Honeywell DT-500, DT-500T Installation Instructions Manual

Step 2 Separate sensor housings.
Insert small screwdriver into slot in bottom and push up on latch. Then gently pull the housings apart at the base.
Corner Mount Knockouts
Wall Mount Knockouts
®
Motion Sensor Installation Instructions
Step 1 Select the mounting location.
Mount at 7'6" / 2.3 m for optimal animal immunity.
Step 5 Wire the sensor.
Observing the proper polarity, wire the unit as shown (use 14-22 AWG). Push as much wire as possible back into the wall when returning the PCB to its housing.
Step 6 Walk-test the sensor.
Apply power to the sensor and let it warm up for three minutes. Begin walk-test after the red LED has stopped flashing.
Step 3 Remove the PCB.
Push down on the latch at the bottom of the housing. Then gently pull the printed circuit board (PCB) forward and up by the terminal strip.
Step 4 Mount the sensor.
Carefully break out appropriate mounting knock­outs on the rear housing, and mount it in the desired location.
Walk across the protected area at the ranges to be covered. The red LED will indicate an alarm condition after two to four normal steps. When there is no motion in the protected area, the LED will be off.
Wiring Hole
Aim the DT-500/DT-500T away from:
NOTE: For proper wiring methods, refer to the National Electrical Code NFPA 70.
WARNING: DO NOT touch the antenna when removing the PCB from the rear housing.
Antenna
Red Alarm LED
W1 (Cut W1 Wire to Disable LED)
Model DT-500T Only
Model DT-500T Only
IntelliSense and DUAL TEC are registered trademarks of Honeywell, Inc.
PRODUCT SPECIFICATIONS
Range:
DT-500, DT-500T 11 m x 9 m (35' x 30')
Alarm relay:
Energized Form A (NC) 100 mA, 30 VDC
Tamper:
25 mA, 30 VDC
Power requirements:
10 - 14.5 VDC 35 mA, 12 VDC
RFI immunity:
30 V/m 10 MHz - 1000 MHz
PIR white light immunity:
6,500 Lux
Frequencies:
Center band 2.45 GHz
Sensitivity:
2 - 4 steps within field of view
SUPERVISION
If the microwave technology stops sending or receiving signals, or the system electronics are not in normal working order, the sensor's red LED will latch ON and alarm relay will open.
The sensor can only recover from this state by cycling power. If the problem still exists after cycling power, the sensor will fail the power-up self-test, the red LED will latch ON, and alarm relay will open. Self-test is performed at power-up and every two hours after that.
NOTE: The sensor should be tested at least once each year to ensure proper operation.
DT-500 Series DUAL TEC
®
Motion Sensor Supplemental Information
DETECTION PATTERNS
TOP VIEW Wall Mounted Wide Angle Lens with Microwave Pattern
SIDE VIEW Wide Angle Lens
FCC Notice: This equipment has been tested and found to comply with
the limits for a field disturbance sensor, pursuant to Part 15 of the FCC Rules. The user is cautioned that changes or modifications not expressly approved by IntelliSense could void the user's authority to operate this equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. How­ever, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:  Reorient or relocate the receiving antenna.  Increase the separation between the equipment and receiver.  Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
 Consult the dealer or an experienced radio/TV technician for help.
IC Notice: Operation is subject to the following two conditions: (1) this
device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
This device requires a radio licence, unless it is installed totally inside a building. (User must obtain this licence.) Une licence est requise pour ces dispositifs, sauf pour ceux installés tout à fait à l'intérieur d'un bâtiment. (Il faut que l'utilisateur obtienne cette licence.)
All Rights Reserved Copyright 2001 IntelliSense. 5-051-502-00 Rev H
Operating temperature:
-10° to 49° C (14° to 120° F) (UL: 0o to 49o C (32o to 120o F))
PIR fields of view (edges):
Standard lens 22 long range 12 intermediate 6 lower 4 down
Dimensions:
13 cm x 7 cm x 4 cm 5" H x 2-7/8" W x 1-5/8" D
Weight:
200 g (7 oz) Packaged product: 260 g (9 oz)
Approvals/listings:
FCC certified IC certified UL listed ULC Listed* C-Tick
IMPORTANT: This sensor does not respond to walk-tests in a conventional manner. Rather, it tracks motion and analyzes the signals to confirm a valid alarm condition. Internally the sensor registers, then confirms an alarm con­dition. To observe this, take 2 to 4 steps into the pattern then stop and watch the LED.
ANIMAL IMMUNITY
To achieve the highest level of attainable animal immunity, please use the following recommended mounting guide­lines:
 Mount the sensor at the standard height of 2.3 m
(7' 6").
 Make sure an animal cannot get within 1.9 m (6')
of the sensor, such as by jumping on furniture or shelving.
 Make sure the sensor is level with the wall. Use
a leveling tool and position it vertically across the face of the sensor. Improper installation can reduce animal immunity levels.
 Make sure the sensor has a clear line-of-sight to all
areas you wish to protect. If the PIR sensor is blocked, the unit will not alarm.
 Aim the sensor toward the interior of the room, point-
ing away from windows, moving machinery, and heat-
ing/cooling sources. Each installation should be tested to determine the level of attainable animal immunity, and tested again whenever the animal configuration changes. The following worksheet provides additional guidelines for determining the level of expected immunity:
NOTE: Animal immunity characteristics have not been verified by Underwriter's Laboratories, Inc.
IMPORTANT: For UL certificated installations, the DT-500 must be con­nected to a UL listed power supply or UL listed control unit capable of providing a minimum of four hours of standby power.
*NOTE: The ULC label or listed marking on a product is the only evidence provided by Underwriters Laboratories of Canada to identify products that have been produced under the Listing and Follow-up Service.
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
SUPERVISION
If the microwave technology stops sending or receiving signals, or the system electronics are not in normal working order, the sensor's red LED will latch ON and alarm relay will open.
The sensor can only recover from this state by cycling power. If the problem still exists after cycling power, the sensor will fail the power-up self-test, the red LED will latch ON, and alarm relay will open. Self-test is performed at power-up and every two hours after that.
NOTE: The sensor should be tested at least once each year to ensure proper operation.
ANIMAL IMMUNITY WORKSHEET Total combined animal weight(s) 45 kg (100 lb.)
Flooring Material: Flooring materials within the sensors field­of-view will effect the levels of animal immunity. Generally, a carpeted floor will achieve a higher level of immunity than a cement floor.
Carpet: deduct 0 Wood: deduct 2.25 kg (5 lb.) Tile/Cement: deduct 4.5 kg (10 lb.) ­ ___________
Animal Heat Radiation*: Generally, the longer the hair on an animal, the less heat or infrared energy they radiate. A long hair animal tends to achieve a higher level of animal immunity than a short hair animal.
Long Hair: deduct 0 Medium Hair: deduct 2.25 kg (5 lb.) Short Hair: deduct 4.5 kg (10 lb.) ­ ___________
Estimated animal immunity level = ___________ *Use in installations with dogs and cats.