D Montageanweisung
DCPSU-24
24 VDC Power Supply Unit
F Instructions d’installation
I Istruzioni di montaggio
NL Installatievoorschrift
DK Installasjonsinstruktus
N Installationsinstruktioner
FIN Asennusohje
S Installation instruktioner
E Instrucciones de montaje
INSTALLATION INSTRUCTIONS
Model DCPSU-24 -1.3 DCPSU-24-2.5 DCPSU2-24-4
W
54 mm 72 mm
90 mm
H 89 mm 89 mm
89 mm
D1 54 mm 54 mm
54 mm
D2 59 mm 59 mm
59 mm
-25 to +55 C°
30 to 85 %RH
non-condensing
Protection: IP20
2
H O
Derate to 60%
of output current
Derate to 60%
of output current
Derate to 60%
of output current
35 mm DIN rail
(DIN EN 50022)
A1 A2 A3
100 to 240 Vac
44 to 66 Hz
22.8 to 26.4 Vdc
1.3A
2.5A
4A

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Straße 17, 71101 Schönaich, Germany
Subject to change without notice.
EN1B-0596GE51 R0915A (32307881-001, 23/03/2015)
A4 A5 A6
Output Power OK
Output Power Fault
Green LED
OUT
INSTALLATION
Safety measures before installation.
Always isolate the equipment from the mains supply before commencing installation or wiring.
Installation
Installation must be carried out according to the prevailing local conditions and safety regulations (e.g. VDE 0100) national
accident prevention regulations (e.g. UVV-VBG4 or BGV A3) and the generally accepted rules of technology. This equipment
is a component designed for installation into electrical systems and machines, and fulls the requirements of the low voltage
guidelines (2014/35/EU).
The required minimum spacing to neighbouring components must be observed to guarantee the required cooling. When installed
into machinery, normal operation is forbidden until it is determined that the machine fulls the requirements of the machinery
guidelines (2006/42/EG). EN 60204 must be observed. The EMC requirements (2014/30/EU) must be fullled before operation is
commenced. The observance of the required limitations for the EMC legislation is the responsibility of the installer.
PARALLEL CONNECTION
If units have their outputs connected in parallel, their output voltages must be adjusted to the same value (± 100 mV).
Impedances from the units to the star point must be equal.
Note that leakage current, EMI, inrush current and harmonics can increase when using multiple power supplies.