Honeywell DTC 100/4 TD User Manual

DTC 100/4 TD
1
Differential thermostat for regulation of two heating
circuits in combination of solar and classic heating
with temperature display and regulation of burner or
electric heating element
DTC 100/4 TD
Installation and maintenance instructions
ID-2106-13-DTC100-4TD-Honeywell-170039
DTC 100/4 TD
2
DEAR CUSTOMER
Congratulations !
You have bought a DTC 100/4TD differential thermostat, manufactured according to the latest quality and safety standards. It is made according to the state of art and efficiently utilises solar energy or alternative sources for domestic water heating. It is designed in compliance with strict criteria and requirements of West European markets and enables efficient use of solar energy which enables considerable savings of other sources for domestic water heating. Our products are available in the markets for several years and satisfy the needs of de­manding customers from hot Greece to north Germany. We are convinced that the use of our product will satisfy your needs too and help you to save your money.
Thanks for your confidence !
The set consist of:
1. Differential thermostat DTC 100/4TD
2. T1 collector sensor with silicone conductor
3. T2 hot water tank sensor with PVC conductor
4. T3 sensor for installation in boiler or to upstream conduit in front of mixing valve (PVC)
5. T4 hot water tank sensor with PVC conductor
6. Fixing screws with wall inserts (2 pcs)
7. Clip for T4 sensor fastening with fixing springs
8. Instructions for use
9. Warranty certificate
In case any of these are missing or damaged, demand your seller to supply you with a replacement.
Read these instructions carefully, as this will allow you to benefit from all the possibilities offered by this product.
WARNING !
All examples listed in the instructions are merely indicative. The manufacturer accepts no responsibility for incorrect hydraulic connection of machine part of installation. Machine and electric installations should comply with all safety regulations defined by law and the rules.
We reserve the right to modify the instructions and the technical data of the product without prior notice
DTC 100/4 TD
3
GENERAL
DTC 100/4TD is a microprocessor aided double differential thermostat, designed for heating of domestic water from two heating sources (collectors, boilers, heat pumps,...), using its logic of additional energy source switching on (boiler of central heating system). The thermostat controls two pumps or two motors actuated ball valves (EMV 800...) and one burner or electric heating element.
The thermostat enables regulation of four parameters, i.e.:
1. Regulation of maximum temperature in hot water tank from 10 to 90°C.
2. Regulation of difference for higher exchanger from 2 to 15K (after-heating circuit)
3. Regulation of difference for lower exchanger from 2 to 15K (collector circuit)
4. Setting two working regimes - C.n.b (normal) and C.d.t. (switching off the limitation of boiler temperature for collector circuit). With first two regulation options you define how much the value of the source temperature (collector, boiler,...) should exceed the temperature of water around the exchanger in hot water tank, that the regulator activates the pump or opens the valve. The difference is set in relation to the volume of heat losses of the system which depend on lenghts of pipelines from source to hot water tank and on pipeline insulation. Built-in digital display enables prompt reading of the temperatures of individual sensors and of all set values as well.
OPERATION:
DTC 100/4TD double differential thermostat measures the temperature of two heating sources (collectors, boiler, ...) and of two spots in user (hot water tank). Heating effect is provided, when heating unit (heating element in hot water tank) exceeds the temperature of the user (water in hot water tank) for at least 3 - 5K. Consequently minimum adjustable difference is 2K (factory set to 5K). When the temperature of the source exceeds the temperature around the exchanger for at least 5K, the thermostat opens the valve (EMV...) or activates the pump; it closes the valve or stops the pump, when temperature difference is one degree lower than pre-set value. The thermostat also switches off a pump if pre-set temperature is reached in hot water tank (adjustable from 10 to 90°C). If gas flow boiler, oil boiler or electric heating element (which is switched off during summer seasons), is connected to after-heating circuit, the regulator can switch on the boiler by means of the third output, if domestic water is to be additionally heated by means of after­heating circuit. In summer seasons a few days of cloudy weather can appear or use of domestic water increases. In such cases domestic water is to be after-heated from additional source (central heating system boiler or electric heating element). Classic differential thermostat would require hot boiler throughout the year, which is not recommended from ecological and economic point of view. DTC 100/4TD, with its third additional output, enables activation of after-heating source. When after-heating of water is required, regulator first switches on the burner of the boiler and when the condition of difference for after-heating circuit is also assured (pre-set difference of boiler has higher temperature than hot water tank), pump is switched on.
DTC 100/4 TD
4
When pump operates for primary heating circuit (collectors), operation of after-heating circuit and burner of boiler or electric heating element is prevented. This assures maximum energy savings during summer seasons and is also the main role of solar systems. The set comprises four sensors (T1, T2, T3, T4). Two of them are mounted into individual heating sources and two into upper half of individual exchangers in hot water tank. T1 and T2 are designed for primary (main) heating circuit, which heats entire quantity of water in hot water tank (lower exchanger), where T1 is a sensor of heating source (generally collectors) and T2 is a sensor in lower part of hot water tank. T3 and T4 are designed for additional, i.e. after-heating circuit which additionally heats water in hot water tank (upper exchanger). T3 is a sensor of heating source (generally boiler) and T4 is a sensor in upper part of hot water tank.
TEHNICAL DATA:
Supply voltage ....................................... 230V, 50Hz +/- 10%
Power consumption ............................... 4 VA
Pump relay rating .................................. 3A/230VAC cos 0.6
Type of thermostat ................................. P
Max. measured temperature ................. 180°C
Min. measured temperature .................. -20°C
Adjustable temperature range ............... 10 - 90°C
Temperature difference settings ............
2 - 15K
Hysteresis of difference ......................... 2°K
Hysteresis of the thermostat .................. 3°K
Nr. of sensors ........................................
4
Nr. of outputs ......................................... 3 (230 VAC)
INSTALLATION OF THERMOSTAT:
Install the thermostat on hot water tank casing or close to it. Do not mount it under pipe fittings or valves due to possible water dripping on its housing.
EXTERNAL CONNECTIONS:
DTC 100/4 TD
5
VDR resistor
Thermo-shrinkable
tubes
ELECTRIC CONNECTION:
Grounding wires should be connected to special terminal pins situated on right side of terminal strips.
WARNING:
Boiler control should be performed behind the main switch for burner but in front of boiler thermostat. Care must be taken that differential thermostat and boiler connection are performed at the same phase otherwise inter-phase contact can occur.
SENSOR INSTALLATION IN COLLECTOR:
Install it as immersion sensor in collecting pipe at the top of the collectors in provided sleeve
For cables longer than 15m we recommend over-voltage protection with VDR resistor.
flow direction
T piece 1/2”
pipe 1/2”
extension conductor
sensor conductor
Connection
to terminal pins
BOILER
TERMINAL CONNECTION 1,2 T1 sensor – heating source sensor (collectors, boiler…) 3,4 T2 sensor – hot water tank sensor 5,6 T3 sensor – heating source sensor for higher heating circuit (boiler) 7,8 T4 sensor – hot water tank sensor in upper part of hot water tank
neutral conductor 9 neutral conductor 10 phase for boiler (burner) switching on 11
neutral conductor 12 phase of pump for secondary heating circuit 13 neutral conductor 14 phase of pump for collector heating circuit 15 phase connector for mains 230V, 50 Hz 16 neutral conductor - connector for mains 230 V, 50 Hz