
2
TO BOILER SENSOR
TO ADVANCED FEATURE MODULE
T87F
ZONE 1
R882C
N.O. N.C. COM.
N.O. N.C. COM.
BW
W
CIRCULATOR ZONE 1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
GROUND MUST BE AN EARTH GROUND CONNECTION. FOR EXTERNAL TRANSFORMER VA REQUIREMENTS,
3
REFER TO APPLICA TION SECTION.
4
R882C IS PROVIDED WITH NEC CLASS 1 ENCLOSURE.
5
B1 AND S1 ARE 3/16 INCH QUICK CONNECT TERMINALS. ALL OTHER TERMINALS ARE 1/4 INCH.
C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
6
R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION
7
FOR USE WITH IGNITION CONTROLS.
T87F
ZONE 2
R882C
N.O. N.C. COM.
N.O. N.C. COM.
BW
CIRCULATOR ZONE 2
T87F
ZONE 3
R882C
N.O. N.C. COM.
N.O. N.C. COM.
B
3 4
CIRCULATOR ZONE 3
4
M11482B
Fig. 10. Multizone system with R882C Switched Circulator.
68-0189—2 10
Page 11
L7148F ELECTRONIC AQUASTAT® CONTROLLER
24VCOM
C
2
L1 L2
1
IRCULATOR
DISCONNECT SWITCH
L7148F
C2
L1
HIGH LIMIT DIAL
6
DATA PORT
TO ADVANCED FEATURE MODULE
6 6
G
C1
L2X
L1X
L2
COM
6
C
THERMOSTAT
STATUS
L2X
L1X
OPTIONAL VENT DAMPER PLUG
6
B2 B1
5
R
6
5
R
W
TO BOILER SENSOR
R
C
4
C R
S1 S2
TO THERMOSTAT OR SWITCH CLOSURES FOR ZONES
PILOT BURNER GROUND (THROUGH PILOT TUBING)
1
2 3
4 5
6
SV9501/SV9502; SV9601/SV9602
24 VOLT COMMON
24 VOLT THERMOSTAT OR PRESSURE SWITCH
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
GROUND MUST BE AN EARTH GROUND CONNECTION. B1 AND S1 ARE 3/16 INCH QUICK CONNECT TERMINALS.
ALL OTHER TERMINALS ARE 1/4 INCH. C, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE. FOR EXTERNAL TRANSFORMER VA REQUIREMENTS,
REFER TO APPLICA TION SECTION. R IS A CONVENIENCE TERMINAL FOR 24V HOT
CONNECTION FOR USE WITH IGNITION CONTROLS.
24 VOLT HOT
EFT OUTPUT
M11479B
Fig. 11. Wiring L7148F with SV9501/SV9502/SV9601/SV9602 SmartValve™ System Controls.

CHECKOUT

Check to make certain that the Electronic Aquastat Controller has been properly installed and adjusted. Put the system into operation and observe the action of the device through several cycles to make certain that it provides proper control

TROUBLESHOOTING

When attempting to diagnose system performance, reference to the diagnostic LED can help to identify specific areas not working properly. Table 3 shows the LED codes. Fig. 12 provides a troubleshooting chart.
of the system as described in the Operation section.
Table 3. LED Codes.
Number of Blinks Indication
Constant On Power on—normal operation.
2 Sensor error—check connection
and/or replace sensor.
3 or 4 L7148F failures—replace control
11 68-0189—2
Page 12
L7148F ELECTRONIC AQUASTAT® CONTROLLER
START
BOILER IS COLD. BOILER IS NOT REACHING PROPER
TEMPERATURE OR WILL NOT TURN ON.
CHECK: L7148F DIAGNOSTIC LED ON?
YES
SET ROOM THERMOSTAT AT 10 DEGREES ABOVE ROOM TEMPERATURE.
SET BOILER 10 DEGREES (OR MORE) ABOVE CURRENT WATER TEMPERATURE.
BOILER TURNS ON?
YES
CHECK: CIRCULATOR PUMP RUNNING?
YES
BOILER SHUTS OFF AT HIGH LIMIT SETTING?
NO
BOILER SHUTS OFF ABOVE HIGH LIMIT SETTING?
NO (BELOW HIGH LIMIT)
NO
CHECK FOR 120 VAC AT L1X, L2X. CHECK FOR 24 VAC AT R, C.
NO
SHORT TERMINALS W-R (T-TW) ON L7148F. BOILER STARTS?
CHECK: L7148F DIAGNOSTIC LED FLASHING?
NO
L7148F IN RESET MODE (WAIT FIVE
CHECK:
MINUTES FOR CONTROL TO RESET). VENT DAMPER OPEN?
NO
120 VAC AT C1, C2?
YES
L7148F IS OKAY. CHECK OTHER SYSTEM COMPONENTS: CIRCULATOR. ZONE VALVES.
YES
CHECK:
TRIADICATOR ACCURACY. SENSOR FULLY INSERTED INTO WELL. THERMO WELL IN GOOD CONDITION. THERMO WELL LOCATED PER BOILER OEM INSTRUCTIONS.
NO
TURN POWER ON; CHECK ALL WIRING CONNECTIONS; REPLACE TRANSFORMER AS APPROPRIATE.
YES
THERMOSTAT OR THERMOSTAT WIRING PROBLEM. CHECK SYSTEM PER INSTRUCTIONS PROVIDED WITH THERMOSTAT.
YES
TWO BLINKS: CHECK SENSOR CONNECTIONS. IF GOOD, REPLACE SENSOR. THREE OR FOUR BLINKS: INTERNAL ERROR, REPLACE L7148F.
YES
CHECK FOR 24V AT B1, B2.
NO
CHECK VENT DAMPER CABLE AND CONNECTIONS. REPLACE VENT DAMPER CABLE OR DAMPER AS APPROPRIATE.
CHECK:
NO
REPLACE L7148F.
ROOM THERMOSTAT STILL SET 10 DEGREES ABOVE CURRENT ROOM TEMPERA TURE?
YES
L7148F IS OKAY. CHECK IGNITION AND GAS VALVE SYSTEM AS DESCRIBED IN LITERATURE PROVIDED WITH THOSE PRODUCTS.
RESET THERMOST AT AND REPEA T VOLTA GE CHECK.
YES
NO
CHECK: L7148F DIAGNOSTIC LED FLASHING?
NO
YES
TWO BLINKS: REPLACE SENSOR. THREE OR FOUR BLINKS: REPLACE L7148F.
TRIADICATOR ACCURACY.
CHECK:
THERMO WELL LOCATED PER BOILER OEM INSTRUCTIONS.
M20069
Fig. 12. L7148F troubleshooting flowchart.
Home and Building Control Home and Building Control Honeywell International Honeywell Europe S.A. Honeywell Latin American
Honeywell Honeywell Limited-Honeywell Limitée Home and Building Control 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley, MN 55422 Scarborough, Ontario 17 Changi Business Park Central 1 Belgium Suite 200
68-0189—2 G.R. Rev. 10-01 www.honeywell.com
M1V 4Z9 Singapore 486073 Sunrise FL 33325
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Loading...