Honeywell L6007, L6008, L6006, L4007, L4008 User Manual

L4006,7,8; L6006,7,8 Aquastat® Controllers
FOR VERTICAL MOUNTING AND HORIZONTAL SENSOR INSERTION
FOR SURFACE MOUNTING

GENERAL

WITH REMOTE BULB
PRODUCT DATA

FEATURES

• L4006, 7, and 8 provide Spst switching for high or low limit or circulator control.
• L4006G includes two Spst switches that provide high limit and circulator control.
• L4006,7; L6006,7 models are available for insertion in: vertical or horizontal immersion well, vertical or horizontal direct immersion, and surface mounting.
• L4008, L6008 include remote bulb for mounting controller at a location away from the sensing element.
• Totally enclosed Micro Switch™ snap-acting switches operate on temperature rise to set point.
• Models calibrated for high limit use are also suitable for low limit control if a separate high limit controller is used.
• Visible control point scale and external adjustment screw, permit easy setting.
• Remote bulb models may be used to sense air temperature in ducts and in outside air sensing applications.
Aquastat® Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required.
Contents
General ............................................................................. 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 8
Operation .......................................................................... 14
Adjustments ...................................................................... 15
Checkout .......................................................................... 17
Material Safety Data Sheet .............................................. 18
60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

SUPER TRADELINE®/TRADELINE MODELS

SUPER TRADELINE controls offer features not available on TRADELINE or standard models, and are designed to replace a wide range of Honeywell and competitive controls.
TRADELINE models are selected and packaged to provide ease of stocking, ease of handling, and maximum replacement value. Specifications of SUPER TRADELINE and TRADELINE controls are the same as those of standard models except as noted below.
SUPER TRADELINE Model: L6006A Aquastat Controller.
SUPER TRADELINE Features:
SUPER TRADELINE package with cross reference label and
special instructions. Factory-set stop at 240° F (116° C). Vertical or horizontal mount. Tube of heat-conductive compound. Insulation: 1-1/2 in. to 3 in. (38 mm to 76 mm).
TRADELINE Models: L4006A,B,E; L4008E; L6006C;
L6008A Aquastat Controllers.
TRADELINE Features Available:
TRADELINE package with cross reference label and special
instructions. Some TRADELINE models include immersion well. Factory-set stops at 180° F, 240° F, or 250° F (82° C, 116° C,
or 121° C). Vertical or horizontal mount. Tube of heat-conductive compound. Insulation depths of 1-1/2 in. or 3 in. (38 or 76 mm).
NOTE: The following specifications are standard. Variances,
available as options, are listed in Tables 1 and 2.
Electrical Ratings (A):
Models with 2° F (1° C) fixed differential:
120 Vac 240 Vac
Full Load 2.6 1.3
Locked Rotor 15.6 7.8
Models with 5° F (3° C) fixed differential or 5° F to 30° F (3° C to 17° C) adjustable differential:
110/120 Vac 200/240 Vac 277 Vac
Full Load 8.0 5.1 4.2
Locked Rotor 48.0 30.6 25.2
Millivoltage 0.25 at 0.25 to 12 Vdc
a
L6008G only.
Switching:
L4006, L4007, L4008: Spst. L6006, L6007, L6008: Spdt (breaks R-B and makes R-W on
temperature rise at setpoint).
Pressure Rating:
Capillary Bulb (Direct Immersion): 200 psi (1379 kPa). Immersion Well: 255 psi (1758 kPa).
Sensing Bulb Material: Copper.
Sensing Bulb Fill: Liquid—toluene or silicone oil.
Sensing Bulb Dimensions: 2-7/8 in. (73 mm) long,
3/8 in. (10 mm) diameter.
Wiring: Screw terminals.
Maximum Ambient Temperature: 150° F (66° C).
a
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2104—10 2
Catalog or price sheets for complete ordering number.
1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
Approvals:
Underwriters Laboratories Inc: Remote bulb devices and well-mounted devices shipped
without well are component recognized: File No. MP466, Guide No. MBPR2.
L4006A shipped with well, L4006G, L4007A,B; L6006C for
surface mounting, L6006B for direct immersion mounting,
and L6007A are listed: File No. MP466, Guide No. MBPR. L6008G is listed: File No. E4436, Guide No. XAPX. Canadian Standards Association: File No. LR1620,
Guide No. 400-E-O.
ANSI Miswiring: Models with 1/4 in. (6.35 mm) tab terminal
meet ANSI Appliance Miswiring Standard.
Mounting:
Horizontal and vertical models mount directly to an immersion
well installed in a boiler fitting. L4006H and L6006C contain
a bracket and clamp for surface mounting on the pipe or
tank. Remote bulb models have three mounting holes
in rear of case for screw mounting to a vertical surface.
The L6006B direct immersion model also mounts directly to
a boiler fitting.
Finish: Gray.
Dimensions:
Installation: (See Figures 1, 2, and 3). Immersion Well: (See Fig. 4). Boiler Fitting and Bulb: (See Fig. 5).
Accessories and Parts:
137536A Scale Lock Assembly: Includes one 137536-767
Scale Lock and one 80844C-767 Screw, No. 3-48 x 3/16
(5 mm). Q615A1004 Weatherproof Enclosure (for remote bulb devices
only). 107408 Heat-Conductive Compound (4-oz. can). 104488 Spring Clip (stainless steel). 124904 Well Adapter. Immersion Well Assemblies and Compression Fittings:
See form no. 68-0040, Wells and Fittings for Temperature
Controllers, for list and ordering information.
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
1 (25)
5/16
(8)
2 (51)
5-5/8 (136)
1-7/8
(48)
KNOCKOUT FOR 3/4 (19) CONDUIT ON VERTICAL INSERTION MODELS ONLY
ELEMENT FOR HORIZONTAL IMMERSION
KNOCKOUT FOR 3/4 (19 ) CONDUIT ON ALL MODELS. SIMILAR KNOCKOUT ON BOTTOM FOR HORIZONTAL INSERTION AND REMOTE BULB MODELS.
2-1/8 (54)
3/4
(19)
3/16
(5)
RESET BUTTON (L4006E,
L4008E
ONLY)
ELEMENT FOR VERTICAL IMMERSION
11/16
(18)
M8957A
Fig. 1. Approximate case installation dimensions
in inches (mm) for direct insertion models.
ALTERNATE POSITION OF SENSING ELEMENT CAPILLARY
3/4 (19)
4-3/16
3/8 (10)
SENSING ELEMENT CAPILLARY
(106)
15/16
(24)
1-1/4
(32)
MOUNTING HOLE FOR 3/16 IN. (5 MM) SCREW (3)
13/64 (5) (3)
ALTERNATE POSITION OF SENSING ELEMENT CAPILLARY
M8823
Fig. 2. Approximate installation dimensions
in inches (mm) for remote bulb models. Other
dimensions are the same as Fig. 1.
3 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
2 (51)
2-3/4 (70)
7/8 IN. (22 MM) STANDARD KNOCKOUT (2)
C
L
2 (51)
1
(25)
5-5/8 (136)
M8958A
1/2 — 14 IN. NPT
7/16 (11)
3 (76)1-1/2 (38)
M8789A
Fig. 4. Approximate immersion well dimensions in inches
(mm) for all models except L4006C and L6006B.
1/2 OR 3/4 — 14 IN. NPT
3/8
(10)
1-5/16 (33)
3 (76)
M8799A
Fig. 5. Approximate boiler fitting and bulb dimensions
in inches (mm) for L4006C and L6006B.
Fig. 3. Approximate installation dimensions
in inches (mm) for surface mount models.
60-2104—10 4
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
Standard Models:
L4006,A,B,C,E,G; L4007,A,B; L4008A,B.E; L6006A,B,C; L6007A, L6008,A,G,H
Table 1. L4006, L4007, L4008 Controller (SPST Switching) Specifications.
Switching On
Temperature
a
Rise Available Options
available.
— NPT brass spud 1/2 in. or
3/4 in. (13 mm to 19 mm)
— Special capillary assembly.
Model Application
L4006A High or low
limit
Range °F (°C)
40° F to 180° F (4° C to 82° C) or 100° F to 240° F (38° C to 116° C)
Midscale
Differential
°F (°C) Insertion
2° F or 5° F fixed (1° C or 3° C) or 5° F to 30° F adjustable (3° C to 17° C)
Horizontal Breaks — TRADELINE models
— Insertion 3-3/8 in. or
5 in. (86 or 127 mm) — Celsius scale markings. — Factory-set stops at 160°,
180°, 185°, 200°, 220°, or
230° F (71°, 82°, 85°, 93°,
104°, or 110° C). — Insulation depths of
1-1/2 in. , 3 in. or 4 in.
(38 mm, 76 mm, or
102 mm). — Screw and mounting
brackets. — Plastic tubing over well. — Modified dial with stop. — Special cover and knobs. — With ground screw.
L4006B Circulator 100° F to 240° F
(38° C to 116° C)
5° F (3° C) fixed or 5° F to 30° F (3° C to 17° C) adjustable
Horizontal Makes — TRADELINE model
available. — Insulation depth 1-1/2 in. or
3 in.
(38 mm or 76 mm). — NPT brass spud 3/4 in.
(19 mm) — Screw in front of case on
dial suitable for
Powerpile
control.
— Factory-set stop at
240° F (116° C).
L4006C High or low
limit
65° F to 200° F (18° C to 93° C)
3-1/2° F (2° C) fixed
Horizontal direct immersion
Breaks — TRADELINE model
available. — Less cover. — Capillary 10 in.
(254 mm). — NPT brass spud 3/4 in.
(19 mm).
L4006E
High limit 130° F to 290° F
(54° C to 141° C)
Manual reset Horizontal or
vertical
Breaks — TRADELINE model
available.
b
— Insulation depth
1-1/2 in. or 3 in.
(38 or 76 mm). — NPT brass spud 1/2 in. (13
mm) — Factory-set stop at
250° F (121° C). — Capillary 8 in. (203 mm).
a
Some models include copper well or fitting; specify when ordering. Also specify boiler tapping size 1/2 or 3/4 in. (13 to 19 mm) NPT and insulation depth.
b
Manual reset (trip-free) switch breaks circuit and locks out when controlled medium reaches setpoint. Controlled temperature
must drop 20° F (11° C) below setpoint before contacts can be manually reset.
5 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
Table 1. L4006, L4007, L4008 Controller (SPST Switching) Specifications. (Cont.)
Model Application
L4006G High limit
and circulator control
Range °F (°C)
100° F to 200° F (38° C to 93° C)
Midscale
Differential
°F (°C) Insertion
10° F (6° C) fixed Horizontal Two switches
Switching On
Temperature
a
break simultaneously
Rise Available Options
— External adjustment knob. — Insulation depth 4 in.
(102 mm).
— Factory-set stop at
160° F (71° C). — Celsius scale markings. — Without well.
L4007A High or low
limit
100° F to 240° F (38° C to 116° C)
2° F or 5° F (1° C or 3° C) fixed,
Horizontal or vertical
Breaks — Insulation depth
1-1/2 in. or 3 in.
(38 mm or 76 mm).
5° F to 30° F (3° C to 17° C) adjustable
L4007B Circulator 100° F to 240° F
(38° C to 116° C)
5° F (3° C) fixed or
Vertical Makes — Celsius scale markings.
5° F to 30° F (3° C to 17° C) adjustable
L4008A High or low
limit
100° F to 240° F (38° C to 116° C) or 130° F to 270° F (54° C to 132° C)
5° F (3° C) fixed, 5° F to 30° F (3° C to 17° C) adjustable
Remote bulb direct immersion
Breaks — Remote capillary
5-1/2 ft (1.7 m),
8-1/2 ft (2.6 m) or
10 ft (3.0 m). — Factory-set scale stops at
120°, 170°, or 200° F (49°,
77°, or 93° C) — Celsius scale markings. — Front cover screw.
L4008B Circulator 100° F to 240° F
(38° C to 116° C)
5° F (3° C) fixed or 5° F to 30° F
Remote bulb direct immersion
Makes — Capillary 5-1/2 ft
(1.7 m).
(3° C to 17° C) adjustable
L4008E
High limit 40° F to 80° F
(4° C to 27° C) or 130° F to 270° F (54° C to 132° C)
Manual reset Remote bulb Breaks — Factory-set scale stops at
140°, 200°, or 250° F (60°,
93°, or 121° C). — Capillary 5-1/2 ft or
b
20 ft (1.7m or 6.1 m).
a
Some models include copper well or fitting; specify when ordering. Also specify boiler tapping size 1/2 or 3/4 in. (13 to 19 mm) NPT and insulation depth.
b
Manual reset (trip-free) switch breaks circuit and locks out when controlled medium reaches setpoint. Controlled temperature
must drop 20° F (11° C) below setpoint before contacts can be manually reset.
60-2104—10 6
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
Table 2. L6006, L6007, L6008 Controller (SPDT Switching) Specifications.
Midscale
Differential
°F (°C) Insertion
5° F (3° C) fixed
Horizontal — SUPER TRADELINE model or 5° F to 30° F (3° C to 17° C) adjustable
a
Available Options
available. — Modified dial with stop. — NPT brass spud 1/2 in. or 3/4
in. (13 mm to 19 mm)
Model Application
L6006A Circulator and low
limit or high limit
Range °F (°C)
100° F to 240° F (38° C to 116° C) or 100° F to 290° F (38° C to 143° C)
— 3-3/8 in. (86 mm) insertion. — Without well. — Adapter for horizontal or
vertical mount. — Insulation depth 1-1/2 in. or
3 in. (38 mm or 76 mm).
L6006B Circulator and low
limit or high limit
100° F to 240° F (38° C to 116° C)
5° F (3° C) fixed or 5° F to 30° F (3° C to 17° C) adjustable, or
Horizontal — Direct immersion.
— Insulation depth 1-1/2 in.
(38 mm). — 3/4 in. (19 mm ) brass
compression fitting.
30° F (17° C) fixed.
L6006C Circulator, low limit,
and high limit
65° F to 200° F (18° C to 93° C)
5° F (3° C) fixed or 5° F to 30° F
Horizontal or vertical surface mounted
— TRADELINE model available. — Strap-on, surface mount.
(3° C to 17° C) adjustable
L6007A Circulator and low
limit or high limit
L6008A Circulator and low
limit cooling
L6008G Two-stage Aquastat
Controller to cycle two-stage gas valve.
L6008H (maximum
Low fire Aquastat Controller
40° F to 180° F (4° C to 82° C)
100° F to 240° F (38° C to 116° C) or
-30° F to +70° F (-35° C to +21° C)
130° F to 230° F (54° C to 110° C) or 60° F to 160° F (16° C to 71° C)
150° F to 200° F (66° C to 93° C)
Fixed Horizontal or
vertical
5° F (3° C) fixed
Remote bulb — TRADELINE models or 5° F to 30° F (3° C to 17° C) adjustable
3-1/2° F (2° C)
Remote bulb — Capillary 6 ft (1.8 m). fixed
15° F (8° C)
Remote bulb — Capillary 33 in. (0.8 m). fixed
— Insulation depth 1-1/2 in. or 3
in. (38 mm or 76 mm).
available. — Modified dial with stop. — Capillary 5-1/2 ft (1.7 m).
— Adjustable interstage
differential; 5° F to 10° F
(2° C to 6° C).
temperature of element 405° F (207° C))
a
Some models include copper well or fitting; specify when ordering. Also specify boiler tapping size 1/2 or 3/4 in. NPT and
insulation depth.
7 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS

INSTALLATION

When Installing This Product…

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check product operation as provided in these instructions.
WARNING
Explosion Hazard. Can cause serious injury, death or property damage.
This product is intended for use only in systems with a pressure relief valve.
WARNING
Electrical Shock Hazard. Can cause serious injury or death.
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
CAUTION
Equipment Damage Hazard. Use of incorrect device or improper installation can damage the system.
1. Do not replace immersion-type Aquastat Controller with strap-on Aquastat Controller.
2. Do not secure draw nut so tightly that retainer clamp can collapse tubing.
IMPORTANT
1. Terminals on these Aquastat relays are approved for copper wire only.
2. Controller may be used with or without immersion well. If used, well must snugly fit sensing bulb for best thermal response. Insert bulb until it rests against the bottom of the well. Use well of correct length and bend the tubing, if necessary, to provide enough force to hold the bulb against the bottom of the well. Avoid making a sharp bend in the tubing as it can produce a break in the tubing and cause loss of fill. This condition causes the High and Low Limit controls to be made continuously.
3. If well does not snugly fit on bulb, use the heat­conductive compound, included with Super Tradeline and Tradeline models, as follows: Fold the plastic bag of compound lengthwise and twist gently. Snip the end of the bag and insert into the well. Slowly pull out the bag while squeezing firmly to distribute compound evenly in the well. Insert the bulb into the well. Bend the tubing, if necessary, to provide force to hold the bulb against the bottom of the well and to hold the outer end of the bulb firmly in contact with the side of the well. Wipe off excess compound.
The manufacturer usually provides a tapping for insertion of the controller sensing element. This tapping is located at a point where typical water temperature can be measured. Depending on the model, the element is inserted in an immersion well, through a boiler fitting, or directly immersed.
Installation should be made by a qualified service technician. Follow the instructions furnished by the system manufacturer, if available. Otherwise, refer to appropriate procedure listed below.

Mounting Immersion Well and Direct Immersion Models (L4006A,B,C,E,G; L4007A,B; L6006A,B; L6007A)

Installing Immersion Well Models (L4006A,B,E,G; L4007A,B; L6006A; L6007A)
On an existing installation, shut off the power and remove the old control. If the old immersion well appears suitable, and if the adapter clamp on the Aquastat Controller fits the old well spud, this well does not need to be replaced.
To replace the well:
1. If the system is filled, drain the system to a point below the boiler tapping.
2. Remove the old well from the boiler tapping.
3. Install the immersion well included with the controller. If
the boiler tapping is greater than 1/2 in. (13 mm), use a reduction fitting to adapt the boiler opening to the 1/2 in. (13 mm) threads that are standard with the well or fitting. Fittings with 3/4 in. (19 mm) threads are also available.
4. Fill the system. Make sure that the well is screwed in tightly enough to prevent leakage. Do not use the case as a handle to tighten the well after the controller is secured to the well.
To install the controller:
1. Loosen the screw (at the top of the case, above the scale setting), and remove the cover. Loosen the two screws that secure the adapter clamp. (See Fig. 6).
2. Insert the sensing element into the immersion well.
3. Fasten the case of the Aquastat Controller to the well
with the adapter clamp. Make certain that the clamp is properly positioned over the groove of the well spud. Also, be sure the flange at the opening of the well fits snugly into the opening of the case. The sensing bulb must bottom in the well.
NOTE: Some models include up to 3 in. (76 mm) extra capil-
lary tubing inside the case. In these models, pull out the extra tubing, if needed.
60-2104—10 8
M8806A
A
SETPOINT INDICATING DIAL
DIFFERENTIAL ADJUSTMENT WHEEL
ADAPTER CLAMP SCREWS
INSERTION ELEMENT
2
1
WITH VERTICAL MOUNTING OF IMMERSION WELL, ELEMENT IS ATTACHED TO BOTTOM OF THE CASE.
SELECT MODELS HAVE SCREW
2
TERMINAL, NOT TAB TERMINAL.
Fig. 6. Internal view of L6006A.
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
2. Insert the immersion sensing bulb through the bulb compression fitting. Adjust the adapter clamp so that the clamp fits over the groove at the opening of the bulb compression fitting.
3. Tighten the adapter clamp screws so that the Aquastat Controller is firmly attached to the bulb compression fitting.

Mounting Remote Bulb Models (L4008A,B,E; L6008A,G,H)

1
The remote temperature-sensing bulb can either be installed in an immersion well (See Fig. 8) that extends into the boiler or tank, or it can be directly immersed in the controlled medium (See Fig. 9). For installations that do not use a well, secure the remote bulb with a bulb compression fitting (See Fig. 10), or capillary compression fitting. (See Fig. 11).
Order well, well adapter, bulb compression fitting or capillary compression fitting separately. See form no. 68-0040, Wells and Fittings for Temperature Controllers. If used, well must snugly fit sensing bulb for the best thermal response. Insert bulb until it rests against the bottom of the well. Hold it there while tightening the tubing clamp. (See Fig. 8).
Installing Direct Immersion Models (L4006C, L6006B)
Models that provide for direct immersion of the sensing element into the boiler include a bulb compression fitting assembly instead of an immersion well. Install the fitting in the boiler tapping as follows:
1. Be sure the sealing washer is in place as shown in Fig. 7. Make sure that the spud of the bulb compression fitting is screwed in tightly enough to prevent leaking.
The boiler manufacturer usually provides a tapping for the insertion of the Aquastat Controller sensing element. This tapping should be located at a point where typical water temperature can be measured. Never locate the bulb or protecting immersion well close to a hot or cold water inlet or a steam coil.
If the system is filled, drain system to a point below the boiler tapping, or wherever the sensing bulb is to be installed.
The bulb can also be installed in the supply line of an indirect water heater, in the direct water heater itself, or in the feed riser, about 6 in. (153 mm) above the boiler. If the riser is valved, the bulb can be installed between the boiler and the valve.
ADAPTER CLAMP
NOTE: Do not make sharp bends or kinks in the capillary.
Make bends no sharper than 1 in. (25 mm) radius.
After installing the controller, carefully coil the excess capillary
SPLIT SLEEVE
DAPTER CLAMPS FIT OVER GROOVE
at the bottom of the controller case.

Mounting Immersion Well

1. Screw the well into the boiler, tank, or pipe tapping.
2. Insert the bulb in the well, pushing the tubing until the
bulb bottoms in the well.
3. Attach the retainer clamp to the end of the well spud.
SEALING WASHER
Loosen the draw nut and spread the jaws of the clamp with the screwdriver if necessary. (See Fig. 8).
4. With the retainer clamp attached to the well spud (be sure the jaws of the clamp hook over the ridge at the end
BULB COMPRESSION
SENSING BULB
FITTING
M8774A
Fig. 7. Direct immersion model
with fitting partially removed.
of the spud, as shown at points A in Fig. 8), adjust the tubing to fit through the retainer clamp groove, as shown at point B in Fig. 8.
5. Tighten the draw nut so that the retainer clamp is firmly attached to the well spud and the tubing is held securely in place.
9 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
DRAW NUT
B
TUBING
NOTCHES FOR CAPILLARY TUBE (4)
7/8 IN. (22 MM) DIAMETER KNOCKOUT BOTH ENDS
JAWS
SPREAD JAWS TO FIT OVER RIDGE ON WELL SPUD
SCREWDRIVER
MOUNTING CLAMP
MOUNTING CLAMP
A
SPUD
Fig. 8. Immersion well fitting.
220
200
240
180
0
16
100
140
120
1
BULB
WELL
M8777A
27-1/2 IN. (70 MM) SENSOR
CLAMP B
CLAMP A
SPLIT SLEEVE
CLAMP SCREWS (2)
BULB COMPRESSION FITTING
INSERTION LENGTH APPROX. 3-3/16 IN. (81 MM)
SEALING WASHER
BULB
M8815A
Fig. 10. Bulb compression fitting.
Use with L4006A,B; L6008A.
5. Place clamps A and B on the assembly so that the
sleeve is drawn into the fitting when the screws are tightened.
NOTE: Make sure that the nub on clamp A engages the
space between the sleeve and the clamp.
6. Tighten the clamp screws evenly.

Mounting With Capillary Compression Fitting

1. Screw the fitting into the boiler or pipe tapping.
2. Place the packing nut on the tubing.
3. Slide the bulb completely through the fitting.
4. Place the composition disk and four slotted brass
washers on the tubing in the order shown in Fig. 11. Turn the brass washers so the slots are 180 degrees apart.
IMMERSION BULB
BOILER PLUG
CAPILLARY TUBING
LEFT SNAP SWITCH (NO. 2)
RIGHT SNAP SWITCH (NO. 1)
SELECT MODELS HAVE SIX TERMINALS.
1
10 FT. (3.0 M) CAPILLARY TUBE
MOUNTING HOLES (3)
Fig. 9. Internal view of L4008L or L6008G.

Mounting With Bulb Compression Fitting

1. Screw the fitting into the boiler or pipe tapping.
2. Slide the sealing washer onto the bulb.
3. Insert the bulb into the fitting until the bulb bottoms.
4. Slide the split sleeve into the fitting. (See Fig. 10).
M4673A
COMPOSITION DISK (SLOTTED)
EXAMPLE OF SLOTTED WASHERS ASSEMBLED
PACKING NUT
IN PAIRS:
M8816A
Fig. 11. Capillary compression fitting. Use with L4008.
5. Slide the seal assembly into the fitting and tighten the
packing nut.

Duct Mounting

1. Drill a 3/4 in. (19 mm) hole in the duct wall large enough to admit the sensing bulb into the holder.
2. Using the holder as a template, mark and drill holes for the bulb holder mounting screws. (See Fig. 12).
60-2104—10 10
M8970A
Fig. 12. Bulb support.
3. Break the holder to the desired length. (See Fig. 13).
NOTE: The holder must be long enough to hold the sensing
bulb in freely circulating air away from the duct wall. Neatly coil the excess capillary at the controller case or at the bulb holder.
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS

Mounting Remote Bulb Models For Outdoor Air Sensing

These models have a 5 ft (1.5 m) capillary that establishes the maximum distance between the case and the outdoor mounting.
Install the bulb on the outside of the building in the shield provided (See Fig. 15) where it can be exposed to representative air temperature, but not to direct sunlight. Mount the bulb high enough so that accumulated snow, leaves, or other debris cannot obstruct circulation of air around it, and where children cannot reach it. Avoid vents from the building.
Install the case at the indoor location selected, fastening the screws through holes in the back of the case. Bring out the bulb and tubing through a 3/4 in. (19 mm) hole in the outside wall, avoiding sharp bends or kinks. Leave excess tubing coiled near the case. Do not make sharp bends near the case or bulb.
Slip the bulb through the supports in the shield. Pinch the split supporting clip until it holds the bulb firmly in position. If the seal-off tube protrudes from under the shield, bend it under as shown in Fig. 15.
M7216A
Fig. 13. Removing excess bulb support.
PINCH TOP EDGES OF HOLDER TOGETHER AT EACH SEGMENT
CAPILLARY TUBING
SENSING BULB
BE SURE EXTENSION TUBE IS UNDER BULB HOLDER, AS SHOWN
M7217A
Fig. 14. Securing capillary in bulb holder.
4. Place the capillary in the bulb holder channel. Pinch the
top edges of the holder together at each segment. (See Fig. 14).
5. Insert the bulb holder into the controlled area through the hole prepared in step 1.
6. Fasten the bulb holder to the duct wall with the screws provided.
Hold the shield over the mounting position and form a small­radius bend in the tubing. Place the split plug around the tubing and move the shield into the mounting location as a unit. Push the split plug into the hole until it is wedged securely in place. Fasten the shield in place on the wall with the screws provided.
NOTE: If the tubing is properly shaped and the split plug
installed as directed, the shield will cover the split plug, and the hole in the wall will be hidden from sight.
SPLIT WOOD PLUG
INSERT BULB IN CLAMP
OUTDOOR SENSING BULB
34886A BULB SHIELD
SEAL-OFF TUBE
3/4 IN. (19 MM) HOLE IN WALL
CAPILLARY TUBING
M8800A
Fig. 15. Mounting bulb in shield outside building.

Mounting L6008A Remote Bulb Controller

Mounting with Guard Bracket
Mount the bulb in the guard bracket as shown in Fig. 16. Locate the bulb and bracket combination, in freely circulating air, in the controlled area. With screws provided, fasten the bracket in place.
11 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
A
Mounting on Suction Line
1. In cooling units with more than one suction line, place the sensing bulb on the common line.
2. Make certain the bulb is at least 2 ft (0.6 m) from the point at which the suction line leaves the cooler. This prevents the outside temperature from being transmitted to the remote bulb through the copper tubing of the suction line.
3. Place the remote sensing bulb on the side of the horizontal suction line between the coil and trap (not on the trap).
4. Attach the sensing bulb to the suction line with clips or straps. (See Fig. 17).
5. Coil the excess length of capillary tubing near the L6008A case.
SUPPORTING CLIP
SENSOR
M8791A

Wiring

Disconnect power supply before beginning installation to prevent electrical shock or equipment damage.
All wiring must comply with local codes and ordinances regarding wire size, type of insulation, enclosure, etc.
Figures 19 through 28 show typical hookups.
When wiring a switch equipped with a 1/4 in. (19 mm) tab terminal connector, use 18 AWG to 22 AWG (0.8 mm
0.3 mm
2
) gauge wire with an AMP Inc. part no. 2-520129-2
fully insulated flag receptable connector or equivalent.
ENCLOSED SENSING BULB
PIPE
12 IN.
DJUSTABLE PIPE STRAP
2
to
MOUNTING BRACKET
Fig. 16. Securing remote bulb in clip
when mounting with guard bracket.
SUCTION LINE
COOLER WALL
COIL
L6008A CIRCULATOR LOW LIMIT CONTROLLER
CAPILLARY
Fig. 17. Attaching remote bulb to horizontal suction line.
REMOTE BULB

Mounting Surface Mount Models

The L4006H and L6006C are designed for surface mounting on piping or tanks. Mount the controller directly on the tank surface using the adjustable mounting bracket as shown in Fig. 18. The controller can be mounted in any position.
When mounting the L4006H or L6006C on piping, the pipe should be 1 in. (25 mm) diameter or larger for accurate temperature sensing. Remove any insulation from the pipe. Thoroughly scrape off all scale, rust, or paint. Mount the
LEAVES COOLER
SUCTION LINE
BULB CLIPS TO SUCTION LINE
M8805A
AQUASTAT CONTROLLER CASE
®
M8771B
Fig. 18. Mounting L4006H or L6006C directly on surface.
24 VOLT THERMOSTAT
LOW WATER CUTOFF
2
L4006A OR L4007A LOW LIMIT AQUASTAT CONTROLLER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
USE L4006E FOR MANUAL RESET.
2
GAS
®
VALV E
PRESSURE CONTROL
PILOTSTAT CONTROL
L1 (HOT)
L2
M2856B
1
Fig. 19. Typical gas-fired system with domestic hot water.
controller using adjustable bracket provided. Turn on power.
60-2104—10 12
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
PROTECTORELAY
CONTROL
24 VOLT THERMOSTAT
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
L4006A OR L4007A HIGH LIMIT CONTROLLER
2
4
3
T
T
IGNITION
BURNER MOTOR
Fig. 20. Typical oil-fired gravity system.
R
B
INDICATING
W
L6008A CIRCULATOR AND LOW LIMIT CONTROLLER
LIGHT
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
COOLING EQUIPMENT
Fig. 21. L6008A used to control cooling
equipment and indicating light.
PROTECTORELAY CONTROL
IGNITION
BURNER MOTOR
LINE VOLTAGE LOW VOLTAGE
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
L6006C USED AS HIGH LIMIT CONTROL.
3
L6006C USED AS AN OPERATING CONTROL.
4
R-B OPENS, R-W CLOSES ON TEMPERATURE RISE.
1
2
4
3
T
T
HIGH LIMIT CONTROLLER
CIRCULATOR AND LOW LIMIT CONTROL
2
W
R
B
24V THERMOSTAT
SWITCHING RELAY
3 4
CIRCULATOR
L1 (HOT)
1
L2
OIL VALVE (IF USED)
M1054B
L1 (HOT)
1
L2
M8780A
L1 (HOT)
L2
1
M8960B
24 VOLT THERMOSTAT
RA832A SWITCHING RELAY
TT
XX
2
L4006A OR L4007A LOW LIMIT AQUASTAT CONTROLLER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
USE L4006E FOR MANUAL RESET.
2
1
4
L4006B OR L4007B CIRCULATOR AQUASTAT CONTROLLER
®
®
1
L1
L2
(HOT)
CIRCULATOR
PROTECTORELAY CONTROL
L4006A OR L4007A HIGH LIMIT AQUASTAT CONTROLLER
®
IGNITION
BURNER
1
2
4
3
T
T
M2855B
Fig. 23. Typical oil-fired hydronic heating system that
provides year-round domestic hot water using RA832A.
24V THERMOSTAT
RA89A RELAY
2
13
CIRCULATOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
SELECT MODELS HAVE 1/4 IN. (6) TAB TERMINAL FOR W TERMINAL.
2
L6008A CIRCULATOR LOW LIMIT CONTROLLER
4
W
L4008A OR E HIGH LIMIT CONTROLLER
R
B
RA817A PROTECTORELAY CONTROL
1
L1
L2
(HOT)
T
1
2
IGNITION TRANSFORMER
BURNER MOTOR
T
3
4
M8785B
Fig. 24. Typical connection diagram for an oil-fired,
hydronic heating system that provides year-round
domestic hot water using RA817A.
Fig. 22. Typical oil-fired hydronic
system with domestic hot water.
13 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
L1
L2
(HOT)
1
L6006
CIRCULATOR
LOW LIMIT
CONTROL
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
2
WHEN USING CIRCULATOR LOW LIMIT CONTROL, REMOVE L1-L2 JUMPER.
R
AND
W
B
LOW VOLTAGE LINE VOLTAGE
PILOTSTAT
L1
3
B
R
C1
CIRCULATOR
LINE VOLTAGE GAS CONTROL
L2
2
L8148A
C2 B1 B2
THERMOSTAT
T
T
1
12212
OIL BURNER RELAY LINE VOLTAGE TERMINALS
SERIES 80
M8783C
L4006
HIGH LIMIT
CONTROLLER
MILLIVOLTAGE THERMOSTAT
MILLIVOLTAGE
SAFETY SHUTOFF PILOTSTAT¨ POWER UNIT
VALVE OPERATOR
OPERATOR COIL
POWER UNIT COIL
PILOT BURNER
M1156A
Fig. 27. Typical Powerpile System wiring diagram.
HEATING LOAD
NO. 1
L6008G
WW
JUMPER
HEATING LOAD
NO. 2
BB
RR
21
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
L2
L1 (HOT)
M8968B
1
Fig. 28. Typical oil burner installation using L4008G.
Fig. 25. Typical wiring hookup using L6006 or
L6007 with L8148A.
LINE VOLTAGE CONTROL CIRCUIT
L1 (HOT)
1
L2
LOW VOLTAGE CONTROL CIRCUIT
L1 (HOT)
1
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
1
AND OVERLOAD PROTECTION AS REQUIRED.
L4006
L4006
LINE VOLT THERMOSTAT
LOW VOLTAGE THERMOSTAT
1K
ELECTRIC HEAT RELAY
LOAD
LOAD
M1155A
Fig. 26. Typical systems with 120 volt
electric heat primaries.

OPERATION

For proper selection of settings, follow the boiler manufacturer recommendations.

High Limit Controller

R-B terminals provide high limit switching function (contacts open at set point on temperature rise). (See Figures 30 and 31). R-B terminals shut off burner if water temperature exceeds high limit setting. Burner restarts when temperature drops to high limit setting, less differential.
NOTE: On manual reset models, the reset button on the front
of the case must be pushed in to allow the burner to operate after a high limit shutdown.
60-2104—10 14
BREAKS R-B MAKES R-W
2
2
ON RISE
BREAKS R-W MAKES R-B ON FALL
BREAKS R-B MAKES R-W ON RISE
BREAKS R-W MAKES R-B ON FALL
INTERSTAGE DIFFERENTIAL
TEMPERATURE RISE
SETPOINT (ADJUSTABLE)
1
DIFFERENCE BETWEEN THE TEMPERATURES AT WHICH THE TWO SWITCHES MAKE R-W. ADJUSTABLE FROM 3°F TO 10°F (1.7°C TO 5.6°C) ON STANDARD MODELS, OR FROM 3.6°F TO 12°F (2.0°C TO 6.7°C); 55°F TO 175°F (13°C TO 79°C) MODELS.
2
TWO SPDT SWITCHES OPERATE IN SEQUENCE. EACH SWITCH DIFFERENTIAL IS FIXED AT APPROXIMATELY 3°F (1.7°C) ON STANDARD MODELS, OR AT 3.6°F (2.0°C); 55°F TO 175°F (13°C TO 79°C) MODELS.
LEFT SWITCH DIFFERENTIAL
RIGHT SWITCH DIFFERENTIAL
Fig. 29. Operation of L6008G.
BREAKS ON RISE
2
MAKES ON FALL
TEMPERATURE RISE
LEFT SWITCH DIFFERENTIAL
1
M2999B
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS

Low Limit Controller

R-B terminals provide low limit switching function (contacts open at set point on temperature rise). Maintains minimum boiler temperature for domestic hot water. Turns on boiler at temperature setting, less differential.

Circulator Controller

R-W terminals provide circulation control function (contacts close at set point on temperature rise). Prevents circulation of water that is below the desired heating temperature. Breaks circulator circuit on temperature drop below setting less differential; remakes on rise to setting.

L6008G Adjustable Interstage Differential

When the temperature at the sensing element rises above the set point of the controller, the switch on the right makes R-W. If the temperature continues to rise through the preselected interstage differential of the controller, the switch on the left makes R-W.
Conversely, on a temperature fall, the switch on the left makes R-B, providing first step switching. If the temperature continues to fall, the switch on the right makes R-B to provide sequencing of equipment.

ADJUSTMENTS

Adjusting Differential

Set the differential to correspond with the boiler manufacturer recommendations. To adjust models with adjustable differential, rotate the wheel on the back of the snap switch, (See Fig. 32), until the desired reading is aligned with the V notch in the frame. The wheel provides an adjustment from 5° F to 30° F (3° C to 17° C). Replace the cover on the Aquastat Controller.
SETPOINT (ADJUSTABLE)
1
DIFFERENCE BETWEEN THE TEMPERATURES AT WHICH THE TWO SWITCHES BREAK ON TEMPERATURE RISE.
SWITCHES OPERATE IN SEQUENCE. RIGHT SWITCH
2
FIRST-ON TEMPERATURE RISE.
RIGHT SWITCH DIFFERENTIAL
BREAKS ON RISE
2
MAKES ON FALL
Fig. 30. Operation of L4008L.
INTERSTAGE DIFFERENTIAL
1
M4671A
DIFFERENTIAL WHEEL
1
1
SELECT MODELS HAVE A SCREW TERMINAL INSTEAD OF TAB TERMINAL.
NOTCH IN FRAME
SNAP SWITCH
M8969
Fig. 31. Adjusting the differential.
15 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS
Adjust the control point to correspond with the boiler manufacturer recommendations. To adjust, insert a screwdriver in the slotted screw type head located beneath the window in the cover. Turn the scale to the desired control point.

Adjusting L6008G Interstage Differential

The L6008G Controller has an adjustable interstage differential. The set point adjustment knob determines the temperature at which the right switch operates. The left switch can be adjusted to operate from 3° F to 10° F (1.7° C to 5.6° C) above the point of operation of the right switch. See Figure 30 for the operation of the L6008G. The interstage differential is adjusted by turning the star wheel with a narrow screwdriver inserted into the rectangular hole in the chassis. (See Fig. 32).
LEFT SWITCH
RIGHT SWITCH
M8972
STAR WHEEL (INTERSTAGE DIFFERENTIAL ADJUSTMENT)
1
SELECT MODELS HAVE FOUR TERMINALS.
1
Fig. 32. Interstage differential adjustment on an L6008G.

L6008A Location Differential Calibration

The L6008A1093 is calibrated for applications where the bulb and controller case are located in the same control space.
If the bulb and controller case are located in separate rooms, and if the temperature in the two rooms is different, an adjustment is required. Adjust the dial setting (control space temperature setting) to compensate for the difference in temperature.
1. If the L6008A case is located in a room with a higher temperature than indicated on the dial setting, raise the dial setting the number of degrees listed in Table 3.
2. If the L6008A case is located in a room with a lower temperature than indicated on the dial setting, lower the dial setting the number of degrees listed in Table 3.
Table 3. Temperature Adjustments.
Difference Between Desired
Room Temperature and
Case Temperature Reduce Dial Setting
°F °C °F °C
00—0
533/40.5
10 6 1-1/2 1
15 8 2 1
20 11 2-3/4 2
25 14 3-1/2 2
30 17 4-1/4 3
35 20 5 3
40 22 5-3/4 4
45 25 6-1/2 4
50 28 7 4
55 31 8 5
60 33 8-1/2 5
70 39 10 6
80 45 11-1/2 7
EXAMPLE:
In the example shown in Fig. 33, the L6008A case is located in a room with a lower temperature than the controlled space. Adjusting the controlled space setting (dial setting) is necessary to compensate for the temperature difference of 35° F (20° C) between the two rooms. Table 3 indicates that the dial setting should be lowered 5° F (3° C) to compensate for the 35° F (20° C) temperature difference.

Manual Reset

If the device includes manual reset (L4006E, L4008E), be sure to press the (red) reset button on the front of the case to make sure that the controller is not locked out on safety. When checking the system, adjust the limit setting low enough so the temperature of the controlled medium reaches the high limit setting. When the limit setting is reached, the Aquastat Controller locks out and the burner shuts down. When the temperature of the controlled medium drops to the high limit setting, less the differential, push the manual reset button to make the system operative again. Reset the control to the proper high limit setting.
60-2104—10 16
WALL
REMOTE SENSING BULB
CONTROLLED SPACE TEMPERATURE
o
F (46oC)
115
ROOM TEMPERATURE
o
F (27oC)
80
L6008A CASE
Fig. 33. L6008A calibration.
M8790A
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS

CHECKOUT

WARNING
Explosion Hazard. Can cause serious injury, death or property damage.
This product is intended for use only in systems with a pressure relief valve.
Check to make certain that the Aquastat Controller is properly installed and adjusted. Put the system into operation and observe the action of the controller through several cycles to make certain it provides proper control of the system as described in the OPERATION section. Make any additional adjustments necessary for assuring comfort requirements.
17 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS

MATERIAL SAFETY DATA SHEET

Section 1. Product And Company
Manufacturer: Honeywell Inc., 1985 Douglas Drive North, Minneapolis, MN 55422.
Identification
Product Name: Heat Conductive Compound
MSDS ID: DS9021
Synonyms: MS1699
Product Use: Heat conductive material used to enhance contact and heat transfer in temperature sensor applications.
Ingredient CAS Number Percent PEL TVL
#2 Lithium Complex Grease (70%):
Mineral Oil 64742-65-0 35-50
Mineral Oil 64742-62-7 20-25
Lithium Hydrostearate/Sebacate Complex
Zinc Alkyldithiophosphate 68649-42-3 0-2
Aluminum Paste (30%):
Aluminum, as Al 7429-90-5 20-25
Aliphatic Petroleum Distillates 8052-41-3 10-15
Stearic Acid 57-11-4 1-2
Aromatic Petroleum Distillates 64742-95-6 1-2
Additional Information: Part No. 120650 (0.5 oz tube); Part No. 107408 (4 oz can); Part No. 197007 (5 gallon container). May also
contain minute amounts of lithium and molybdenum lubricant compounds.
68815-49-6 4-9
Date Released: October 8, 1999
NFPA Ratings: Health 0; Flammability 1; Reactivity 0; Personal Protection B

Section 2. Composition, Information on Ingredients

3
5 mg/m
3
5 mg/m
15 mg/m
2900 mg/m
5 mg/m
3
3
3
3
5 mg/m
3
5 mg/m
10 mg/m
525 mg/m
3
5 mg/m
3
3

Section 3. Hazard Identification

Acute Health Effects:
Skin: Excessive contact may cause skin irritation and dermatitis.
Eye: Direct contact with eye will cause irritation.
Inhalation: No adverse effects are expected.
Ingestion: Ingestion of product may cause nausea, vomiting and diarrhea.
Chronic Health Effects:
Existing skin rash or dermatitis may be aggravated by repeated contact.
OSHA Hazard Classifications: None.
Carcinogenicity: Not considered to be a carcinogen by either OSHA, NTP, IARC, or ACGIH.

Section 4. First Aid Measures

Eye Contact: Flush eyes with water for 15 minutes. Remove any contact lenses and continue to flush. Obtain medical attention if irritation develops and persists.
Skin Contact: Remove excess with cloth or paper. Wash thoroughly with mild soap and water. Obtain medical attention if irritation develops and persists.
Ingestion: Contact physician or local poison control center immediately.
Inhalation: Remove patient to fresh air and obtain medical attention if symptoms develop.

Section 5. Fire Fighting Measures

Material Flash Point: > 383° F (195° C). Will burn if exposed to flame.
Extinguishing Media: Carbon dioxide, dry chemical or foam.
Special Fire Fighting Procedures: None.
Explosion Hazards: None. Aluminum powder can react with water to release flammable hydrogen gas. In this form of the product, this reaction is not expected.
60-2104—10 18
L4006,7,8; L6006,7,8 AQUASTAT® CONTROLLERS

Section 6. Accidental Release Measures

Scrape up and dispose of as solid waste in accordance with state and federal regulations.

Section 7. Handling and Storage

Store in dry place. Keep container closed when not in use.

Section 8. Exposure Controls and Personal Protection.

Ventilation: No special ventilation is required when working with this product.
Respiratory Protection: None required.
Eye Protection: Not normally required. However, use chemical safety goggles or faceshield if potential for eye contact exists, especially if material is heated.
Hand/Clothing Protection: Not normally required. Protective gloves and clothing are recommended, as material is difficult to remove from skin and clothing.
Other Protective Equipment: None required.

Section 9. Physical and Chemical Properties

Appearance/Odor: Aluminum color, semi-solid material, pleasant odor.
Solubility in Water: Negligible.
Reactivity: Hazardous polymerization will not occur.
Incompatibilities: Strong oxidizing agents and halogens.
Hazardous Decomposition Products: Carbon dioxide, carbon monoxide.

Section 11. Toxicology Information.

No data available.

Section 12. Ecological Information

Chemical Fate Information: Hydrocarbon components will biodegrade in soil; relatively persistent in water.

Section 13. Disposal Consideration

Dispose of as solid waste in accordance with local, state and federal regulations.

Section 14. Transportation Information

DOT Classification: Not classified as hazardous.

Section 15. Regulatory Information

SARA Title III Supplier Notification: Include in Section 311/312 inventory reports if amounts exceed 10,000 pounds. Aluminum compounds are subject to the reporting requirements under Section 313 of Emergency Planning and Community Right-To-Know Act of 1986 (40 CFR 372). Ingredients listed in TSCA Inventory.
Specific Gravity: 0.86.

Section 10. Stability and Reactivity

Stability: Stable.

Section 16. Other Information

This information is furnished without warranty, expressed or implied, except that it is accurate to the best of our knowledge.
19 60-2104—10
L4006,7,8; L6006,7,8 AQUASTAT
CONTROLLERS
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2006 Honeywell International Inc. 60-2104—10 J.I. Rev. 12-06