Honeywell DKG 972 User Manual

Page 1
Gas Burner Safety Control DKG 972
For 2-stage atmospheric gas burners
Flame detection:
- Ionisation probe
- Infrared-flicker detector IRD 1020.1
- UV flame sensor UVD 971
INTRODUCTION
The burner control box DKG 972 controls and supervises atmospheric burners for gas. They are approved and certified according to the applicable European standards and regulations. The microprocessor-based programming sequence ensu­res extremely stable timings independent of voltage varia­tions, ambient temperature and/or switch-on cycles. The built-in information system not only provides a continuous monitoring of the actual state of the box (very helpful es­pecially for monitoring the start-up phase) but also informs about the cause of a possible lock out. The lock out cause is stored in such a way that it can be retrieved even after a power failure. The control box is designed for maximum safety in case of fluctuations in the voltage supply. If the mains voltage drops below the permitted level, operation is interrupted and the control box automatically prevents the start sequence from being repeated. In this way, the safety of the system is not put at risk by a drop in the mains voltage. This low-voltage protection works not only during start-up but also perma­nently during operation.
CONSTRUCTIONAL FEATURES
The control box circuitry is protected by a flame resistant, transparent plug-in type plastic housing. A central fixing screw locks the control box to the wiring base. The plug-in control box incorporates the microprocessor based timer, flame check and reset circuits. Manual reset from lock out and set to lock out is provided by a push button with an integrated LED information system. A variety of cable entry points provides complete flexibility for electrical wiring. The wiring base S98 is equipped with spare- and extraterminals and allows together with a variety of cable entry points utmost flexibility of electrical wiring.
The DKG 972 are compatible with the TFI 812. Different are only the pre- and post-ignition times.
Max. heating power according the limits in the Gas Appliance Directive.
TECHNICAL DATA
Operating voltage 220 / 240 V (-15... +10%)
or 110 / 120 V (-15... +10%)
Fuse rating 10 A fast, 6 A slow Power consumption ca. 12 VA Max. load per output
- term. 3 ignition trafo 1.0 A, cos ϕ 0.2
- term. 5 + 6 solenoid valves 0.5 A, cos ϕ 0.4
- term. 7 alarm indicator 0.5 A, cos ϕ 0.4
- term. 4 auxiliary blower 2.0 A, cos ϕ 0.4 total load 4.0 A, cos ϕ 0.4
Reset time from lock out none
Re-cycling / repetition (max. 4x) after a loss-of-flame during operation
Sensitivity 1 µA min. ionisation current required 1.5 µA Sensitivity for stray light 0.4 µA Ionisation probe insulation probe - earth
Stray capacitance probe- earth
max. cable length < 3 m Flame detectors
IRD 1020.1 side-on or end-on viewing
UVD 971 end-on viewing Weight incl. Wiring base 190 g Mounting position any Protection class IP 40 Approved ambient parameter for control and flame detector max. 95% at 30° C
- for operation -20° C... +60° C
- for storage -20° C... +80° C Build-up of ice, penetration of water and condensing water are inadmissible Approvals according to European standards EN 298 and EN 230, as
Classified acc. to EN 298 ATLLXN
50 Hz (±5%)
60 Hz (±5%)
max. 16 A during 0,5 sec
greater than 50 M
less then 1000 pF
well as all other relevant Directives and standards
Table of timings (sec.)
Model waiting time start pre-ignition time Stray light monitoring safety time post-ignition time delay 2nd-stage
05 12 3 5 5 4 25 10 12 3 5 10 9 25
EN1C-0127SZ20 R0305
tw tvz tf ts tn tv2
1
Page 2
APPLICATION FEATURES
1.2 Lock-out diagnoses
1. Information system
The information system is microprocessor based and re­ports on all aspects of burner control box operation and flame supervision. It informs continuously about the actual programming sequence the unit is just performing. Besides monitoring of the programming sequence it also allows to identify errors during start-up of operation without any additional testing devices. The automatically performed diagnosis is a valuable tool which facilitates service/ maintenance work and therefore saves costs. The analyses of the error cause can be done directly on stage or if not possible afterwards as the lock out reason is stored in a non­volatile lock out mode memory. The information system communicates with the outside world using a LED (the used Flash-Code is similar to the Morse-Code). The messages are optically transmitted by a appropriately flashing LED. Using an additional terminal (optional), the messages can be recorded and displayed in easy readable form.
1.1 Programming sequence display
The built-in microprocessor controls not only the pro­gramming sequence but the information system too. The individual phases of the programming sequence are displayed as Flash-Code. The following messages can be distinguished:
In case of a failure the LED is permanently illuminated. Every 10 seconds the illumination is interrupted by a flash code, which indicates the cause of the error. Therefore the following sequence is performed which is repeated as long as the unit is not reset.
Sequence:
illuminated phase dark phase Flash-Code dark phase
❘ ❚ ❚ ❚ ❚
for 10 sec for 0.6 sec for 1.2 sec
Error diagnosis Error message Flash-Code Possible fault lockout ❘ ❚ ❚ ❚ ❚ within lock out safety time
no flame establishment
stray light ❘ ❘ ❚ ❚ ❚ stray light
during monitored phase, detector may be faulty
Flash-Code for manual lock out manual/external ❘ ❘ ❚ ❚ ❚ ❚ ❚ ❚ ❚ ❚
lock out (see also 3. lock out and reset)
2. Flame detection
Message Flash-Code waiting time ❘ ❘ ❘ .
tw pre-ignition ❘ ❘ ❘ ❘ .
tvz safety time ts ❚ ❘ .
post ignition tn delay time to valve V2 ❚ ❘ ❘ .
tv2 running _
low mains voltage ❘ ❚ ❚ _ Internal fuse defect ❘ ❚ _
> control box defect
Description
= short pulse= long pulse
. = short pause _ = long pause
The following types of flame detectors are suitable:
– Ionisation probe, temperature resistant material, well
insulated (material and insulation same as for ignition electrode).
– Infrared-flicker detector type IRD 1020.1 with mounting
flange M 93 or the UV solid state flame sensor UVD 971. Flame detection using an ionisation probe is only possible in conjunction with mains supplies which provides a neu­tral earth connection. Connecting the IRD 1020.1 or UVD 971 the correct wiring has to be observed.
2.1 Stray light monitoring
The stray light check is performed at the end of the pre­purge time for thr duration as mentioned in the table of timings.
DKG 972
2
Page 3
3. Lock out and reset
6. Mounting and electrical wiring
The unit can be reset or brought into lock out mode in two different ways:
Internal In the lock out case the unit can be reset by pushing the built­in button meaning a new start-up cycle is performed.
External Instead of using the built-in lock out button the same function can be achieved by using an external button which connects terminal 9 with A (see also circuit and block diagram).
If the pushputton (internal or external) is pressed during normal operation or during the start sequence for more then 3 sec. and afterwards released, the control box will perform a shutdown.
Please note The unit can only be brought to lockout mode or be reseted if power is applied to the unit.
4. Low-voltage protection
at 220 / 240V (110 / 120V) nominal voltage
The mains voltage has to be more than 187 V order to allow the unit to perform a start-up.
(94 V
eff
eff
) in
The mains voltage is not only monitored in the start-up phase but also permanently during operation. If the voltage drops below < 160 V the control box proceed to safety shut-down and goes into
(80 V
eff
) during start-up or run time
eff
a waiting status. If the voltage rises again, the control box performs automatically a start-up as soon as the mains voltage is > 187 V
(94 V
eff
) .
eff
Wiring base: – 3 earth terminals with additional terminal for burner
earthing
– 3 neutral terminals with internal permanent connection to
neutral terminal 8 – 2 independant spare terminals (S1 and S2) – extra terminals A, B and C are standard (wiring base S98
12-pin) – 2 slide-in plates and 2 easy knock out holes plus 2 knock
out holes in the base bottom faciliate the base wiring
Please note To assist trouble-free operation the main neutral connection terminal 8 in the wiring base must be fully tightened. The terminal screws are already in the undone position. To connect a wire to the terminal, the screw only needs to be fastened.
General: The control box and detector probes should not be subjected to excessive vibration.
5. Safety
The design and control sequence of the DKG 972 controls will comply with the currently applicable standards and regulations (see also TECHNICAL DATA).
DKG 972
3
Page 4
INSTALLATION INSTRUCTIONS AND MAINTENANCE
3. Fault finding
1. Important notes
– The controls must be installed by qualified personnel
only. The relevant national regulations have to be observed.
– On commissioning the wiring has to be carefully check-
ed according the appropriate diagram, Incorrect wiring can damage the unit and endanger the installation.
– The fuse rating has to ensure that the limits specified in
TECHNICAL DATA will not be exceeded. If these precau­tions are not observed, the effect of a short circuit can cause severe damage to the control and installation.
– For safety reasons a minimum of one control shutdown
every 24 hours has to be observed.
– Disconnect the mains before the control box is plugged
in or out.
– The control box is a safety device and must not be
opened!
2. Function control
For safety reasons the flame detection system should be tested on commissioning the installation as well as after a service or longer shut-down.
a) Attempt to start with gas valve closed:
– At the end of the safety interval
-> Lockout
b) After a normal start, with the burner in operation, close
the gas valve: – After restart at the end of the safety interval
-> Lockout
The built-in information system facilitate the trouble shooting in the case of problems occurring during start-up or during operation. A list of possible lock out messages can be found in APPLICATION FEATURES chapter 1.2.
Please note: The control box is locked in lock out mode and the reasen for the lock out is displayed until the control box is reset, either by an internal or external reset (see also subject “3. Lock out and reset").
Removing the control box from its wiring base or by interrupting the supply line may not reset a lock out. Therefore, by applying power, it needs 2-3 secs. before the control box goes to lock out again and the cause of the last lock out.
Error Possible fault
Burner not working - Thermostat circuit open
- Faulty electrical wiring
- Mains voltage < 187 V (< 80 V)
- Terminal A continuously on power (e.g. terminal A is used as a support terminal)
After 2-3 secs. after applying - Control box has not been reseted power. the unit goes to lock out
Burner starts, - stray light signal during waiting flame not established, time lock out - no ignition or no fuel
Burner starts, - no or too low flame signal (min. flame established, valves see TECHNICAL DATA) after safety time, - wrongly wired, phase and neutral lock out reversed
- Ionisation probe dirty, broken or has contact to frame ground
- too little light on flame sensIor (IRD)
DKG 972
4
Page 5
CIRCUIT AND TIMING DIAGRAM DKG 972
ST RT EV
Ph
max. 10 A fast
6 A slow
HS
GW
123456789 A
V1
IS
M
Z
V2
SA
N
tw tf tvz tn ts tv2
IRD- OR UVD CONNECTION
IRD 1020.1
UVD 971
blue
black
brown
term. 8
term. 1
term. 9
HS Mains switch GW Gas proving switch ST Limit thermostat RT Control thermostat EV External reset and lock out button IS Ionisation probe
(IRD 1020.1, UVD 971see separate diagram) Z Ignition V1 Solenoid valve, 1st-stage V2 Solenoid valve, 2nd-stage SA External lock out signal M Auxiliary blower
tw Waiting time tf Stray light monitoring tvz Pre-ignition time tn Post-ignition ts Safety time tv2 2nd-stage delay
BLOCK DIAGRAM DKG 972
Fault display
Oscillator
EEPROM
µC
Watchdog
Reset
µC
Flame
amplifier
RZ
rz
RV1 RV2 RS
rv1
rv2
13456789A
Information
system
rs
Reset and
lock out
Mains
monitoring
Power supply
monitoring
Power supply
DKG 972
5
Page 6
DKG 972 AND SOCKET
4,5
HOLDER M 93 FOR IRD
35
3
62,5
86
24
Reset button
30
44
Earth
30
M4
16
30
57-60
UVD 971 IRD 1020.1
29
29
38,5
24
Slide-in plate
35
25
Underside cable entry ø16 mm
50
60
4
17
HOLDER M 74 FOR UVD
UVD = 29
IRD = 44
35
ø 14
ø20
48
14
15.1
48
ø20.5
26
4.5
3
4,5
4
26
7
21,8
21,8
ø13,5
UVD = 89
IRD = 104
VARIATION IRD
right
axial
left
ORDERING INFORMATION
ITEM DESIGNATION ITEM NO.
Control box DKG 972 Mod. 5 0332005 Control box DKG 972 Mod. 10 0332010 Control box DKG 972 Mod. 10 110 / 120V 50Hz 0332310 Control box DKG 972 Mod. 10 110 / 120V 60Hz 0332410 Socket Wiring base S98 12-pin 75310 Insert plate PG-Plate 70502 optional Cable entry plate 70503 Flame detector IRD 1020.1 end-on 16532 Flame detector IRD 1020.1 left 16533 Flame detector IRD 1020.1 right 16531 optional UVD 971 16722 Support for IRD Holder M93 for IRD 1020 59093 Support for UVD Holder M74 for UVD 59074 Connection cable Plug type, 3 core cable, 0.6 m with tag wire ends 7236001
The above ordering information refers to the standard version. Special versions are also included in our product range. Specifications subject to change without notice
Page 7
Combustion Controls EMEA - Local Honeywell Sales Offices
France Spain
Honeywell SA Honeywell S.A. Parc Technologique de St. Aubin Josefa Valcárcel, 24 Bâtiment Mercury – BP87 28027 Madrid 91193 Gif-Sur-Yvette Cedex SPAIN FRANCE
Phone: (33) 1 60 19 80 00 Phone: (34) 9 13136100 Fax: (33) 1 60 19 81 81 Fax: (34) 9 13 13 61 27
internet: www.honeywell.fr internet: www.honeywell.es
Eastern Europe United Kingdom
Honeywell s.r.o. Honeywell Control Systems Ltd Mlynske Nivy 73 Honeywell House, Arlington Business Park PO Box 75 Bracknell 82007 Bratislava 27 Berkshire, RG12 1EB SLOVAKIA UNITED KINGDOM
Phone: (421) 2 58247 400 Switchboard +44 (0)1344 656000 Fax: (421) 2 58247 415 Information Centre Tel +44 (0)1344 656235 Information Centre Fax +44 (0 )1344 656240
e-mail: info.slovakia@honeywell.com Email: Uk.infocentre@honeywell.com internet: www.honeywelluk.com
Germany, Austria, Switzerland Benelux
Honeywell GmbH Honeywell B.V. Kaiserleistrasse 39 Laarderhoogtweg 18 63067 Offenbach 1101 EA Amsterdam Z.O. DEUTSCHLAND THE NETHERLANDS
Phone: (49) 6 980640 Phone: (31) 2 05656911 Fax: (49) 69 81 86 20 Fax: (31) 2 05 65 66 00
internet: www.honeywell.de internet: www.honeywell.nl
Italy
Honeywell S.r.l. Via P. Gobetti, 2/B 20063 Cernusco sul Naviglio (MI) ITALY
Phone: 39 02 92146 1 Fax: 39 02 92146 888
internet: http://www.honeywell.com/sites/it/
Loading...