Honeywell DS06-100-SUS-LF, DS06-101-SUS-LF, DS06-102-SUS-LF, DS06-103-SUS-LF, DS06-104-SUS-LF Installation Manual

...
33-00014EF-07
DS06 Low Lead Content Dial Set Pressure Regulating Valves
INSTALLATION INSTRUCTIONS

APPLICATION

The Honeywell DS06 Dial Set® Pressure Regulating Valve is a high quality pressure regulating valve that maintains a constant outlet pressure over a wide range of inlet supply pressures. It is suitable for potable water and irrigation applications. The downstream pressure adjustment dial eliminates the need for a pressure gauge when adjusting the pressure setting (static pressure only).

SPECIFICATIONS

Model: DS06 Dial Set Pressure Regulating Valves.
Construction Materials:
Body: Brass. Internal Parts: Stainless steel and engineered
plastics.
Regulator Mechanism: Fabric-reinforced diaphragm.
Seat Design: Balanced single seat construction.
Inlet Pressure (Maximum): 250 psi maximum.
Reduced Pressure Range:
25 to 90 psi (1/2 in. to 2 in.).
Outlet Pressure: Factory set at 60 psi (414 kPa).
Dial Calibration: ± 4 psi.
Differential: 14.5 psi minimum (inlet to outlet).
Fluid Temperature (Maximum):
Water: 140° F (60° C).
Ambient Temperature Range: 33° F to 140° F (1° C
to 60° C).
Pipe Sizes Available: 1/2 in., 3/4 in., 1 in., 1-1/4 in.,
1-1/2 in. and 2 in. available.
Connections:
Can be configured as female thread-by-thread,
single- or double-union, NPT threaded or sweat.
Low Lead Content: < 0.25% Lead.
Gauge Tap: 1/4" NPT.
Approvals:
ASSE 1003 Listed CSA Certified IAPMO/UPC Listed NSF 61 Compliant

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to
follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in these instructions
and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out the
product operation as provided in these instructions.
DS06 LOW LEAD CONTENT DIAL SET PRESSURE REGULATING VALVES

Water Capacities

The suitability of a given regulator size is dependent on the pressure requirements where it will operate. For the pressure regulator valve size required for a specific installation, determine the following:
1. Pressure differential between inlet and outlet
pressure in pounds per square inch (psi),
2. Capacity in gallons per minute, and
Table 1. Water Capacities.
Pressure Differential Between Inlet and Outlet
Pressure Regulator Valve Siz e
1/2" 6 7.26 8.15 7.44 6.47
3/4" 6 11.98 14.44 14.53 14.97
1" 6 11.18 11.23 9.51 9.11
1-1/4" 6 7.53 6.34 7.26 7.13
1-1/2" 6 29.81 32.27 30.87 26.81
2" 6 27.34 25.8 24.48 18.01
Reduced Pressure
Falloff (PSI)
10 10.7 10.66 9.69 8.85 15 14.27 15.72 14.49 13.96 20 17.74 19.59 18.98 18.1
10 17.17 21.05 25.23 26.33 15 19.86 25.14 29.32 32.85 20 21.27 26.42 30.42 33.82
10 18.01 18.98 17.39 16.78 15 25.67 28.14 28.71 26.9 20 30.69 34.7 36.19 35.05
10 20.25 17.88 15.15 14 15 33.02 34.87 32.63 29.68 20 40.07 44.29 46.01 34.61
10 46.14 50.02 49.89 47.82 15 66.22 78.42 86.74 84.14 20 77.14 92.29 103.82 109.68
10 64.81 97.61 78.15 90.09 15 82.82 105.14 119.94 129.62 20 87.66 107.83 120.95 132.09
25 psi 50 psi 75 psi
Flow Capacity
(US gpm)
3. Allowable reduced pressure falloff in psi. Given
these variables, use Table 1 to determine the proper size pressure regulator valve for your application.
Example: An installation has 135 psi inlet pressure, 60 psi outlet pressure (75 psi pressure differential). If a 15 gpm capacity is required with only 10 psi falloff allowable, a 3/4 in. DS06 is required.
Flow Capacity
(US gpm)
Flow Capacity
(US gpm)
Flow Capacity
100 psi or
more
(US gpm)

DSO6 Fixture Unit

Flow rates based on submittal sheet DS06, based on flush tank systems with a 15 psi fall-off defined by IAPMO/ANSI UPC 1-2009.
Table 2.
Size I/s GPM
1/2” 0.99 15.72 21 3/4” 1.58 25.14 40
1” 1.77 28.14 48 1-1/4” 2.19 34.87 70 1-1/2” 4.93 78.42 270
2” 6.61 105.14 400
33-00014EF—07 2
Fixture
Units
Capacities are based on a 100 psi supply pressure and a difference of 50 psi or more between the initial supply pressure and the reduced no-flow pressure.
Check local water pressures before selection.

Procedure

1. Flush the system clear of sediment or debris.
2. Close the supply valve and downstream isolating
valve (if one is installed).
3. Install the DS06 with the arrow on the body
pointing in the direction of water flow. Install, preferably, in horizontal pipework with filter bowl downwards - vertical installation also possible.
The DS06 can be installed directly onto the pipe by using the female NPT threads on each end. If space limitations restrict turning the DS06, install single- or double-unions.
DS06 LOW LEAD CONTENT DIAL SET PRESSURE REGULATING VALVES
CAUTION
!
LOOSEN LOCKING SCREW ONE TURN
ADJUST SETPOINT AT THE DESIRED VALUE BY ACTUATING SELECTOR.
INLET PRESSURE (MAXIMUM): 250 PSI REDUCED PRESSURE RANGE: 25 TO 90PSI 1/2 IN. TO 2 IN. SIZE
NOTE: DO NOT DISMANTLE KNOB
SET-POINT READOUT HAS BEEN CALIBRATED IN THE FACTORY AND SET AT 60 PSI. DISMANTLING THE SELECTOR KNOB WILL CANCEL THIS CALIBRATION. RECALIBRATE USING A PRESSURE GAUGE. SEE RECALIBRATION.
M35046A
3
M35634A
1
4
6
2
LOOSEN THE SETPOINT DIAL LOCKING SCREW.
UNSTRESS THE PRESSURE SPRING BY TURNING COUNTER­CLOCKWISE .
UNSCREW THE BONNET WITH A 1-5/8" WRENCH.
REMOVE CARTRIDGE USING A PLIERS AS A LEVER.
REASSEMBLE BONNET IN REVERSE ORDER.
1-5/8" WRENCH
O-RINGS
WASHER (LIP UP)
5
WHEN REASSEMBLING, ENSURE O-RINGS AND WASHER ARE PROPERLY INSTALLED
NOTE: Heat from soldering can damage internal
parts of the DS06. Always solder the tailpieces separately from the DS06.
4. Open the supply valve slowly and check for
leakage and proper operation of the DS06.

Changing the Downstream Pressure (See Fig. 1)

Remove the dust cap from the DS06. The DS06 is factory set to 60 psi.
To adjust the outlet pressure to a desired setting:
1. Loosen the locking screw by turning counter-
clockwise (Do not remove this screw.)
2. Turn the adjusting knob counter-clockwise
to reduce pressure or clockwise to
increase pressure.
3. Lock the setting by turning the locking screw
clockwise .
4. Replace the dust cap over the dial.
8. Remove cartridge using a pliers as a lever.
9. Reassemble bonnet in reverse order.

Recalibrate

If the dial knob assembly has been disassembled recalibration is necessary.
1. Close shutoff valve on inlet.
2. Release pressure on outlet side (e.g. through
water tap).
3. Close shutoff valve on outlet.
4. Remove dust cap.
5. Loosen slotted screw (do not remove screw).
6. Fit pressure gauge.
7. Slowly open shutoff valve on inlet.
8. Set desired outlet pressure (e.g. 60 psi).
9. Align scale (e.g. 60 psi) in middle of viewing win-
dow.
10. Retighten slotted screw.
11. Slowly open shutoff valve on outlet.
Fig. 1. Changing outlet pressure.

Replacing the Cartridge (Fig. 2)

The working parts of the DS06, including diaphragm, valve seat, strainer, and disk are all contained in a replaceable cartridge. To replace the cartridge:
1. Close shutoff valve on inlet.
2. Release pressure on outlet side (e.g. through
water tap).
3. Close shutoff valve on outlet.
4. Loosen slotted screw (do not remove the screw).
To prevent injury and/or equipment damage, loosen locknut and turn adjusting screw counter-clockwise to remove spring tension.
5. Slacken tension in compression spring by
turning counter clockwise until it does not move
anymore.
6. Unscrew Bonnet.
7. Remove slip ring.
Fig. 2. Replacing the DS06 cartridge.
3 33-00014EF—07
DS06 LOW LEAD CONTENT DIAL SET PRESSURE REGULATING VALVES

Cleaning

1. Close shutoff valve on inlet.
2. Release pressure on outlet (e.g. through water
tap).
3. Close shutoff valve on outlet.
4. Unscrew filter bowl using a 1-5/8" wrench.
5. Remove filter, clean and reinsert.
6. Place O-ring onto filter bowl.
7. Screw in filter cup hand-tight.
8. Slowly open shutoff valve on inlet.
9. Slowly open shutoff valve on outlets.
DUST CAP (BLACK)
LOCKING SCREW
ADJUSTING KNOB
DIAL RING
BONNET
SPINDLE
SPRING
WASHER
CARTRIDGE
GASKETS (2) TAILPIECES (2) NUTS
(2)
PLUGS (2)
REPLACEMENT FILTER

OPERATION

DS06 is a spring loaded pressure reducing valve that operates by means of force equalizing system. The force of a diaphragm operates against the force of an adjustment spring. If the outlet pressure and therefore diaphragm force fall because water is dawn, the then greater force of the spring causes the valve to open. The outlet pressure then increases until the forces between the diaphragm and the spring are equal again. The inlet pressure has no influence in either opening or closing the valve. Because of this, inlet pressure fluctuation does not influence the outlet pressure, thus providing inlet pressure balancing. See Fig. 4 for the internal construction of the DS06.
NOTE: Minimum ambient rating is 33° F (1° C).
4
M35052
Fig. 4. Internal construction of DS06.
O-RING SET FOR DO6F
M35053A
Fig. 3. DS06 exploded view.
33-00014EF—07 4
Loading...
+ 8 hidden pages