Honeywell DCP301 User Manual

Page 1
EN1I-6197 Issue 7 (02/04)
DCP301
Digital Program Controller
User’s Manual
Page 2
The Honeywell device described herein has been manufactured and tested for corrent operation and is warranted for a period of one year.
TECHNICAL ASSISTANCE
If you encounter a problem with your unit, please review all the configuration data to verify that your selections are consistent with your application; (i.e. Inputs, Outputs, Alarms, Limits, etc.). If the problem persists after checking the above parameters, you can get technical assistance by calling the following:
In the U.S.A.
・・・・・
1-800-423-9883
In Europe
・・・・・・・
Your local branch office
Page 3
About Icons
Safety precautions are for ensuring safe and correct use of this product, and for preventing injury to the operator and other people or damage to property. You must observe these safety precautions. The safety precautions described in this manual are indicated by various icons. The following describes the icons and their meanings. Be sure to read and understand the following descriptions before reading this manual.
Examples
i
Triangles warn the user of a possible danger that may be caused by wrongful operation or misuse of this product. These icons graphically represent the actual danger. (The example on the left warns the user of the danger of electric shock.)
White circles with a diagonal bar notify the user that specific actions are prohibited to prevent possible danger. These icons graphically represent the actual prohibited action. (The example on the left notifies the user that disassembly is prohibited.)
Black filled-in circles instruct the user to carry out a specific obligatory action to prevent possible danger. These icons graphically represent the actual action to be carried out. (The example on the left instructs the user to remove the plug from the outlet.)
SAFETY PRECAUTIONS
WARNING
Warnings are indicated when mishandling this product might result in death or serious injury to the user.
CAUTION
Cautions are indicated when mishandling this product might result in minor injury to the user, or only physical damage to this product.
Page 4
ii
WARNING
CAUTION
Use the DCP301 within the operating ranges recommended in the specifica­tions (temperature, humidity, voltage, vibration, shock, mounting direction, atmosphere, etc.). Failure to do so might cause fire or faulty operation.
Do not block ventilation holes. Doing so might cause fire or faulty operation.
Wire the DCP301 properly according to predetermined standards. Also wire the DCP301 using designed power leads according to recognized installa­tion methods. Failure to do so might cause electric shock, fire or faulty operation.
Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation.
Inputs to the current input terminals (
31) and (33) on the DCP301 should be
within the current and voltage ranges listed in the specifications. Firmly tighten the terminal screws at the torque listed in the specifications.
Insufficient tightening of terminal screws might cause electric shock or fire. Do not use unused terminals on the DCP301 as relay terminals.
Doing so might cause electric shock, fire or faulty operation. We recommend attaching the terminal cover (sold separately) after wiring
the DCP301. Failure to do so might cause electric shock, fire or faulty opera­tion.
Use the relays on the DCP301 within the service life listed in the specifica­tions. Continued use of the relays after the recommended service life might cause fire or faulty operation.
Before connecting the DCP301 to the measurement target or external con­trol circuits, make sure that the FG terminal is properly grounded (100 max.). Failure to do so might cause electric shock or fire.
Before wiring, or removing/mounting the DCP301, be sure to turn the power OFF. Failure to do so might cause electric shock.
Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
Do not disassemble the DCP301. Doing so might cause electric shock or faulty operation.
Page 5
iii
CAUTION
Use induced lighting surge preventive device if there is the risk of power surges caused by lightning. Failure to do might cause fire or faulty operation.
Before replacing the battery, be sure to turn the power OFF. Failure to do so might cause electric shock.
Do not touch internal components immediately after turning the power OFF to replace the battery. Doing so might cause burns.
Do not insert the battery with the polarities (+,-) reversed.Do not use damaged (broken battery skin, leaking battery fluid) batteries.Do not throw batteries into fires, or charge, short-circuit, disassemble or
heat batteries. Store batteries in low-temperature, dry locations. Failure to observe the above cautions may cause batteries to emit heat or split, or battery fluid to lead.
Store batteries out of the reach of small children. Batteries are small and are easy to swallow. If a child swallows a battery, consult a physician immediately.
Return used batteries to Honeywell sales/service office or your dealer. When disposing of used batteries at the user site, observe local by laws.
Handling Precautions
After turning the power ON, do not operate the DCP301 for at least 15s to allow the DCP301 to stabilize.
Page 6
E
N
1
I
-
X
X
X
X
I
s
s
u
e
X
(
X
X
/
X
X
)
X
X
X
X
XX
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
XX
X
X
U
ser
s M
an
u
al
Unpacking
iv
Check the following when removing the DCP301 from its package.
1. Check the model No. to make sure that you have received the product that you ordered.
2. Check the DCP301 for any apparent physical damage.
3. Check the contents of the package against the Package List to make sure that all accessories are included in the package.
After unpacking, handle the DCP301 and its accessories taking care to prevent damage or loss of parts. If an inconsistency is found or the package contents are not in order, immediately contact your dealer.
Name Model No. Q’ty Remarks
See 1-5 How Model Nos. Are Configured, page 1-5.
1
Mounting bracket
81405411-001
1 set (2)
User's Manual EN1I-6197
1
This manual
Unit indicator label (SI units)
N-3132
1
Request
The filter on the front of the controller is Covered with a protective film to protect the surface of the controller. When you have finished mounting and wiring the controller, fix cellophane adhesive tape on the corners of the filter, and pull in the direction of the arrow to peel off the protective film.
The Model No. is the parts No. for two installation tools.
Product List
Pull towards you.
Handling Precautions
Peeling off the protective film with your fingernail might scratch the surface of the controller.
Body
Page 7
Organization of This Users Manual
v
This manual is organized as follows.
Chapter 1. GENERAL
This chapter describes DCP301 applications, features and basic function blocks. It also gives a list of model numbers.
Chapter 2. NAMES & FUNCTIONS OF PARTS
This chapter describes the names and functions of DCP301 parts, input types and range Nos.
Chapter 3. MOUNTING
This chapter describes how to mount the DCP301 on control panels. This chapter is required reading for designers of control systems using the DCP301.
Chapter 4. WIRING
This chapter describes the precautions when wiring the DCP301 to a control system and how to wire the DCP301. This chapter is required reading for designers of control systems and supervisors of wiring work.
Chapter 5. FUNCTIONS
This chapter describes the functions of the controller. This chapter is required reading for designers of control systems using the DCP301.
Chapter 6. OPERATION
This chapter describes how to switch the basic display states of the DCP301, and select and run programs. This chapter is required reading for designers of control systems using the DCP301 and users of the DCP301.
Chapter 7. PARAMETER SETUP
This chapter describes how to set up parameters on the controller and the meaning of settings.
Chapter 8. PROGRAM SETUP
This chapter describes how to set up programs on the controller and the meanings of settings.
Chapter 9. TROUBLESHOOTING
This chapter describes points to check when the DCP301 is not working properly or how to remedy trouble that might occur.
Chapter 10. SPECIFICATIONS
This chapter describes the general specifications, performance specifications and external dimensions of the DCP301.
Chapter 11. CALIBRATION
This chapter describes calibration procedures for the functions of the DCP301.
Page 8
Contents
vi
Safety Precautions Unpacking Request Organization of the Product Manual Conventions Used in This Manual
Chapter 1. GENERAL
1-1 Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1-2 Basic Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1-3 Data Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1-4 System Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
System configuration by CPL communications . . . . . . . . . . . . . . . . . . . 1-4
1-5 Model Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Model selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-1 Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2-2 Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Basic display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Functions using two or more keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Loader jack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2-3 Input Type and Range No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Chapter 3. MOUNTING
3-1 External Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3-2 Panel Cutout Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3-3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Mounting locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Noise generating sources and countermeasures . . . . . . . . . . . . . . . . . . 3-4
Dust-proof cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Mounting method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Chapter 4. WIRING
4-1 Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4-2 Compensating Lead . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4-3 Terminal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4-4 Layout of Terminals and Recommended Lead Draw-out Direction. . . . . . . 4-5
4-5 Connecting the Ground and Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Ground. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4-6 Wiring of Standard and Add-on Terminal Base . . . . . . . . . . . . . . . . . . . . . . . 4-7
Standard terminal layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Add-on terminal layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Page 9
vii
4-7 Connecting Inputs (analog inputs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Connecting input 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
4-8 Connecting control outputs (outputs 1, 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Relay output (0D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Current output (5G) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Position-proportional output (2G). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Voltage output (6D). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Heat/cool output (3D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Heat/cool output (5K) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4-9 Connecting auxiliary outputs (outputs 2, 3). . . . . . . . . . . . . . . . . . . . . . . . . 4-11
0D, 5G, 6D auxiliary outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
2G, 3D, 5K auxiliary outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
4-10 Connecting Event Output (relay output). . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
4-11 Connecting Time Event Output (open-collector). . . . . . . . . . . . . . . . . . . . . 4-13
4-12 Connecting External Switch (RSW) Input. . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
4-13 Connecting for Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
RS-485 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
4-14 Isolating Inputs and Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Control outputs 0D, 5G, 6D, 3D, 5K. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Control output 2G. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Chapter 5. FUNCTIONS
5-1 Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Data types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5-2 Program Patterns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Patterns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Events 1 to 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Time events 1 to 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
PID set selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
G.Soak (guarantee soak) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
PV start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Pattern link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
5-3 Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Mode type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Mode transition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Mode transition operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Mode transition limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
5-4 Controller and Programmer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
5-5 Input Processing Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5-6 Output Processing Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
Control output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
SP output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
Auxiliary output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
Chapter 6. OPERATION
6-1 Turning the Power ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6-2 Switching the Basic Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Page 10
viii
Display in program operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Display in constant-value operation mode . . . . . . . . . . . . . . . . . . . . . . . 6-5
6-3 Program Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
How to select the program No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6-4 External Switch (RSW) Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
External switch (RSW) inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Program selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Read timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
6-5 Manual Operation and Auto-tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Manual operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Auto-tuning (AT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Chapter 7. PARAMETER SETUP
7-1 Parameter Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Selecting the setting group in the parameter setup . . . . . . . . . . . . . . . . 7-1
Moving individual items in the parameter setup . . . . . . . . . . . . . . . . . . 7-2
Changing individual items and how to return from the setup state . . . 7-2
7-2 How to Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
How to register functions to keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
7-3 Parameter Setup List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
Variable parameter settings “paRa. . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
Description of variable parameter settings . . . . . . . . . . . . . . . . . . . . . . 7-10
Event configuration data settings ev. . . . . . . . . . . . . . . . . . . . . . . . . 7-18
Description of event configuration data. . . . . . . . . . . . . . . . . . . . . . . . . 7-22
PID parameter settings pi d. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23
Setup data settings Set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
Description of setup data settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-33
Table data settings TBL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-40
Description of table data settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-41
Constant-value operation data settings CNST. . . . . . . . . . . . . . . . . 7-42
Chapter 8. PROGRAM SETUP
8-1 Program Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
How to enter program setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Selecting the program No. to set up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Mode transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Programming map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Display details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Setting up pattern items. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Setting up events 1 to 3 items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
Setting up time events 1 to 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
Setting up PID set No. items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Setting up G.Soak (guarantee soak) items. . . . . . . . . . . . . . . . . . . . . . . 8-10
Setting up G.Soak time-out items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10
Setting up PV start items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11
Setting up cycle items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11
Setting up pattern link items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
Deleting programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
Inserting and deleting segments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-13
PARA
Page 11
8-2 Copying Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-14
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-14
8-3 General Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-15
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-15
Chapter 9. TROUBLESHOOTING
9-1 Self-diagnostics and Alarm Code Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Self-diagnostics at power ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Self-diagnostics at each sampling cycle . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Intermittent self-diagnostics during operation . . . . . . . . . . . . . . . . . . . . 9-1
Self-diagnostics only when certain functions are operating . . . . . . . . . 9-2
Alarm code display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Alarm categories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9-2 Trouble during Key Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
The program No. does not change by pressing in basic display
state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
The program No. does not change by pressing in the basic
display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
The controller does not change to RUN mode by pressing in
the basic display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
The controller does not change to HOLD mode by pressing in
the basic display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
The controller cannot be reset by pressing + in the basic
display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
The program is not advanced by pressing + in the basic
display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
The controller does not change to FAST mode by pressing +
in the basic display state. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
The controller does not change to MANUAL mode by pressing
in the basic display state. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
The controller does not change to AUTO mode by pressing in
the basic display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
Auto-tuning (AT) is not started by pressing in the basic display
state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
Auto-tuning (AT) is not canceled by pressing in the basic display
state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
Setting group other than paRa” is not displayed by pressing
by selecting the setting group in parameter set state . . . . . . . . . . . . . . 9-5
Setting group other than Set” is not displayed by pressing by
selecting the setting group in parameter set state . . . . . . . . . . . . . . . . . 9-5
The controller does not enter the setting entry state by pressing
in the parameter setup state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
The controller does not change to setup group selection state and setting entry state continues by pressing in parameter setting
entry state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
The controller does not change to program setup state by pressing
+ in the basic display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
The controller does not change to the setting entry state by pressing
in the basic display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
ENT
PROG
FUNC
PARA
ENT
PARA
PARA
ATATA/M
A/M
FUNC
DISP
PROG
RUN/HOLD
PROG
RUN/HOLD
RUN/HOLD
PROG
ix
Page 12
Items cannot be changed by pressing , in program setup
state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
Event items cannot be changed by repeatedly pressing , in
program setup state. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
Time events cannot be changed by repeatedly pressing , in
program setup state. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
PID set items cannot be changed by repeatedly pressing , in
program setup state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
G.Soak items cannot be changed by repeatedly pressing , in
program setup state. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
PV start items, cycle items and pattern link items cannot be displayed
by repeatedly pressing , in program setup state . . . . . . . . . . . 9-6
Insertion/deletion of segments cannot be confirmed by pressing
+ in program setup state. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
Program deletion cannot be confirmed by pressing + while
entering pattern items in program setup state . . . . . . . . . . . . . . . . . . . . 9-7
The program cannot be copied by pressing + in the basic
display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
General reset is not applied by pressing + + in the basic
display state . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
9-3 Motor Adjustment is Impossible . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-8
Normal wiring for direct motor rotation . . . . . . . . . . . . . . . . . . . . . . . . . . 9-9
Normal wiring for reverse motor rotation. . . . . . . . . . . . . . . . . . . . . . . . . 9-9
Alarm display caused by wrong wiring and causes . . . . . . . . . . . . . . . . 9-9
9-4 Replacing the Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
BAT LED blinking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
Items to prepare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
Replacement procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-11
Chapter 10.
SPECIFICATIONS
10-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Accessories/option list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-7
10-2 External Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-8
Soft dust-proof cover set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-9
Hard dust-proof cover set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-9
Terminal cover set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-9
Chapter 11. CALIBRATION
Precautions before calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
Equipment needed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
11-1 Quick Reference Table for Calibration Items. . . . . . . . . . . . . . . . . . . . . . . . 11-2
11-2 Calibration Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-6
Enter calibration mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-6
Function test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-7
PV calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-10
Cold junction sensor calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-12
Current output calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-12
Index
DISP
CLR
FUNC
PROG
CLR
FUNC
ENT
FUNC
x
Page 13
xi
Conventions Used in This Manual
The following conventions are used in this manual.
Handling Precautions
:
Handling Precautions indicate items that the user should pay attention to when handling the DCP301.
Note : Notes indicate useful information that the user might benefit by
knowing.
: These icons represent keys on the DCP301’s console.
+ : Combinations of icons like these indicate that must be pressed
while holding down.
(1) (2) (3) :The numbers with the parenthesis indicate steps in a sequence or
indicate corresponding parts in an explanation.
>> :Indicates the controller state after an operation.
PROG
RUN/HOLD
RUN/HOLD
PROG
DISP
Page 14
Chapter 1. GENERAL
1-1
Chapter 1. GENERAL
1-1 Features
The DCP301 is a general-purpose single-loop program controller for controlling temperature, pressure, flow rate and other inputs.
High accuracy achieved by multi-range input
Multi-range input allows you to choose between the following input types: thermocouple, resistance temperature detector (RTD), dc voltage and dc current. Accuracy of ±0.1%FS±1 digit and a sampling cycle of 0.1s ensures consistently high-precision control.
Wide range of control output types
A wide range of models supporting various control output types are available: relay time­proportional output, position-proportional output, current output, voltage time-propor­tional output, and heat/cool output.
On models other than heat-cool control output, you can also choose neural net-based auto-tuning and smart-tuning for inhibiting overshoot, in addition 2 degrees of freedom PID.
Enhanced compatibility with PLC
12 external switch inputs (eight optional), three event outputs and five time event outputs (optional) ensure compatibility with automating systems designed around a PLC core.
Easy operation
Up to eight frequently changed parameter setups can be registered to the
PARA
key, facili-
tating recall of item setups. If the Smart Loader Package (sold separately) is used together with the DCP301, pro-
grams and parameters can be set up on a personal computer.
Page 15
Chapter 1. GENERAL
1-2
4 external switch inputs
• RUN
• HOLD
• RESET
• ADV
* indicates options.
Input
• Thermocouple
• Resistance
• dc current
• dc voltage
8 external switch inputs
• Program No.
• FAST
• PV start
• AUTO/MANUAL
• AT
• G.Soak cancel
• Direct/reverse action
Key operation
• Display selection
• Program No.
• RUN/HOLD
• RESET
• ADV
• FAST
• AUTO/MANUAL
• AT
• Program setup
• Parameter setup
MFB input
• Square root extraction
• Bias
• Filter
Control Operation Block
• Mode transition
• PID control
• Auto-tuning
• Neuro & Fuzzy
• Forward/reverse action
• ON-OFF control
• SP limit
• SP bias
• Output change limitter
• Upper/lower limitter
• SP output
Outputs
• Current
• Relay
• Voltage
• Position-proportional
• Heat-cool
Event Outputs
• PV
• SP
• Deviation
• MV
• MFB
• Modes
• Alarm
Time Event Outputs
• Time event
• Segment code
Auxiliary Outputs
• PV
• SP
• Deviation
• MV
• MFB
CPL communications I/O
Loader communications I/O
*
*
*
Program
• 19 patterns x 30 segments
• Events
• Time events
• PID sets
• G.Soak
• PV start
• Cycle
• Pattern link
Parameters
• Variable parameters
• Event configuration
• PID parameters (8 sets)
• Setup
• Tables
• Constant-value operation
*
temperature detector
Lineariza­tion table approxima­tion
1-2 Basic Function Blocks
Page 16
Chapter 1. GENERAL
1-3
1-3 Data Structure
Data is made up of “parameters” that are used mainly for setting controller functions and “programs” that are used for setting operation during program operation of the controller.
• Total of 19 program patterns
SP
Time
Program No.=19 Number of segments=8
SP
Time
Program No.=3 Number of segments=15
Time
Program No.=2 Number of segments=19
SP
(5)
(6)
Time
Program No.=1 Number of segments=6
(18)
(19)
(1)
(2)
(3)
(4)
(12)
(13)
(14)
(15)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
• Parameters
Variable parameters
Event configuration data
PID parameters
Setup data
Table data
Constant-value operation data
Page 17
Chapter 1. GENERAL
1-4
1-4 System Configuration
System configuration by CPL communications
On DCP301 models supporting RS-485 communications (optional), controllers can be connected as slave stations on a communications network.
Personal computer (master station)
DCP301 (slave station)
RS-485
RS-232C
RS-232C/RS-485 converter
Page 18
Chapter 1. GENERAL
1-5
1-5 Model Numbers
Model selection guide
P301 Digital Program Controller (single-
loop model)
0D Relay outputs (on-off, or time-
proportional) 2G Position-proportional output 5G Current output
(controller/programmer selectable)
(changeable to 6D output) 6D Voltage output (current value
adjustment function supported, on-
off, or time-proportional)
(changeable to 5D output) 3D Heat-cool output, relay output +
relay output (PID control or 3-
position-proportional) 5K Heat-cool output, current output +
current output (changeable be-
tween current output and voltage
output)
0 One input channel
ES Free power supply (90 to 264Vac)
00 No auxiliary output 01 1 auxiliary output 02 2 auxiliary outputs
0 External switch inputs (4), time
events not supported, communica-
tions not supported
1 External switch inputs (12), 5 time
events supported, communications
not supported
2 External switch inputs (12), 5 time
events supported, RS-485 commu-
nications supported
00 Additional treatment not supported T0 Tropical treatment
K0 Antisulfide treatment D0 Inspection Certificate supplied B0 Additional treatment + Inspection
Certificate provided
L0 Antisulfide treatment + Inspection
Certificate provided
Y0 Traceability Certificate
Basic
Model Output Function Power Option Option Additions Description
No.
12
Handling Precautions
On 2G, 3D and 5K output models, 2 auxiliary output (option 1) cannot be desig­nated.
Page 19
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-1
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-1 Structure
This controller comprises a body, console, case, standard terminal base and add-on terminal base.
Key cover Cover for preventing erroneous operation.
Lock screw Fixes the case to the body.
Case
Console
Body Contains console and electrical circuits.
Standard terminal base
Add-on terminal base
Contains 7-segment display, LEDs, operation keys and loader connector.
Connectors for connecting power, input, output, event outputs, external switch inputs (4) and auxiliary outputs (options)
Terminal for connecting external switch inputs (8 options), time event outputs (options) and CPL communications (options). The add-on terminal base is provided only on models that support optional external switch inputs (8) and time event outputs.
Page 20
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-2
2-2 Console
The console comprises keys for operating the controller, displays and LEDs.
Basic display state
The “basic display state” is the state in which the controller operating state is displayed on the console.
When the power is turned ON, the controller is in this state. Key operation changes the controller from the basic display state to one of the parameter
setup, program setup, program copy or general reset states. Key operation also returns the controller to the basic display state.
Parameter setups
Program setups
Program copy
General reset
Power ON
Basic display states
Display
Program No. display
Mode indicator LED lamps
Event LEDs
Segment No. display
Basic indicator LED lamps
Upper display
Lower display
Low battery voltage LED (BAT) Control/output state LED
Profile display
• Program No. display In the basic display state, this display indicates the currently selected program No.
In the program setup state, this display indicates the program No. currently being set up. During constant-value operation, this display goes out in the basic display state. When an alarm occurs in the basic display state, alarm code “A L” is displayed.
• Segment No. display In the basic display state, this display indicates the currently selected segment No.
In the program setup state, this display indicates the segment No. currently being set up. During constant-value operation, this display goes out in the basic display state. In the parameter setup state, this display indicates the item No. When an alarm occurs in the basic display state, the alarm code No. is displayed.
Page 21
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-3
Mode indicator LEDs RUN, HLD: Display the READY, RUN, HOLD, FAST and END modes. (See follow-
ing table.)
READY RUN HOLD FAST EN D
RUN Out Lit Out Blinking Out HLD Out Out Lit Out Blinking
Mode
LED
MAN : Lights in the MANUAL mode, and goes out in the AUTO mode. PRG : Lights in the program setup state. Otherwise, this LED is out.
Upper display In the basic display state, displays PV and other values. In the parameter setup state, displays the item code.
Lower display In the basic display state, displays SP, time, output and other values. In the parameter setup state, displays the item setting value.
Low battery voltage LED BAT: Blinks when the battery voltage is low. Otherwise, this LED is out.
Control/output state LED
AT: Blinks during auto-tuning, and lights during smart-tuning. Otherwise, this LED is
out.
OT1: When relay or voltage are assigned to output 1, lights when output is ON and goes
out when output is OFF. In the case of 2G output models, lights when the open­side relay is ON and goes out when the relay is OFF.
Lights when current output is assigned to output 1.
OT2: When relay or voltage are assigned to output 2, lights when output is ON and goes
out when output is OFF. In the case of 2G output models, lights when the closed­side relay is ON and goes out when the relay is OFF. Lights when current output is assigned to output 2, and goes out when auxiliary output is assigned to output 2.
OT3: Out
Basic indicator LEDs
PV: Lights during PV display. Otherwise, this LED is out. SP: Lights during SP display. Otherwise, this LED is out. OUT: Lights during output display. Otherwise, this LED is out. TM: Lights during time display. Otherwise, this LED is out. CYC: Lights during cycle display. Otherwise, this LED is out. CH1: Out CH2: Out
Event LEDs
EV1, EV2, : In the basic display state or parameter setup state, light when each of EV3 events1 to 3 are ON, and go out when OFF.
In the program setup (programming) state, light when each of the items for events 1 to 3 are displayed. Otherwise, these LEDs are out.
T1, T2, T3, : • Light when each of time events 1 to 5 are ON, and go out when OFF. T4, T5 • In the program setup (programming) state, light when each of the items
for time events 1 to 5 are displayed. Otherwise, these LEDs are out.
Profile display Displays the tendencies (rise, soak, fall) of the program pattern. Blinks during G.soak standby, and lights successively after the power is turned ON.
Page 22
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-4
FUNC
+
DISP
PROG
PROG
PROG
A/M
AT
: Program key
: Function key
Loader jack
: Auto/Manual key
: Auto-tuning key
: Parameter key
PROG
FUNC
A/M
AT
PARA
: Enter key
ENT
: Clear key
CLR
: Run/Hold key
RUN/HOLD
: Display key
DISP
: Left arrow key, right arrow key : Up arrow key, down arrow key
To change the display To change the program No. in ascending order
(in READY mode) To execute running of program
(in READY mode) To run the program
(in READY, HOLD, FAST modes) To hold the program
(in RUN mode) To reset the program
(in READY, HOLD, FAST, END modes) To advance the program
(in RUN, HOLD, FAST modes) To run the program fast
(in RUN, HOLD modes) To execute manual operation
(in AUTO mode) To execute automatic operation
(in MANUAL mode) To start auto-tuning
(when not executing auto-tuning) To cancel auto-tuning
(when executing auto-tuning) To change values during manual operation
(when MV or SP is blinking)
+
DISP
+
RUN/HOLD
RUN/HOLD
Category Function Key operation
Basic display state
Keys
Page 23
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-5
Starts parameter setup. So the controller enters se­lection of setup group (major item). (in basic display state)
To change the setup group (major item)
To fix the setup group To moves between individual items (minor items) To start changing individual item setting values
(while setting value is blinking) To end changing individual item setting values
(while setting value is blinking) To change individual item setting values
(while setting value is blinking) To cancel changing individual item setting values
(in basic display state) To selects setup group To end parameter setup To start changing assignment item setting values
(in basic display state) To move to next item by assignment item, and start
changing setting values To change assignment item setting values
(while setting value is blinking) To end changing assignment item setting values
(while setting value is blinking)
To start changing assignment item setting values To end assignment item setup To start program setup (programming)
(in basic display state) To move between program items and segment Nos.
To start changing item setting values (while setting value is blinking)
To end changing item setting values (while setting value is blinking)
To change item setting values (while setting value is blinking)
To clear item setting (while setting value is blinking)
To cancel changing item setting values (while setting value is blinking)
To insert/delete segments To change the program No. in ascending order
To change the program No. in descending order To end program setup (programming)
PARA
ENT
FUNC
+
PARA
ENT
PARA
DISP
FUNC
+
FUNC
+
PROG
FUNC
+
ENT
DISP
FUNC+CLR
ENT
FUNC
+
PROG
DISP
DISP
PARA
PARA
ENT
Category Function Key operation
Parameter setup
key Assignment item setup
Program setup
Page 24
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-6
Category Function Key operation
Program copy
General reset
Do not operate the console keys using a sharp-pointed object such as a propel­ling pencil or needle. Doing so might damage the console.
To start program copy +
PROG
(in basic display state) To change the copy destination program No. To execute program copy
ENT
(while setting value is blinking) To end program copy
DISP
To check general reset
FUNC
+
CLR
+
DISP
(in basic display state) To execute general reset
ENT
To cancel general reset
DISP
Handling Precautions
Page 25
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-7
Functions using two or more keys
PROG
+
RUN/HOLD
: Reset keys
Press
RUN/HOLD
with
PROG
held down in the basic display state to reset the controller. The controller enters the READY mode in the RUN, HOLD, FAST or END modes. The controller cannot be reset in the READY mode by key operation.
PROG
+
DISP
: Advance keys
Press
DISP
with
PROG
held down in the program operation mode in the basic display state to advance the program. In the RUN, HOLD or FAST modes, the program advances to the next segment. The controller cannot advance in the READY mode by key operation.
FUNC
+ : Fast keys
Press with
FUNC
held down in the program operation mode in the basic display state to fast-operate the program. The controller enters the FAST mode from the RUN or HOLD modes.
FUNC
+
PARA
: Parameter setup keys
Press
PARA
with
FUNC
held down in the basic display state to move to selection of the setting
group (major items) in the parameter setup state.
FUNC
+
PROG
: Program setup (programming) keys
Press
PROG
with
FUNC
held down in the program operation mode in the basic display state to move to the program setup (programming) state. Press
PROG
with
FUNC
held down in the program setup state to change the No. of the program to be set up in ascending order.
FUNC
+ : Program No. change keys
Press with
FUNC
held down in the program setup state to change the No. of the program to
be set up in descending order.
FUNC+CLR
: Program item delete keys
Press
CLR
with
FUNC
held down during entry of settings in the program setup state to clear the
setting.
FUNC
+
ENT
: Segment insert/delete keys
Press
ENT
with
FUNC
held down at SP or time item in the program setup state to move to the
segment insert/delete screen.
+
PROG
: Program copy keys
Press
PROG
with held down in the program operation READY mode in the basic display
state to move to the program copy screen.
FUNC+CLR
+
DISP
: General reset keys
Press
CLR
and
DISP
with
FUNC
held down in the READY AUTO mode in the basic display
state to move to the general reset confirmation screen.
Loader jack
This jack is for connecting the loader. Objects other than the loader plug should not be inserted into this jack.
The loader jack is not isolated from internal digital circuits. Be sure to cap the loader jack when it is not in use.
Page 26
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-8
Input Format Range No. Code Temp. Range (°C) Temp. Range (°F)
K (CA) 0 K09 0 to 1200 0 to 2400 K (CA) 1 K08 0.0 to 800.0 0 to 1600 K (CA) 2 K04 0.0 to 400.0 0 to 750 K (CA) 3 K29 -200 to 1200 -300 to 2400 K (CA) 4 K44 -200.0 to 300.0 -300 to 700 K (CA) 5 K46 -200.0 to 200.0 -300 to 400 E (CRC) 6 E08 0.0 to 800.0 0 to 1800 J ( IC) 7 J08 0.0 to 800.0 0 to 1600 T (CC) 8 T44 -200.0 to 300.0 -300 to 700 B (PR30-6) 9 B18 0 to 1800 0 to 3300 R (PR13) 10 R16 0 to 1600 0 to 3100 S (PR10) 11 S16 0 to 1600 0 to 3100 W (WRe5-26) 12 W23 0 to 2300 o to 4200 W (WRe5-26) 13 W14 0 to 1400 0 to 2552 PR40-20 14 D19 0 to 1900 0 to 3400 Ni-Ni-Mo 15 Z13 0 to 1300 32 to 2372 N 16 U13 0 to 1300 32 to 2372 PL II 17 Y13 0 to 1300 32 to 2372 DIN U 18 Z08 -200.0 to +400.0 -300 to +750 DIN L 19 Z07 -200.0 to +800.0 -300 to +1600 Golden iron 20 Z06 0.0 to +300.0K
chromel
Input Format Range No. Code Temp. Range (°C) Temp. Range (°F)
JIS’89 Pt100 32 F50 -200.0 to 500.0 -300 to 900 (IEC Pt100) 33 F46 -200.0 to 200.0 -300 to 400
34 F32 -100.0 to 150.0 -150.0 to 300.0 35 F36 -50.0 to 200.0 -50.0 to 400.0 36 F38 -60.0 to 40.0 -76.0 to 104.0 37 F33 -40.0 to 60.0 -40.0 to 140.0 38 F05 0.0 to 500.0 0.0 to 900.0 39 F03 0.0 to 300.0 0.0 to 500.0 40 F01 0.00 to 100.00 0.0 to 200.0
JIS’89 J Pt100 48 P50 -200.0 to 500.0 -300 to 900
49 P46 -200.0 to 200.0 -300 to 400 50 P32 -100.0 to 150.0 -150.0 to 300.0 51 P36 -50.0 to 200.0 -50.0 to 400.0 52 P38 -60.0 to 40.0 -76.0 to 104.0 53 P33 -40.0 to 60.0 -40.0 to 140.0 54 P05 0.0 to 500.0 0.0 to 900.0 55 P03 0.0 to 300.0 0.0 to 500.0 56 P01 0.00 to 100.00 0.0 to 200.0
2-3 Input Type and Range No.
Inputs
Thermocouple
Resistance temperature detector (RTD)
Page 27
Chapter 2. NAMES & FUNCTIONS OF PARTS
2-9
dc current, dc voltage
Input Format Range No. Code Range (programmable)
4 to 20mA 64 C01 0 to 20mA 65 C08 0 to 10mA 66 M01
-10 to +10mV 67 L02 0 to 100mV 68 L01 -1999 to 9999 0 to 1V 69 L04
-1 to +1V 70 L08 1 to 5V 71 V01 0 to 5V 72 L05 0 to 10V 73 L07
• The unit of code Z06 is Kelvin (K)
• The lower limit readout of code B18 is 20°C (68°F). The lower limit readout (°C) of codes K44, K46, T44, Z08 and Z07 is -199.9°C.
• The lower limit readout (°C) of codes F50, F46, P50 and P46 is -199.9°C.
• The upper limit readout (°C) of codes F01 and P01.
• The PV lower limit alarm does not occur with code F50. However, note that the PV lower limit alarm occurs at a disconnection when
input has been downscaled when input is disconnected during setup.
• The number of digits past the decimal point for dc current and dc voltage is programmable within the range 0 to 3.
Handling Precautions
Page 28
Chapter 3. MOUNTING
3-1
Chapter 3. MOUNTING
3-1 External Dimensions
B-B
37
78.4
110.5
A-A
90.2
91.5
Back plate
Add-on terminal base
Terminal screw
(106x104)
(18)
15
159.5 137
AB
AB
Unit: mm
Mounting bracket 81405411-001
Soft dust-proof cover set (sold separately) 81446087-001
Hard dust-proof cover set (sold separately) 81446083-001
Terminal cover set (sold separately) 81446084-001
96
96
Page 29
Chapter 3. MOUNTING
3-2
92
+0.8
0
46 4696 x (N - 1)
96 x N - 4
92
+0.8
0
92
+0.8
0
N=number of units installed
Panel cutout dimensions
Panel cutout dimensions during multiple mounted
(recommended)
Unit: mm
150min.(when vertically mounted)
99 min. (when horizontally mounted)
(107 min. when hard dust-prevention cover is used)
Panel cutout dimensions when mounting units horizontally and vertically (recommended)
3-2 Panel Cutout Dimensions
Use a steel panel of at least 2mm in thickness for mounting the controller.
When mounting the controller, take care to prevent the temperature at the lower surface of the controller’s case from exceeding the operating temperature range (0 to 50°C), particularly when mounting vertically or during multiple mounting.
Handling Precautions
Page 30
Chapter 3. MOUNTING
3-3
Use the DCP301 within the operating ranges recommended in the specifi­cations (temperature, humidity, voltage, vibration, shock, mounting direc­tion, atmosphere, etc.). Failure to do so might cause fire or faulty operation.
Do not block ventilation holes. Doing so might cause fire or faulty operation.
Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation.
Before wiring, or removing/mounting the DCP301, be sure to turn the power OFF. Failure to do so might cause electric shock.
Do not disassemble the DCP301. Doing so might cause electric shock or faulty operation.
WARNING
3-3 Mounting
CAUTION
Mounting locations
Avoid installing the DCP301 in the following locations:
• Locations outside of the operating temperature range (0 to 50°C) and operating humid-
ity range (10 to 90%RH)
• Locations subject to sulfide gas or other flammable gases
• Locations subject to dust or oil smoke
• Locations subject to the direction sunlight, wind or rain
• Locations that directly subject the body to vibration or impact
• Locations under high-voltage lines, near welders or near sources of electrical noise
• Locations near (within 15m) of high-voltage ignition equipment such as boilers
• Locations where magnetic fields are generated
• Locations subject to flammable liquids or moisture
Page 31
Chapter 3. MOUNTING
3-4
indicates that a function can be used.
The varister may become short-circuited when trouble occurs. Pay attention to this when providing a varister on a controller.
Dust-proof cover
Use the dust-proof cover when using the controller in a dusty or dirty location, and to prevent inadvertent operation.
Two dust proof-covers are provided, hard or soft, each with the following differing func­tions.
Type Confirmation on Display Operation
Hard x
Soft
Noise generating sources and countermeasures
Generally, the following generate electrical noise: (1) Relays and contacts (2) Solenoid coils, solenoid valves (3) Power lines (in particular, 90Vac min.) (4) Induction loads (5) Inverters (6) Motor commutators (7) Phase angle control SCR (8) Wireless communications equipment (9) Welding equipment (10) High-voltage ignition equipment
If the influence of electrical noise cannot be eliminated, we recommend taking the following countermeasures:
- Provision of a CR filters for fast-rising noise
Recommended CR filter: Model No. 81446365-001
- Provision of a varister for noise with a high wave height
Recommended varister: Model No.81446366-001 (100V)
81446367-001 (200V)
Handling Precautions
Page 32
Chapter 3. MOUNTING
3-5
Mounting bracket 81405411-001Panel
Mounting bracket
Mounting method
Firmly secure the top and bottom of the controller by the mounting brackets.
When mounting the controller, secure by lower mounting bracket (1) first.
(1)
Panel
Panel
Mounting bracket
(2)
To secure the controller, tighten the screw on the mounting bracket (supplied) until there is no more play and then tighten a further full turn. Take care not to overtighten the screw. Doing so might deform the case.
Keep the mounting angle to within 10° from the horizontal at both the controller rear
top and bottom.
Lift up from rear by 10° max.
Pull down from rear by 10° max.
Handling Precautions
Page 33
Chapter 4. WIRING
4-1
Chapter 4. WIRING
4-1 Wiring Precautions
Wire the DCP301 properly according to predetermined standards. Also wire the DCP301 using designed power leads according to recognized installation methods. Failure to do so might cause electric shock, fire or faulty operation.
Do not allow lead clippings, chips or water to enter the DCP301 case. Do­ing so might cause fire or faulty operation.
Inputs to the current input terminals (31) and (33) on the DCP301 should be within the current and voltage ranges listed in the specifications. Failure to do so might cause electric shock or faulty operation.
Firmly tighten the terminal screws at the torque listed in the specifications. Insufficient tightening of terminal screws might cause electric shock or fire.
Do not use unused terminals on the DCP301 as relay terminals. Failure to do so might cause electric shock, fire or faulty operation.
We recommend attaching the terminal cover (sold separately) after wiring the DCP301. Failure to do so might cause electric shock, fire or faulty op­eration.
Use the relays on the DCP301 within the service life listed in the specifica­tions. Continued use of the relays after the recommended service life might cause fire or faulty operation.
Use induced lighting surge preventive device if there is the risk of power surges caused by lightning. Failure to do might cause fire or faulty operation.
WARNING
Before connecting the DCP301 to the measurement target or external con­trol circuits, make sure that the FG terminal is properly grounded (100 max.).
Failure to do so might cause electric shock or fire. Before wiring, or removing/mounting the DCP301, be sure to turn the power
OFF. Failure to do so might cause electric shock. Do not touch electrically charged parts such as the power terminals. Doing
so might cause electric shock.
CAUTION
Page 34
Handling Precautions
• Before wiring the DCP301, check the controller catalog No. and terminal Nos. on the label on the rear of the body. After wiring the DCP301, be sure to check the wiring for any mistakes.
• Maintain a distance of at least 50cm between I/O leads or communications leads and the power lead. Also, do not pass these leads through the same piping or wiring duct.
• When wiring with crimped terminals, take care to prevent contact with adjacent terminals.
• When connecting the DCP301’s thermocouples in parallel to other controllers, make sure that the total input impedance of the other controller is at least 1MΩ.
If the input impedance is less than 1M, the DCP301 may not be able to detect sensor disconnection.
• When inputting the DCP301’s I/O (parallel connection in case of input) to an A/ D converter or analog scanner, read data may fluctuate.
To prevent this, adopt one of the following measures.
(1) Use a low-speed, integrating type A/D converter.
(2) Insert an isolator without a switching power supply between the DCP301
and A/D converter.
(3) Average data on a personal computer when reading data.
(4) If possible, set a filter for the input.
• Provide the wiring for the instrument power supply with a mains power shutoff switch within reach of the instrument operator.
• Provide the wiring for the instrument power supply with a delayed operation type (T) 1A current rating, 250V voltage rating fuse. (IEC 127)
• Devices and systems to be connected to this unit must have the basic insula­tion sufficient to withstand the maximum operating voltage levels of the power supply and input/output parts.
4-2
Page 35
Chapter 4. WIRING
4-3
4-2 Compensating Lead
In the case of thermocouple input, connect the bare thermocouple lead to the terminal. If the thermocouple is located a long way from the DCP301 or the thermocouple is connected to a terminal, extend the connection using a compen­sating lead and then connect to the terminal. Use shielded compensating leads only.
• For I/O other than thermocouples, use JCS-364 shielded instrument polyethylene insu­lated vinyl sheath cable or equivalent product. (This is generally referred to “twisted shielded cable for instruments.”) The following cables are recommended.
Fujikura Ltd. 2-core IPEV-S-0.9mm
2
x 1P
3-core ITEV-S-0.9mm
2
x 1T
Hitachi Cable Co. 2-core KPEV 0.9mm
2
x 1P
3-core KTEV-S-0.9mm
2
x 1T
• Shielded, multi-core microphone cord (MVVS) can be used if there is little electro­magnetic induction.
Page 36
Chapter 4. WIRING
4-4
4-3 Terminal Connections
Use crimped terminals that fit onto M3.5 screws.
7.4
7.3 max.
6.6 max.
3.7dia.
Unit: mm
When installing the DCP301 in locations subject to vibration or impact, be sure to use round crimped terminals to prevent the lead from coming loose from the terminal.
When wiring with crimped terminals, take care to prevent contact with adjacent terminals.
The recommended tightening torque for the terminal screws is 0.78 to
0.98Nm.
Handling Precautions
Page 37
Chapter 4. WIRING
4-5
4-4 Layout of Terminals and Recommended Lead Draw-out
Direction
Wiring is carried out on the standard terminal base or add-on terminal base. The following diagram shows the recom­mended draw-out directions for the leads on the standard terminal base.
The lead draw-out directions are the same when using the add-on terminal base.
Standard terminal base
Lead draw-out direction
Lead draw-out direction
(11) to (20) to left ( )
(1) to (10) to left ( )
(21) to (26) to left ( )
(26) to (34) to right ( )
Page 38
Chapter 4. WIRING
4-6
4-5 Connecting the Ground and Power Supply
Power supply
Connect the DCP301 to a single-phase power supply for controllers, and take measures to prevent the influence of electrical noise.
1
3
2
1
2
E
3
4
GND
~
Instrument power supply
Other circuits
GND GND
Recommended
line filter
81446364-001
DCP301
200/200V,
100/100V
insulated transformer
If the power supply generates a lot of electrical noise, we recommend inserting an insulating transformer in the power circuit and using a line filter.
Recommended line filter: Model No. 81446364-001
After providing anti-noise measures, do not bundle primary and secondary power leads together, or pass them through the same piping or wiring duct.
Ground
When it is difficult to ground shielded cable, prepare a separate ground terminal (earth bar).
Ground type: 100 max. Ground cable: 2mm sq. min soft-copper wire (AWG14) Cable length: Max. 20m
3
FG terminal
DCP301
GND terminal plate
GND (100 max.)
Shielded cable
Use only the FG terminal (3) on the DCP301 for grounding. Do not ground across other terminals.
Handling Precautions
Handling Precautions
Page 39
Chapter 4. WIRING
4-7
* On 2G, 3D or 5K models, (17) and (18) are the auxiliary outputs.
On 0D, 5G or 6D models, (14) and (15), and (17) and (18) are the auxiliary outputs.
4-6 Wiring of Standard and Add-on Terminal Base
Standard terminal layout
Add-on terminal layout
10
8
9
6
7
4
5
3
1
2
20
18
19
16
17
14
15
13
11
12
24
25
23
21
22
33
34
31
32
29
30
28
26
27
RSW1
RSW2
RSW3
RSW4
*
mAdc
COM
V, mV
1
3
Y
EV1
EV2
EV3
T
G
2
90 to 264Vac 50/60Hz
Instrument power supply
FG (Frame GND)
Event outputs
2G output
OD output 3D output
5G output 6D output 5K output Auxiliary output
Relay
Relay
4 to 20mA voltage
4 to 20mA voltage
4 to 20mA
Output 1 Output 2
Auxiliary output 1
Auxiliary output 2
External switch input (RSW)
Current input
Input
Resistance temperature detector
Voltage input
Thermocouple input
Auxiliary output 4 to 20mA Recorder, etc.
44
45
46
47
48
43
41
42
55
56
53
54
51
52
49
50
63
64
62
59
60
57
58
61
RSW5
T1
T2
T3
T4
T5
SDA
SDB
RDA
RDB
SG
RSW6
RSW7
RSW8
RSW9
RSW10
RSW11
RSW12
External switch inputs
To terminals
Time event outputs
Load
Load
Load
Load
Load
External
10 to 29Vdc power supply
Bias circuit
RS-485 communications
25
Page 40
Chapter 4. WIRING
4-8
31
32
33
34
31
32
33
34
31
32
33
34
V, mV
C
B
A
31
32
33
34
mA
4-7 Connecting Inputs (analog inputs)
Connecting input 1
Multiple input 1 supports various sensor inputs. Connect as follows according to the sensor being used.
Thermocouple input RTD input
dc voltage input dc current input
Applying voltage across dc current input terminals (31) and (33) may cause
faulty operation.
Take care of polarities (+,-) when wiring inputs.
Use only shielded cable for wiring inputs.
When using a thermocouple input, prevent air blasts from coming into contact
with the terminal. Doing so might cause a reading error.
Handling Precautions
Page 41
Chapter 4. WIRING
4-9
WARNING
4-8 Connecting control outputs (outputs 1, 2)
Before wiring, or removing/mounting the DCP301, be sure to turn the power OFF. Failure to do so might cause electric shock.
Relay output (0D)
Connect as follows.
11
12
13
Load
Power supply
Contact rating, resistive load 5A (30Vdc/120Vac) 4A (240Vac)
Minimum switching current: 100mA
When switching small currents, connect a bleeder resistor to allow current flow of the minimum relay switching input (100mA min.).
Current output (5G)
Connect as follows.
11
12
13
Actuator
4 to 20/0 to 20mAdc Resistive load 600 max.
11
12
13
14
15
16
G
T
Y
1
3
2
Open side
Power supply
Closed side
Open
Closed
Contact rating 4A (120Vac, cosø=0.4) 2A (240Vac, cosø=0.4)
Feedback resistance 100 to 2500
Load
Load
The life of internal relays is limited. Avoid setting the PID constant in such a way that results in excessive repeated ON/OFF switching.
When using a 100/200Vac motor, pay attention to rush current and the contact rating. If necessary, provide an external auxiliary relay.
Separate the wiring for motor terminals (11) (12) (13) and feedback resistor terminals (14) (15) (16). (Do not wire the leads in the same duct or use 6-core cable. Doing so might result in faulty controller operation caused by electrical noise when the motor is started up.)
When controlling without motor feedback with variable parameter M .-Cset to2, terminals (14) (15) (16) need not be connected.
4 to 20mAdc and 0 to 20mAdc can be selected in setup data C 9 0.
Position-proportional output (2G)
Connect as follows paying attention to the switching direction.
Handling Precautions
Handling Precautions
Handling Precautions
Page 42
Chapter 4. WIRING
4-10
11
12
13
SSR
2 to 22mAdc With current adjustment function (setup: C78)
Voltage output is reliant on an internal fixed-current circuit. Set the current value in the setup data so that the optimum voltage is obtained
matched to the conditions of the SSR in use and load. Factory setting: general-purpose SSR voltage value.
Heat/cool output (3D)
Connect as follows.
11
12
13
14
15
16
Load
Power supply
Load
Power supply
Output 1 Contact rating, resistive load 5A (30Vdc/120Vac) 4A (240Vac)
Minimum switching current: 100mA
Output 2 Contact rating, resistive load 5A (30Vdc/120Vac) 4A (240Vac)
Minimum switching current: 100mA
When switching small currents, connect a bleeder resistor to allow current flow of the minimum relay switching input (100mA min.).
Heat/cool output (5K)
Connect as follows.
11
12
13
(SSR)
14
15
16
(SSR)
Load
Load
Output 2
Output 1
Voltage output: 2 to 22mAdc With current adjustment function (setup: C78)
Current output: 4 to 20/0 to 20mAdc Load resistance 600 max.
Voltage output: 2 to 22mAdc With current adjustment function (setup: C79)
Current output: 4 to 20/0 to 20mAdc Load resistance 600 max.
Voltage output (6D)
Connect as follows.
Current output and voltage output can be selected by setups C 7 5 and C 7 6. Voltage output is reliant on an internal fixed-current circuit. Set the current value in the setup data so that the optimum voltage is obtained
matched to the conditions of the SSR in use and load. Factory setting: general-purpose SSR voltage value.
Handling Precautions
Handling Precautions
Handling Precautions
Page 43
Chapter 4. WIRING
4-11
Before wiring, or removing/mounting the DCP301, be sure to turn the power OFF. Failure to do so might cause electric shock.
4-9 Connecting auxiliary outputs (outputs 2, 3)
Optional auxiliary outputs can be added on.
0D, 5G, 6D auxiliary outputs
WARNING
14
15
16
17
18
19
Receiver
Receiver
Auxiliary output 1 (output 2) 4 to 20/0 to 20mAdc Resistive load 600 max.
Auxiliary output 2 (output 3) 4 to 20/0 to 20mAdc Resistive load 600 max.
• 4 to 20mAdc and 0 to 20mAdc can be selected in setup data C 9 0.
Use shielded cable only.
2G, 3D, 5K auxiliary outputs
17
18
19
Receiver
Auxiliary output 2 (output 3) 4 to 20/0 to 20mAdc Resistive load 600 max.
Auxiliary output 1 is not provided for 2G, 3D and 5K outputs.
• 4 to 20mAdc and 0 to 20mAdc can be selected in setup data C 9 0.
Use shielded cable only.
Handling Precautions
Handling Precautions
Page 44
Chapter 4. WIRING
4-12
4-10 Connecting Event Output (relay output)
Event outputs EV1 and EV2 are 1a contact, and event output EV3 is 1a1b. Event outputs are connected on the standard terminal base.
10
8
9
6
7
4
5
EV1 1a
EV2 1a
EV3 1a1b
Load
Power supply
Load
Power supply
Load
Power supply
Standard terminal base
Contact rating, resistive load 1A (30/250Vdc)
Contact rating, resistive load 1A (30/250Vdc)
Contact rating, resistive load 2A (30/250Vdc)
Minimum switching current: 10mA
When switching small currents, connect a bleeder resistor to allow current flow of the minimum relay switching input (10mA min.).
Handling Precautions
Page 45
Chapter 4. WIRING
4-13
4-11 Connecting Time Event Output (open-collector)
Optional time event outputs T1 to T5 (open-collector outputs) can be added on. Time event outputs are connected on the add-on terminal base.
56
53
55
51
52
49
50
10 to 29Vdc
T1
T2
T3
T4
T5
Load
Load
Load
Load
Load
External power supply
Add-on terminal base
Bias circuit
Maximum load current: OFF leakage current:
70mA/load
0.1mA max.
Be sure to connect terminal (55) to the + terminal of the external power supply. Otherwise, open-collector output will not function.
Do not short-circuit the + terminal of the external power supply and terminals (49) to (53) on the DCP301. Doing so will cause faulty open-collector output.
(The DCP301 does not contain a short-circuit prevention circuit.)
When connecting to a semiconductor load such as a programmable controller (sequencer), select a module whose current directions are matching.
Use a module that does not operate by leakage current when the open-collec­tor output of the DCP301 is OFF.
Handling Precautions
Page 46
Chapter 4. WIRING
4-14
4-12 Connecting External Switch (RSW) Input
The DCP301 is provided with four external switch inputs as standard (eight optional). The optional eight inputs are located on the add-on terminal base. Wire the external switch inputs across the standard and add-on terminal bases.
25
23
24
21
22
RSW1
RSW2
RSW3
RSW4
COM
45
43
44
41
42
48
46
47
RSW5
RSW6
RSW7
RSW8
RSW10
RSW11
RSW12
RSW9
Add-on terminal base
Standard terminal base
Contact
Contact
Contact
Contact
Contact
Contact
Contact
Contact
Contact
Contact
Contact
Contact
The external switch inputs on the DCP301 have built-in power supplies (open voltage 12Vdc). Be sure to use no-voltage contacts for external contacts.
Use no-voltage contacts such as gold contacts whose small current can be switched ON/OFF. On some relay contacts, the small current cannot be switched ON/OFF. Use no-voltage contacts having a sufficient minimum switching ca­pability with respect to the contact current and open voltage of the DCP301.
When using a semiconductor (e.g. open-collector) as a no-voltage contact, use a semiconductor whose contact terminal voltages at contact ON are 3V max., and whose leakage current at contact OFF is 0.1mA.
External switch inputs on the DCP301/302 can be connected in parallel. When connecting in parallel with other controllers, thoroughly check the condi-
tions of the other controller before configuring the control system.
Handling Precautions
Page 47
Chapter 4. WIRING
4-15
Internal circuit for controller components for connecting external switch inputs
24
21
25
12Vdc
12Vdc
48
41
12Vdc
12Vdc
Standard terminal base
External switch input
External switch input
Internal circuit Internal circuit
Add-on terminal base
Page 48
Chapter 4. WIRING
4-16
4-13 Connecting for Communications
Some controller models support the RS-485 communications interface. Select the RS-485 communications models by selected the required catalog No.
Connect as follows.
The DCP301 operates as a slave station.
RS-485 interface
57
58
59
60
61
SDA
SDB
RDA RDB
SG
Add-on terminal base
Multi-drop connection of slave stations is possible.
Make sure that different addresses are set for each slave station.
Provide terminating resistor (total of 4 in the case of a 5-wire system connec-
tion) on both ends of the communications path. Use terminating resistor of 150Ω±5%, 1/2W min.
In the case of a 3-wire system connection, short-circuit terminals (57) and (59), (58) and (60) on the DCP301.
Do not short-circuit the RDA and RDB, or SDA and SDB terminals. Doing so might damage the DCP301.
Handling Precautions
Handling Precautions
Page 49
Chapter 4. WIRING
4-17
5-wire system RS-485 mutual connection
57
58
59
60
61
SDA
SDB
RDA RDB
SG FG
57
58
59
60
61
SDA
SDB
RDA RDB
RDA RDB
SDA SDB
SG FG
SG FG
57
58
59
60
61
SDA
SDB
RDA RDB
SG FG
Terminating resistor
Terminating resistor
Terminating resistor
Terminating resistor
Slave station DCP301
Shielded cable
Shielded cable
Shielded cable
Master station
Slave station DCP301
Slave station DCP301
Provide terminating resistor of 150Ω±5%, 1/2W min. at both ends of the communications path. Grounding of the shielded FG terminal should be carried out at only one end and not both ends.
Be sure to connect SG terminals each others. Failure to do so might cause unstable communications.
Handling Precautions
Page 50
Chapter 4. WIRING
4-18
3-wire system RS-485 mutual connection
Provide terminating resistor of 150Ω±5%, 1/2W min. at both ends of the communications path. Grounding of the shielded FG terminal should be carried out at only one end and not both ends. When there are only three RS-485 terminals, terminals marked * are wired internally.
57
58
59
60
61
SDA
SDB
RDA RDB
SG FG
57
58
59
60
61
SDA
SDB
RDA RDB
RDA RDB
SDA SDB
SG
FG
SG FG
57
58
59
60
61
SDA
SDB
RDA RDB
SG FG
Terminating resistor
Terminating resistor
Slave station DCP301
Slave station DCP301
Slave station DCP301
Shielded cable
Master station
Shielded cable
Shielded cable
*
*
Be sure to connect SG terminals each others. Failure to do so might cause unstable communications.
Handling Precautions
Page 51
Chapter 4. WIRING
4-19
4-14 Isolating Inputs and Outputs
The following figures show isolation between inputs and outputs. Solid lines show isolated items, and dotted lines show non-isolated items.
Control outputs 0D, 5G, 6D, 3D, 5K
31
11 12
14 15
17 18
4 5
6 7 8 9
10 49
56
32 33 34
21
25 41
48 57
61
Input 1 (full multiple-input PV supported)
Output 1
(relay, current, voltage output)
Output 2
(relay, current, voltage output, auxiliary output)
Output 3 (auxiliary output)
Event output 1 (relay output 1a)
Event output 2 (relay output 1a)
Event output 3 (relay output 1a1b)
Time event outputs 1 to 5 (open-collector output)
Loader communications I/O
Loader jack
12 external switch inputs
Communications I/O (RS-485)
Digital circuit
31
11 12 13 14 15 16 17 18
4 5
6 7 8 9
10 49
56
32 33 34
21
25 41
48 57
61
Input 1 (full multiple-input PV supported)
Output 1 (control output 1a relay x 2)
Motor feedback input
Output 3 (auxiliary output)
Event output 1 (relay output 1a)
Event output 2 (relay output 1a)
Event output 3 (relay output 1a1b)
Time event outputs 1 to 5 (open-collector output)
Loader communications I/O
Loader jack
12 external switch inputs
Communications I/O (RS-485)
Digital circuit
The loader jack is not isolated from internal digital circuits. Be sure to cap the loader jack when it is not in use.
Control output 2G
Handling Precautions
Handling Precautions
The loader jack is not isolated from internal digital circuits. Be sure to cap the loader jack when it is not in use.
Page 52
Chapter 5. FUNCTIONS
5-1
Chapter 5. FUNCTIONS
5-1 Data
Data types
The DCP301 supports the following data types. For further details, see Chapter 7, Parameter Setup and Chapter 8, Program Setup.
Data that can be changed even in RUN mode
Data Parameters
Program
Data (e.g. event type)
Control parameters of PID sets 1 to 8
Basic data that can be changed only in READY mode
Linearization table data
Data (e.g. SP, PID) of constant-value operation
SP and time data
Events 1 to 3 data
Time events 1 to 5 time data
PID set No. data for use in control
G.Soak ON/OFF data
PV START ON/OFF data
Cycle count data
Pattern link destination program No. data
Variable parameters
Event configuration data
PID parameters
Setup data
Table data
Constant-value operation data
Pattern
Event
Time event
PID set No.
G.Soak
PV start
Cycle
Pattern link
Page 53
Chapter 5. FUNCTIONS
5-2
5-2 Program Patterns
Patterns
SP and time comprise the settings for a single segment in a pattern. Up to 30 segments can be linked to create a broken-line whose vertical axis is SP and horizontal axis is time. This system is called the “RAMP-X” system.
SP setting: Within range of SP limitter upper and lower limits Timesetting: 0 to 99h, 59min or 0 to 99min, 59s
(Select the time unit in setup data C 6 4.)
SP is the point that corresponds to the time elapsed in the current segment on a straight line made by jointing the start point (SP setting value of the previous segment) to an end point (SP setting value of the current segment).
Accordingly, segments are categorized as follows:
• Rising ramp (rising ramp, rising tendency) Previous segment SP setting value < current segment SP setting value
• Falling ramp (falling ramp, falling tendency) Previous segment SP setting value > current segment SP setting value
• Soak (soak) Previous segment SP setting value = current segment SP setting value
In the case of the No.1 segment, both the start and end points become the soak segment of the No.1 segment SP setting values.
SP (other than No.1 segment) is calculated as by the following formula: SP = (current segment SP setting value - previous segment SP setting value) x (current
segment elapsed time ÷ current segment time setting) + previous segment SP set­ting
Time setting of current segment
SP setting value of current segment
SP setting value of previous segment
Page 54
Chapter 5. FUNCTIONS
5-3
Events 1 to 3
Events 1 to 3 are event configuration data. These are used after setting the event type, event standby, hysteresis and ON delay time.
A total of three event types are available: PV type events, controller status events, and
time events.
PV type events
Basic specifications The following page shows event type PV, deviation, absolute value deviation, SP, MV
and MFB. In the figures, the thick lines show ON-OFF changes in state. The upper line expresses the ON state, and the lower line the OFF state.
EV and H stand for event setting value and hysteresis, respectively. Output in the READY state is OFF.
Event standby Events function as follows when event standby has been set to ON.
- If the controller is in the state in the figure when changing from the READY to
the RUN mode and after restoring the power, operation is the same as when event standby is set to OFF. The up-facing arrow in the figure indicates a change to ON, and a down-facing arrow indicates a change to OFF.
- If the controller is outside the state in the figure when changing from the READY
to the RUN mode and after restoring the power, the state is OFF. After entering the
state, the up-facing arrow in the figure indicates a change to ON, and a down-
facing arrow indicates a change to OFF.
Event ON delay The event No. to apply the delay to and the delay time can be set regardless of event
type. Delay functions to turn output ON when the event is continuously ON for the preset delay time after the event OFFON condition is satisfied.
When event ON delay is combined with event standby, event standby must first be canceled before event ON delay functions.
Segment progression
- Output is OFF until the program progresses to the segment containing the event
setting.
- When the program progresses to the segment containing the event setting, event ON/
OFF operation is carried out according to the event setting value.
- The previous setting is valid until the program progresses to a segment containing a
new event setting. For this reason, set as follows to disable the event set in the previous segment from a
certain segment onwards:
Direct action events: Upper limit value of event setting Reverse action events: Lower limit value of event setting
Note, however, that some types of event turn ON even if events are set as shown above.
- When the program has progressed to the No.1 segment by the cycle or pattern link
functions, the previous setting is disabled. Output is OFF unless the No.1 segment contains an event setting.
Other On 5G output models, when setup data C 1 8 is set to 1, and SP output (programmer
functions) is selected, the MV direct/reverse event does not function.
Page 55
Chapter 5. FUNCTIONS
5-4
H
EV
PV
H
EV
PV
PV reverse
H
SP+EV
PV
Deviation reverse
H
EV
SP
SP reverse
H
EV
MV
MV reverse
H
EV
MFB
MFB reverse
H
SP+EV
PV
Deviation direct
H H
EVEV
SP
PV
Absolute value deviation direct
H
EV
SP
SP direct
H
EV
MV
MV direct
H
EV
MFB
MFB direct
H H
EVEV
SP
PV
Absolute value deviation reverse
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Page 56
Chapter 5. FUNCTIONS
5-5
Controller status events
Controller status events are turned ON and OFF according to the controller mode, alarm status and other statuses.
Though the event standby function does not function, the ON delay function does. Event setting values (operating point), hysteresis and event standby are not set.
Basic operations The following basic operation types are provided:
RUN+HOLD+FAST+END READY RUN HOLD FAST END G.Soak standby MANUAL Auto-tuning executing Constant-value operation MFB estimated position control, sum of all alarms PV range alarm Controller alarms Low battery voltage Console setup in progress Loader setup in progress ADV
When the DCP301 reaches the state designated by the event type, the event is turned ON. Otherwise, the event is OFF.
Alarms Alarms are divided into PV range alarm groups (alarm code Nos. 01 to 16) and control-
ler alarm groups (alarm code Nos. 70 to 99, and low battery voltage). When the event type is set to the sum of all alarms, the alarm turns ON even if at least
one of the alarms occurs. When the event type is set to PV range alarm, the alarm turns ON even if at least one of
the alarms in the PV range alarm group occurs. When the event type is set to controller alarm, the alarm turns ON even if at least one
of the alarms in the controller alarm group occurs.
ADV This is ON for 1s after executing program advance. The event ON delay is disabled
and a delay is not applied.
Time events
When the event 1 to 3 type is set to time event, the event can be used in the same way as time events 1 to 5. However, note that events 1 to 3 do not have segment No. event functions.
Though the event standby function does not function, the ON delay function does.
Page 57
Chapter 5. FUNCTIONS
5-6
Time events 1 to 5
Either of time events or segment No. events can be selected by the time event type item in the event configuration data setup.
Time events
Segment 1
ON time OFF time Output ON Output OFF
ON<OFF
Segment 2 3
ON time OFF time Output ON Output OFF
Output turns OFF at end of segment even if OFF time is not set.
Segment 5 6
ON time OFF time Output ON Output OFF
ON continued
Segment 3B 3C
ON time OFF time Output ON Output OFF
No ON
ON=OFF ON>OFF
Segment 4
Segment time
5
ON time OFF time Output ON Output OFF
G.Soak standby
ON-OFF time is invalid even if set in excess of segment 4 time.
Advance to segment 5
ON=0
Segment 7
ON time OFF time Output ON Output OFF
Segment time start
The ON and OFF times or only the ON time can be set for each event No. and segment. The fol­lowing describes ON/OFF of output.
When the ON time is smaller than the OFF time, output is ON for the duration from the ON time to the OFF time. (See segments 1, 6 and 7 in the figure.)
When only the ON time is set, output is ON for the during from the ON time to the seg­ment end point. (See segments 2 and 5 in the figure.)
When both the ON time and OFF time are not set, output is OFF. (See segment 3 in the figure.)
Setting only the OFF time without an ON time is not possible. (See segment 3B in the figure.)
Setting an ON time to be greater to or equal than the OFF time is not possible. (See segment 3C in the figure.)
Only ON and OFF times set within the seg­ment time are valid. Times straddling the next segment are invalid. The ON and OFF times set in the next segment are valid. (See segments 4 and 5 in the figure.)
Accordingly, the ON and OFF times settings at the segment end point are ignored.
However, ON and OFF times set for segment end points when the END mode is shifted to are valid. (See segment 9 in the figure, and compare with segment 10 in the END mode.)
When the ON time is set to 0 (no OFF time setting, or OFF time is greater than 0), output becomes OFF at time 0.
If output at the previous segment end point was ON at this time, the output status at the seg­ment switching point does not momentarily become OFF. (See segments 5 and 6 in the figure.)
The G.Soak standby time is not included in the ON and OFF times. (See segment 7 in the figure.)
Page 58
Chapter 5. FUNCTIONS
5-7
Segment 8
ON time OFF time Output ON Output OFF
G.Soak standby
Segment 9
ON time OFF time Output ON Output OFF
ON=segment time
Segment 10
Segment time
ON time OFF time Output ON Output OFF
END mode
ON=segment time
Segment 8 time start
When 0N=0, output turns ON when there is input to segment 8.
If the ON time is set to 0 in the case of G.Soak standby, output becomes ON from the G.Soak standby state, and the ON time is started at completion of the G.Soak standby time.
The output time = G.Soak time + OFF time (See segment 8 in the figure.)
ON and OFF time settings the same time as the segment end point are valid in the case of the final segment END mode. (See segment 10 in the figure.)
Segment No. events
The current segment No. is output as binary code. When all of T1 to T5 are selected as segment No. events in the time event type setup, all
ON-OFF operations are as shown in the following table. When T1 to T4 are assigned in part to segment No. events, only the assigned time events
operate as shown in the following table, and the remaining events operate as regular time events.
123456789101112131415
T1 ON OFF O N OFF ON OFF ON OFF ON OFF ON OFF O N OFF ON T2 OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF O N ON T3 OFF OFF OFF ON O N ON O N OFF OFF OFF OFF ON ON ON ON T4 OFF OFF OFF OFF OFF OFF OFF ON ON ON O N ON O N ON ON T5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
T1 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF T2 OFF OFF ON ON OFF OFF O N ON OFF OFF ON ON OFF OFF O N T3 OFF OFF OFF OFF ON ON O N ON OFF OFF OFF OFF ON ON O N T4 OFF OFF OFF OFF OFF OFF OFF OFF ON O N ON O N ON ON ON T5 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
Event No.
Segment
No.
Event No.
Segment
No.
Page 59
Chapter 5. FUNCTIONS
5-8
12 43
PID set No.
PID set segment designation
Zone 8
Zone 7
Zone 6
Zone 5
Zone 4
Zone 3
Zone 2
Zone 1
All SP ranges are divided to eight zones.
PID set automatic switching
C P. 1 7
C
P. 1
6
C
P. 1
5
C
P. 1
4
C
P. 1
3
C
P. 1
2
C
P. 1
1
Eight sets of PID parameters, PID1 to PID8, are used for control operation. When the PID set No. is set to each seg­ment by designating the PID set segment, control output is calculated by each of the PID parameters.
There are two ways of selecting PID sets: by designating the PID set segment and PID set auto-switching. The method can be selected by setting setup data C 1 1.
C 1 1 set to 0: Designation of PID set segment C 1 1 set to 1: PID set auto-switching
These two methods cannot be set simultaneously.
When setup data C 1 1 is set to 1, PID items in the program setup are not displayed.
By designation of PID set segment, the PID set No. is set for each segment, and control output is calculated by each of the PID parameters.
By PID set auto-switching, the SP full-scale is divided into eight zones according to the settings of C P . 1 1 to C P . 1 7, and the PID constant to be used according to the SP value is automatically selected to calculate the control output.
PID set selection
G.Soak (guarantee soak)
G.Soak ON/OFF and G.Soak width can be set for each seg­ment. The G.Soak time can also be set by the variable param­eter G S . t item.
The G.Soak function ensures a segment execution time with PV close to SP. G.Soak functions not only in soak segments but also in ramp segments.
At the segment start point, PV and SP are compared, and the absolute value of the resulting deviation continues for the G.Soak time or longer. When the absolute value is smaller than the G.Soak width, operation of that segment is started.
The controller is in the G.Soak standby state until this condi­tion is satisfied, and the linear lamp on the left of the profile display blinks. The operation state is the same as hold at the segment start point (time is set to 0). However, note that in the FAST mode, the controller does not enter the G.Soak standby state even if G.Soak is set to ON. The G.Soak standby state can also be canceled by external switch output. The following cancel conditions can be selected by the setup date C 5 2 to C 5 4 settings.
(1) G.Soak cancel when external switch input contact is ON or
PV satisfies the G.Soak cancel conditions
(2) G.Soak cancel when external switch input contact is ON
and PV satisfies the G.Soak cancel conditions
SP
SP
PV
G.Soak width
G.Soak width
Segment execution time
G.Soak standby time
Time count start
Segment set time
Time
G.Soak at segment start point
Note
Page 60
Chapter 5. FUNCTIONS
5-9
A
C
A'
B
SP pattern
Start point
Current
PV value
Start point
Start point
(1)
(1)'
(1)"
PV start
If PV start is set in the program setup, PV is started by regular RUN operation.
The first point where PV matches the SP in the program pattern (including bias for both PV and SP) is searched for, and operation is started from that point.
However, note that if a matching point is not found, op­eration is started from the beginning of segment 1.
When PV has started, event operating points and the time of time events are automatically corrected. If the PV start function is selected by setup data C 5 2 to C 5 4 settings relating to external switch input, PV start can be executed without setting PV start in the program setup.
PV start is valid for segments in the currently selected program, and invalid for the segment at the pattern link destination.
Cycle
The cycle function is for repeating operation from the No.1 segment of the program pattern to the final set segment for a preset number of cycles. The number of cycles can be set up to 9999.
When a number of cycles “n” is set, the operation count becomes n+1”.
When executing cycle operation, operation at the end point of the final segment is not carried out, and operation is restarted with the settings of events 1 to 3 and time events 1 to 5 cleared. At this time, PV is not started and opera­tion starts from the No.1 segment even if PV start is set.
If the SPs at the pattern start and end points do not match, the SP changes in a stepped manner during cycle opera­tion.
SP
Cycle 1
Time
(1)
(2)
(3)
(4)
(5)
(6)
PV start points (1) PV starts at point A where the PV value first
crosses the SP pattern.
(1)' PV starts at point B where the PV value first
crosses the SP pattern.
(1)'' Point C of segment 1 is the PV start point
since there is no point where the PV value crosses the SP value.
Page 61
Chapter 5. FUNCTIONS
5-10
SP
SP
SP
Program No.2 pattern-linked to program No.1
Program No.1
Program No.2
Time
Time
Time
Program No.1 Program No.2
Pattern link
pattern link is a function for linking patterns together. The link destination program No. is set by the pattern link item.
When the pattern link item is set to 0 (initial setting), patterns are not linked. When the No. of the current pro­gram itself is set to the pattern link item, this creates an endless loop.
If the SPs at the link source end point and the link desti­nation start point do not match, the SP changes in a stepped manner during link operation.
When cycle operation has been set, the pattern link func­tion works after cycle operation has ended. After pattern link operation ends, operation begins from the No.1 seg­ment of the link destination pattern, so operation is re­started with the settings of events 1 to 3 and time events 1 to 5 cleared.
If PV start is programmed to the link destination pattern, the PV start function operates after the link is made.
After the link has been made, PID operation is not ini­tialized, and is continued.
Page 62
Chapter 5. FUNCTIONS
5-11
5-3 Modes
Mode types
The following modes are available on the DCP301.
READY
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
RUN
HOLD
END
FAST
READY
Program operationMode
Constant-value operation
RUN
Program operation
Operation is carried out according to SP, times, events, etc. set to program patterns No.1 to 19.
Constant-value operation
Operation is carried out according to SP or events set in the constant-value operation data. Time events 1 to 5 turn OFF.
READY
In this mode, the DCP301 is ready for operation. MV output is fixed, and events to be operated according to event setting values turn OFF.
However, events to be operated according to controller states are active. Parameters for all of the setup data, some event configuration data and some constant-
value operation data can be set or changed in the READY mode. During program opera­tion, program pattern Nos.1 to 19 can be selected.
Page 63
Chapter 5. FUNCTIONS
5-12
RUN
In this mode, the program is running. MV outputs are active in PID control or ON-OFF control, and events and time events are
active. In the program operation mode, program operation progresses according to the elapsed
time. However, note that progress of program operation stops in the same way as the HOLD
mode when the controller is in the G.Soak (Guarantee Soak) standby state.
HOLD
In this mode, the program is held. Progress of program operation stops. However, note that MV outputs are active in PID
control or ON-OFF control, and events and time events are active in the same way as in the RUN mode. The HOLD mode is not available during constant-value operation.
FAST
In this mode, the program is fast-forwarded. This mode is like the RUN mode except that progress of the program operation time is
speeded up. The time scale is selected by the variable parameter F A S T setting. MV outputs are active in PID control or ON-OFF control, and events and time events are
active. The controller does not enter the G.Soak standby state even if G.Soak (Guarantee Soak)
is set. The FAST mode is not available during constant-value operation.
END
In this mode, operation of the program has ended. MV outputs are active in PID control or ON-OFF control, and events and time events are
active with program operation stopped at the program end point. The END mode is not available during constant-value operation.
AUTO
In this mode, program operation is automatic. MV output is active according to controller control. (However, note that when programmer functions are selected on 5G output models, SP
output is active according to controller control.)
MANUAL
In this mode, program operation is manual. MV output can be changed by , , , on the console or communications. (However, note that when programmer functions are selected on 5G output models, SP
output can be changed by , , , on the console or communications.)
Page 64
Chapter 5. FUNCTIONS
5-13
READY AUTO READY MANUAL
RUN AUTO RUN MANUAL
RUN
RESET
Mode transition
During program operation
The solid lines in the following diagram show mode transition operations. The broken lines show end of operation.
END AUTO END MANUAL
READY AUTO READY MANUAL
RUN AUTO RUN MANUAL
HOLD AUTO HOLD MANUAL
FAST AUTO FAST MANUAL
RESET
HOLD
RUN
FAST FAST
RUN
RESET
RUN
RESET
HOLD
ADV
ADVADVADV
RESET
Mode changes to READY or END at end of operation.
• When shifting between the AUTO and MANUAL modes, the modes in the square frames can be shifted between.
• Selection of the READY or END modes at end of operation is set up in the setup data.
During constant-value operation
The solid lines in the following diagram shows mode transition operation.
When shifting between the AUTO and MANUAL modes, the modes in the square frames can be shifted between.
Switching between program operation and constant-value operation
In the READY mode, select operation by the constant-value operation data “M .O D E” operation mode item.
0: Program operation 1: Constant-value operation
Note
Note
Page 65
Chapter 5. FUNCTIONS
5-14
Mode transition operations
The following describes mode transition operations. Though program end is not an operation, it is described below as it is a factor in mode
transition.
RUN
This operation involves shifting to the RUN mode from the READY, HOLD or FAST modes. To shift from the READY mode to the RUN mode, the DCP301 must be in the basic display state even in key, external switch input or communication operations.
HOLD
This operation involves shifting to the HOLD mode from the RUN or FAST modes. The HOLD mode is not available in the constant-value operation mode.
RESET
This operation involves shifting to the READY mode from the RUN, HOLD, FAST or END modes.
In the program operation mode, this mode includes returning to the No.1 segment.
ADV
This operation involves advancing one segment in the READY, RUN, HOLD or FAST modes.
The ADV mode is not available in the constant-value operation mode.
FAST
This operation involves shifting to the FAST mode from the RUN or HOLD modes. The FAST mode is not available in the constant-value operation mode.
AUTO
This operation involves shifting to the AUTO mode from the MANUAL mode.
MANUAL
This operation involves shifting to the MANUAL mode from the AUTO mode. When the DCP301 enters the MANUAL mode, the basic display state changes as fol-
lows.
- When controller functions are selected, PV and output value (%) are displayed.
- When programmer functions are selected, PV and SP are displayed. When the DCP301 enters the MANUAL mode from the AUTO mode by external switch
inputs or communications, the display changes to the basic display state even in the pa­rameter setup or program setup states.
Program end
When operation progresses in the RUN or FAST modes in the program operation mode, or when the segment has been advanced in the ADV mode, the program ends when all end points in the program setup including cycles and pattern links have been reached.
You can select in the setup setting in which of the READY or END modes program operation ends.
The program does not end in the constant-value operation mode.
Page 66
Chapter 5. FUNCTIONS
5-15
Mode transition limitations
Mode transition can be carried out operating the console keys, external switching input and communications. The following table shows which operations are enabled in each of the modes.
Operation RUN HOLD RESET ADV * FAST
(to RUN mode) (to HOLD mode) (to READY mode) (to FAST mode)
(to next segment mode)
Com­muni­cations
Key
Switch
Key
Switch
Com­muni­cations
Com­muni­cations
Key
Switch
Key
Switch
Com­muni­cations
Com­muni­cations
Key
Switch
Original mode
READY
—— ——∆∆— ————
RUN
❍❍ ❍❍ ❍❍ ❍❍
HOLD
❍❍—— — ❍❍ ❍❍ ❍❍
FAST
❍❍ ❍❍ ❍❍ ❍❍———
END ——————
❍❍——————
READY
❍❍————————————
RUN ——————
❍❍——————
Operation MANUAL AUTO
(to MANUAL mode) (to AUTO mode)
Original mode
AUTO
❍❍———
MANUAL
❍❍
AUTO
❍❍———
MANUAL
❍❍
Com­muni­cations
Key
Switch
Key
Com­muni­cations
Switch
Constant­value operation
Program operation
Program operation
Constant­value operation
: Operation is enabled.
: Operation is enabled if in basic display state.
: No.1 segment is returned to if controller is still in READY mode.
: Operation is disabled.
* With ADV by communications, mode transition is not limited to the next segment; the
mode advances to the segment specified in the communications message.
Page 67
Chapter 5. FUNCTIONS
5-16
5-4 Controller and Programmer
On 5G output models (output catalog No. appended with 5G), you can choose between use as a controller or a programmer. Set this in setup data C 1 8. You can also choose between controller or programmer functions even if the DCP301 is used for program operation or constant-value operation.
The DCP301 is limited to use as a controller at all times on other models.
Controller
When the DCP301 is used as a controller, PID control operation is carried out according to PV, SP AND PID setting values, and the resulting manipulated variable (MV) is out­put as an analog output.
ON-OFF control, heat/cool PID control and 3-position-proportional is also possible de­pending on the type of output supported by the model of DCP301.
In the MANUAL mode, the MV can be incremented or decremented in the basic display state by the console keys.
PV
MV
DCP301 controller
Controlled system
Programmer
When the DCP301 is used as a programmer, PID control operation is not carried out, and the SP is output in the scaled 4 to 20mA range.
In the MANUAL mode, the SP can be incremented or decremented in the basic display state by the console keys.
PV
PV
4 to 20mA
MV
PV
MV
PV
MV
DCP301 programmer
SP output
RSP input
Controller Controller Controller
Controlled system Controlled system Controlled system
Page 68
Chapter 5. FUNCTIONS
5-17
5-5 Input Processing Functions
Input processing is carried out in the order shown below.
(resistance temperature detector)
(thermocouple)
Input range type
Wiring resistance compensation
Analog input 1
A/D conversion
Cold junction compensation
Upper/lower limit value scaling
Upper/lower limit alarm
Square-root extraction
Temperature unit range
Linearization approximation
Digital filter
Bias
PV1
(DC current and voltage)
Setting: Setup data
C03
Setting: Setup data
C72
Setting: Setup data
C0 7
(thermocouple and resistance temperature detector) Setting: Setup data
C02
(DC current and voltage) Setting: Setup data
C0 4
to
C06
Setting: Setup data
C08
Table data
T-A. 1
to
T-B.B
Setting: Variable parameter
FL
Setting: Variable parameter
PBi
Page 69
Chapter 5. FUNCTIONS
5-18
5-6 Output Processing Functions
Three outputs are provided as output processing functions: control output, SP output and auxiliary output.
Control output
When the DCP301 is selected for use as a controller, control output is operational. How outputs are processed varies according to the output type supported on the model.
5G output
Over-range
READY mode
MANUAL mode
Current output 4 to 20mA (0 to 20mA)
Initialization of PID control
operation
PID control operation
Output change limitter
Output upper/lower limit limitter
Manipulated variable (MV1)
Output 1
AT execution
MV in READY mode
Preset manual value
Manual MV
MV at over-range
AT operation
Setting: Variable parameters 1 OUT/rpi d
Setting: PID parameters p/ 1 / d/8E PID parameters dP/di /dd PID parameters br
Setting: Variable parameters OTL
Setting: Variable parameter AT
Setting: PID parameters OL/OH
Setting: Setup data C 12/C 13
Setting: Setup data C 14/C 15
Setting: Setup data C 16
Page 70
Chapter 5. FUNCTIONS
5-19
0D, 6D output
AT execution
Over-range
MANUAL mode
PID control operation
Initialization of PID control operation
Output change limitter
Output upper/lower limit limitter
Voltage output 1 adjustment
Time-proportional relay output Time-proportional voltage output
Output 1
Manipulated variable (MV1)
Output 1 time-proportional output cycle
ON/OFF control
MV at over-range
READY mode
MV in READY mode
Preset manual value
Manual MV
AT operation
ON/OFF control operation
Setting: PID parameters p/ 1 / d/RE PID parameters dP/di /dd PID parameters br
Setting: Variable parameters OTL
Setting: PID parameters OL/OH
Setting: Variable parameter AT
Setting: Setup data C 12/C 13
Setting: Setup data C 14/C 15
Setting: Variable parameter DI FF
Setting: Setup data C 16
(6D output) Setting: Setup data C78
Setting: Variable parameter Cy. 1
Setting: Variable parameters 1 OUT/rpi d
In ON-OFF control, the DCP301 cannot be set to the MANUAL mode. (The DCP301 can be set to the MANUAL mode as ON-OFF control is not possible in the READY mode.)
Handling Precautions
Page 71
Chapter 5. FUNCTIONS
5-20
2G output
Over-range
READY mode
MFB automatic adjustment execution
PID control operation
Initialization of PID control operation
Output change limitter
Output upper/lower limit limitter
MFB operation
Motor control operation
Manipulated variable (MV1)
Motor control method selection
AT execution
MV in READY mode
MANUAL mode
Manual MV
Preset manual value
MFB automatic adjustment
MV at over-range
AT operation
Output 1
open-side relay
Output 1
closed-side relay
Setting: Variable parameters 1 OUT/rpi d
Setting: PID parameters p/ 1 / d/RE PID parameters dP/di /dd PID parameters br
Setting: Variable parameters OTL
Setting: Variable parameter AT
Setting: PID parameters OL/OH
Setting: Setup data C 12/C 13
Setting: Setup data C 14/C 15
Setting: Setup data C 16
Setting: Variable parameter DI FF
Setting: Variable parameter M.-AT
Setting: Variable parameter M.-C
Setting: Variable parameters M.-CL/M.-OP/M.-T
Page 72
Chapter 5. FUNCTIONS
5-21
READY mode
MANUAL mode
READY/AUTO modes READY/AUTO modes
Time-proportional relay output Current output 4 to 20mA (0 to 20mA) Time-proportional voltage output
PID control operation
Initialization of PID control operation
Output change limitter
(odd-numbered PID sets)
Output upper/lower limit limitter
(even-numbered PID sets)
Heat-side Cool-side
Output upper/lower limit limitter
MV (heat)
Output 1 time-proportional output cycle
Voltage output 1 adjustment
Output 1
Time-proportional relay output Current output 4 to 20mA (0 to 20mA) Time-proportional voltage output
MV (cool)
Output 2 time-proportional output cycle
Voltage output 2 adjustment
Output 2
Manipulated variable (MV1)
Heat-cool MV operation
Over-range
Manual MV
3-position control
3-position control operation
Preset manual value
MV in READY mode (heat)
3-position control
MV in READY mode (cool)
3-position control operation
50%
MV at over-range
Setting: Variable parameters 1 OUT/rpi d
Setting: PID parameters p/ 1 / d/RE
Setting: Variable parameters OTL
Setting: Setup data C 12/C 13
Setting: Setup data C 14/C 15
Setting: Variable parameter DI FF
Setting: PID parameters OL/OH
Setting: Setup data C 16
Setting: Setup data C 17
(relay/voltage output) Setting: Variable parameter CY. 1
(relay/voltage output) Setting: Variable parameter CY.2
(voltage output) Setting: Setup data C78
(voltage output) Setting: Setup data C79
Setting: PID parameters OL/OH
Setting: Setup data
Variable parameters
C45
Dv-L/HY-L
Setting: Setup data
Variable parameters
C45
Dv-H/HY-H
3D, 5K outputs
In 3-position control, the DCP301 cannot be set to the MANUAL mode
Handling Precautions
Page 73
Chapter 5. FUNCTIONS
5-22
SP output
When the DCP301 is selected for use as a programmer, control output is operational. On 5G output models, SP output is processed is as follows.
Auxiliary output
Auxiliary output 1
When auxiliary output 1 or 2 are supported on 0D, 5G or 6D output models, auxiliary output 1 is processed as follows.
Auxiliary output 2
When auxiliary output 2 is supported on 0D, 5G or 6D output models, auxiliary output 2 is processed as follows.
When auxiliary output 1 is supported on 2G, 3D or 5K output models, auxiliary output 2 is processed as follows.
MANUAL mode
Main output types
Upper/lower limit scaling
SP1 output
Output 1
READY mode
Upper/lower limit scaling
Manual SP1
MV in READY mode
Current output 4 to 20mA (0 to 20mA)
Setting: Setup data C 16
Setting: Setup data C 18
Setting: Setup data C 19/C20
Setting: Setup data C 19/C20
Auxiliary output 1 type
Upper/lower limit scaling
Output 2
4mA (0mA)
Current output 4 to 20mA (0 to 20mA)
When READY mode is entered at auxiliary output type SP and deviation
When auxiliary output type is NOP When auxiliary output type is set to MFB on non-
2G output models When auxiliary output type is set to MV by program-
mer function on 5G output models
Setting: Setup data C46
Setting: Setup data C47 /C48
Auxiliary output 2 type
Upper/lower limit scaling
Output 3
4mA (0mA)
Current output 4 to 20mA (0 to 20mA)
When READY mode is entered at auxiliary output type SP and deviation
When auxiliary output type is NOP When auxiliary output type is set to MFB on non-2G
output models When auxiliary output type is set to MV by program-
mer function on 5G output models When auxiliary output type is set to MV by 3-position­proportional control on 3D output models
Setting: Setup data C49
Setting: Setup data C50/C5 1
Page 74
Chapter 6. OPERATION
6-1
Chapter 6. OPERATION
6-1 Turning the Power ON
The DCP301 is not equipped with a power switch or protective fuses. If necessary, prepare these externally. When a voltage of 90 to 264Vac is applied across terminals (1) and (2) on the DCP301, display appears for about 10s
after which control and other operations are started. During controller startup until start of operations, the LEDs on the profile display light successively at uneven intervals clockwise from top right. The following diagram shows the flow of operations at startup.
Startup flow
Power ON
NO
YES
Start of operations
Check start of general reset
Press key.
RAM backup normal?
ENT
Continuation of program operation/constant-value oper­ation modes
Continuation of READY/RUN/HOLD/FAST/END modes Continuation of AUTO/MANUAL modes (Continuation of manual value if in MANUAL mode) Continuation of program No./segment No. Continuation of segment progress time Continuation of display No. of basic display state in
AUTO mode
Parameter=factory shipment setting Delete entire program. Program operation mode READY mode AUTO mode Program No.1=1/segment No.=1 Segment progress time=0
Cancellation of auto-tuning/smart-tuning Cancellation of MFB automatic adjustment by 2G output Initialization of G.Soak standby time Initialization of PID operation Initialization of event output state Setting display state Basic display state Display No. of basic display state in MANUAL mode
With the following modes and items, the state when the power is turned OFF continues when the power is turned back ON.
• READY, RUN, HOLD, FAST, END modes
• AUTO, MANUAL modes
• MANUAL values in MANUAL mode
• Program No., segment No.
• Progress time in segment
• Display No. if in basic display state in AUTO mode
Handling Precautions
Page 75
Chapter 6. OPERATION
6-2
6-2 Switching the Basic Display
The “basic display state” of the controller collectively refers to the display state of the program No. display, segment No. display, upper display, lower display, basic indicator LED lamps and event LEDs.
Each press of
DISP
successively switches the basic display state. Operation of other displays and LEDs is carried out
in the same way even when setting up parameters, for example. However, switching by
DISP
is not possible.
The following figure shows the conventions used for displays in this manual.
PROFILE
(2)
(1)
(3)
(4)
(5)
(6)
Current segment Next segment
Falling ramp
Soak
Rising ramp
Rising ramp
Soak
Falling ramp
PV
SP
: LED lit
: LED blinking
PV SP
Program/segment No. Display
Basic indicator LED lamps
Program No. Segment No.
Pattern
tendency
Upper display
Lower display
Event LEDs
Output states of events 1 to 3, time events 1 to 5
Supplementary explanation
In the program operation mode, READY indicates the currently selected program/segment No. Displays other than READY indicate the currently operating program/seg-
ment No. In the constant-value operation mode, nothing is displayed and this dis-
play is blank.
In the program operation mode, the profile is displayed only when the program has been set up. The profile is not displayed when the program is not set up.
When there is no subsequent segment even if the program is set up, the three LEDs on the right do not light. In the constant-value operation mode, nothing is displayed and this display is blank.
Profile Display
Page 76
Chapter 6. OPERATION
6-3
Display in program operation mode
DISP
functions
Output Model No. Display
0D, 5G, 6D Display 1 Display 2 Display 5 Display 6 Display 7
Display 1 (repeated)
2G Display 1 Display 2 Display 3 Display 5 Display 6
Display 7 Display 1 (repeated)
3D, 5K Display 1 Display 2 Display 4 Display 5 Display 6
Display 7 Display 1 (repeated)
Display 1
PV SP
PV
SP
Program No. Segment No.
Pattern
tendency
Output states of events 1 to 3, time events 1 to 5
The digit to which SP values can be entered blinks in the MANUAL mode when pro­grammer functions are selected.
Display 2
PV
OUT
PV
Output value (%)
Program No. Segment No.
Pattern
tendency
Output states of events 1 to 3, time events 1 to 5
The digit to which SP values can be entered blinks in the MANUAL mode when control­ler functions are selected.
Display 3
Program No. Segment No.
Pattern
tendency
Motor valve opening (%)
Output states of events 1 to 3, time events 1 to 5
F B
This display is exclusive to 2G output models (output catalog No. appended with 2G).
Page 77
Chapter 6. OPERATION
6-4
Display 4
OUT
Heat-side output (%)
Cool-side output (%)
Program No. Segment No.
Pattern
tendency
Output states of events 1 to 3, time events 1 to 5
This display is exclusive to heat/cool output models (output catalog No. appended with 3D or 5K).
Display 5
PV
TM
PV
Time
Program No. Segment No.
Pattern
tendency
Output states of events 1 to 3, time events 1 to 5
Either of h:min or min:s is selected as the time unit in setup settings. Select eitherremaining segment time or total operating time in setup settings as the details whose
time is to be displayed.
Display 6
PV
CYC
PV
Number of remaining cycles
Program No. Segment No.
Pattern
tendency
Output states of events 1 to 3, time events 1 to 5
When the remaining number of cycles is “0”, subsequent cycle operation is not carried out.
Page 78
Chapter 6. OPERATION
6-5
Display 7
SP TM
SP
Time
Program No. Segment No.
Pattern
tendency
Output states of events 1 to 3, time events 1 to 5
The digit to which SP values can be entered blinks in the MANUAL mode when pro­grammer functions are selected. Either of “h:min” or min:s is selected as the time unit in setup settings. Select either remaining segment time or total operating time in setup settings as the details whose time is to be displayed.
Display in constant-value operation mode
DISP
functions
Output Model No. Display
0D, 5G, 6D Display 1 Display 2 Display 1 (repeated) 2G Display 1 Display 2 Display 3 Display 1 (repeated) 3D, 5K Display 1 Display 2 Display 4 Display 1 (repeated)
Display 1
PV SP
PV
SP
Output state of events 1 to 3
The digit to which SP values can be entered blinks in the MANUAL mode when control­ler functions are selected.
Display 2
PV
OUT
PV
Output value (%)
Output state of events 1 to 3
The digit to which SP values can be entered blinks in the MANUAL mode when pro­grammer functions are selected.
Page 79
Chapter 6. OPERATION
6-6
Display 3
This display is exclusive to 2G output models (output catalog No. appended with 2G).
Display 4
OUT
Heat-side output (%)
Cool-side output (%)
Output state of events 1 to 3
This display is exclusive to heat/cool output models (output catalog No. appended with 3D or 5K).
Motor valve opening (%)
Output state of events 1 to 3
F B
Page 80
Chapter 6. OPERATION
6-7
6-3 Program Selection
The program No. can be selected on the console within the range 1 to 19.
How to select the program No.
Program No.1
Program No.2
Program No.3
Program No.4
PROG
PROG
PROG
key
key
key
key
key
key
When the controller is in the basic display state in the program operation READY mode:
Each press of
PROG
increments the program No. The
display reverts to 1 after 19.
Each press of decrements the program No. The display reverts to 19 after 1.
Both already set or non-set program Nos. can be selected
The program No. cannot be selected when selecting the program No. by exter-
nal switch input.
The program No. cannot be selected during constant-value operation.
Pressing does not change the program No. when values currently being
entered are displayed in the MANUAL mode.
Handling Precautions
Page 81
Chapter 6. OPERATION
6-8
6-4 External Switch (RSW) Operations
External switch (RSW) inputs
In all, the DCP301 is provided with 12 external switch inputs. Each of these inputs are differentiated by RSW1, RSW2 and so forth to RSW12. On models whose option 2 cata­log No. is “0”, only inputs RSW1 to RSW4 are mounted.
(RSW: external switch input)
External switch input types
The functions of RSW1 to 4, and RSW8 to 12 are fixed. The functions of RSW5 to 7 are selected by the setup setting.
External Function Detection Method
Switch No.
RSW1 RUN Rising edge RSW2 HOLD Rising edge RSW3 RESET Rising edge RSW4 ADV Rising edge
Selected by setup from the following functions RSW5 FAST Rising edge RSW6 PV start Rising edge RSW7 AUTO/MANUAL Rising/falling edge
AT start/stop Risi n g / falling edge
G.Soak cancel by OR conditions Status
G.Soak cancel by AND conditions Status
Direct/reverse action switching Status RSW8 Program No. selection Weighting 1 Status RSW9 Program No. selection Weighting 2 Status RSW10 Program No. selection Weighting 4 Status RSW11 Program No. selection Weighting 8 Status RSW12 Program No. selection Weighting 10 Status
With PV is valid only in the program operation mode and READY mode, and the PV start RUN mode is entered regardless of the PV start setting in the program. Note, however, that RUN mode is entered from the start point of the selected segment in READY mode when there is no SP for the PV start.
With G.Soak cancel by OR conditions, G.Soak standby is canceled when the external switch turns ON or when the PV enters the G.Soak width.
With G.Soak cancel by AND conditions, G.Soak standby is canceled when the exter­nal switch turns ON or when the PV enters the G.Soak width.
When the external switch turns ON by direct/reverse action switching, control opera­tion is the opposite to that set in setup parameter C 0 1 . When the external switch turned OFF, control operation is that set in setup parameter C 0 1.
Page 82
Chapter 6. OPERATION
6-9
Program selection
The program can be selected in the program operation READY mode. The table below shows program selection by external switch inputs. Two external switch states are pro­vided for selection of programs 10 to 15. When program selection by external switch inputs is set to “0”, the program can be selected by the console keys and by communica­tion with a personal computer.
External Weighting State
Switch No.
RSW8 1 OFF ON OFF ON OFF ON OFF ON OFF ON RSW9 2 OFF OFF ON ON OFF OFF ON ON OFF OFF RSW10 4 OFF OFF OFF OFF ON ON ON ON OFF OFF RSW11 8 OFF OFF OFF OFF OFF OFF OFF OFF ON ON RSW12 10 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
Program No. Selection 0123456789
External Weighting State
Switch No.
RSW8 1 OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON RSW9 2 OFF ON OFF ON ON OFF ON OFF OFF ON OFF ON RSW10 4 OFF OFF OFF OFF OFF ON OFF ON ON ON ON ON RSW11 8 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON RSW12 10 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
Program No. Selection 10 11 12 13 14 15
External Weighting State
Switch No.
RSW8 1 OFF ON OFF ON OFF ON OFF ON OFF ON RSW9 2 ON ON OFF OFF ON ON OFF OFF ON ON RSW10 4 ON ON OFF OFF OFF OFF ON ON ON ON RSW11 8 OFF OFF ON ON ON ON ON ON ON ON RSW12 10 ON ON ON ON ON ON ON ON ON ON
Program No. Selection 16 17 18 19 0
Page 83
Chapter 6. OPERATION
6-10
Read timing
Timing of RSW1 to 7
Inputs RSW1 to RSW7 are read according to the following timing. (1) When input changes state from OFF to ON, the time from the change up to reading is
0.2s max.
(2) When input changes state from ON to OFF, the time from the change up to reading is
0.2s max.
(1) (2)
External switch input state
ON read
OFF read
Timing of RSW8 to 12, RUN and PV start
The time from the change in input state up to reading when selecting program Nos. by RSW8 to RSW12 is 0.4s max.
Accordingly, due to the relationship with RUN operation, be sure to observe timings to (4) in the following diagram.
PV start operation also must conform to RUN operation. (1) The time from fixing of the selected No. up to the rising edge of the RUN signal is
0.4s min.
(2) The time from the rising edge of the RUN signal up to holding of the program No. is
0.2s min.
(3) The time from holding of RUN signal OFF up to the rising edge of the RUN signal is
0.2s min.
(4) The time from the rising edge of the RUN signal up to holding of RUN signal ON is
0.2s min.
(5) The time from fixing of the selected No. up to changing of the program No. is 0.4s
max.
(6) The time from the rising edge of the RUN signal up to start of RUN is 0.4s max.
(1) (2)
(5)
(4)(3)
(6)
State of No. different from that selected
State of No. di from that sele
c
State of selected No.
Program selection No.
(5 inputs)
RUN signal
Program No. No. different from that selected
Selected No.
When operating the controller by external switch inputs, operation can be carried out more reliably if a margin is added to the minimum time for the above read times.
Handling Precautions
Page 84
Chapter 6. OPERATION
6-11
6-5 Manual Operation and Auto-tuning
Manual operation
In the MANUAL mode, controller outputs can be manipulated by or on the con­sole.
Controller functions
When outputs are displayed in the basic display state, only one digit in the output value blinks. If the output value is incremented or decremented by or , actual output also increments or decrements. Output values differ from values being entered to setting items in that
ENT
need not be pressed. The blinking digit can be moved by pressing or . On 2G output models, when only estimated position-proportional control is selected by
variable parameter M .-C setting 2, “——” not the value is displayed as the output dis­play in the MANUAL mode.
Pressing displays O p e n , and the open-side relay turns ON. Pressing displays C l O S , and the closed-side relay turns ON. Bump-less and preset output changes when shifting from the AUTO to the MANUAL
mode can be selected by setup parameter C 15 setting. When shifting from the MANUAL to the AUTO mode, output is bumpless.
(However, when the total time for the PID parameter of the PID set in use is set to “0”, a sudden change in output occurs.)
Programmer functions
On 5G output models, when programmer functions are in operation with setup data C 18 setting 1, SP can be manually manipulated. When SP is displayed in the basic display state, only one digit in the SP value being entered blinks. When the SP value is incremented or decremented by or , the actual SP output also increments or decrements. SP values differ from values being entered to setting items in that
ENT
need not be pressed. The blinking digit can be moved by pressing or . Output changes when shifting from the AUTO to the MANUAL mode are bumpless
regardless of setup data C 15 setting. When shifting from the MANUAL to the AUTO mode, the SP becomes the program pattern SP, which results in a sudden change in out­put.
Auto-tuning (AT)
When operating in the AUTO mode in either of the RUN, HOLD, FAST or END modes, setting values can be automatically written to the PID set in use by auto-tuning (AT). The following can be selected by variable parameter A t setting.
0: AT is disabled. 1: General AT is executed. 2: Overshoot-inhibited AT is executed. 3: AT by neural net is executed.
Auto-tuning does not function when programmer functions are selected on 3D or 5K
heat/cool output models and 5G output models.
During execution of auto-tuning, progress of program operation time stops. Accord-
ingly, the controller is in a similar state to the HOLD mode even in the RUN or FAST modes.
Page 85
Chapter 6. OPERATION
6-12
Auto-tuning will not function properly unless the control target is connected.
The time from start to end of auto-tuning varies according to the control target.
When auto-tuning is executed, control is stopped, OFF and ON outputs are
switched in the case of relay output and voltage output, and the manipulated variable upper and lower limits of the currently selected PID set are switched several times in the case of current output and position proportional output. If this causes controller trouble, manually set the PID value.
Sometimes a suitable PID value cannot be obtained depending on the control target. If this happens, manually set the PID value.
Auto-tuning in all instances involves calculating the downtime and critical sensitivity of the line according to two limit cycles and PID values according to suitable charac­teristic equations for each, and automatically writing these PID values.
During execution of auto-tuning, PV fluctuates according to fluctuations in MV. Be­fore executing auto-tuning, make sure that fluctuations in PV will not cause controller trouble.
Normally, suitable values are written by setting variable parameter At setting to 1 or 3. However, when executing auto-tuning on a line that easily overshoots, either set to 2, or also use smart-tuning for carrying out overshoot inhibit control. Setting to 3 ex­ecutes AT by neural net so that the suitable value is calculated for wider range applica­tions.
The point at which output at auto-tuning is inverted (lower limit to upper limit, and vice versa) is determined as follows from SP and PV at start of auto-tuning.
PV
SP
2/3
1/3 1/3
2/3
PV
SP
PV>SP
At start At SP=PV operation
PV<SP
AT start
Normal end AT start Normal end
Time Time
Auto-tuning can be started byAT, external switch inputs and communications. Dur- ing auto-tuning, the AT LED blinks.
If one or more of the following conditions occurs during auto-tuning, auto-tuning is canceled without PID constants being written, and the AT LED goes out.
- Cancel by
AT
- Cancel by external switch input
- Cancel by communications
- Change in mode (shift to MANUAL mode or READY mode)
- Execution of automatic motor valve opening adjustment on 2G output models
- When variable parameter A t setting is changed to “0”
- When input 1 becomes out-of-range
Handling Precautions
Page 86
Chapter 7. PARAMETER SETUP
7-1
Chapter 7. PARAMETER SETUP
7-1 Parameter Setup
Parameters can be set up when the DCP301 is in the basic display state. If the DCP301 is not in the basic display state, press
DISP
to set the controller to the basic display state.
Selecting the setting group in the parameter setup
Parameter setup is divided into two stages: setting group (major item) and individual item (minor item).
If you press
FUNC
+
PARA
in the basic display state, the display changes to selection of setting group (major item), the setting group is displayed on the upper display, and the lower display goes out.
If you press
PARA
, or , the setting group display changes in order.
Name Remarks
Variable param­eters
Event configuration data
PID parameters
Setup data Table data Constant-value
operation data
Setting group 1 (major items) selection
Basic Display State
Setting group 2 (major items) selection
Setting group n (major items) selection Individual items
Individual items
Individual items
DISP
key
FUNC
+
PARA
keys
ENT
key
PARA
key
ENT
key
PARA
key
ENT
key
PARA
key
, , , key
, , , key
, , , key
PARA
key key key
PARA
key key key
PARA
key key key
P A R A
E V
P 1 D
S E T T B L C N S T
This parameter is not displayed when variable parameter L O C is 2 or 4
This parameter is not displayed when variable parameter L O C is 2 or 4 This parameter is not displayed when constant-value operation data
M .O D E is 1
This parameter is not displayed when setup data
C 1 8 is 1 by 5G output
This parameter is not displayed when setup data C 4 5 is 1 by 3D output This parameter is not displayed when variable parameter
L O C is 1, 2 or 4
This parameter is not displayed when variable parameter
L O C is 2 or 4
This parameter is not displayed when variable parameter L O C is 2 or 4
Upper
Display
If you press
ENT
when the setup group to be selected is displayed, the display moves to
the individual (minor) item level. The following table shows the setting groups.
Page 87
Chapter 7. PARAMETER SETUP
7-2
Moving individual items in the parameter setup
With individual items, item codes are displayed in the upper display and setting values are displayed in the lower display.
The program No. display goes out, and the item No. is displayed in the segment No. display. However, note that the segment No. display also goes out in the case of setup data.
Individual items are arranged in a matrix as shown on the following page, and can be displayed in order by pressing , , or . The size of individual item matri­ces varies according to the setting group.
Changing individual items and how to return from the setup state
If you press
ENT
when an individual item is displayed, the setting value blinks. This state is referred to as the “setting value entry state.” In this state, pressing or can in­crement or decrement the setting value that is blinking. Also, pressing or moves the position of the digit that is blinking.
If you press
ENT
when the setting value is at the desired value, blinking stops, the display returns to its normally lit state, and the new setting value is stored to internal memory.
To cancel changing of setting values, press
PARA
or
DISP
. When
PARA
is pressed, the value
stops blinking and the display returns to its normal lit state. If you press
DISP
, the display returns to the basic display state. If “- - - -” is displayed at the lower display when an individual item is displayed, or the controller does not enter the setting value entry state by pressing
ENT
, that item cannot be set nor changed.
Page 88
Chapter 7. PARAMETER SETUP
7-3
• Example of individual item matrix (setup date)
Setting group selection
(major items)
Individual items
(minor items)
Setting value
blinking
Basic Display State
Change setting value.
ENT
key
ENT
key
PARA
key
DISP
key
ENT
key,
*
PARA
key key key key key
key key key key
DISP
key
key
key, key, key
Individual items
(minor items)
*
key stores setting values to memory.
key cancels storage of setting values to memory.
ENT
PARA
*
ENT
stores setting values to memory.
PARA
does not store setting values to memory.
C0 1
C02
C03
C0 1
C02
C03
C 11
C
12
C
13
C8
1
C82
C83
C9 1
C92
C93
C9 1
C92
C93
C99
C00
C09
C10
C
19
C20
C 89
C90
C 99
C00
C0
1
C09
C
10
C00
Page 89
Chapter 7. PARAMETER SETUP
7-4
7-2 How to Use
PARA
Use
PARA
for calling up individual items in frequently changed parameters.
How to register functions to keys
Up to eight individual items in the parameter setup can be assigned to each
PARA
key. The
assignment item must be registered to use this feature. This feature allows you to call up individual items more easily in the following order:
FUNC
+
PARA
selection of setting group individual item matrix.
How to register assignment items
To register an assignment item, add the following base corresponding to the setting group to the item No., and then set the resultant value to setup data C 5 5 to C 6 2 (
PARA
assign-
ment items 1 to 8)).
Base Setting Group
1000 Constant-value operation data 1500 PID parameters 2500 Variable parameters 3500 Event configuration data 4000 Table data 4500 Setup data
Page 90
Chapter 7. PARAMETER SETUP
7-5
Example
Let’s register four individual items to
PARA
. If you press
PARA
in the basic display state, the 1st to 4th individual items in the table below are displayed successively. In this ex­ample, let’s change the setting values.
Order Item to Call by
PARA
1 Setup data C 0 1 2 PID parameter P -2 3 Variable parameter F L 4 Variable parameter F A S T
The settings for registering these individual items are as follows. Setup Data Setting “S E t”
Item Code Setting
No. [auxiliary Item Value Remarks
display]
55
PARA
assignment
item 1
56
PARA
assignment
item 2
57
PARA
assignment
item 3
58
PARA
assignment
item 4
4501 This is produced by adding item No.1
of C 0 1 to setup data radical 4500.
1511 This is produced by adding item No.11
of
P -2 to PID parameter radical 1500.
2503 This is produced by adding item No.3
of
F L to setup data radical 2500.
2520 This is produced by adding item No.20
of
F A S T to variable parameter
radical 2500.
C 5 5
C 5 6
C 5 7
C 5 8
• For details on item Nos., see 7-3 Parameter Setup List (pages 7-7 to 7-42).
• When the “
PARA
assignment item setting is set to a value that does not corre-
spond to an existing item, that setting is ignored. For example, though factory setting 1000 corresponds to constant-value op-
eration data 0th of base 1000, 0th does not exist, so the setting will be treated an invalid data and will not be registered.
Operations by
PARA
If you press
PARA
in the basic display state, registered individual items are called up.
Each press of
PARA
successively calls up (up to eight) registered individual items. Only individual items to which valid assignment settings have been registered can be called up.
PARA
operations are not limited by the setting of “variable parameter setup” L O C (key
lock) setting.
PARA
operations are described on the following page.
Handling Precautions
Page 91
Chapter 7. PARAMETER SETUP
7-6
Basic Display State
Max. 8 items
ENT
key
ENT
key
ENT
key
ENT
key
ENT
key
ENT
key
ENT
key
ENT
key
PARA
key
PARA
key
PARA
key
PARA
key
PARA
key
PARA
key
PARA
key
PARA
key
PARA
key
DISP
key
DISP
key
DISP
key
DISP
key
DISP
key
PARA
Display item by key assign­ment item 1
(blinking)
PARA
Display item by key assign­ment item 2
(blinking)
PARA
Display item by key assign­ment item 3
(blinking)
PARA
Display item by key assign­ment item 8
(blinking)
Display item by key assign­ment item 1
(normally lit)
PARA
Display item by key assign­ment item 2
(normally lit)
PARA
Display item by key assign­ment item 3
(normally lit)
PARA
Display item by key assign­ment item 8
(normally lit)
PARA
*
*
*
*
When invalid assignments are registered, that item is
skipped and the next registered item is displayed.
* Items that can be changed: When these items are displayed blinking, the setting
values can be changed by , , and .
ENT
stores data to memory.
Items for reference: These are displayed at all times.
Handling Precautions
Page 92
Chapter 7. PARAMETER SETUP
7-7
No. Item Code Item Factory User Setting
Setting Setting
1 L O C
0
2 P R T C
0
3 F L
0.0
4 P B 1
0U
5 S B 1 0U 6 O T L
0.0
7 1 O U T 0.0
(50.0)
8 R P 1 D
0
9 A T
0
10 S T
0
11 2 P 1 D 0
0: Key lock disabled 1: Display of setup data settings disabled 2: Display of parameter settings and program settings
disabled 3: Use of operation keys disabled 4: Display of parameter settings and program settings
displayed, and use of operation keys disabled [Note]
Two or more key lock setting values for actual key lock
items and items assigned to can be displayed
and set.
0: Changing program settings enabled 1: Changing program settings disabled
0.0 to 120.0s [Note]
0.0 disables the filter.
-1000 to 1000U
-1999 to 9999U
0.0 to 10.0% (0.1%s steps) [Note]
0.0 disables the limit.
0.0 to 100% [Note]
On heat/cool models, the factory setting is 50.0. 0: Automatic judgment of initialization is carried out by
advance operation. 1: Initialization is carried out by advance operation. 2: Initialization is not carried out by advance operation. 0: AT is disabled. 1: General AT is executed. 2: Overshoot-inhibited AT is executed. 3: AT by neural net is executed. [Note]
On heat/cool models, “– – – –” is displayed, and
setting is not possible. 0: Smart-tuning is disabled. 1: The brake value is fixed to inhibit overshoot. 2: Overshoot is inhibited while automatically reviewing
the brake value. [Note]
On heat/cool models, “– – – –” is displayed, and
setting is not possible. 0: 2 degrees of freedom PID is disabled. 1: 2 degrees of freedom PID is enabled. [Note]
On heat/cool models, “– – – –” is displayed, and
setting is not possible.
PARA
Key lock
Program protect
Input 1 digital filter
Input 1 bias SP1 bias MV change limitter (CH1)
PID operation initial MV (CH1)
PID operation initialization
Auto-tuning method selection (CH1)
Smart-tuning method selection
(CH1)
Advanced PID selection (CH1)
7-3 Parameter Setup List
“U” and “%FS” used in the “Factory Setting” and “Setting” columns in the table mean the following:
U: The decimal point changes according to the input range type setting. For example,
when one digit past the decimal point is allowed, -1999U becomes 199.9, and 9999U becomes 999.9.
%FS: The numbers and decimal point position changes according to the input range setting.
For example, when the input range is 0.0 to 800.0°C, 0%FS is 0.0 and 100%FS is
800.0.
Variable parameter settings “P A R A
Note
Page 93
Chapter 7. PARAMETER SETUP
7-8
No. Item Code Item Factory User Setting
Setting Setting
12 G 5 .T 2.0 13 C P . 1 1 0U
14 C P . 1 2 200U
15
C P . 1 3 400U
16
C P . 1 4 600U
17 C P . 1 5 800U
18 C P . 1 6 1000U
19 C P . 1 7 1200U
20 F A S T 0
21 D 1 F F 5U
5.0
0.0
22 C Y . 1 10
23 C Y . 2 10
24 C Y . 3
25 D V -L 5U
26 D V -H 5U
27 H Y -L 5U
28 H Y -H 5U
0.1 to 60.0s
-1999 to 9999U [Note]
When setup data C 1 1 setting is 0 (PID set auto­switching OFF), “– – – –” is displayed and setting is not possible.
-1999 to 9999U [Note]
On heat/cool models, “– – – –” is displayed and setting is not possible. On other models, when setup data C 1 1 setting is 0 (PID set auto-switching OFF), “– – – –” is displayed and setting is not possible.
0: 2X 1: 10X 2: 60X (10X) 3: 120X (10X) [Note]
When setup data C 6 4 setting is 1 (program time
unit:min/s), the FAST factor is 10X for settings 2 and 3. 0 to 1000U [Note]
This setting is displayed on 0D and 6D models.
0.5 to 25.0% [Note]
This setting is displayed on 2G output models.
-100.0 to 50.0% [Note]
This setting is displayed on heat/cool models. [Note]
On 5G output models, “– – – –” is displayed and
setting is not possible. 5 to 120s (relay output) 1 to 60s (voltage output) [Note]
On models whose output 1 is neither relay output nor
voltage output, “– – – –” is displayed and setting is not
possible. 5 to 120s (relay output) 1 to 60s (voltage output) [Note]
On models whose output 2 is neither relay output nor
voltage output, “– – – –” is displayed and setting is not
possible. [Note]
“– – – –” is displayed and setting is not possible. 0 to 1000U [Note]
On models other than 3D output models, “– – – –” is
displayed and setting is not possible.
G.Soak time (CH1) PID auto-switching point 1-1 PID auto-switching point 1-2 PID auto-switching point 1-3 PID auto-switching point 1-4 PID auto-switching point 1-5 PID auto-switching point 1-6 PID auto-switching point 1-7 FAST factor
ON-OFF control differential
Position-propor­tional dead zone
Heat/cool control dead zone
Output 1 time­proportional output cycle
Output 2 time­proportional output cycle
Unused
3-position control deviation lower limit 3-position control deviation upper limit 3-position control lower limit hyster­esis 3-position control upper limit hyster­esis
Page 94
Chapter 7. PARAMETER SETUP
7-9
No. Item Code Item Factory User Setting
Setting Setting
29 M .-C 0
30 M .-A T 0
31 M .-C L 1000
32 M .-O P 9000
33 M .-T 30.0
0: MFB control (conventional) + estimated position
control 1: MFB control (conventional) only 2: Estimated position control only [Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible. 0: Adjustment disabled 1: Adjustment enabled [Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
On 2G output models, when M .-C setting is 2, “– – – –
” is displayed and setting is not possible. 0 to (fully open adjustment - 500) [Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
On 2G output models, when M .-C setting is 2, “– – – –
” is displayed and setting is not possible. (fully closed adjustment + 500) to 9999 [Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
On 2G output models, when M .-C setting is 2, “– – – –
” is displayed and setting is not possible.
5.0 to 240.0s [Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
Motor control method selection
Motor valve opening automatic adjust­ment
Motor valve opening adjustment fully closed position
Motor valve opening adjustment fully open position
Motor valve opening adjustment fully open/closed time
Page 95
Chapter 7. PARAMETER SETUP
7-10
Description of variable parameter settings
L O C (key lock)
0: Key lock disabled 1: Display of setup data settings disabled 2: Display of parameter settings and program settings disabled 3: Use of operation keys disabled 4: Display of parameter settings and program settings displayed, and use of operation
keys disabled
• When L O C is set to 1, the following keys are disabled. Basic display state:
FUNC+CLR
+
DISP
(general reset)
Only S E T can be selected by setting group selection in the parameter setup state.
• When L O C is set to 2, the following keys are disabled. Basic display state:
FUNC
+
PROG
(program setup)
+
PROG
(program copy)
FUNC+CLR
+
DISP
(general reset) Only P A R A can be selected by setting group selection in the parameter setup state. However, note that items assigned to
PARA
can be called up by
PARA
in the basic dis-
play state.
• When L O C is set to 3, the following keys are disabled. Basic display state:
PROG
(program selection)
(program selection)
RUN/HOLD
(RUN, HOLD)
PROG
+
RUN/HOLD
(RESET)
PROG
+
DISP
(ADV)
FUNC
+ (FAST)
A/M
(AUTO, MANUAL)
AT
(AT start, AT cancel)
FUNC+CLR
+
DISP
(general reset)
However, note that MV (when controller functions are selected) and SP (when pro­grammer functions are selected) can be changed in the basic display state in the MANUAL mode.
• When L O C is set to 4, all keys disabled when L O C is set to 2 and 3 are disabled.
P R T C (program protect)
0: Changing program settings enabled 1: Changing program settings disabled When P R T C is set to 1, the following keys are disabled. Basic display state: +
PROG
(program copy)
FUNC+CLR
+
DISP
(general reset)
Program setup state:
ENT
(start of value entry)
FUNC
+
ENT
(segment insert/delete)
Page 96
Chapter 7. PARAMETER SETUP
7-11
O T L (MV change limit)
The MV is increased or decreased by the same value so that the output change is taken as the limit setting value when the output change (%) after PID operation is greater than this limit setting.
The following example shows the actual change in MV when the MV changes from 20% to 22% with the change limit setting at 0.5%. MV is output at 0.5% setting value incre­ments every 0.1s, and reaches 22% in 0.4s.
%
22
21
20
t t + 0.1 t + 0.2 t + 0.3 t + 0.4
s
I O U t (PID operation initial MV)
PID operation is started in the following cases using the I O U t setting value:
• When the mode changes from READY AUTO to RUN AUTO
• When the power is turned ON in the RUN AUTO (or HOLD, FAST, END AUTO) mode
• At completion of auto-tuning
As the PV, SP and PID parameters settings bear a relation to PID operation, the first MV resulting from PID operation will not necessarily match the I O U t setting value.
R P I D (PID operation initialization)
When SP changes suddenly by ADV (advance) operation, rate action in PID operation may cause the MV in the operation to change excessively. For this reason, excessive changes can be suppressed by initializing PID operation.
However, as initialization of PID operation may result in lost continuity, initialization may adversely influence PID operation depending on the circumstances in which the controller is being used.
Initialization ON/OFF and conditions can be selected by the R P I D setting.
Page 97
Chapter 7. PARAMETER SETUP
7-12
S t (smart-tuning method selection)
0: Smart-tuning is disabled. 1: The brake value is fixed to inhibit overshoot. 2: Overshoot is inhibited while automatically reviewing the brake value.
• When the control direction is set to reverse action, overshoot is inhibited. When set to direct action, undershoot is inhibited. Both functions are referred to collectively as “overshoot inhibit.”
When set to 1, the value of PID parameter setting item B R is used as it is to inhibit overshoot.
When set to 2, the value of B R is reviewed at each rise (reverse action) or fall (direct action, and overshoot is inhibited while the value is automatically rewritten.
Review is executed only in the direction in which the B R value is increased (overshoot inhibit effect becomes more apparent).
When operation is carried out for a long time with this parameter set to 2, overshoot inhibit may function too strongly, and it may take a long time to arrive at SP. So, when overshoot disappears, note down the B R value at that time, set S T to 1, and reset the B R value to the noted down value.
• The AT LED lights while reviewing the B R value when set to 2.
• Do not set to 2 when normal control is not being carried out due to inappropriate tuning of the PID constant, for example.
Also, hunting is more likely to occur when B R is set to a large value on quick-starting lines. Set the B R value to 0 then to 2.
• On heat/cool models, smart-tuning does not function.
2 P I D (2 degrees of freedom)
0: 2 degrees of freedom is disabled. 1: 2 degrees of freedom is enabled.
• 2 degrees of freedom is a function for improving the response to disturbance during setup without losing conventional characteristics at rise (or fall).
When set to 1, optimum PID constants can be set individually for inhibiting distur­bance in addition to conventional the PID constant.
These constants are set automatically during AT execution, and is memorized. They can also be set and changed independently.
In particular, on 2G output models, suppressing changes in MV to lessen the frequency of motor operation during setup, and manually applying weak PID differential for in­hibiting disturbance to lengthen service life, for example, proves effective.
• These PID are switched automatically by applying fuzzy rules on the slope between deviation and PV.
• When I (reset time) is set to 0, control is carried out without integration in all states regardless of the setting value of D I (disturbance inhibit reset time).
• On heat/cool models, 2 degrees of freedom does not function.
Page 98
Chapter 7. PARAMETER SETUP
7-13
D I F F
• ON-OFF control differential When P is set to 0.0 on both 0D and 6D output models, control is set to ON-OFF control, and operational period at that time is set.
Differential
gap
PV
OFF
ON
Reverse action
Differential
gap
PV
OFF
ON
Direct action
SPSP
• Position-proportional control dead zone On 2G output models, a dead zone between the motor open and motor closed positions is set.
As a general guideline, the minimum value is the value where this dead zone changes to stop motor hunting once a fixed value set to manual output is being output.
If this value is set without any margin, the motor will be operating at all times, which will considerably shorten its service life.
The factory setting is 5%. Use this as a guideline, and take the control results and motor service life into consideration when setting the dead zone.
MFB (%)
*
Dead zone
Open-side
relay ON
Closed-side
relay ON
Control output (%)
*: Dead zone setting value
*
• Heat/cool control dead zone On heat/cool models, this sets how the relationship between heat-side output and cool­side output should be processed with respect to the MV resulting from PID operation. Heat-cool control is calculated as follows:
PV
SP
Heat-side output
Cool-side output
MV
(PID operation result)
Dead zone
Heat-cool output calculation
PID set selection
(1 of 4 sets)
Heat-side PID set Constants OL, OH
Constants P, I, D, Re
PID operation
(fixed to reverse action)
Cool-side
PID set
Heat-side
PID set
Cool-side PID set Constants OL, OH
Note 2)
Note 4)
Note 3)
Note 1)
Page 99
Chapter 7. PARAMETER SETUP
7-14
Dead
zone
Output
(heat)
Output
(cool)
MV
100%50%
0%
100%
Control output values
Dead zone<0
Dead
zone
Output
(heat)
Output
(cool)
MV
100%50%
0%
100%
Dead zone>0
Output
(heat)
Output
(cool)
MV
100%50%
0%
100%
Dead zone=0
Heat-side output
Cool-side output
MV
100%50%
0%
100%
Cool-side OH
Heat-side OL
Heat-side OH
Cool-side OL
Note 1) On heat/cool models, this sets how the relationship between heat-side output
and cool-side output should be processed with respect to the MV resulting from PID operation.
Note 2) Constants OL and OH function as follows:
Note 3) When MV 50%, the heat-side PID set is switched to.
When MV < 50%, the cool-side PID set is switched to.
Note 4) PID set selection is carried out by setting value and external switch.
Page 100
Chapter 7. PARAMETER SETUP
7-15
D v -L (3-position control deviation lower limit)
D v -H (3-position control deviation upper limit)
H Y -L (3-position control lower limit hysteresis)
H Y -H (3-position control upper limit hysteresis)
In 3-position control, control is carried out in the following three states in the RUN, HOLD, FAST and END modes.
State Heat-side Output Cool-side Output MV
1 OFF (0.0%) ON (100.0%) 0.0% 2 OFF (0.0%) OFF (0.0%) 50.0% 3 ON (100.0%) OFF (0.0%) 100.0%
SP
PV
OFF
ON
OFF
ON
Output (heat) Output (cool)
HY-L DV-L DV-H HY-H
Even in 3-position control, output is time-proportional in the READY mode. This is set in setup data C 1 6 (MV (heat) in READY mode) and C 1 7 (MV (cool) in READY mode).
When connecting an actuator that may burn by time-proportional output, set setup data C 1 6 and C 1 7 so that output in the READY mode is 0%.
Handling Precautions
Loading...