
DeltaNet FS90 Operating Instructions
OPERATING INSTRUCTIONS
SYSTEM OPERATION
A normally functioning DeltaNet Fire & Security System is indicated
by the green RUN and green POWER LEDs on the powered Control
Board. If a Communication Board is installed, the Communication
Board red TRANSMIT and RECEIVE LEDs blink as data is
communicated.
Power Supply Supervision
The power supply circuits for the DeltaNet FS90 Fire & Security
system are monitored for Integrity. Trouble conditions in these circuits
are indicated by Low Battery (yellow) and Power (green) LEDs on the
CA control board. In the normal, supervisory, condition, the yellow
Low Battery LED is off and the green Power LED is on. A trouble
condition in the power supply circuits is indicated when either the
green Power LED is blinking or the yellow Low Battery LED is on. If
this occurs, contact a service technician to determine the nature of the
trouble condition by removing the batteries from the system and
testing their condition. With the batteries out of the system, proper
functioning of the power supply, battery changer and battery
supervision circuits should be verified. Any faulty component must be
replaced.
Modes of Operation
The DeltaNet Fire & Security System can operate independently
(Stand-Alone Mode) or as a Data Gathering Panel (DGP) in a higherorder system (DGP Mode). DGP Mode is in effect when a
Communication Board is plugged into the Motherboard and active
communication takes place. If communication fails, the system
operates in Stand-Alone Mode.
LJ Communication/Display Board Switch
When the LJ Board MULTIPLE ALARM-TROUBLE LED is on,
multiple abnormal conditions (alarm, trouble, prealarm) exist on AE
Board loops. The LJ Board displays one address at a time, beginning
automatically with the address of the highest-priority device.
An address remains displayed until a new, higher priority device goes
into an abnormal condition or until the PREVIOUS/NEXT switch is
pushed. Use the PREVIOUS/NEXT switch to display other addresses
as follows.
PRINTER/DISPLAY ASSEMBLY AND LH INTERFACE BOARD
OPERATING INSTRUCTIONS
The two front Printer/Display Assembly switches are:
— Printer On-Line Switch with integral LED.
— Paper Advance Switch.
LH Interface Board switches are:
— ACK—UP to acknowledge indicated point in LCD display.
— ALL PT/ALM SUM—UP to request All Point Log; DOWN to
request Alarm Summary Log.
— PREVIOUS/NEXT—UP to revert LCD display to former point;
DOWN to advance LCD display to subsequent point.
FRONT PANEL SWITCHES/LEDS
Control Board Switches
ACKNOWLEDGE
— Pushing the ACKNOWLEDGE switch silences the local audible
and changes blinking LEDs to ON. The ACKNOWLEDGE switch
does not affect indicating zone outputs and does not silence alarm
signals. Pushing the ACKNOWLEDGE switch acknowledges all
alarms present in the panel.
— If the panel is a DGP, the ACKNOWLEDGE switch does not
function when the DGP is communicating with the higher-order
system. The ACKNOWLEDGE switch becomes functional when
communication is broken.
SILENCE
Pushing the SILENCE switch does the following:
— Silences devices connected to indicating zones.
— Silences devices connected to Control Modules with indicating
characteristic set.
— Silences the local audible.
— Turns on the Control Board SILENCE LED.
— Changes blinking LEDs to on.
RESET
Pushing the RESET switch removes power to all initiating zones for
fifteen seconds and sends out a fifteen-second reset signal that
returns all input-zone status indicators to normal. After reset, zones
that return to alarm or trouble are annunciated as new alarms or
troubles.
PANEL TEST
Performing a Panel Test reveals whether all boards are controlled by
the panel microprocessor. Pushing the PANEL TEST switch turns on
all LEDs, except Communication Board LEDs and turns on the local
audible. A Panel Test does not interrupt alarms or troubles reporting in
the system.
Pushing the PANEL TEST switch turns on all LJ Communication/
Display Board LEDs and causes the LJ Board to display the address
8888.
Pushing the MANUAL EVACUATION switch does the following:
— Turns on all indicating zones.
— Turns on all AE Board Control Modules that have the indicating
characteristic set during system setup.
— Causes a common alarm indication.
— Causes the local audible to pulse.
Manual evacuation is terminated by pushing either the SILENCE
or the RESET switch.
Honeywell DeltaNet FS90 Fire & Security System
Control Unit
LOCAL SERVICE REPRESENTATIVE
Name:
Address:
Phone:
Refer to Installation Instructions: Honeywell form no. 95-7421-3, issued 10-2007
74-5069

DELTANET FS90 OPERATING INSTRUCTIONS
Table 1. CA Board Switch and LED Functions.
Switch/
LED Normal Operation Setup Mode
MicroProcessor
Reset Switch
Acknowledge
/Silence
Switch
Reset Switch Resets FS90. The system removes power to all initiating zones for 15 seconds,
Panel Test
Switch
Manual
Evacuation
Switch
Setup Switch Enters Setup Mode. Exits Setup Mode.
Alarm LED Indicates a common alarm in the system via blinking LED. Indicates the system is ready to enter
Trouble LED Indicates a common trouble via a blinking yellow LED. Indicates the system is ready to enter
Silence LED Indicates the Silence switch has been activated to silence the outputs. Indicates the system is ready to enter
Low Battery
LED
Ground Fault
LED
Isolate LED Indicates one of the Disconnect switches on a module is activated or a point has been
Power LED Indicates power is on. Indicates system is ready to enter
Run LED Indicates system is ready to operate. Indicates system is ready to enter input
Setup LED Off On to show system is in Setup Mode.
Resets microprocessor. Exits Setup Mode. Any changes made
Acknowledges troubles and alarms or silences outputs as follows:
Acknowledge position (UP): The local audible silences and blinking LEDs change to
steady on. The Acknowledge/Silence switch does not affect indicating zone outputs or
silence alarm signals.
NOTE: Zones set up as central are acknowledged when the new status reports to
the central processor. FS90 acknowledgement of these zones is not required
Silence position (DOWN): The indicating zone devices silence, the FS90 local audible
silences, the CA Board Silence LED turns on and blinking LEDs change to steady on.
activates the CA Board reset out signal for 15 seconds and returns all input zone status
indicators and their associated outputs to normal. After the 15-second reset time any
zone(s) remaining in alarm or trouble annunciates as a new alarm or trouble.
Initiates a test of all LEDs except the communication board transmit and receive LEDs.
The test turns on the LEDs and sounds the local audible. The test indicates that all
function boards are operational and controlled by the CA Board microprocessor. The
panel test does not affect alarm or trouble reporting in the system.
Initiates a manual evacuation signal. All indicating zones turn on and a common alarm
indication and pulsing local audible occur (if audible is selected and the system is in the
stand-alone mode). Toggle the Acknowledge/Silence switch to silence the output and
then toggle the Reset switch to return the system to normal.
Indicates a low battery condition if system power supply is off. If a Battery Supervision
Module is installed, this LED indicates low battery or absence of batteries at all times.
Indicates a ground fault in the system. Indicates various time menus when
isolated or locked out.
unless communication with the central fails and stand-alone mode is in effect.
NOTE: Operators may also silence zones set up as central from the central
processor.
during Setup Mode will be lost if this
switch is activated.
Advances pointer to next function.
Selects or deselects characteristics.
Enter characteristics into date file and
moves pointer.
Not used.
group address menu.
code menu.
the special options menu.
Indicates various time menus when
used with ground fault and disconnect
LEDs.
used with low battery and disconnect
LEDs.
Indicates various time menus when
used with low battery and ground fault.
output menu.
menu.
MAINTENANCE PROCEDURES
The system must be maintained in accordance with the system
documentation and procedures and practices contained in applicable
NFPA and UL standards, including NFPA 70, 72, 90A, 92A and 92B.
DeltaNet FS90 Systems Maintenance and Repair Manual for further
details, including testing, fuse replacement and replacement parts.
For service, contact your local Honeywell Automation & Control
Solutions office as listed in the phone book, or contact a regional
office as shown at the end of this document.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
www.honeywell.com/buildingsolutions
® U.S. Registered Trademark
© 2007 Honeywell International Inc.
74-5069 J.I. 11-07
Directive 2002/96/EC of the European parliament and the Council of
27 January 2003 on Waste Electrical and Electronic Equipment
(WEEE).
This product may contain small amounts of chemicals
and substances that may be banned from disposal in
landfills. At the end of the useful life of this product, it is
the owners’ responsibility to safely decommission the
product and arrange for disposal in accordance with all
applicable environmental laws and regulations, including