Honeywell SDC 3-40, SDC 3-10, SDC 7-21, SDC 9-21, SDC 12-31 Service Manual

...
Page 1
EN2H-0221GE51 R0808
Smile SDC heating and
district heating controller
SERVICE MANUAL
Page 2
EN2H-0221GE51 R0808
Page 3
SDC / DHC Contents
EN2H-0221GE51 R0808 3
Contents
1 Software version ..........................................................................................................11
2 Safety instructions.......................................................................................................11
2.1 Intended use .....................................................................................................11
2.2 Requirements for start-up..................................................................................11
2.2.1 Power supply ........................................................................................12
2.2.2 Connection conditions ..........................................................................12
2.2.3 Cable cross-sections ............................................................................12
2.2.4 Maximum cable lengths........................................................................12
2.2.5 Cable installation ..................................................................................12
2.2.6 Grounding and zeroing .........................................................................13
2.3 Hot-water temperature greater than 60 °C ........................................................13
2.4 Connection of accessory parts ..........................................................................14
2.5 Maintenance and cleaning ................................................................................14
2.6 Safety precautions for EMC-compliant installation ............................................15
3 Overview.......................................................................................................................20
4 Abbreviations ...............................................................................................................21
5 Operation......................................................................................................................22
5.1 Display and operating elements ........................................................................22
5.1.1 Display (basic display)..........................................................................23
5.1.2 Operating elements ..............................................................................24
5.1.2.1 Input button (press / turn)........................................................24
5.1.2.2 "Daytime room temperature" button ........................................24
5.1.2.3 "Night-time room temperature" button.....................................25
5.1.2.4 "Daytime hot-water temperature" button .................................25
5.1.2.5 "Operating mode" button (basic display) .................................26
5.1.2.6 "Switching time programs / Holiday programs" button ............33
5.1.2.7 "System information" button....................................................35
5.1.2.8 "Manual mode" / "Emission measurement" button ..................44
Page 4
Contents SDC / DHC
4 EN2H-0221GE51 R0808
5.1.2.9 Access to the technician / OEM area ......................................46
5.1.2.10 Heating curve..........................................................................47
5.2 Menu-selection level..........................................................................................48
5.2.1 "Time - Date" menu ..............................................................................54
5.2.2 "Timeprograms" menu ..........................................................................55
5.2.2.1 Selection of the control circuit .................................................56
5.2.2.2 Selection of the program .........................................................56
5.2.2.3 Selection of day of the week and cycle ...................................56
5.2.2.4 Programming switching times and cycle temperatures ...........57
5.2.3 "System Parameters" menu..................................................................72
5.2.3.1 Language selection .................................................................72
5.2.3.2 Time program..........................................................................73
5.2.3.3 Operating mode ......................................................................74
5.2.3.4 Parameter reset ......................................................................76
5.2.3.5 Complete reset........................................................................77
5.2.4 "DHW" menu ........................................................................................77
5.2.4.1 Night-time hot-water temperature............................................78
5.2.4.2 Legionella protection day ........................................................78
5.2.5 "Direct Heating Circuit" / "Mixed Heating Circuit 1" / "Mixed
Heating Circuit 2" menu........................................................................78
5.2.5.1 Reduced operation..................................................................79
5.2.5.2 Heating system .......................................................................80
5.3 Error messages.................................................................................................80
5.4 Parameter settings ............................................................................................81
5.4.1 "Hydraulics" menu (HYDRAULIC) ........................................................81
5.4.2 "System parameters" menu (SYSTEM)................................................85
5.4.3 "Hot-water circuit" menu (DHW) ...........................................................89
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC) ...................................92
5.4.5 "Mixed heating circuit 1 / 2" (MIX.VALVE - 1 / MIX.VALVE - 2)
menus ...................................................................................................95
5.4.6 "Heat generator" menu (HEAT GENER................................................99
Page 5
SDC / DHC Contents
EN2H-0221GE51 R0808 5
5.4.7 "District hot water" menu (DIST.HEATING) ........................................104
5.4.8 "Return increase" menu (RETURN CONTR)......................................105
5.4.9 "Solar" menu (SOLAR) .......................................................................106
5.4.10 "Solid" menu (SOLID FUEL) ...............................................................107
5.4.11 "Buffer" menu (BUFFER)....................................................................108
5.4.12 "Total flow regulation" menu (MAIN SUPPLY)....................................109
5.4.13 "Cascading" menu (CASCADE) .........................................................110
5.4.14 "Data bus" menu (BUS) ......................................................................111
5.4.15 "Relay test" menu (RELAY TEST ) ....................................................111
5.4.16 "Error messages" menu (ALARM) ......................................................112
5.4.17 "Error messages 2" menu (ALARM 2) ................................................113
5.4.18 "Sensor calibration" menu (SENSOR ADJ.) .......................................113
6 Control Functions ......................................................................................................114
6.1 Variable adjustment of the hydraulic parameters (variable inputs and
outputs) ...........................................................................................................114
6.1.1 Connection and settings table ............................................................116
6.2 Switching time program enabling ....................................................................117
6.3 Suppressing the cycle temperature on time program level..............................118
6.4 Enabling "Separate Control Mode"..................................................................118
6.5 Switching from SDC to DHC ...........................................................................119
6.6 Selection of hydraulic parameter presettings ..................................................119
6.7 The variable inputs and outputs of device series SDC/DHC 43 ......................119
6.8 General functions and their operation .............................................................120
6.8.1 Outside temperature sensing..............................................................120
6.8.1.1 Building type .........................................................................120
6.8.2 Heating circuit outside temperature assignment.................................121
6.8.3 Outside temperature emergency operation value...............................121
6.8.4 Outside temperature disable...............................................................122
6.8.5 Climate zone.......................................................................................122
6.8.6 Design temperature ............................................................................122
6.8.7 Summer switch-off..............................................................................123
Page 6
Contents SDC / DHC
6 EN2H-0221GE51 R0808
6.8.8 System frost protection.......................................................................124
6.8.9 Pump forced operation .......................................................................127
7 Hydraulic Components..............................................................................................128
7.1 Heat generator: Boiler .....................................................................................128
7.1.1 Heat generator start-up protection......................................................128
7.1.2 Heat generator minimum temperature limit.........................................129
7.1.3 Maximum temperature limit heat generator ........................................130
7.1.4 Heating circuits minimum temperature limit ........................................130
7.1.5 Heat generator sensor control mode ..................................................130
7.1.6 Minimum burner runtime.....................................................................131
7.1.7 Switching: Multi-stage heat generator/Switching differential...............131
7.1.8 Operation for modulating burners .......................................................136
7.1.9 Modulation of P part (Xp)....................................................................137
7.1.10 Modulation of sample time Ta.............................................................137
7.1.11 Modulation of integral action time Tn ..................................................138
7.1.12 Modulation of runtime .........................................................................138
7.1.13 Modulation of start time ......................................................................138
7.1.14 Modulation of start power ...................................................................139
7.1.15 OpenTherm ........................................................................................140
7.1.16 Use of boiler sensor 2.........................................................................141
7.1.17 External heat generator cut-off ...........................................................141
7.1.18 Heat generator forced discharge ........................................................141
7.1.19 Exhaust gas temperature monitoring ..................................................142
7.1.20 Burner counter mode ..........................................................................143
7.2 Heat generation, heat exchanger, district heating ...........................................144
7.2.1 On/Off operation of the district heating valve......................................145
7.2.2 Continuous heat exchanger valve control...........................................145
7.2.3 District heating return temperature limit..............................................147
7.2.4 Return temperature limit for hot-water loading....................................149
7.2.5 Hot-water pre-regulator with district heating systems .........................150
7.2.6 Mode of operation: Hot-water pre-control ...........................................151
Page 7
SDC / DHC Contents
EN2H-0221GE51 R0808 7
7.2.7 Quick hot-water control.......................................................................152
7.2.8 Mode of operation of hot-water control mode "external
operation" ...........................................................................................154
7.2.9 Conditional parallel operation for mixed heating circuits.....................155
7.2.10 Circulation pump control mode ...........................................................155
7.2.11 Switch-off of district heating control ....................................................156
7.2.12 Return interval flushing .......................................................................156
7.2.13 Heat meter for additional limitation according to the volume flow
or thermal output ................................................................................156
7.2.14 Charging pump (CHP) ........................................................................157
7.2.15 Primary pump .....................................................................................158
7.2.16 Boiler circuit pump ..............................................................................158
7.2.17 Return increase ..................................................................................159
7.2.17.1 Bypass pump (RBP)..............................................................160
7.2.17.2 Return maintenance through controlled feed water addition 160
7.2.17.3 Indirect return increase .........................................................161
7.3 Heating circuit .................................................................................................161
7.3.1 General heating circuit functions ........................................................161
7.3.1.1 Heating curve........................................................................161
7.3.1.2
Heating curve setting (heating curve)....................................162
7.3.1.3 Reduced operation................................................................164
7.3.1.4 Heating system .....................................................................164
7.3.1.5 Heating circuit temperature limit............................................164
7.3.1.6 Heating circuit temperature offset .........................................165
7.3.1.7 Heating circuit pump extended running time .........................165
7.3.1.8 Screed function .....................................................................165
7.3.2 Heating circuit constant temperature control ......................................168
7.3.3 Fixed-value control .............................................................................168
7.3.4 Consideration of the room temperature/room influence......................169
7.3.4.1 Heating circuit room connection............................................169
7.3.4.2 Heating circuit room factor ....................................................170
Page 8
Contents SDC / DHC
8 EN2H-0221GE51 R0808
7.3.4.3 Heating circuit room controller ..............................................171
7.3.4.4 Switch-on/switch-off optimisation ..........................................171
7.3.4.5 Room setpoint ramp..............................................................175
7.3.4.6 Heating limit function.............................................................175
7.3.4.7 Heating circuit room frost protection limit ..............................177
7.3.4.8 Mixed heating circuits cooling switch-over ............................177
7.3.4.9 Heating circuit name .............................................................180
7.3.4.10 Room thermostat function (maximum room
temperature limit) ..................................................................181
7.3.5 Hot-water production ..........................................................................187
7.3.5.1 Hot-water tank loading (SLP) ................................................187
7.3.5.2 Circulation pump (CIR.).........................................................194
7.3.6 Solar/Solid fuel/Buffer.........................................................................196
7.3.6.1 Solar function ........................................................................196
7.3.6.2 Buffer tank function ...............................................................199
7.3.6.3 Solid fuel function..................................................................212
7.3.7 Tank loading switch-over....................................................................213
7.3.8 Hydraulic buffer relief (HBR)...............................................................215
7.3.9
Easy enabling and disabling of a heating pump .................................216
7.3.10 Other system components..................................................................217
7.3.10.1 Global fault message input....................................................217
7.3.10.2 Global fault message output .................................................217
7.3.10.3 Timer 217
7.3.10.4 External switching modem ....................................................218
7.3.10.5 External information ..............................................................219
7.3.10.6 Demand contact....................................................................219
7.3.11 Bus communication ............................................................................221
7.3.11.1 Bus address of central device ...............................................221
7.3.11.2 Control functions via the data bus.........................................222
7.3.11.3 Operation of wall devices ......................................................227
7.3.12 Cascading of heat generators in the bus system................................232
Page 9
SDC / DHC Contents
EN2H-0221GE51 R0808 9
7.3.12.1 General description of cascading of control devices .............232
7.3.12.2 Function of the cascade parameters.....................................233
7.3.12.3 Mode of operation of cascade control ...................................234
7.3.13 Commissioning, maintenance and troubleshooting help ....................237
7.3.13.1 Automatic set function...........................................................237
7.3.13.2 Emission measurement (not for DHC 43) .............................238
7.3.13.3 Relay/function test.................................................................239
7.4 Error messages...............................................................................................243
7.4.1 Basic display/fault stack fault messages ............................................248
7.4.1.1 Sensor calibration .................................................................249
7.4.1.2 Full controller reset................................................................249
7.4.1.3 Controller time correction ......................................................249
8 Technical data............................................................................................................250
8.1 General ...........................................................................................................250
8.1.1 Installation recommendations .............................................................251
8.2 Sensor resistance values ................................................................................251
8.2.1 NTC 20 ...............................................................................................251
8.2.2 PT 1000 ..............................................................................................252
8.3 Sensor measurement ranges ..........................................................................252
8.4 Digital inputs....................................................................................................253
9 Log ..............................................................................................................................254
Index....................................................................................................................................255
Page 10
Contents SDC / DHC
10 EN2H-0221GE51 R0808
Page 11
SDC / DHC Software version
EN2H-0221GE51 R0808 11
1 Software version
This documentation is valid for software version V 3.0 of your control device. The software version is displayed after switch-on for approx. 8 s. If you are using an older software version, please contact your heating technician.
2 Safety instructions
2.1 Intended use
The SDC / DHC Smile family of controllers was designed for the sole purpose of regulating and controlling hot-water, heating and district heating systems (including hot-water production) that do not exceed a maximum flow temperature of 120 °C.
2.2 Requirements for start-up
ATTENTION
The heating system must be complete and filled with water so that the pumps do not run dry and the heating boiler is not damaged.
The control equipment must be installed in accordance with the installation instructions.
All electrical connections (voltage supply, burner, mixer motor, pumps, sensor wiring etc.) must be carried out by the technician in accordance with the applicable VDE regulations and correspond with the circuit diagrams.
If floor heating is connected, a limiting thermostat must also be installed in the flow line after the heating circuit pump. This switches off the pumps at excessive flow temperatures.
Before starting up the controller, have the heating technician check all requirements listed above.
The current time and date are already set at the factory and are backed up by a battery.
The time switch functions based on a basic program and the control functions are preset for common heating systems with low­temperature boilers.
NOTE
Page 12
Safety instructions SDC / DHC
12 EN2H-0221GE51 R0808
2.2.1 Power supply
Do not disconnect the controller from the mains supply!
The battery for saving all individualised data is otherwise unnecessarily strained. The frost-protection function of the controller is deactivated.
2.2.2 Connection conditions
All electrical connection work may only be carried out by qualified personnel!
2.2.3 Cable cross-sections
1.5 mm2 for all cables carrying 230 V (power supply, burner,
pumps, actuator).
0.6 mm2 for bus cables (recommended type J-Y(St)Y 2 x 0.6).
0.5 mm2 for sensors, selectors and analog signal cables.
2.2.4 Maximum cable lengths
Sensor, selector and analog inputs
We recommend using cables no longer than 200 m. Longer connection lines could be used, but increase the risk of interference.
Relay outputs
Unlimited cable length.
Bus connections
Max. length of 100 m from the first bus subscriber to the last one (incl. wall modules).
2.2.5 Cable installation
Install cables for sensors apart from the cables carrying 230 V! Branch boxes in the sensor cable must be avoided!
Page 13
SDC / DHC Safety instructions
EN2H-0221GE51 R0808 13
2.2.6 Grounding and zeroing
Local regulations on the connection of equipment must be observed!
2.3 Hot-water temperature greater than 60 °C
ATTENTION
Note that there is a danger of scalding at all hot-water draw­off points (kitchen, bathroom etc.) in the following cases. Add sufficient cold water in these cases.
When the automatic anti-legionella mechanism is activated, the hot water is automatically heated to the anti-legionella temperature (65 °C at the factory) on the selected day and at the selected time to kill any legionella bacteria found in the hot-water tank.
In the manual mode / emission measurement operating mode, the hot water is heated up to the highest possible boiler temperature, as the burner and all pumps are switched on and the mixer is opened fully. There is an acute danger of scalding at all connected hot-water draw-off points! Add sufficient cold water or switch off the hot-water loading pump (at the switch of the pump, if present). Heating and hot water are in unregulated continuous operation. This operating mode is for special use by the chimney sweep for emission measurement or if the controller is defective. The high hot-water temperatures can be prevented, however, by setting the boiler thermostat to a max. boiler temperature of approx. 60 °C.
Automatic anti-
legionella mechanism
Manual mode /
Emission
measurement
Page 14
Safety instructions SDC / DHC
14 EN2H-0221GE51 R0808
2.4 Connection of accessory parts
WARNING
According to VDE 0730, a separator for each mains terminal is to be provided in the voltage supply to the control equipment. Observe the local regulations regarding grounding and zeroing.
As soon as the mains voltage is applied to terminals 21, 22, 2, 6, 12 and 18, headers X3 and X4 can also carry mains voltage.
If the heating circuit and hot-water loading pumps do not have an On / Off switch, but manual switch-on and switch-off capability is still desired, the appropriate switches must be installed by the customer. All accessory parts (sensors, selectors etc.) are to be connected to the respective circuit diagram.
2.5 Maintenance and cleaning
The controller is maintenance-free. The device can be cleaned externally with a moist (not wet) cloth.
Page 15
SDC / DHC Safety instructions
EN2H-0221GE51 R0808 15
2.6 Safety precautions for EMC-compliant installation
Mains lines and sensor/data bus lines must be installed separate from each other. A minimum of 2 cm space must be present between the lines. It is permissible to cross lines.
x
a
b
y
ç
é
æ
a Mains 230 V AC x 15 cm
b Data bus line 12 V AC y 2 cm
For control devices with their own mains connection, separate installation of mains and sensor/bus lines must absolutely be ensured. If cable ducts are used, they are to be provided with cut­off bridges.
Page 16
Safety instructions SDC / DHC
16 EN2H-0221GE51 R0808
When installing control or wall devices, a minimum spacing of 40 cm to other electrical equipment with electromagnetic emissions, e.g. relays, motors, transformers, dimmers, microwave ovens and televisions, audio speakers, computers, cordless telephones etc., is to be ensured.
x
ç
é
æ
x 40 cm
A minimum spacing of 40 cm is to be ensured between wall devices and central devices. Multiple central devices in the data bus system can be mounted directly next to one another.
Page 17
SDC / DHC Safety instructions
EN2H-0221GE51 R0808 17
The mains connection of the heating system (boiler – panel – control equipment) must be designed as a separate circuit. Neither fluorescent lamps nor any machines which are potential sources of interference may be connected/connectable.
ç
é
æ
ç
é
æ
a
b
c
d
e
a Safety fuse 16 A
b Boiler room emergency switch
c Connect boiler room lighting and electrical outlets to
separate circuits only!
d Wall devices
e Heat generator
Shielded cables must be used for the data bus lines.
For a recommended layout, see 8 Technical data, pg. 250
Page 18
Safety instructions SDC / DHC
18 EN2H-0221GE51 R0808
The earth connection of the cable shielding must occur on one side at the protective conductor connection, e.g. at the cladding plate of the heat generator, protective conductor terminal etc. Multiple earth connections of a single cable are not permissible (buzzing loop).
a
PE
b
ç
é
æ
ç
é
æ
a No earth connection here! b Central device
Page 19
SDC / DHC Safety instructions
EN2H-0221GE51 R0808 19
With star-topology data bus systems, double earth connections may not be made. The earth connection must be made on one side of the star!
a Shielding b Two-lead data bus line
c Distributor terminal d Branch box
The outside sensor may not be installed near transmitters or receivers (e.g. on garage walls near garage door opener receivers, amateur radio antennas, radio alarm systems or directly next to large transmission equipment etc.).
Page 20
Overview SDC / DHC
20 EN2H-0221GE51 R0808
3 Overview
The modular SDC / DHC control device is available in an installable switch cabinet version and a surface-mounted wall version with the following equipment features:
Type
Number of output relays
Burner stage 2
or
District heating valve
CLOSED
Burner stage 1
Direct heating circuit
Variable output 3
Mixed heating circuit 1
Mixed heating circuit 2
Tank loading pump
Variable output 2
Variable output 1
SDC 3-10
3 x x x
SDC 3-40
3 x
SDC 7-21 1)
7 x x x x
SDC 9-21 2)
7 + two variable relays
x x x x – x x x
SDC 12-31 3)
10 + two variable relays
x x x x x x x x
1)
DHC 43-1
2)
DHC 43-2
3)
DHC 43-3
Page 21
SDC / DHC Abbreviations
EN2H-0221GE51 R0808 21
4 Abbreviations
The following abbreviations are used in this documentation/in the display of the control device:
RED
Lowering operation
BS 2
Buffer sensor 2 (bottom)
OS
Outside sensor
BLP
Buffer loading pump
OS2
Outside sensor 2
RBP
Return bypass pump
FGS
Flue gas sensor
RP
Return pump
OT
Outside temperature
SD I
Switching differential I
BUS
System data bus
SD II
Switching differential II
OC1
Burner stage 1 operating hour counter
TS
Tank sensor
OC2
Burner stage 2 operating hour counter
TLP
Tank loading pump
DC
Direct heating circuit
SLS
Solar loading switch-over
DCP
Direct heating circuit pump
SLSS
Solar loading switch-over sensor
ECO
Switch-off operation
SFD
Solar forced dissipation
EHR
Electric heating rod
SLP
Solar loading pump
SFB
Solid fuel boiler sensor
STL
Stratified tank loading pump
SFR
Solid fuel buffer sensor
VO
Variable output (general)
FC
Fixed-value control
VO1
Variable output 1
SFP
Solid fuel pump
VO2
Variable output 2
PI
Pulse input
VI
Variable input (general)
BP
Boiler circuit pump
VI1
Variable input 1
CC
Constant control
VI2
Variable input 2
CRS
Collector return sensor
VI3
Variable input 3
CTBS
Collector tank/buffer sensor
FM1
Flow sensor of mixed heating circuit 1
CFS
Collector flow sensor
FM2
Flow sensor of mixed heating circuit 2
MM
Mixer motor
PHE
Parallel heat generator enable
MC
Mixed heating circuit
HG
Heat generator
MHP
Mixed heating circuit pump
HGS
Heat generator sensor
P1
Switching time program
WD
Wall device for room temperature sensing
P2
Switching time program
HW
Hot water
P3
Switching time program
CIR
Circulation pump
BS
Buffer sensor (top)
CHP
Charging pump
Page 22
Operation SDC / DHC
22 EN2H-0221GE51 R0808
5 Operation
5.1 Display and operating elements
1011
2
1
3
4
7
6
8
9
5
1 "Manual mode" / "Emission measurement" button (not on
district heating controllers)
2 "Operating modes" button (basic display)
3 "Switching time programs" / "Holiday programs" button
4 "System information" button
5 Display
6 Cover clip for service socket
7 "Daytime room temperature" button
8 "Night-time room temperature" button
9 "Daytime hot-water temperature" button
10 Input button (press / turn)
11 Operating mode symbols (heating programs)
Page 23
SDC / DHC Operation
EN2H-0221GE51 R0808 23
5.1.1 Display (basic display)
1
2 3 4
5
C
1 Day of the week / Date 4 Operating mode symbols
2 Time 5 Heat generator temperature
3 Active operating mode
The illumination of the display is switched on by pressing any button or using the input button î and switches off automatically
if no buttons are pressed for a longer period of time.
During start-up of the unit and after a power failure, a segment test with automatic fault diagnosis is carried out. The respective device type and the software version number then appear briefly.
The basic display that then appears shows the day of the week, the date, the time and the heat generator temperature in automatic mode. Different values appear in the basic display depending on the set operating mode (AUTOMATIC, PARTY etc.). Thus, for example, in the ABSENT operating mode, the indication ABSENT TIL appears instead of the date and the return date instead of the temperature. Active summer deactivation is
indicated by a beach umbrella symbol
À, and active frost
protection is indicated by a snowflake symbol
Á.
Page 24
Operation SDC / DHC
24 EN2H-0221GE51 R0808
5.1.2 Operating elements
5.1.2.1 Input button (press / turn)
By pressing once, you can:
Confirm input / values
By pressing and holding (approx. 3 s), you can:
Switch to the menu-selection level
Move up one menu level
By turning the input button î, you can:
Change values (clockwise increases called-up values, anticlockwise decreases them)
Navigate through menus
5.1.2.2 "Daytime room temperature" button
Sets the desired room temperature (room setpoint) in automatic
mode during the heating cycles and in the PARTY and HEATING
operating modes. In operating mode 1, the set value for all heating circuits is the same. In operating mode 2, the set value applies for the respective heating circuit. To set the operating mode, see 5.2.3.3 Operating mode, pg. 74.
Press ¥ button.
Set flashing room temperature specification to the desired
value by turning the input button î.
Confirm set value by pressing the
¥ button or the input
button î.
Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).
20 °C
5 ... 30 °C
ð
¥
Setting
C
Factory setting
Setting range
Page 25
SDC / DHC Operation
EN2H-0221GE51 R0808 25
5.1.2.3 "Night-time room temperature" button
Sets the lowered room temperature in automatic mode between
the heating cycles and in the ABSENT and RED. HEATING
operating modes.
In operating mode 1, the set value for all heating circuits is the same. In operating mode 2, the set value applies for the respective heating circuit. To set the operating mode, see
5.2.3.3 Operating mode, pg. 74.
Press ¦ button.
Set flashing room temperature specification to the desired
value by turning the input button
î.
Confirm set value by pressing the ¦ button or the input
button î.
Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).
16 °C
5 ... 30 °C
5.1.2.4 "Daytime hot-water temperature" button
Sets the daytime hot-water temperature during the hot-water operational-readiness times in automatic mode and in the PARTY and HEATING operating modes. This set value also applies for exclusively hot-water operation (manual summer operation).
Press § button.
Set flashing hot-water temperature to the desired value by
turning the input button î.
Confirm set value by pressing the § button or the input
button î.
Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).
50 °C
¦
Setting
C
Factory setting
Setting range
§
Setting
C
Factory setting
Page 26
Operation SDC / DHC
26 EN2H-0221GE51 R0808
5 °C (hot-water economy temperature) ... Maximum hot-water heater temperature limit (service setting)
Pressing and holding (approx. 3 s) the § button brings you to the reload function, where the reload time can be set in minutes. With a reload time of 0 minutes, loading is started once and the hot-water tank is loaded to the daytime setpoint. The time for this superimposed hot-water circuit loading can be set between 0 and 240 minutes. The current week program is superimposed here.
5.1.2.5 "Operating mode" button (basic display)
Sets the operating mode and returns to the basic display from every operating level.
Setting range
One-time hot-water
circuit loading
Page 27
SDC / DHC Operation
EN2H-0221GE51 R0808 27
Overview of the operating modes
Symbol Operating mode Display Setting
ç
ABSENT
P1 (P2, P3)*, return date
è
PARTY
P1 (P2, P3)*, party end time
é
AUTOMATIC
C
P1 (P2, P3)*
ê
SUMMER
C
P1(P2, P3)*
ë
HEATING
C
ì
RED. HEATING
C
í
STANDBY
C
* P2 and P3 only after enabling, see "System Parameters"
menu, parameter 2 = P1 to P3
Page 28
Operation SDC / DHC
28 EN2H-0221GE51 R0808
The selected operating mode appears in plain text, whereby a marking at the bottom edge of the display points to the respective operating mode symbol at the same time. In operating mode 1, the set value for all heating circuits is the same. In operating mode 2, the set value applies for the respective heating circuit. To set the operating mode, see 5.2.3.3 Operating mode, pg. 74.
Press button.
Select operating mode by turning the input button î. The
marking is located above the corresponding operating mode symbol.
Confirm set operating mode by pressing the button or the
input button î.
With short-term operating modes (ABSENT, PARTY), set the
desired value by turning the input button î and confirm with the button or the input button î.
Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).
Press the button for approx. 3 s to return to the basic display from any operating level.
Holiday mode is set via the "Switching time programs / Holiday programs" button (see 5.1.2.6 "Switching time programs / Holiday programs" button, pg. 33).
5.1.2.5.1 Absence mode (short-term program)
With the ABSENT operating mode, heating operation is temporarily deactivated and protected from frost during brief absences. During the absence, all heating circuits are adjusted to the specified lowered room temperature. Once the set time expires, the heating circuits automatically return to the operating mode that was active before the switch to the absence operation. Short-term programs such as PARTY or ABSENT are skipped here.
See 5.1.2.5 "Operating mode" button (basic display) , pg. 26
Short absence while heating operation is active.
Setting
Return to the basic
display
NOTE
Setting
Application
Page 29
SDC / DHC Operation
EN2H-0221GE51 R0808 29
An active absence program can be cancelled in case of early return.
Press button.
Turn input button î and switch to automatic operation.
The active absence program has been cancelled.
P1 as from activation
P1 (P2, P3) / 0.5 to 24 h to the current time
P1 (P2, P3)
Program-controlled resumption of heating operation. After activation of the absence program, heating operation is interrupted until the following switch-on time of the current automatic program P1 (or P2 or P3, if enabled).
0,5 ... 24 h
The set value is added on to the current time and represents the return time. When the absence program is called up again, the last set value is saved and suggested as the initial value.
An active absence program appears in the basic display with information on the return time.
5.1.2.5.2 Party mode (short-term program)
Party mode causes one-time intermediate heating of all heating circuits up to a specified point in time and bridges an upcoming or already active absence cycle totally or partially. Once the set time expires, the heating circuits automatically return to the operating mode that was active before the party program. Short-term
programs such as ABSENT or PARTY are skipped here.
See 5.1.2.5 "Operating mode" button (basic display) , pg. 26
One-time extension of heating operation or intermediate heating during lowering operation outside the schedule.
Cancellation
Factory setting
Setting range
Display
Setting
Application
Page 30
Operation SDC / DHC
30 EN2H-0221GE51 R0808
An active party program can be cancelled early.
Press button.
Turn input button î and switch to automatic mode.
The active party program has been cancelled.
P1 as from activation
P1 (P2, P3) / 0.5 to 24 h to the current time P1
P1 (P2, P3)
Program-controlled resumption of heating operation. After activation of the party program, heating operation is continued until the following switch-on time of the current automatic program P1 (or P2 or P3, if enabled)
0,5 ... 24 h
The set value is added on to the current time and represents the end of the party time. When the party program is called up again, the last set value is saved and suggested as the initial value.
An active party program appears in the basic display with information on the party end time.
5.1.2.5.3 Automatic mode
In automatic operation, max. three time programs with different heating operation times are available. They are called up during start-up as factory-set and unlosable default programs P1, P2 or P3 and can, if necessary, be overwritten with their own switching times in the "Timeprograms" menu (see 5.2.2 "Timeprograms" menu, pg. 55).
Default programs P2 and P3 cannot be selected until the PROGRAM = P1 to P3 parameter is enabled in the "System Parameters" menu. Without enabling, only program P1 is active.
See 5.1.2.5 "Operating mode" button (basic display) , pg. 26
Cancellation
Factory setting
Setting range
Display
C
NOTE
Setting
Page 31
SDC / DHC Operation
EN2H-0221GE51 R0808 31
Disabling / enabling default program P2 to P3
Disabling
"System Parameters" menu, program parameter = P1. All heating circuits and the hot-water circuit solely refer to the default / individually programmed switching times in the program P1 parameter. Program P1 does not appear in the display in this operating mode (see 5.2.2 "Timeprograms" menu, pg. 55 and
5.2.3.2 Time program, pg. 73).
Enabling
"System Parameters" menu, program parameter = P1 to P3 (see
5.2.2 "Timeprograms" menu, pg. 55 and 5.2.3.2 Time program,
pg. 73).
An active automatic program appears in the basic display with the current date and time. If default programs P2 and P3 were
enabled, the corresponding symbol, Â,Ã or Ä, is also displayed depending on the selected program. The symbols are only displayed with the time program P1 to P3 active.
5.1.2.5.4 Manual summer operation (excluding heating operation)
With manual summer operation, only the hot-water circuit remains operation and controls the heat generator temperature based on the specified hot-water temperature and the specified hot-water switching time program. Heating operation is stopped, and protection from frost is provided. This feature is only available when control mode is set to 1.
See 5.1.2.5 "Operating mode" button (basic display) , pg. 26
Disabling / enabling default programs P2 to P3
Disabling
"System Parameters" menu, program parameter = P1. All heating circuits and the hot-water circuit solely refer to the default / individually programmed switching times in the time program = P1 parameter. Program P1 does not appear in the display in this operating mode (see 5.2.2.1 Selection of the control circuit, pg. 56 and 5.2.3.2 Time program, pg. 73).
C
C
Display
C
Setting
C
Page 32
Operation SDC / DHC
32 EN2H-0221GE51 R0808
Enabling
"System Parameters" menu, program parameter = P1 to P3 (see
5.2.2.1 Selection of the control circuit, pg. 56 and 5.2.3.2 Time
program, pg. 73).
Manual summer operation appears in the basic display with the information SUMMER. If default programs P2 and P3 were
enabled, the corresponding symbol, Â, Ã or Ä, is also displayed depending on the selected program. The symbols are only displayed with the time program P1 to P3 active.
5.1.2.5.5 Continuous heating operation
The HEATING operating mode ensures continuous heating operation without time limitations based on the specified daytime room temperature. Hot-water production occurs continuously based on the specified daytime hot-water temperature.
The HEATING operating mode remains active until another
operating mode is activated.
Activated continuous heating operation appears in the basic
display with the information HEATING.
5.1.2.5.6 Continuous lowering operation
The RED. HEATING operating mode causes continuously reduced heating operation based on the specified lowered room temperature. On the heating circuit levels, the reduced operating mode ECO (frost-protected deactivation mode) or RED (lowering mode) is set accordingly. The minimum temperature limit of the respective heating circuit must be taken into account.
See the "Direct Circuit" or "Mixed Heating Circuit 1" / "Mixed Heating Circuit 2" menu, reduced parameter = reduced operation and 12 parameter = minimum temperature limit.
Hot-water production occurs continuously based on the specified hot-water economy temperature (see "DHW" menu, hot water parameter = hot water at night).
C
Display
C
NOTE
Display
C
Page 33
SDC / DHC Operation
EN2H-0221GE51 R0808 33
The RED. HEATING operating mode remains active until another operating mode is activated.
Activated continuous lowering operation appears in the basic display with the information RED. HEATING.
In standby mode, the entire system is switched off and protected from frost (all frost-protection functions active).
Hot-water production is disabled and protected from frost. At storage temperatures below 5 °C, a reload to up to 8 °C takes place.
Total deactivation of heating and hot water with full building protection.
The heat generator and hot-water production remain in operation in case of external demand or demand by other heating circuits on the bus network. The heating circuit pumps are switched on briefly every day (pump anti-blocking protection).
The standby mode remains active until another operating mode is activated.
Activated continuous standby mode appears in the basic display with the information STANDBY.
5.1.2.6 "Switching time programs / Holiday programs" button
Using this button, you can create individualised switching time programs for heating and hot-water operation and set holiday mode.
See 5.1.2.6.1 Holiday mode, pg. 34 and 5.2.2 "Timeprograms" menu, pg. 55.
NOTE
Display
C
Application
NOTE
Display
Page 34
Operation SDC / DHC
34 EN2H-0221GE51 R0808
5.1.2.6.1 Holiday mode
In holiday mode, the heating circuits can be switched off and protected from frost or operated based on the settings for the RED. HEATING operating mode for the duration of the holiday based on the presetting ("Direct circuit" or "Mixed heating circuit 1" / "Mixed heating circuit 2" menu, parameter 25 = holiday operating mode).
Press button.
The menu-selection level Switching time programs / Holiday programs appears in the display.
Turn input button î to the left.
HOLIDAY appears in the display.
Press input button î.
HOLIDAY 01 appears in the display.
Press input button î.
The year flashes in the display.
Set year with the input button î.
Press input button î.
The day on which the holiday is to begin flashes in the display.
Set the day the holiday will begin with the input button î.
Press input button î.
TIL - - appears in the display.
Set the day you will return from holiday with the input
button î.
Press input button î.
The desired holiday timeframe is saved.
You can now enter additional holiday timeframes (up to 15 holiday blocks).
Longer absence while heating operation is active.
Setting
Application
Page 35
SDC / DHC Operation
EN2H-0221GE51 R0808 35
At outside temperatures below the frost-protection limit (see
5.2.3 "System Parameters" menu, pg. 72) the heating circuits are
controlled as follows:
Without wall devices: Based on a lowered room temperature specification of 3 °C.
With wall devices: Based on the room frost-protection limit of the respective heating circuit of 10 °C (see "Direct Heating Circuit" or "Mixed Heating Circuit 1", "Mixed heating circuit 2" menu, parameter 08 = room frost-protection limit).
An active holiday program can be cancelled in case of early return.
Press and hold the button for approx. 3 seconds until the
following appears in the display: "Holiday off".
Current date
Current date... (current date + 250 days)
An active holiday program appears in the basic display with information on the return date.
5.1.2.7 "System information" button
Calls up system information, such as temperatures and counter data.
The information on the outside temperature appears first after the
¤ button is pressed. Turning the input button î causes the
system temperatures and the counter and consumption states and operating states of the connected system components to
appear. Pressing the input button
î causes the respective
setpoint values to appear.
Collector flow temperature: No setpoint
Solar tank temperature: No setpoint
Outside temperature: Averaged value
The displayed information (see the following example) is independent of the installed or enabled system components and control circuits.
Control during
holidays
Cancellation
Factory setting
Setting range
Display
¤
Exceptions
NOTE
Page 36
Operation SDC / DHC
36 EN2H-0221GE51 R0808
Operating overview
Average/current outside temperature value
Outside temperature min. to max. (0:00 to 24:00 hours)
Heat generator temperature setpoint/actual value
Hot-water temperature setpoint/actual value
Flow temperature setpoint/actual value
Flow temp of mixed heating circuit 1 setpoint/actual value
Variable input 1 setpoint/actual value
Operating hours
Activations of heat generator
Program/operating mode direct heating circuit/pump status
Program/operating mode mixed heating circuit 1/pump status
Actuator of mixed heating circuit 1/status
Program/operating mode mixed heating circuit 2/pump status
Actuator of mixed heating circuit 2/status
Program/operating mode hot-water circuit/pump status
Heat generator status
Direct heating circuit pump function/status
Variable output 1 function/operating state
Turn input button to the left Turn input button to the right
Press button
Variable output 2 function/operating state
Flow temp of mixed heating circuit 2 setpoint/actual value
Variable input 2 setpoint/actual value
Variable input 2 setpoint/actual value
Page 37
SDC / DHC Operation
EN2H-0221GE51 R0808 37
If the ¤ button is pressed and held for approx. 3 s, the INFO TIME parameter appears.
With this parameter, the time it takes for automatic return to the basic display can be specified.
OFF No return. The last selected information display
continuously remains in the basic display until the next change.
1 ... 10 min Automatic return from the information level after the
specified time (in 0.5 minute increments).
OFF
5.1.2.7.1 Temperature displays
Information Display Condition Remarks
Outside temperature (1)
Determined value/Current value
Outside temperature (1)
Min./max. value (0:00 to 24:00 hours)
Outside sensor connected and no fault message
Outside temperature (2)
Determined value/Current value
Variable input configured as OS2
Connection OS2 to variable input VI1, VI2 or VI3
Outside temperature (2)
Min./max. value (0:00 to 24:00 hours)
OS2 connected, no fault message
EM-SET (energy management setpoint)
"EM-SET" Highest hot-water setpoint
and highest heating circuit setpoint in the system
Heat generator temperature (1)
Setpoint/Actual value
Heat generator specified
Code 1 only appears if BS2 is present
Heat generator temperature (2)
Setpoint/Actual value
Variable input configured as BS2
Connection BS2 to variable input VI1, VI2 or VI3
Setting time for
automatic return
Setting range
Factory setting
Page 38
Operation SDC / DHC
38 EN2H-0221GE51 R0808
Information Display Condition Remarks
Return temperature
Setpoint/Actual value
Return sensor connected and one of the functions for return increase is active
Connection of return sensor to associated variable input 1 or 2, VI can no longer be called up
Flow sensor of district heating valve VF1
Setpoint/Actual value
With district heating
controllers
Return sensor of district heating valve VFB
Setpoint/Actual value
With district heating
controllers
External heat generator disable
Disabled mode ON/OFF
External heat generator disable (VI1-VI3) specified
External contact to variable input VI1, VI2 or VI3
Flue gas temperature
Limit signal value/Actual value
Variable input configured as AGF
Connection only to variable input VI1
Water heater temperature (1)
Setpoint/Actual value
If hot-water circuit is present
Code 1 only appears if SF2 is present
Water heater temperature (2)
Setpoint/Actual value
Variable input configured as SF2
Connection to variable input VI1, VI2 or VI3
Water heater temperature controller
Load condition ON/OFF
Thermostat mode Thermostat instead of sensor
(SF1 only)
Demand via switching contact (VI1)
Demand ON/OFF
VI configured as demand contact
External contact to variable input VI1, VI2 or VI3
Demand via switching contact (VI2)
Demand ON/OFF
VI configured as demand contact
External contact to variable input VI1, VI2 or VI3
Demand via switching contact (VI3)
Demand ON/OFF
VI configured as demand contact
External contact to variable input VI1, VI2 or VI3
Mixed heating circuit 1 flow temperature
Setpoint/Actual value
Mixed heating circuit 1 specified
Mixed heating circuit 1 return temperature
Actual value Return temperature with
return maximum limit
Page 39
SDC / DHC Operation
EN2H-0221GE51 R0808 39
Information Display Condition Remarks
Mixed heating circuit 2 flow temperature
Setpoint/Actual value
Mixed heating circuit 2 specified
Mixed heating circuit 2 return temperature
Actual value Return temperature with
return maximum limit
Direct heating circuit room temperature
Setpoint/Actual value
Direct heating circuit specified
Setpoint inquiry without room temperature sensing: Current room setpoint of direct heating circuit
Mixed heating circuit 1 room temperature
Setpoint/Actual value
Mixed heating circuit 1 specified
Setpoint inquiry without room temperature sensing: Current room setpoint of mixer heating circuit 1
Mixed heating circuit 2 room temperature
Setpoint/Actual value
Mixed heating circuit 2 specified
Setpoint inquiry without room temperature sensing: Current room setpoint of mixed heating circuit 2
Direct heating circuit thermostat function
DC THERMOSTAT
Thermostat function specified
OFF = temperature limit exceeded
Mixed heating circuit 1 thermostat function
MC1 THERMOSTAT
Thermostat function specified
OFF = temperature limit exceeded
Mixed heating circuit 2 thermostat function
MC2 THERMOSTAT
Thermostat function specified
OFF = temperature limit exceeded
Solid fuel boiler temperature
Actual value VO1/2 configured as
solid fuel loading pump
Connection of FSKF to associated variable input 1 or 2, VI can no longer be called up
Solid fuel boiler buffer temperature
Actual value Solid fuel loading pump at
variable output, corresponds to KSPF or FPF, depending on configuration
Page 40
Operation SDC / DHC
40 EN2H-0221GE51 R0808
Information Display Condition Remarks
Buffer tank temperature at top
Setpoint/Actual value
VO1/2 configured as buffer tank loading pump
Connection of PF1 to associated variable input 1 or 2, VI can no longer be called up
Buffer tank temperature at bottom
Setpoint/Actual value
VO1/2 configured as buffer tank loading pump
Connection of PF2 to variable input VI1, VI2 or VI3
Solar collector flow temperature
Actual value VO1/2 configured as
solar tank loading pump
Special sensor
Solar tank temperature
Actual value VO1/2 configured as
solar tank loading pump
Solar collector return temperature
Actual value VO1/2 configured as
solar tank loading pump
Connection of KRLF to variable input VI1, VI2 or VI3
Solar tank switch­over temperature
Actual value Solar loading valve activated
5.1.2.7.2 Operating states
An operating state inquiry occurs after the information menu is called up by turning the input button anti-clockwise. The following displays appear only under the specified conditions and may not be available (depends on device version).
Information Display Condition Remarks
Direct heating circuit operating status
Direct heating circuit specified
Heating program: Holiday, Absent Til, Party Til, Auto, Summer, Heating, Red. Heating, Standby
Switching time program: P1 (P2, P3) control mode: Day, RED, ECO
Mixed heating circuit 1 operating status
Mixed heating circuit 1 specified
Heating program: Holiday, Absent Til, Party Til, Auto, Summer, Heating, Red. Heating, Standby
Switching time program: P1 (P2, P3) control mode: Day, RED, ECO
Page 41
SDC / DHC Operation
EN2H-0221GE51 R0808 41
Information Display Condition Remarks
MC1 actuator operating status
Mixed heating circuit 1 specified
Mixed heating circuit 1 opens, closes or does not move
Mixed heating circuit 2 operating status
Mixed heating circuit 2 specified
Heating program: Holiday, Absent Til, Party Til, Auto, Summer, Heating, Red. Heating, Standby
Switching time program: P1 (P2, P3) control mode: Day, RED, ECO
MC2 actuator operating status
Mixed heating circuit 2 specified
Mixed heating circuit 2 opens, closes or does not move
District heating valve operating status
District heating valve opens, closes or does not move
With district heating controllers
Heat generator operating status (st. 1)
Heat generator specified Information on the switching
state of the multi-stage heat generator
Heat generator operating status (st. 2)
Multi-stage heat generator specified
Information on the switching state of the second stage of the heat generator
Operating status of modulating heat generator
Modulating burner specified
If a single-stage modulating heat generator is set, display of actual value and setpoint occurs in %
Hot-water circuit operating status
Hot-water circuit specified
Hot-water program: Holiday, Absent Til, Party Til, Auto, Summer, Heating, Red. Heating, Standby
Switching time program: P1 (P2, P3) control mode: Day, RED, ECO
Page 42
Operation SDC / DHC
42 EN2H-0221GE51 R0808
Information Display Condition Remarks
Function and status of direct heating circuit pump
Outputs specified
based on function
Solar (SOP), circulation (CIR), electric heating rod (ELH), feeder (CHP), boiler circuit (KKP1, KKP2), fault message (SMA), return (RLP), buffer (PLP), solid fuel (FSP), heating circuit (HKP), constant (KP), timer (CLOCK)
Function and status of variable output 1
Outputs specified
based on function
Solar (SOP), circulation (CIR), electric heating rod (ELH), feeder (CHP), boiler circuit (KKP1, KKP2), fault message (SMA), return (RLP), buffer (PLP), solid fuel (FSP), heating circuit (HKP), constant (KP), timer (CLOCK)
Function and status of variable output 2
Outputs specified
based on function
Solar (SOP), circulation (CIR), electric heating rod (ELH), feeder (CHP), boiler circuit (KKP1, KKP2), fault message (SMA), return (RLP), buffer (PLP), solid fuel (FSP), heating circuit (HKP), constant (KP), timer (CLOCK)
District heating valve volume flow
Heat generator specified With district heating
controllers
District heating valve capacity
Heat generator specified With district heating
controllers
Heat generator (1) start-ups
Heat generator specified Information on the number
of heat generator switch-ons (burner start-ups) of the multi-stage heat generator.
Operating hours of heat generator (1)
Heat generator specified Information on the number
of heat generator operating hours of the multi-stage heat generator.
Page 43
SDC / DHC Operation
EN2H-0221GE51 R0808 43
Information Display Condition Remarks
Heat generator switch-ons stage 2
Multi-stage heat generator specified
Information on the number of heat generator switch-ons (burner start-ups) of the second stage.
Heat generator operating hours stage 2
Multi-stage heat generator specified
Information on the number of heat generator operating hours of the second stage.
Test temperature for measurement purposes
KVT sensor connected and VI configured.
Controller-independent test temperature, sensor connection to variable input VI1, VI2 or VI3
Operating status of ext. switching modem
VI configured as switching modem
Control modes based on the switching state of the modem: AUTO (automatic) STBY (standby), HEAT (continuous heating), RED (continuously reduced).
Solar heating capacity
VO1/2 configured as solar tank loading pump
Solar loading pump at variable output
Solar heat balance
VO1/2 configured as solar tank loading pump
Solar loading pump at variable output
Switch-ons
Solar loading pump
VO1/2 configured as solar tank loading pump
Solar loading pump at variable output
Operating hours
Solar loading pump
VO1/2 configured as solar tank loading pump
Solar loading pump at variable output
Page 44
Operation SDC / DHC
44 EN2H-0221GE51 R0808
5.1.2.8 "Manual mode" / "Emission measurement" button
5.1.2.8.1 Manual mode
If this button is pressed and held longer than 5 s in the basic display, the controller is switched to manual mode. In this operating mode, the required heat generator temperature is
specified manually with the input button î according to the respective heating need. A controller set to manual mode has no effect in heat circuit expansion.
The heat generator setpoint is set between the minimum and maximum heat generator temperatures and appears flashing at the bottom left-hand side. The current heat generator temperature appears statically on the right-hand side in the basic display. The set switching differential corresponds to the value of automatic control and is symmetrical to the set value.
Controller malfunctions (emergency operation), errors
The maximum heat generator temperature limit is paramount to the heat generator switching differential and stops the heat generator in case of exceedance.
With control devices operated purely as a heating circuit expansion, the setting of the temperature has no effect.
The last value to which the control device adjusted the heat generator temperature appears as a recommendation.
Press button or button, to return to the last selected operating mode.
C
C
Application
NOTE
Cancellation
Page 45
SDC / DHC Operation
EN2H-0221GE51 R0808 45
5.1.2.8.2 Emission measurement (not with district heating controllers)
ATTENTION
Emission measurements may only be carried out by the chimney sweep.
Pressing the button controls the heat generator for a duration of 20 min based on the set maximum temperature limit. The remaining time is displayed and counted down.
With two-stage heat generators, both stages are in operation (measurement at nominal output).
The heat generator is adjusted to the maximum heat generator temperature. All heating circuits and the hot-water production adjust their setpoint to the respective maximum temperature.
ATTENTION
There is a danger of scalding by hot water, as the hot-water temperature can exceed the set setpoint temperature.
Emission measurement by the chimney sweep.
Emission measurement can be cancelled at any time with the
or button.
Function
Application
Cancellation
Page 46
Operation SDC / DHC
46 EN2H-0221GE51 R0808
5.1.2.9 Access to the technician / OEM area
Entering a technician or OEM code enables additional setting options in the parameter menu. The technician code is: 1234.
For access to the OEM area, please ask your field-service contact partner.
Procedure:
Press the and buttons simultaneously. The first
number of the 4-digit code flashes.
Set the first code number by turning the input button.
Press the input button. The second number flashes.
Enter all remaining code numbers as described in Steps 2 and
3. After entering the last code number, the controller is enabled for the respective area (technician or OEM).
Press and hold the rotary button longer than 3 seconds. You
reach the menu-selection level and can enter / modify parameters.
Pressing the button jumps back to the previous selection.
Pressing the button, pressing and holding the input button longer than 3 seconds or waiting until the set info time expires causes a jump back to the basic display.
Page 47
SDC / DHC Operation
EN2H-0221GE51 R0808 47
5.1.2.10 Heating curve
Determines the heating curve for the heating circuits.
The heating curve describes the relationship of the flow temperature change to the outside temperature change. With a larger heating surface, such as with floor heaters, the heating curve has a less extreme slope than with a smaller heating surface (e.g. radiators).
The set value refers to the lowest outside temperature used for heat demand calculation.
ATTENTION
This parameter must be set by the technician and should no longer be changed.
Press and hold input button î for 3 s.
Turn the input button î to select the desired heating circuit (HC,
MC-1 or MC-2) and confirm it by pressing the input button î. The design temperature (system) appears at the bottom right­hand side of the display.
Press input button î.
The slope of the heating curve appears at the bottom left-hand side of the display.
Set the flashing heating curve value by turning the input button
î (design temperature also flashes and is changed
automatically depending on the slope of the heating curve).
Confirm by pressing the input button î.
Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).
Press
button to return to the basic display.
0,2 ... 3,5
C
Setting
Setting range
Page 48
Operation SDC / DHC
48 EN2H-0221GE51 R0808
Direct heating circuit (HC) = 1,5
Mixed heating circuit 1 (MC-1) = 1
Mixed heating circuit 2 (MC-2) = 1
x
y
a
x Boiler / flow temperature [°C]
y Outside temperature [°C]
a T
room
[°C]
5.2 Menu-selection level
The control device contains a menu-selection level that is structured differently, depending on the respective device version.
Press and hold input button î for approx. 3 seconds.
The menu selection always begins with the TIME – DATE
menu.
Turn input button î to select additional menus.
Press input button
î to confirm the selected menu.
Factory setting
Access
Page 49
SDC / DHC Operation
EN2H-0221GE51 R0808 49
9
Variable input 2
Climate zone
Temperature offset
of heat generator
during hot-water
circuit loading
Room thermostat
function
Room thermostat
function
Burner switching
differential II
Starting point of
flexible district
heating return
temperature
Heat balance
Buffer discharge
protection
Quick hot-water
connection
Variable output 2
test
Fault message 9
Sensor of variable
input 2
8
Variable input 1
Demand contact
module for variable
input 3
Tank discharge
protection
Room frost
protection limit
Room frost
protection limit
Burner switching
differential I
Max. return
temperature
setpoint
Priority parallel
switch-over
Buffer start-up
protection
Switch-over of
base load with
grouping
Variable output 1
test
Fault message 8
Sensor of variable
input 1
7
Variable output 2
Demand contact
module for variable
input 2
Hot-water circuit
control mode
Heating limit
Heating limit
Minimum burner
runtime
Runtime of district
heating valve 2
Heat generator
cycle disable
Follow-up switch-
off differential
Peak-load stage
Tank loading pump
test
Fault message 7
Buffer sensor of
collector
6
Variable output 1
Demand contact
module for variable
input 1
Max. temperature
limit for hot-water
circuit
Sensor control
mode
Runtime of district
heating valve 1
Control mode
Switch-on
differential
extension
Guidance stage
Mixer motor 2 test
Fault message 6
Collector sensor
5
Direct heating
circuit pump output
System frost
protection
Transducer for hot-
water circuit
Limit mode of
maximum limit
Adjustment time
Buffer maximum
temperature limit
Heat generator
cycle disable
Forced discharge
Stage reversal
Mixed heating
circuit pump 2 test
Fault message 5
Mixed heating
circuit 2 flow
sensor
4
Switch-over
Mixed heating
circuit 2 output
Summer/Heat limit
Legionella
protection
temperature
Room factor
Room factor
Maximum
temperature limit
Secondary flow
boost
Collector
maximum
temperature
Switch-off
differential
Buffer switching
differential
Switch-over
capacity of stage
sequence
Mixed heating
circuit 2 bus
authorisation
Mixer motor 1 test
Fault message 4
Mixed heating
circuit 1 flow
sensor
3
Day - Month
Mixed heating
circuit 1 output
Operating mode
Legionella
protection time
Room connection
Room connection
Minimum
temperature limit
District heating
valve minimum
travel
Follow-up time of
pump
Solar loading
pump minimum
runtime
Switch-on
differential
Boiler temperature
offset
Regulation
Switch-off delay
Mixed heating
circuit 1 bus
authorisation
Mixed heating
circuit pump 1 test
Fault message 3
Hot-water sensor
2
Year
Hot-water loading
pump output
Time program
Legionella
protection day
Heating system
Heating system
Start-up protection
Maximum flow
temperature
setpoint limit
Switch-off
differential
Switch-off
differential
Max. temperature
Max. temperature
Connection delay
Direct heating
circuit bus
authorisation
Direct heating
circuit pump test
Fault message 2
Heat generator
sensor
1
Time
Hydraulic
schematic
Language
selection
Hot water at night
Reduced operation
Reduced operation
Design
Offset
Return
temperature
setpoint
Switch-on
differential
Min. temperature
Min. temperature
Regulation
Switching
differential
Central device
address
Heat generator
test
Fault message 1
Outside sensor
0
Heating curve
slope
Heating curve
slope
Parameter
Date
Hydraulics
System parameter
Hot water
Direct heating
circuit
Mixed heating
circuit 1/2
Heat generator
District heating
Return increase
Solar
Solid fuel
Buffer
Total flow control
Cascading
Data bus
Relay test
Fault messages 1/2
Sensor calibration
Programming
Configuration
Configuration
(heating circuits,
control paths)
Service functions
Page 50
Operation SDC / DHC
50 EN2H-0221GE51 R0808
19
Frost protection
mode
Sample time Ta
Modulation of
proportional part
Xp
Fault message 19
18
Cycle temperature
enable
P-part Xp
Fault message 18
17
Behaviour
of
heat
generator during
extended running
time
Return maximum
temperature limit
Flue gas
temperature limit
Fault message 17
16
Type code
Circulation pump
Screed function
Screed function
Flue gas
temperature
monitoring
Switch-over
temperature
Fault message 16
15
Locking code for
heating technician
Follow-up time of
pump
Follow-up time of
pump
Charging pump
extended running
time
Max. volume flow
Solar loading
switch-over test
cycle
Fault message 15
14
Automatic set
function
Economy interval
cycle
Temperature offset
of heating circuit
Temperature offset
of heating circuit
Boiler circuit pump
extended running
time
Max. thermal
output
Final switch-off
temperature
Fault message 14
13
Logical fault
messages
Circulation pump
economy interval
pause
Maximum
temperature limit
Maximum
temperature limit
Flow time of boiler
circuit pump or
parallel heat
generator enable
Calibration of
volume flow
Heat capacity of
medium
Fault message 13
Mi
xe
d
h
ea
ti
ng
circuit 2 room
sensor
12
Anti-blocking
function
Circulation pump
switching time
program
Minimum
temperature limit
Minimum
temperature limit
Hot-water circuit
loading 1-2 stage
Calibration of
thermal output
Density of medium
Fault message 12
Mi
xe
d
h
ea
ti
ng
circuit 1 room
sensor
11
Indirect return
increase via mixed
heating circuit
Automatic exit time
Hot-water loading
pump extended
running time
Constant
temperature
setpoint
Constant
temperature
setpoint
Boiler start-up
discharge stage II
District heating
valve return limit
Volume flow
B
u
ff
er
l
oa
di
ng
pump extended
running time
Fault message 11
Direct heating
circuit room sensor
10
Variable input 3
Building type
Switching
differential of hot-
water circuit
Assignment of
outside sensor
Assignment of
outside sensor
Connection delay
stage II
Max
.
return
temperature
setpoint during
hot-water circuit
loading
Reset heat
balance
Buffer control
mode
System
Fault message 10
Sensor of variable
input 3
Parameter
Date
Hydraulics
System parameter
Hot water
Direct heating
circuit
Mixed heating
circuit 1/2
Heat generator
District heating
Return increase
Solar
Solid fuel
Buffer
Total flow control
Cascading
Data bus
Relay test
Fault messages 1/2
Sensor calibration
Programming
Configuration
Configuration
(heating circuits,
control paths)
Service functions
Page 51
SDC / DHC Operation
EN2H-0221GE51 R0808 51
29
curve for
emergency
operation without
outside senso
r
Heat generator
forced discharge
28
Fault memory 2
g
temperature of
mixed heating
circuit
Heating
circuit
minimum
temperature limit
switching
differential
27
Heating circuit
minimum
temperature limit
26
Room setpoint
ramp
Room setpoint
ramp
Base load offset
25
Cooling switch-on
temperature
Holiday control
mode
Holiday control
mode
Outside
temperature
disable
24
Room control Tn
Room control Tn
Modulation of start
power
23
Locking code for
operating level
Room control C-
factor
Room control C-
factor
Modulation of start
time
22
Actuator end
position function
Modulation of
runtime
21
Adjustment of the
real time clock
(RTC)
Actuator runtime
Modulation of
adjustment time Tn
Reset fault
messages
20
I-part Tn
Modulation of
sample time Ta
Fault message 20
Parameter
Date
Hydraulics
System parameter
Hot water
Direct heating
circuit
Mixed heating
circuit 1/2
Heat generator
District heating
Return increase
Solar
Solid fuel
Buffer
Total flow control
Cascading
Data bus
Relay test
Fault messages 1/2
Sensor calibration
Programming
Configuration
Configuration
(heating circuits,
control paths)
Service functions
Page 52
Operation SDC / DHC
52 EN2H-0221GE51 R0808
39
Hot-water circuit
pre-control spread
Resetting of stage
1 burner start-up
and operating hour
counters
38
Inverse outside
temperature
disable
37
Burner counter
mode
36
35
Parameter reset
Hot-water capacity
limit
34
Heating capacity
limit
33
Selection
SDC/DHC
32
31
Full-load control
30
OEM maximum
limit
Parameter
Date
Hydraulics
System parameter
Hot water
Direct heating
circuit
Mixed heating
circuit 1/2
Heat generator
District heating
Return increase
Solar
Solid fuel
Buffer
Total flow control
Cascading
Data bus
Relay test
Fault messages 1/2
Sensor calibration
Programming
Configuration
Configuration
(heating circuits,
control paths)
Service functions
Page 53
SDC / DHC Operation
EN2H-0221GE51 R0808 53
H
ea
ti
ng c
i
rcu
it
name
Heating circuit
name
Heating circuit
name
47
Lowering ramp
Lowering ramp
46
Pre-heat time at
0°C
Pre-heat time at
0°C
45
Without room
sensor
Without room
sensor
44
Min. jump back
temperature
Min. jump back
temperature
43
Max. pre-heat time
Max. pre-heat time
OEM
42
Min. pre-heat time
Min. pre-heat time
Heating technician
41
Switch-on
optimisation
Switch-on
optimisation
User
40
Offset
valve
position of hot-
water circuit pre-
control
Resetting of stage
2 burner start-up
and operating hour
counters
Parameter
Date
Hydraulics
System parameter
Hot water
Direct heating
circuit
Mixed heating
circuit 1/2
Heat generator
District heating
Return increase
Solar
Solid fuel
Buffer
Total flow control
Cascading
Data bus
Relay test
Fault messages 1/2
Sensor calibration
Programming
Configuration
Configuration
(heating circuits,
control paths)
Service functions
Page 54
Operation SDC / DHC
54 EN2H-0221GE51 R0808
5.2.1 "Time - Date" menu
The following current calendar values can be specified in this menu:
Time
Year
Day - Month
Time change mode (summer / winter time)
All listed daytime values are set at the factory and generally do not need to be updated.
An internal, pre-programmed calendar ensures automatic time change on the annually recurring summer / winter time switchover dates. If necessary, the automatic time change can be deactivated. The current weekday, Mo to Su is determined from the calendar date and does not need to be set.
Corrections for rare fault cases
See 5.2 Menu-selection level, pg. 48
Turn input button î and select the "Time - Date" menu.
Turn input button î and select the desired calendar value
(time, year, day - month, change).
Press input button
î and change the corresponding value by
turning the input button
î.
Press input button î to confirm the set value.
Turn input button î to select and change additional calendar
values.
Returning to the basic display takes place by pressing the button or automatically after the set information time (see
5.1.2.7 "System information" button, pg. 35).
NOTE
Application
Access
Setting
Returning
Page 55
SDC / DHC Operation
EN2H-0221GE51 R0808 55
5.2.2 "Timeprograms" menu
Individualised switching time programs for heating and hot-water operation can be created in this menu. Here, the factory-set default programs P1 (and, if enabled, P2 and P3 as well) of each heating circuit and the hot-water circuit are overwritten by individualised switching times and temperature specifications. This is especially advantageous if correspondingly adapted heating programs are to be created in case of periodically recurring assignments with different assignment times (e.g. shift work). Max. three heating cycles, each with a switch-on and switch-off time, are available for each day of the week for programming switching times. Each heating cycle can also be combined with a freely-selectable temperature specification.
The default programs are not lost when overwritten by individually created programs. Individualised programs, however, are deleted when default programs are reloaded and must be recreated. For this reason, individualised switch-on / switch-off times and temperature specifications should always be entered in the tables provided for this purpose (see 9 Log, pg. 254).
Press button.
Returning to the basic display takes place by pressing the button or automatically after the set information time (see
5.1.2.7 "System information" button, pg. 35).
NOTE
Access
Returning
Page 56
Operation SDC / DHC
56 EN2H-0221GE51 R0808
5.2.2.1 Selection of the control circuit
After accessing the "Timeprograms" menu, the desired control circuits can be selected with the input button î in the following
sequence:
Direct heating circuit (HC)
Mixed heating circuit 1 (MC-1)
Mixed heating circuit 2 (MC-2)
Hot-water circuit (DHW)
Press input button î to access the selected circuit.
5.2.2.2 Selection of the program
If the switching time programs P2 and P3 have been enabled (see "System Parameter" menu, program parameter = P1 to P3), the program selection appears.
If switching time programs P2 and P3 are disabled, program selection is automatically skipped (see "System Parameters" menu, program parameter = P1).
5.2.2.3 Selection of day of the week and cycle
Once the program is selected, the first cycle of the first day of the week (MO 1) and the relevant section in the top time bar flash.
The other cycles are selected by turning the input button î and confirmed by pressing the input button î.
Page 57
SDC / DHC Operation
EN2H-0221GE51 R0808 57
5.2.2.4 Programming switching times and cycle temperatures
5.2.2.4.1 Switch-on time
The switch-on time is the start of heating or, with enabled switch­on optimisation, the start of assignment.
After selecting the day of the week and the corresponding cycle, the respective switch-on time appears flashing and can be set
with the input button î. The time bar in the top part of the display provides an overview of all programmed cycles between 0:00 and 24:00 hours on the selected day of the week.
The switch-on time cannot be set below the switch-off time of a previous cycle or below 0:00 hours of the selected day of the week.
If the switch-on time is changed, the corresponding time bar display is adjusted to the left-hand side.
If the switch-on time is made equal to the switch-off time, the corresponding cycle is deleted. A subsequent cycle is automatically shifted to the position of the deleted cycle upon acceptance.
With subsequent insertion of a cycle that has been bumped up, the corresponding day of the week must be reprogrammed.
A flashing switch-on time is accepted by pressing the input button
î.
5.2.2.4.2 Switch-off time
The switch-off time is the end of heating or, with enabled switch­off optimisation, the end of assignment.
Once the switch-on time is accepted, the associated switch-off time appears flashing and can be changed with the input button î. The
time bar in the top part of the display provides an overview of all programmed cycles between 0:00 and 24:00 hours on the selected day of the week.
NOTE
Page 58
Operation SDC / DHC
58 EN2H-0221GE51 R0808
The switch-off time cannot be set higher than the switch-on time of a subsequent cycle.
If the switch-on time is changed, the corresponding time bar display is adjusted to the right-hand side.
If the switch-off time is made equal to the switch-on time, the corresponding cycle is deleted. A subsequent cycle is automatically shifted to the position of the deleted cycle upon acceptance.
With subsequent insertion of a cycle that has been bumped up, the corresponding day of the week must be reprogrammed.
A flashing switch-off time is accepted by pressing the input button î.
5.2.2.4.3 Cycle temperature
Once the switch-off time is accepted, the associated cycle temperature appears flashing and can be changed immediately
with the input button î. With heating circuits, the displayed cycle temperature is always based on the desired room temperature; with the hot-water circuit, it is based on the desired normal hot­water temperature in the selected cycle.
A flashing cycle temperature is accepted by pressing the input button î.
At the same time, the last called-up cycle appears flashing so that it may be monitored; additional cycles can then be selected directly and edited in the same way in the order: switch-on time, switch-off time, cycle temperature.
NOTE
Page 59
SDC / DHC Operation
EN2H-0221GE51 R0808 59
Switching time programming (programs P2 and P3 disabled)
Upon accessing the menu-selection level, the "Timeprograms" menu always appears first.
Enabling of programs P2 and P3 in the "System Parameters"
menu (see 5.2 Menu-selection level, pg. 48 ).
Select heating circuit:
Select day and cycle:
Change:
Temperature
End of heating
Monitoring
Start of heating
Mo­Hcy-1
HC MC -1 MC -2 DHW
Mo­Hcy-2
Mo­Hcy-3
Only appears if there are switching times in the second heating cycle.
Tu­Hcy-1
Su­Hcy-3
Default time
We Th Fr Sa
Return:
Return to the basic display:
3 s
Copy circuit
Change:
Change:
Copy day
HC Direct heating circuit
MC-1 Mixed heating circuit 1
MC-2 Mixed heating circuit 2
DHW Hot-water heating circuit
Hcy Heating cycle
Page 60
Operation SDC / DHC
60 EN2H-0221GE51 R0808
Default switching time program (P1) for heating and hot water
Uniform, continuous heating and hot-water operation on all days of the week
Default program P1
Heating operation Heating circuit Day
from to
Heat generator heating circuit
Mo to Su 6:00 22:00
Hot-water circuit Mo to Su 5:00 22:00
Mixed heating circuit 1 / 2 Mo to Su 6:00 22:00
Page 61
SDC / DHC Operation
EN2H-0221GE51 R0808 61
Switching time programming (program P2 and P3 enabled)
Upon accessing the menu-selection level, the "Timeprograms" menu always appears first. Enabling of programs P2 and P3 in the "System Parameters" menu (see 5.2 Menu-selection level, pg. 48 ).
Select heating circuit:
Select day and cycle:
Select program:
Change:
Change:
Temperature
End of heating
Monitoring
Start of heating
Mo­Hcy-1
HC
P1 P2 P3
MC -1 MC -2 DHW
Mo­Hcy-2
Mo­Hcy-3
Only appears if there are switching times in the second heating cycle
Tu­Hcy-1
Su­Hcy-3
Default time
We Th Fr Sa
Copy day
Return:
Return to the basic display:
3 s
Copy circuit
Change:
HC Direct heating circuit
MC-1 Mixed heating circuit 1
MC-2 Mixed heating circuit 2
DHW Hot-water heating circuit
Hcy Heating cycle
Page 62
Operation SDC / DHC
62 EN2H-0221GE51 R0808
Default program P1
Heating operation Heating circuit Day
from to
Heat generator heat­ing circuit
Mo to Su 6:00 22:00
Hot-water circuit Mo to Su 5:00 22:00
Mixed heating circuit 1 / 2
Mo to Su 6:00 22:00
Default program P2
Heating operation Heating circuit Day
from to from to
Mo to Th 6:00 8:00 16:00 22:00
Fr 6:00 8:00 13:00 22:00
Boiler heating circuit
Sa to Su 6:00 22:00
Mo to Th 5:00 8:00 15:30 22:00
Fr 5:00 8:00 12:30 22:00
Hot-water circuit
Sa to Su 6:00 23:00
Mo to Th 6:00 8:00 16:00 22:00
Fr 6:00 8:00 13:00 22:00
Mixed heating circuit 1 / 2
Sa to Su 7:00 23:00
Default program P3
Heating operation Heating circuit Day
from to
Mo to Fr 7:00 18:00 Heat generator heat-
ing circuit
Sa to Su Reduced
Mo to Su 6:00 18:00 Hot-water circuit
Sa to Su Reduced
Mo to Su 7:00 18:00 Mixed heating
circuit 1 / 2
Sa to Su Reduced
Page 63
SDC / DHC Operation
EN2H-0221GE51 R0808 63
5.2.2.4.3.1 Copying switching time programs (days)
Block programming enables the switching times and cycle temperatures of any day of the week to be copied
1 – To any days within the week (Mo, Tu, We, ..., Su)
2 – To all weekdays (Mo to Fr)
3 – To the weekend (Sa to Su)
4 – To the entire week (Mo to Su)
Calling up the copy function (days)
See flowcharts on pg. 65
Press input button î to confirm the copy function.
Turn input button î to select the source day (MO to SU) to be
copied. The respective automatic program P1 (P2, P3) of the source day is copied in the display with the time switch symbol and the program index.
Press input button î to confirm the source day.
The source day appears flashing.
Turn input button î to select the following setting values and
confirm by pressing the input button
î:
The following target days (Mo to Su) individually
All days of the week (1 to 7) as a week block
All weekdays (1 to 5) as a weekday block
The weekend days (6 to 7) as a weekend block
Acceptance is confirmed by acknowledging DAY COPY OK.
After acknowledgement, the following target days appear one after another automatically with each additional press of the input
button
î and can be skipped and accepted if necessary.
Pressing the button causes an immediate return to the basic display.
Only complete days with all cycles and temperature specifications and the respective program can be copied.
Source day
Target day
NOTE
Page 64
Operation SDC / DHC
64 EN2H-0221GE51 R0808
5.2.2.4.3.2 Copying switching time programs (heating circuits)
Block programming also enables the copying of all switching times and temperature specifications of a heating circuit to another heating circuit.
Calling up the copy function (heating circuits)
See flowcharts on pg. 65
Press input button î to confirm the copy function.
Turn input button î to select the source circuit to be copied
(HC, MC-1, MC-2, DHW). If automatic program P1, P2 or P3 (see "System Parameter" menu, PROGRAM parameter = P1 to P3) was enabled, the desired switching time program P1, P2 or P3 of the source circuit can be selected. If not enabled, program selection is skipped.
Press input button î, to confirm the source circuit.
Based on the same chart, the desired target circuit and, if enabled, the desired program can be selected and accepted.
Acceptance is confirmed by acknowledging COPY OK. The copy function is then called up again to copy additional circuits, if necessary.
Heating circuits cannot be copied to hot-water circuits or the re­verse due to the different temperature specifications. If a heating circuit (HC, MC-1, MC-2) is selected as the source circuit, the hot­water circuit (DHW) switches off as the target circuit.
A hot-water circuit as the source circuit is also the target circuit. In this case, only switching time programs P1 to P3 are copied among one another.
Pressing the
button causes an immediate return to the basic
display.
Source circuit
Target circuit
NOTE
Page 65
SDC / DHC Operation
EN2H-0221GE51 R0808 65
Block programming
The copy function enables a source day to be copied to any target days or to all days of the week (week programming). All cycles of the source day are copied. Individual heating cycles cannot be copied.
î
ö
î
ö
ö
HC
Select heating circuit:
Select copy function:
Select program:
Mo Hcy-1
Mo Hcy-2
Mo Hcy-3
MC -2MC -1
P1 P2 P3
DHW
Default time
Tu Hcy-1
Copy circuit
Su Hcy-3
Copy day
We Th Fr Sa
1)
HC Direct heating circuit
MC-1 Mixed heating circuit 1
MC-2 Mixed heating circuit 2
DHW Hot-water heating circuit
1) Program selection for source and target circuits are
skipped if programs P2 and P3 are disabled in the "System Parameter" menu.
Page 66
Operation SDC / DHC
66 EN2H-0221GE51 R0808
Copy day
Copy from Mo
Copy Mo to Tu
Copy day OK
Select and copy other target days if necessary
Wednesday as with Monday
Return to the basic display:
Tuesday as with Monday
Source day
Source day
Select source day: Example: Monday
Copy source day to first target day:
Acknowledge:
Select first target day: Example: Tuesday
Copy source day to second target day
Acknowledge:
Select second target day: Example: Wednesday
Second target day
Mo ... Su
1 target day or 1-7 (Mo ... Su) or 1-5 (Mo ... Fr) or 6-7 (Sa ... Su)
Copy Mo to We
Copy day OK
Page 67
SDC / DHC Operation
EN2H-0221GE51 R0808 67
Copying heating circuits
Heating circuits cannot be copied to hot-water circuits since they have different cycle temperatures: If a heating circuit is selected as the source circuit, the hot-water circuit can no longer be called up as the target circuit. The hot-water circuit as the source circuit is also the target circuit. In this case, only programs of the hot­water circuit are copied among one another if they were enabled in the "System Parameter" menu.
Source circuit MC -2 P3
Select copy function:
Select source circuit:
Source circuit HC
Select source circuit program:
Select target circuit:
Target circuit HC
1)
Select target circuit program:
Copy:
Copy
-OK-
Copy additional heating circuits if necessary
Program P1 (direct heating circuit) = Program P2 (mixed heating circuit 2)
Acknowledge:
Exit:
Basic display
1)
HC MC-1 MC-2 DHW
Default time
Copy circuit
Source circuit HC P1
Source circuit MC -1
Source circuit MC -2
Source circuit MC -1 P2
Target circuit MC -1
Target circuit MC -2
Target circuit MC -2 P3
Target circuit MC -2 P1
Target circuit MC -2 P2
NOTE
Page 68
Operation SDC / DHC
68 EN2H-0221GE51 R0808
HC Direct heating circuit
MC-1 Mixed heating circuit 1
MC-2 Mixed heating circuit 2
DHW Hot-water heating circuit
1) Program selection for source and target circuits are
skipped if programs P2 and P3 are disabled in the "System Parameter" menu.
5.2.2.4.4 Reloading default programs
See flowchart on pg. 70
Individually created switching time program P1, P2 or P3 can be overwritten with the original default switching time program P1, P2 or P3.
For this purpose, select the DEFAULT-TIME function within the heating circuit selection after accessing the "Timeprograms" menu.
After confirming by pressing the input button î, the circuit dedicated to reloading appears flashing (HC, MC-1, MC-2, ALL).
If the automatic programs P1, P2 and P3 (see "System
Parameter" menu, program parameter = P1 to P3) were enabled,
the desired switching time program P1, P2 or P3 of the heating circuit affected by the reload can be selected. If not enabled, program selection is skipped.
Resetting then occurs by pressing and holding the input button approx. 5 s until acknowledgement appears in the display.
Resetting is confirmed by acknowledging COPY OK.
The DEFAULT-TIME function is then called up again to replace other circuits with their default programs if necessary.
Resetting
Page 69
SDC / DHC Operation
EN2H-0221GE51 R0808 69
ATTENTION
With the setting value ALL, all heating circuits and the hot­water circuit are overwritten with their default switching times with regard to the selected program.
When overwriting occurs, individually created switching time programs are permanently lost and must be recreated from scratch.
Pressing the button causes an immediate return to the basic display.
Page 70
Operation SDC / DHC
70 EN2H-0221GE51 R0808
Reloading default programs
Switching time programs P2 and P3 disabled
HC Direct heating circuit
MC-1 Mixed heating circuit 1
MC-2 Mixed heating circuit 2
DHW Hot-water heating circuit
Page 71
SDC / DHC Operation
EN2H-0221GE51 R0808 71
Reloading default programs
Switching time programs P2 and P3 enabled
DHW
HC Direct heating circuit
MC-1 Mixed heating circuit 1
MC-2 Mixed heating circuit 2
DHW Hot-water heating circuit
Page 72
Operation SDC / DHC
72 EN2H-0221GE51 R0808
5.2.3 "System Parameters" menu
The system parameters refer to general limiting parameters and specification values within the heating system.
See 5.2 Menu-selection level, pg. 48
Returning to the basic display takes place by pressing the button or automatically after the set information time (see
5.1.2.7 "System information" button, pg. 35).
5.2.3.1 Language selection
Several languages can be selected for all information that appears in the display.
After selecting the language and confirming it by pressing the input button î, additional communication takes place in the
respective language.
DE German
GB English
FR French
IT Italian
NL Dutch
ES Spanish
PT Portuguese
HU Hungarian
CZ Czech
PL Polish
RO Romanian
RU Russian
TR Turkish
S Swedish
N Norwegian
German
Access
Returning
Setting values
Factory setting
Page 73
SDC / DHC Operation
EN2H-0221GE51 R0808 73
5.2.3.2 Time program
This parameter specifies enabling of the switching time programs for program selection and for individualised switching time programming. In the state of delivery, only one switching time program is enabled. This achieves simplification of operation with a large portion of applications for which only one switching time program is used.
P1 Program 1 = enabled, programs 2 and 3 = disabled
P1 to P3 All three programs enabled
P1
In contrast to the previous description, the following setting options are available when programs P1 to P3 are enabled:
Operating mode selection: In the AUTOMATIC and SUMMER operating modes, switching time program P1, P2 or P3 can be selected.
Switching time programming: With switching time pro­gramming, the three switching time programs, P1 to P3, can be selected for each heating circuit.
5.2.3.2.1 Control mode selection
In the AUTOMATIC and SUMMER control modes, switching time program P1, P2 or P3 can be selected.
5.2.3.2.2 Switching time programming
With switching time programming, the three switching time programs, P1 ... P3 can be selected.
Set values
Factory setting
Effects
Page 74
Operation SDC / DHC
74 EN2H-0221GE51 R0808
5.2.3.3 Operating mode
Two operating modes can be selected. They determine whether the operating mode, the daytime temperature and the night-time temperature apply for all heating circuits or can be specified individually for each heating circuit.
1, 2
1 The selected setting applies for all heating circuits together.
2 Each heating circuit can be assigned an individualised set-
ting.
1
5.2.3.3.1 Individualised daytime room temperature for each heating circuit
Press ¥ button.
Select desired heating circuit (HC, MC-1 or MC-2) by turning
the input button î.
Confirm selected circuit by pressing the input button î.
Set flashing room temperature specification to the desired
value by turning the input button
î.
Confirm set value by pressing the ¥ button.
Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).
5 ... 30 °C
20 °C
Setting range
Set values
Factory setting
Setting
C
Setting range
Factory setting
Page 75
SDC / DHC Operation
EN2H-0221GE51 R0808 75
5.2.3.3.2 Individualised night-time room temperature for each heating circuit
Press ¦ button.
Select desired heating circuit (HC, MC-1 or MC-2) by turning
the input button î.
Confirm selected circuit by pressing the input button î.
Set flashing room temperature specification to the desired
value by turning the input button î.
Confirm set value by pressing the ¦ button.
Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).
5 ... 30 °C
16 °C
5.2.3.3.3 Individualised operating mode for each heating circuit
Each heating circuit can be assigned an individualised operating mode.
Press button.
Select desired heating circuit (HC, MC-1 or MC-2) by turning
the input button
î.
Confirm selected circuit by pressing the input button
î.
Select flashing operating mode by turning the input button î.
Confirm set operating mode by pressing the button or the
input button î.
With short-term operating modes (ABSENT, PARTY), set
desired target value by turning the input button î and confirm set value by pressing the input button î.
Alternative: Automatic acceptance of the value after the set information time (see 5.1.2.7 "System information" button, pg. 35).
This parameter specifies the end of heating operation depending on the outside temperature based on the following criteria:
Setting
C
Setting range
Factory setting
Setting
C
Page 76
Operation SDC / DHC
76 EN2H-0221GE51 R0808
Quick increase in outside temperature
If the averaged outside temperature is below the set value and the current outside temperature is 2 K above the set value, heating operation is interrupted.
Slow increase in outside temperature
Deactivation is also initiated when the averaged and current outside temperature exceeds the set value.
Undoing deactivation
Deactivation is undone when the averaged and current outside temperature exceeds the set value by 1 K.
The summer deactivation function is undone:
In case of an outside sensor defect
In case frost protection is active
During deactivation phases (standby mode, manual summer operation, summer deactivation) lasting longer than 24 hours all pumps are switched on for approx. 20 s and the mixers are temporarily opened during this time to protect against blocking by corrosion.
In connection with a second outside sensor, the current averaged outside temperature is accepted for summer deactivation if the average value of both sensors is specified during outside sensor assignment.
Active summer deactivation is represented by a beach umbrella symbol in the basic display.
Only active in the AUTOMATIC operating mode.
20 °C
OFF, set value of system frost protection to 40 °C
5.2.3.4 Parameter reset
With the reset parameter, it is possible to reset any inadvertently made changes in the parameter menu to the factory setting.
NOTE
Factory setting
Setting range
Page 77
SDC / DHC Operation
EN2H-0221GE51 R0808 77
ATTENTION
A reset should only be carried out if all individually entered values are to be replaced by the values specified at the factory.
When the PARAM. RESET display flashes, press the input
button î. SET flashes in the display.
Press and hold the input button î for 5 s.
If a reset is carried out, the RESET OK confirmation appears
briefly. Verification is then started with a call-up of the first parameter in the respective menu once again.
After the parameter values are reset, a return to the first parameter in the "System Parameter" menu occurs.
5.2.3.5 Complete reset
To reset all settings, a complete reset of the device can be carried out.
A complete reset is initiated when the , ¥, ¦ and § keys are pressed simultaneously until the controller restarts.
5.2.4 "DHW" menu
This menu contains all parameters required to program the hot­water circuit, except the hot-water switching time programs.
Setting
Page 78
Operation SDC / DHC
78 EN2H-0221GE51 R0808
5.2.4.1 Night-time hot-water temperature
This parameter specifies the temperature in the hot-water generator between the operational-readiness times in automatic mode.
40 °C
5 °C to set normal hot-water temperature value
If a hot-water thermostat (see parameter 05 = transducer for hot­water circuit) is used to detect the hot-water temperature, this parameter is skipped.
5.2.4.2 Legionella protection day
OFF
OFF, MO to SU, ALL
OFF The legionella protection function is not active.
MO to SU Legionella protection is activated on the selected
day of the week at the legionella protection time set in the following parameter.
ALL The legionella protection function is activated daily
at the legionella protection time set in the next parameter.
If a hot-water thermostat (see 05 parameter = transducer for hot­water circuit) is used to detect the hot-water temperature, these parameters are skipped.
5.2.5 "Direct Heating Circuit" / "Mixed Heating Circuit 1" / "Mixed Heating Circuit 2" menu
These menus contain all parameters required to program the heating circuit, except the switch time programs. Max. one direct heating circuit and two mixed heating circuits (mixed heating circuit 1 and mixed heating circuit 2) are available as heating circuits.
The following described heating circuit parameters are available separately for setting for each heating circuit.
Factory setting
Setting range
NOTE
Factory setting
Setting range
Set values
NOTE
Page 79
SDC / DHC Operation
EN2H-0221GE51 R0808 79
5.2.5.1 Reduced operation
During reduced operation, you can select between two operating modes.
ECO
ECO, RED
RED (lowering operation)
The heating circuit pump of the direct heating circuit continues functioning during reduced operation (see 5.2.3.2 Time program, pg. 73). The flow temperature is determined based on the lowered room temperature from the associated reduced heating curve. The set maximum temperature is not undershot.
Building with minimal insulation values and high cooling loss.
ECO (switch-off operation)
During reduced operation, the direct heating circuit is switched off completely with outside temperatures above the set frost­protection limit. The maximum heat generator temperature is not functional. The heating circuit pump is switched off after a delay to avoid safety deactivation by reheating the heat generator (pump follow-up).
If the outside temperature is or becomes lower than the specified outside temperature frost-protection limit, the controller switches from deactivated (deactivation mode) to lowered lowering operation and controls the heating circuit temperature based on the set lowering curve taking the set minimum heat generator specification into account.
Building with high insulation values (full heating protection).
The mode set here also applies for the ABSENT and RED.
HEATING operating modes.
Factory setting
Setting range
Set values
Application
Application
NOTE
Page 80
Operation SDC / DHC
80 EN2H-0221GE51 R0808
5.2.5.2 Heating system
This parameter refers to the type of the heating system (floor, radiator or convector heating) and can be matched to the exponent of the respective heat distributor. Using its progressive characteristics, the set value determines the curve characteristics of the heating curve of the direct heating circuit and compensates for the losses in output in the low-temperature range with it.
The following settings are recommend depending on the type of heating system:
UFH Slightly progressive heating curves for floor or other
area heating.
RAD Progressive standard heating curves for all radiator
heating with m-values between 1.25 and 1.35.
CONV Progressive heating curves for convector and
baseboard heating.
RAD (radiator systems)
UFH (floor heating) with mixed heating circuits
UFH, RAD, CONV
5.3 Error messages
ATTENTION
Inform the heating technician whenever any fault messages are output.
The control device contains substantial error-notification logic. The error messages appear in continuous alteration with the basic display. Multiple errors that occur at the same time appear one after another in the order in which they occurred. The following types of error message exist:
Sensor measured values that do not lie in the measurement range are evaluated as an interruption or short-circuit. They appear depending on the type and allocation with fault code 10 to 20 and index 0 for short-circuit or 1 for interruption.
These error messages evaluate the respective switching status. They appear depending on the type and allocation with fault code 30 to 40 and index 0, 1 or 2.
Factory setting
Setting range
Sensor error
messages
Heat generator error
messages
Page 81
SDC / DHC Operation
EN2H-0221GE51 R0808 81
These error messages evaluate the control result to be expected. They appear depending on the type and allocation with fault code 50 to 60 and index 0, 1 or 2.
These error messages refer to address faults such as double issuance or non-recognition of address settings on the data bus. They appear with fault code 70 and index 0 or 1, depending on the type and assignment.
5.4 Parameter settings
5.4.1 "Hydraulics" menu (HYDRAULIC)
The parameters in this menu refer to the general system hydraulics and the functions and configuration of the programmable inputs and outputs for the respective system components. Representative of many individual settings, the applications are only defined by the 1st parameter of this setting table.
Example: The controller is to cover system No 0202. Provided that the controller features enough relays, parameter 01 must be set to value 0202.
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
01 Hydraulic
schematic
0, 0101, 0102, ... n 0
OFF No function 1
1 Hot-water charging
pump
4 Circulating pump
02 Hot-water charging
pump output
5 Electric heating rod
Logical error
messages
Bus error messages
Page 82
Operation SDC / DHC
82 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
OFF No function 3
2 Direct heating circuit
controlled by weather conditions
3 Mixed heating circuit
controlled by weather conditions
6 Constant regulator
7 Fixed-value regulator
8 Return maintenance
30 Mixed heating circuit as
continuous hot-water pre-regulator (district heating)
03 Mixed heating
circuit 1 output
39 Hot-water pre-regulator
(district heating)
04 Mixed heating
circuit 2 output
For setting values, see parameter 03
3
OFF No function 2
2 Direct heating circuit
pump
4 Circulating pump
5 Electric heating element
6 Constant regulation
10 Feeder pump
11 Boiler circuit pump 1
12 Boiler circuit pump 2
13 Group alarm
14 Time switch
15 Solar charging pump
25 Cooling switchover
05 Direct heating
circuit pump output
27 Hydraulic buffer relief
Page 83
SDC / DHC Operation
EN2H-0221GE51 R0808 83
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
OFF No function OFF
4 Circulating pump
5 Electrical heating circuit
9 Bypass pump
10 Feeder pump
11 Boiler circuit pump 1
12 Boiler circuit pump 2
13 Group error message
15 Solar charging pump
16 Buffer charging pump
17 Solid fuel charging pump
18 Stratified tank charging
pump (DHC)
19 Solar charging
switchover
25 Cooling switchover
26 Primary pump
06 Variable output 1
27 Hydraulic buffer relief
07 Variable output 2 For setting values, see parameter
06
OFF
Page 84
Operation SDC / DHC
84 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
OFF No function OFF 1 Outside sensor 2
2 Heat generator sensor 2
3 Tank sensor 2
4 Buffer sensor 2
5 Request contact
6 External error message
input
7 Return maximum limit of
mixed heating circuit 1
8 Return maximum limit of
mixed heating circuit 2
9 Return temperature
sensor
10 External heat generator
cutoff
11 External switching
modem
12 External information
13 Total flow sensor
14 Collector return sensor
15 District hot-water strat-
ified tank charge sensor
16 Exhaust gas sensor
18 Solids buffer sensor
19 Buffer sensor 1
29 Hygrostatic switch-off
30 Room sensor NTC 20 of
direct heating circuit
31 Room sensor NTC 20 of
mixed heating circuit 1
08 Variable input 1
32 Room sensor NTC 20 of
mixed heating circuit 2
Page 85
SDC / DHC Operation
EN2H-0221GE51 R0808 85
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
09 Variable input 2 For setting values, see parameter
08; does not include setting value 16 (exhaust gas sensor), however
OFF
10 Variable input 3 For setting values, see parameter
08; does not include setting value 16 (exhaust gas sensor), limit sensor of district heating VFB, however
OFF
11 Indirect return lift-
ing via mixed heating circuit
OFF, ON OFF
5.4.2 "System parameters" menu (SYSTEM)
The parameters in this menu refer to general limit parameters and specification values in the heating system used.
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
DE German
GB English
FR French
IT Italian
NL Dutch
ES Spanish
PT Portuguese
HU Hungarian
CZ Czech
PL Polish
RO Romanian
RU Russian
TR Turkish
S Swedish
Lan­guage selec­tion**
Language selection
N Norwegian
Page 86
Operation SDC / DHC
86 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
P1 Only one switching time
program enabled
P1 Time
program
Time program
P1 to P3
Three switching time programs enabled
1 Common adjustment for
all heating circuits
1 Operat­ing mode
Operating mode
2 Separate adjustment for
the individual heating circuits
Summer Summer switch-
off
OFF, setting value of parameter 05 to 30°C
20
05 System frost pro-
tection
OFF, –20°C to Setting value of summer parameter
3
1 Direct heating circuit 1
2 Mixed heating circuit 1
3 Mixed heating circuit 2
4 Hot-water circuit
06 Request contact
module for variable input 1
ALL All controllers
07 Request contact
module for variable input 2
For setting values, see parameter 06
1
08 Request contact
module for variable input 3
For setting values, see parameter 06
1
09 Climate zone –50 ... 0°C –12
1 Light construction 2
2 Medium construction
10 Building type
3 Heavy construction
Page 87
SDC / DHC Operation
EN2H-0221GE51 R0808 87
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
OFF No automatic exit 2 11 Automatic exit
time
0,5 ... 5 min
Automatic jump back to the basic display occurs after the set time
ON Anti-blocking protection
active
ON 12 Anti-blocking
protection
OFF Anti-blocking protection
not active
13 Logical fault
messages
OFF, ON OFF
14 Automatic set
function
OFF, ON OFF
15* Locking code for
heating technician
OFF, 0001 to 9999 1234
16* Type code Controller type corresponding to
type code table
Type
OFF Cycle temperature
disabled
ON 18 Cycle temperature
enable
ON Cycle temperatures
enabled
OFF Continuous frost
protection as per parameter 05
OFF 19 Frost-protection
mode
0.5 to 60 min
Cyclic operation
Page 88
Operation SDC / DHC
88 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
21* Adjustment of the
real time clock (RTC)
–10 ... 10 s 0
23 Locking code for
operating level
OFF, 0000 ... 9999 OFF
25 Cooling switch-on
temperature
2 ... 10 K 6
28 Error memory 2 OFF, ON OFF
29* Characteristic
curve for emergency operation without outside sensor
–50 to 30°C 0
Selec­tion of SDC/ DHC
Selection of SDC/DHC
SDC, DHC SDC
Para­meter reset
Parameter reset SET by pressing the input button
* OEM
** Other controllers also allow other language variants.
Page 89
SDC / DHC Operation
EN2H-0221GE51 R0808 89
5.4.3 "Hot-water circuit" menu (DHW)
This menu contains all parameters required to program the hot-water circuit, except the switch time programs.
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
Hot water
Hot water at night 10°C to normal hot-water
temperature
40
OFF No legionella protection OFF
Mon to Sun
Legionella protection on specified day of week
Legio protect ion day
Legionella protection day
ALL Legionella protection
every day
03 Legionella
protection time
00:00 ... 23:00 hours 02:00
04 Legionella
protection temperature
10 °C to setting value of parameter 06
65
1 Hot-water circuit
temperature sensor
1 05 Transducer for hot-
water circuit
2 Hot-water circuit
temperature controller (thermostat)
06 Maximum
temperature limit for hot water circuit
20°C to heat generator maximum temperature
If parameter 07 = 7: 20 to 90°C. In automatic mode, from hot­water circuit minimum temperature.
65
Page 90
Operation SDC / DHC
90 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
1 Parallel operation 2
2 Priority operation
3 Conditional priority
4 Parallel operation based
on weather conditions
5 Priority operation with
intermediate heating
6 Priority isolating circuit
7 External operation
07 Hot-water circuit
operating mode
8 Conditional parallel
operation for mixed heating circuit (DHC only)
OFF No discharge protection ON 08 Tank discharge
protection
ON Discharge protection
activated
09 Temperature in-
crease of heat generator with hot­water circuit charging
0 ... 50 K
Difference between hot-water circuit charging temperature and hot-water circuit setpoint temperature
15
10 Switching
differential of hot­water circuit
2 ... 20 K
Value of hot-water circuit switch­ing differential. Symmetrical effect around the hot-water circuit setpoint
5
11 Hot-water charging
pump follow-up time
0 ... 60 min 5
Page 91
SDC / DHC Operation
EN2H-0221GE51 R0808 91
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
AUTO Active hot-water circuit
time program
AUTO
1 P1, direct heating circuit
2 P2, direct heating circuit
3 P3, direct heating circuit
4 P1, mixed heating
circuit 1
5 P2, mixed heating
circuit 1
6 P3, mixed heating
circuit 1
7 P1, mixed heating
circuit 2
8 P2, mixed heating
circuit 2
9 P3, mixed heating
circuit 2
10 P1, hot-water circuit
11 P2, hot-water circuit
12 Circulation pump
switching time program
12 P3, hot-water circuit
13 Economy interval
pause of circu­lating pump
0 ... setting value of parameter 14
Switch-on interval while the circulating pump is running
5
14 Economy interval
cycle (period duration)
1 ... 60 min 20
1 Normal operation 1 16 Circulating pump
2 Switched off during hot-
water circuit charging
Page 92
Operation SDC / DHC
92 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
AUTO Setpoint at heat gen-
erator depending on demand
AUTO 17 Behaviour of heat generator during follow-up time
OFF Heat generator off
during follow-up time of solar charging pump
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC)
This menu contains all parameters required to program the un­mixed heating circuits, except the switching time programs.
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
Heat­ing curve
Slope OFF, 0.02 to 3.50 1.5
ECO Switch-off operation ECO Re-
duced
Reduced operation
RED Lowering operation
UFH Under floor heating RAD
RAD Radiator
Heat­ing system
Heating system
CONV Convector heater
Page 93
SDC / DHC Operation
EN2H-0221GE51 R0808 93
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
OFF Display of heat
generator temperature, room sensor off, operation active
OFF
1 Display of room
temperature, room sensor active, operation active
2 Display of room
temperature, room sensor active, operation disabled
03 Room connection
(in conjunction with room sensor)
3 Display of room
temperature, room sensor off, operation active
OFF
10 ... 500 %
Influence active
04 Room factor
RC Room controller active
OFF
07 Heating limit OFF, 0.5 to 40 K OFF
08 Room frost-
protection limit
5 ... 30°C 10
09 Room thermostat
function
OFF, 0.5 to 5 K OFF
0 Regulation to average
value (outside sensor 1 + outside sensor 2)
0
1 Regulation to outside
sensor 1
10 Assignment of
outside sensor
2 Regulation to outside
sensor 2
11 Constant
temperature setpoint
10 ... 95°C 20
Page 94
Operation SDC / DHC
94 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
12 Minimum
temperature limit
10°C to setting value of parameter 13
20
13 Maximum
temperature limit
Setting value of parameter 12 to Setting value of parameter 30 in "Heat generator" menu (OEM maximum limit)
75
14 Temperature
increase of heating circuit
–5 ... 20 K Direct
heating
circuit = 0
15 Extended pump
over-run
0 ... 60 min 5
OFF OFF
1 Functional heating
16 Screed function
2 Screed-drying heating
23 Room control
C-factor (SDW 30 only)
1 ... 100 8
24 Room control Tn
(SDW 30 only)
5 ... 240 min 35
STBY Standby STBY 25 Holiday operating
mode
RED Lowering operation
26 Room setpoint
ramp
OFF, 0.5 to 60 K/h OFF
OFF OFF
1 Adaption off
2 Adaption on
41 Switch-on
optimisation
3 Adaption restart
42 Min. pre-heat time 0 ... setting value of parameter 43 0,5
43 Max. pre-heat time Setting value of parameter 42 to
30 h
5
44 Min. jump back
temperature
0 ... 30°C 5
45 Without room
sensor
0 ... 10°C 1
Page 95
SDC / DHC Operation
EN2H-0221GE51 R0808 95
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
46 Pre-heat time at
0°C
0 ... 30 h 1
47 Lowering ramp 0 ... 500 % 100
Heat­ing circuit name
Heating circuit name
00000 ... ZZZZZ
5.4.5 "Mixed heating circuit 1 / 2" (MIX.VALVE - 1 / MIX.VALVE - 2) menus
These menus contain all parameters required to program the mixed heating circuit, except the switching time programs.
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
Heat­ing curve
Slope OFF, 0.02 to 3.50 1
ECO Switch-off operation ECO Re-
duced
Reduced operation
RED Lowering operation
UFH Floor heating
RAD Radiator
Heat­ing system
Heating system
CONV Convector heater
RAD
Page 96
Operation SDC / DHC
96 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
03 OFF Display of heat
generator temperature, room sensor off, operation active
OFF
1 Display of room
temperature, room sensor active, operation active
2 Display of room
temperature, room sensor active, operation disabled
Room connection (in conjunction with room sensor)
3 Display of room
temperature, room sensor off, operation active
OFF
10 ... 500 %
Influence active
04 Room factor
RC Room controller active
OFF
07 Heating limit OFF, 0.5 to 40 K OFF
08 Room frost-
protection limit
5 ... 30 °C
10
09 Room thermostat
function
OFF, 0.5 to 5 K OFF
0 Regulation to average
value (outside sensor 1 + outside sensor 2)
0
1 Regulation to outside
sensor 1
10 Assignment of
outside sensor
2 Regulation to outside
sensor 2
Page 97
SDC / DHC Operation
EN2H-0221GE51 R0808 97
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
11 Constant tem-
perature setpoint (only if output was set to constant regulator)
10 ... 95°C
20
12 Minimum
temperature limit
10°C to setting value of parameter 13
20
13 Maximum
temperature limit
Setting value of parameter 12 to Setting value of parameter 30 in "Heat generator" menu (OEM maximum limit)
75
14 Temperature
increase of heating circuit
–5 ... 20 K Mixed
heating circuit = 4
15 Follow-up time of
pump
0 ... 60 min 5
OFF OFF
1 Functional heating
16 Screed function
2 Screed-drying heating
17 Return maximum
temperature limit
10 ... 90 °C
90
18* P part XP 1 ... 50 %/K 2
19* Sampling time Ts 1 ... 600 s 20
20* I part Tn 1 ... 600 s 270
21* Actuator runtime 10 ... 600 s 120
1 Continuous control
signal in end position
1 22* Actuator end
position function
2 Control signal
suppressed at end position (actuator de­energised)
23 Room control C-
factor (SDW 30 only)
1 ... 100 8
Page 98
Operation SDC / DHC
98 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
24 Room control Tn
(SDW 30 only)
5 ... 240 min 35
STBY Standby STBY 25 Holiday operating
mode
RED Lowering operation
26 Room setpoint
ramp
OFF, 0.5 ... 60 K/h OFF
28 Cooling
temperature of mixed heating circuit
OFF, 18 to 24 OFF
39 Spread of hot-
water circuit pre­regulator
2 ... 20 K 5
40 Offset valve
position of hot­water circuit pre­regulator
0 ... 100 % 0
OFF OFF
1 Adaptation off
2 Adaptation on
41 Switch-on op-
timisation
3 Adaptation restart
42 Minimum pre-heat
time
0 ... setting value of parameter 43 0.5
43 Maximum pre-heat
time
Setting value of parameter 42 to 30 h
5
44 Min. jump back
temperature
0 ... 30 °C 5
45 Without room
sensor
0 ... 10 °C 1
46 Pre-heat time at
0 °C
0 ... 30 h 1
47 Lowering ramp 0 ... 500 % 100
Page 99
SDC / DHC Operation
EN2H-0221GE51 R0808 99
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
Heat­ing circuit name
Heating circuit name
00000 ... ZZZZZ
* OEM
5.4.6 "Heat generator" menu (HEAT GENER.
The parameters in this menu refer to the type of the respective heat generator and the associated specific control functions.
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
OFF Without heat generator 1
1 Oil/gas - one stage
2 Oil/gas - two stages
3 Oil/gas - 2 x one stage
4 Modulating burner
01 Design
5 Open Therm
OFF No start-up protection 1
1 Unlimited start-up
protection
2 Start-up protection
controlled by weather conditions
02 Start-up protection
(not if parameter 01 = OFF)
3 Start-up protection
disconnected
03 Minimum tem-
perature limit (not if parameter 01 = OFF)
5°C to setting value of parameter 04
38 (5 with automatic operation)
04 Maximal
temperature limit (not if parameter 01 = OFF)
Setting value of parameter 03 to setting value of parameter 30 (OEM maximum limit)
80
Page 100
Operation SDC / DHC
100 EN2H-0221GE51 R0808
Para­meter
Designation Setting range / Setting values Factory
setting
Setting
1 Minimum limit based on
request
1
2 Limited minimum limit
05 Limit mode
minimum limit (not if parameter 01 = OFF)
3 Unlimited minimum limit
1 Burner switch-off in case
of defect
1
2 External burner switch-
off
06 Sensor operating
mode
3 Burner enable in case of
defect
07 Minimum burner
runtime
0 ... 20 min 2
One stage: 2 ... 30 K 6 08 Burner switching
differential I
Two stages: 2 ... (setting value of parameter 09 – 0.5 K)
09 Burner switching
differential II (not if parameter 01 = 2)
(setting value of parameter 08 +
0.5) to 30 K
8
10 Connection delay
stage II
0 ... 60 min (0 = 10 s) 0
1 Unlimited enable during
start-up relief
2 11 Boiler start-up
relief stage II
2 Time-out during start-up
relief
1 Two-stage hot-water
circuit charge (with delay of full-load stage)
1
2 Two-stage hot-water cir-
cuit charge (unlimited)
12 Storage charge
1–2 stages
3 One-stage hot-water
circuit charge (partial stage only)
Loading...