Honeywell Hm506h8908, Hm512, Hm509 Service Manual

69-2144-03
3 Failure to
4 Heating
5 Input voltage
TROUBLESHOOTING
Fault Description
ll tank with
water.
element overheated.
insufcient.
Steps to Fix To be Performed by Professional HVAC Technician Only
• Ensure inlet water is on.
• Check for leaks around the tank seal and solenoid valve.
• Turn off water supply and replace in-line water filter.
• Press/hold RESET button until the red Call Service light turns off.
• If tank still fails to fill, press and hold the EMPTY button for 3 seconds (if unit fails to drain, unplug unit and make sure water in tank is cool).
• Follow tank cleaning instructions in the Professional Installation Guide. Ensure you have a firm grip of the tank prior to releasing the tank, especially if water is present.
• Clear any excess debris from the tank’s bottom orifice to the solenoid valve.
• Reassemble tank and plug unit back in. Press the RESET button.
• If water still fails to flush into the tank, replace the solenoid valve.
• Press and hold the EMPTY button for 3 seconds.
• Follow tank cleaning steps in the Professional Installation Guide.
• Reassemble tank and press the RESET button.
• If fault returns, replace with applicable unit.
• Problem most likely due to voltage variation from service provider, or faulty wiring in the home. If problem is due to TrueSTEAM service alone, the fault should correct itself when voltage levels return to normal.
• Press and hold the RESET button until CALL SERVICE light shuts off.
• Initiate a humidistat call for humidity and monitor for fault light to return.
• If fault returns, check the line cord input voltage before and during humidistat call. Line voltage should not drop below 102Vrms to ensure TrueSTEAM operates properly.
6 Water
7 HVAC power
TROUBLESHOOTING
Fault Description
overow
sensed.
not present.
Steps to Fix To be Performed by Professional HVAC Technician Only
• Ensure drain hose is not kinked or submerged in water at the drain. Check functionality of condensate pump if used.
• Check for water coming out of drain/overflow line. If continuous water flow is present, follow the cleaning steps in the Professional Installation Guide (69-2036).
• After cleaning, set humidistat on and monitor operation.
• If fault returns, unplug TrueSTEAM.
• Loosen cover screw and remove cover.
• Disconnect water level sensor wiring and lift snap-hinge clamp to remove water sensor assembly. See image on page 5.
• Clean probes using warm soapy water so that the metal is exposed. It is OK to use steel wool or brush.
• Reassemble the sensor assembly in the unit, reattach and secure cover.
• Plug unit in, and press RESET button.
• If fault reappears, replace water sensor assembly and/or solenoid valve.
• Turn humidistat off.
• At thermostat, validate that the FAN setting turns the blower on. If not, check the circuit breaker. If circuit is tripped, reset or replace fuse.
• If fault persists, unplug TrueSTEAM and remove cover.
• Validate proper TrueSTEAM wiring to R and C terminals, using installation guide (69-2036).
• Ensure proper connection quality of the wires.
• Inspect R and C wires at the HVAC equipment board, ensuring no breaks and good connection if wire nuts are used.
• Hook AC volt meter across R and C to validate 20-30VAC is present. To measure, it may be necessary to close furnace interlock switch.
• Secure TrueSTEAM cover and plug unit in. Press the RESET button.
• If fault persists, recheck wiring or replace unit.
Note: If using VisionPRO IAQ to
control TrueSTEAM, it is not necessary to monitor HVAC power. DIP 4 may be turned on to disable monitor.
8–11 The backup
12 Temperature
13 Tank failed
14 Heater failed
TROUBLESHOOTING
Fault Description
weld monitor input is active when the backup heater relay is off.
of the elec­tronic circuit board is too high.
to drain.
to boil water.
Steps to Fix To be Performed by Professional HVAC Technician Only
• Replace the TrueSTEAM unit.
Ensure ventilation holes in the
• Ensure the TrueSTEAM is
• Turn humidistat off and allow
• Turn humidistat on and press
• Confirm humidity call starts
• Allow unit to run and check for
• If steam is present, replace
• Water in tank may be hot (>140ºF
• Press and hold the EMPTY
• If unit fails to drain, turn
• Once cool, follow tank cleaning
• Reassemble tank and press the
• If fault persists, replace the
• Press and hold EMPTY button
• Reassemble tank and press the
• Initiate humidistat call.
• If fault returns, replace the unit.
cover are clear of obstruction, and that 1 foot of clearance is maintained around the cover’s ventilation holes.
installed in a location with conditioned air 32°F (0°C) to 104°F (40°C).
time for electronic board to cool. Unplugging unit and removing cover will facilitate this.
RESET button.
(HUMIDIFYING light turns on).
steam leaks around tank and ventilation holes.
TrueSTEAM.
[60ºC]) and can cause burns.
button for 3 seconds.
humidistat to OFF, or unplug the humidifier and wait for water in tank to cool. Ensure tank water is cool before proceeding.
steps in the Professional Installation Guide (69-2036EFS).
RESET button.
solenoid valve.
for 3 seconds, and follow tank cleaning steps in the Professional Installation Guide.
RESET button.
Fault
Red
Description Light Blinks
15 No Airow.
6 7 8 9
TROUBLESHOOTING
Steps to Fix To be Performed by Professional HVAC Technician Only
• Unplug TrueSTEAM and remove cover
• Validate proper wiring to terminals R and C, using the diagrams in the installation guide (69-2036).
• Ensure proper connection quality of the wires.
• Inspect R and C wires at the HVAC equipment board, ensuring no breaks and good connection if wire nuts are used.
• Hook AC volt meter across airflow switch normally-open (N.O.) terminal and R.
• Set thermostat FAN to off and reduce system setpoint.
• Validate 0 VAC reading on AC Volt Meter
• Set thermostat FAN to on.
• Once blower starts, validate 20­30VAC reading on AC volt meter.
• If voltage is not present, check wiring and switch functionality. Differential pressure switch may require a new install location (away from duct bends, etc), or it may need to be replaced.
• If voltage is present, continue to troubleshoot to validate proper airflow monitoring.
• Keep AC volt meter across airflow switch N.O. terminal and R from HVAC unit.
• Turn humidistat off.
• Ensure DIP 4 and 5 are in off (down) position.
• Secure TrueSTEAM cover and plug in unit. Press the RESET button.
• Set thermostat FAN to off and reduce system set point.
• Set humidistat call and monitor device. (may take 15-20 minutes)
• When sound of blower clears, validate within 2 minutes that the AC volt meter reads 20-30VAC.
• If time for switch to change state takes longer than 2 minutes, try a new install location for the switch, where state change is faster.
TrueSTEAM
HM512, HM509, and HM506
TROUBLESHOOTING AND
PARTS REPLACEMENT GUIDE
M28180A
SOLENOID VALVE REPLACEMENT
M28182
M28182
CAUTION: Ensure outside of tank is cool before removing to prevent possible injury.
Ensure the TrueSTEAM is empty, and unplug.
1. Shut off and disconnect the water line from the bottom
2. of the unit. Unlock the red lever and disengage the tank from the
3. valve assembly and remove tank. Remove TrueSTEAM from the mounting bracket.
4.
Remove the cover with a athead or Torx screwdriver.
5. Disconnect the valve wire plug from the circuit board.
6.
Using a athead screwdriver, disengage the frame’s
7. backplate at the four locations. Slide the valve out of the back of the frame, and ease
8. the wiring out of the TrueSTEAM frame. Reassemble with the new solenoid valve, following
9. steps 2–8 in reverse order.
IN-LINE WATER FILTER
Turn off water supply at the source (i.e. saddle valve)
1.
Push in on the lter’s compression snap-lock ttings
2. where the 1/4-in. water line connects. Pull out the water line as you are pushing in the snap-
3. locks.
Install the new water lter, ensuring directional water
4.
ow is accurate per the lter label, by inserting the water lines on either end of the lter.
Initiate a call for humidity by turning the humidistat on.
5.
Check the lter after 5 minutes of humidier operation
6. to ensure no water leakage.
WATER TANK
Press and hold the EMPTY button for 3 seconds.
1. Water will drain from the tank and the CLEAN TANK
2. light will blink as it drains. When the CLEAN TANK is on solid, the tank is empty.
3. Turn the water valve arm to the UNLOCK position.
4. Grip the solenoid toggle valve and slide it back to disengage. Hold bottom of the tank while pressing down the safety
5. release button on the cover and slide the handle forward. The sediment screen is on the inside of the tank at the
6. bottom. Push the release button away from the tank wall to disengage the screen. Pull out and clean or replace the screen.
7. Clean tank and reattach.
8.
WATER SENSOR ASSEMBLY
Unplug the TrueSTEAM.
1.
Remove the cover with a athead or Torx screwdriver.
2. Disconnect the water sensor wire from the electric
3. circuit board.
Remove the Torx screw holding down the water sensor
4. assembly. Lift the metal hinge and remove the sensor assembly
5.
, .
Replace with the new sensor assembly and connect
6. the new wires to the assembly and the circuit board. Reattach the cover.
7. Plug in the TrueSTEAM.
8.
A
REPLACEMENT PARTS
Part Part Number
10-foot Remote Hose and Nozzle Kit 20-foot Remote Hose and Nozzle Kit Cover 50028004-001 2 Duct Nozzle 50028003-001 3 Remote Nozzles 50028001-001 4
Mounting Bracket 50020012-001 5 Solenoid Valve 50027997-001 6 In-Line Water Filter 50028044-001 7 HM512/HM509 Water Tank 50033181-001 8 HM506 Water Tank 50033182-001 9 Water Level Sensor Assembly Saddle Valve 32001616-001 11 Back-flow Water Valve 50030142-001 12
Differential Pressure Switch 50027910-001
50024917-001 1
50024917-002 1
50027998-001 10
B
Fig. Ref
13
REPLACEMENT PARTS
3
13
2
12
8
11
10
9
5
6
7
1
TROUBLESHOOTING
TrueSTEAM has internal diagnostics that monitor system operation, maintenance schedules, and faults. If a system fault is detected, the system will attempt to recover itself up to
ve times in a 24 hour period. If unable to recover in that time,
the red Call Service LED light will activate.
If the TrueSTEAM Call Service light is red, a system fault has
occurred from which the humidier can not recover by itself.
The table below shows the possible faults, along with steps to
x TrueSTEAM.
If the red Call Service LED light is on, press/release the RESET button. The red Call Service LED light will begin blinking in a series that indicates what fault occurred. Refer to
the table below for the fault signied by the number of blinks
that occur.
Press/hold the RESET button to clear the Service Timer light.
Press and hold the EMPTY button for 3 seconds to drain the tank.
4
1 Water/Heat-
2 Water
A
TROUBLESHOOTING
Fault Description
er tempera­ture sensor failed.
sensors failed.
Steps to Fix To be Performed by Professional HVAC Technician Only
• Unplug TrueSTEAM and remove
• Check water sensor connection
• Reattach cover and plug
• If fault reappears, press and hold
• Reassemble tank and press the
• If fault returns, replace the unit.
• Unplug TrueSTEAM and remove
• Disconnect water level
• Clean sensor probes using warm
• Reassemble the sensor
• Plug unit back in and press the
• If fault reappears, replace sensor
B
cover.
to electronic board.
TrueSTEAM in.
the EMPTY button for 3 seconds and follow tank cleaning steps in the Professional Installation Guide (69-2036).
RESET button.
cover.
sensor wiring, remove screw and lift clamp.
Remove water sensor
assembly.
soapy water so that the metal is exposed. It is OK to use steel wool or brush.
assembly in the unit, reattach and secure cover.
RESET button.
assembly.
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Continued on other side…
Toronto, Ontario M1V 4Z9
http://yourhome.honeywell.com
® U.S. Registered Trademark © 2008 Honeywell International Inc. All Rights Reserved 69-2144—03 M.S. 06-08
2 3 4 5
Loading...