Honeywell DVI 980, DVI 982 User Manual

A Honeywell Company
(Honeywell Nr. S4865)
Gas Burner Safety Control
For 1- or 2-stage forced draught and atmospheric gas burners, with DC valves Possible flame detectors:
- Ionisation probe
- Infrared flicker detector 1020.1
- UV flame sensor UVD 971
INTRODUCTION
The burner control boxes DVI980/982 controls and supervises forced draught and atmospheric gasburners. They are approved and certified according to the applicable European standards and regulations. The use on direct air heaters according DIN 4794 is also possible. The microprocessor-based programming sequence ensures extremely stable timings independent of voltage variations, ambient temperature and/or switch-on cycles. The built-in
DVI 980/982
information system not only provides a continuous monitoring of the actual state of the box (very helpful especially for monitoring the start-up phase) but also informs about the cause of a possible lock out. The lock out cause is stored in such a way that it can be retrieved even after a power failure. The control box is designed for maximum safety in case of fluctuations in the voltage supply. If the mains voltage drops below the permitted level, operation is interrupted and the control box automatically prevents the start sequence from being repeated. In this way, the safety of the system is not put at risk by a drop in the mains voltage. This low-voltage protection works not only during start-up but also permanently during operation.
CONSTRUCTION FEATURES
Microprocessor, electronic components, output relais, ignition spark generator and flame amplifier are placed on the printed circuit board. These plus the optional lockout- and reset circuit are well protected inside a flame resistant plastic housing. The LED for displaying the information system are placed on top of the housing.
TYPES AVAILABLE
DVI 980 1-stage DVI 982 2-stage
MODELS
The following functions can be configured by factory:
• with or without air proving switch
• IR-data transmission over Palm Pilot, PC or hand-held
• volatile or non volatile lock out
• recycling (numbers eligible) or lock out / blocked after loss-of-flame during operation
• recycling (numbers eligible) or lock out / blocked without flame establishment after safety time
• with or without internal reset button
• potential free output for flame signal
• with or without lock out lamp (LED)
Table of timings (sec.)
Model max. reaction time or supervised pre-ignition ignition time stray light safety time delay 2nd stage
01 60 24 0 4 5 5 10 02 60 10 0 4 5 5
05 60 30 0 4 5 5
EN1C-0121SZ20 R0305
air proving switch pre-purge time time total monitoring (DVI 982)
tlw tv1 tvz tz tf ts tv2
TECHNICAL DATA
Operating voltage 220 / 240 V (-15... +10%)
50/60 Hz (±5%) Fuse rating 10 A fast, 6 A slow Power consumption ca. 12 VA Max. load per output
- term. X2/6 motor 2.0 A, cos ϕ 0.4 Variation A
- term. X3 ,X5, X6 solenoid valves 90mA, DC Variation B
- term. X3, X9, X5, X6 solenoid valves 90mA, DC
only DC-valves can be connected!
- term. X2/8 lock out 1.0 A, cos ϕ 0.4 total load max. 6 A during 0,5 sec Air proving switch 1 working contact STB Safety temperature delimiter 1 working contact Ignition spark generator Ignition frequency up to 40 Hz Energy ignition spark 10 µAs Ignition voltage 20 kV Sensitivity (operation) 1 µA Min. required ion. current 1.5 µA Sensitivity for stray light 0.4µA Flame signal output Optocoupler
max 70V DC/100mA Ionisation probe insulation Probe - earth
greater than 50 M Stray capacity Probe - earth
less than 1000 pF Cable length < 3 m Flame detectors
IRD 1020.1 end-on viewing
UVD 971 end-on viewing Weight incl. Wiring base 190 g Mounting position any Protection class IP 40 Approved ambient parameter
- for operation -20° C... +60° C
- for storage -20° C... +80° C Build-up of ice, penetration of water and condensing water are inadmissible Approvals according to European standard
EN 298, as well as all other relevant Directives and standards
1
APPLICATION FEATURES
1. Information system
The information system is microprocessor based and reports on all aspects of burner control box operation and flame supervision. It informs continuously about the actual programming sequence the unit is just performing. Besides monitoring of the programming sequence it also allows to identify errors during start-up of operation without any additional testing devices. The automatically performed diagnosis is a valuable tool which facilitates service/ maintenance work and therefore saves costs. The analyses of the error cause can be done directly on stage or if not possible afterwards as the lock out reason is stored in a non-volatile lock out mode memory. The information system communicates with the outside world using a LED (the used Flash-Code is similar to the Morse-Code). The messages are optically transmitted by a appropriately flashing LED. Using an additional terminal (optional), the messages can be recorded and displayed in easy readable form.
1.1 Programming sequence display
The built-in microprocessor controls not only the program­ming sequence but the information system too. The indivi­dual phases of the programming sequence are displayed as Flash-Code. The following messages can be distinguished:
Message Flash-Code waiting for ❘ ❘ .
air proving switch pre-purge ❘ ❘ ❘ .
tv1 pre-ignition ❘ ❘ ❘ ❘ .
tvz safety time ❚ ❘ .
ts delay 2nd stage ❚ ❘ ❘ .
tv2 running _
1.2 Lock-out diagnoses
In case of a failure the LED is permanently illuminated. Every 10 seconds the illumination is interrupted by a flash code, which indicates the cause of the error. Therefore the following sequence is performed which is repeated as long as the unit is not reset.
Sequence:
illuminated phase dark phase Flash-Code dark phase
❘ ❚ ❚ ❚ ❚
for 10 sec for 0.6 sec for 1.2 sec
Error diagnosis:
Error message Flash-Code Possible fault lock out ❘ ❚ ❚ ❚ ❚ within safety time
safety time no flame establishment stray light ❘ ❘ ❚ ❚ ❚ stray light
during monitored phase, detector may be faulty
air proving switch ❚ ❚ ❘ ❘ ❘ air proving switch in closed position contact welded
air proving switch ❘ ❘ ❘ ❚ ❚ air proving switch does not time-out close within specified time
air proving switch ❘ ❘ ❘ ❘ ❚ air proving switch opens opened during start or operation
loss of flame ❚ ❚ ❚ ❚ ❘ loss of flame signal during
operation
Flash-Code for manual lock out manual/external ❘ ❘ ❚ ❚ ❚ ❚ ❚ ❚ ❚ ❚
lock out (see also 3. lock out and reset)
Error RV1 ❚ ❚ ❚ ❚ ❘ ❘ ❚ ❚ ❚ ❚ or STB opens Safety temperature delimiter STB opens. For reset, the supply line must, for a short time, be interrupted after pushing the reset button.
low mains voltage ❘ ❚ ❚ _ Internal fuse defect ❘ ❚ _
> control box defect
Description
= short pulse= long pulse
. = short pause _ = long pause
2. Flame detection
The following types of flame detectors are suitable: – Ionisation probe, temperature resistant material, well
insulated (material and insulation same as for ignition electrode).
– Infrared-flicker detector type IRD 1020.1 with mounting
flange M 93 or the UV solid state flame sensor UVD 971. Flame detection using an ionisation probe is only possible in conjunction with mains supplies which provides a neutral earth connection. Connecting the IRD 1020.1 or UVD 971 the correct wiring has to be observed.
2.1 Stray light monitoring
The stray light check is performed at the end of the pre­purge time for the duration as mentioned in the table of timings.
DVI 980/982
2
Loading...
+ 4 hidden pages