Honeywell DPTM50D, DPTM110D, DPTM550D, DPTM1100D, DPTM100D User Manual

...
3-WIRE DIFFERENTIAL PRESSURE TRANSMITTERS
WITH DIGITAL DISPLAY AND CURRENT/VOLTAGE OUTPUT
The differential pressure transmitters of the DPTM series are used for measuring differential pressure, positive pressure, and vacuum. The transmitters are suitable for:
air-conditioning,
building automation,
environmental protection,
valve and flap control,
filter and blower monitoring,
fluid and level monitoring, and
control of air flows.
Models
order no.
DPTM50D -50...0...+50 Pa1) n.a. 20 kPa 40 kPa
DPTM110D -100...0...+100 Pa1) n.a. 20 kPa 40 kPa
DPTM550D -500...0...+500 Pa1) n.a. 20 kPa 40 kPa
DPTM1100D -1 kPa...0...+1 kPa2) n.a. 40 kPa 70 kPa
DPTM100D 0...100 Pa1) 0...250 Pa1) 20 kPa 40 kPa
DPTM250D 0...250 Pa1) 0...500 Pa1) 20 kPa 40 kPa
DPTM500D 0...500 Pa1) 0...1 kPa1) 20 kPa 40 kPa
DPTM1000D 0...1 kPa2) 0...2.5 kPa2) 40 kPa 70 kPa
DPTM5000D 0...5 kPa3) 0...10 kPa3) 60 kPa 120 kPa
1)
pressure displayed in Pa, temperature error at 0…50 °C ≤ ± 5% of full scale (FS)
2)
pressure displayed in kPa, temperature error at 0…50 °C ≤ ± 2.5% of full scale (FS)
3)
pressure displayed in kPa, temperature error at 0…50 °C ≤ ± 1% of full scale (FS)
pressure range
1 (pre-set) 2
overload
capacity
burst
pressure
DPTM50D-5000D
SPECIFICATION DATA & MOUNTING INSTRUCTIONS
FEATURES
Monitoring gaseous, non-aggressive media
Piezo-resistive pressure transducer
Up to 40 kPa (60 kPa) overload capacity
Rugged design; protection class IP54
Easy installation and wiring connection
Measurement range adjustable by jumper
Response time adjustable by jumper
Output signal adjustable by jumper
Red digital display
Display of values > +1000 Pa in kPa
Re-zeroing possible by pushbutton
NOTE: These sensors are not suitable for use in
installations under periodic inspection by the U.S. Food and Drug Administration.
SPECIFICATION
Supply voltage 18...30 Vac/dc, 50/60 Hz Output signal 0...10 Vdc (factory setting) /
4…20 mA Pressure medium Air, non-aggressive gases Working temperature 0...50 °C Linearity and hysteresis error ≤ ± 1.0% of FS Temperature error at 0...50°C See section "Models" Storage temperature -10...+70 °C Humidity 0...95% rh, non-condensing Repetition accuracy ≤ ± 0.2% of FS Response time 1 s (factory setting) / 100 ms Process connection 6 mm hose pipe Electrical connection Screw terminal block for wire
up to 1.5 mm² Housing material ABS and POM Cable entry M20x1.5 (polyamide) Protection class IP54 as per EN60529 EMV EN60770, EN61326 Weight approx. 130 g
® U.S. Registered Trademark EN0B-0616GE51 R1007
Copyright © 2007 Honeywell Inc. • All rights reserved
DPTM50D-5000D DIFFERENTIAL PRESSURE TRANSMITTERS WITH CURRENT/VOLTAGE OUTPUT
j
j
A
j
FUNCTION
DPTM50D-5000D Differential Pressure Transmitters are equipped with an integrated piezo-resistive pressure transducer. The pressure to be measured is applied to and thus deflects a thin membrane made of mono-silicon. The membrane's semiconductor resistors (arranged to simul­taneously compensate for the temperature response) detect this mechanical deflection and generate an electrical output signal. The output signal is converted into the 0…10 V or 4…20 mA analog signal which changes (within the specified error limits) in proportion to the applied pressure and is shown in the LED display.
NOTE: The devices are factory pre-set to pressure range 1.
This can be changed (except for +/- models) to pressure range 2 by removing the corresponding jumper (see Fig. 3).
NOTE: The devices are factory pre-set to a response time
of 1 second. This can be changed to 100 ms by removing the corresponding jumper (see Fig. 3).
NOTE: The devices are factory pre-set to an output signal
of 0…10 V. This can be changed to 4…20 mA by removing the corresponding jumper (see Fig. 3).
ACCESSORIES
DPSK: Included in delivery. Duct Kit, incl. 2 m of silicone
hose and two joining pipes
DPSL: Ordered separately. L-shaped mounting brackets
with screws.
DIMENSIONS
4.5
8.5
MOUNTING
WIRING
Range:
high
low
Response:
fastmAslow Mode: Output:
V
Jumper yes Jumper no
Differential Pressure Transmitter
DIGITAL DISPLAY
2341
Fig. 2. Mounting
PRESSURE RANGE jumper inserted = pressure range 1 jumper removed = pressure range 2
RESPONSE TIME
umper inserted = 1 sec
umper removed 100 msec=
NOT USED
NALOG OUTPUT
umper inserted = 0...10 V
jumper removed = 4...20 mA
1
2
LOAD
3
4
18...30Vac/dc
0...10 V / 4...20 mA GROUND DO NOT USE!
IP 54
Fig. 1. Dimensions (in mm)
REZEROING: Remove tubes and push button approx. 5 sec.
Fig. 3. Wiring details
P2 (LOW PRESSURE)
P1 (HIGH PRESSURE)
STORAGE POSITION FOR JUMPERS
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Fema Controls Honeywell GmbH
P.O. Box 1254 71099 Schönaich Germany phone: (49) 7031-637-02
fax: (49) 7031-637-850 http://www.honeywell.de/fema Subject to change without notice.
EN0B-0616GE51 R1007