Honeywell dcp100t Operator's Manual

EN1I-6240
PREFACE
This manual is intended for use in support of day-to-day operation of the Honeywell DCP 100T Digital Controller Programmer. For information on installation, commissioning, configuration etc., refer to the associated Installation Manual (see below).
Title Document No.
DCP 100T Digital Controller Programmer Installation ManualEN1I-6241
In normal operation, the operator must not remove the controller from its housing or have unrestricted access to the rear terminals, as this would provide potential contact with hazardous live parts.
Installation and configuration must be undertaken by technically competent servicing personnel. This is covered in the Installation Manual (see above).
Con tents
1 IN TRO DUC ING THE DCP 100T 1-1
2 FRONT PANEL CON TROLS, IN DI CA TORS
AND DIS PLAYS 2-1
2.1 Con trols 2-1
2.2 In di ca tors 2-2
2.3 Dis plays 2-3
2.4 Alarm Status In di ca tion 2-4
2.5 View ing Pro gram and Con trol ler Pa rame ters 2-4
3 PRO GRAMS 3-1
3.1 Se lect ing and Run ning a Pro gram 3-1
3.2 Chang ing the Pro gram Ti me base 3-1
3.3 Hold ing a Pro gram Manu ally 3-1
3.4 Jump ing to the Next Seg ment 3-1
3.5 View ing Pro gram Pro gress/Status 3-2
3.6 Abort ing a Pro gram 3-3
3.7 “End of Pro gram” In di ca tion 3-3
3.8 View ing Pro gram and Con trol ler Pa rame ters 3-3
4 AD JUST ING THE SET POINT 4-1
5 US ING THE SELF- TUNE FA CIL ITY 5-1
6 US ING THE PRE- TUNE FA CIL ITY 6-1
7 MAN UAL CON TROL 7-1
8 DE FIN ING AND VIEW ING A PRO GRAM
(PRO GRAM DE FINE MODE) 8-1
(iii)
8.1 En try into Pro gram De fine Mode 8-1
8.2 Pa rame ters Com mon to All Pro grams (Global) 8-2
8.3 Pa rame ters which Ap ply to a Spe cific Pro gram as a Whole 8-3
8.4 Pa rame ters in Any/Each Seg ment In a Spe cific Pro gram 8-5
8.5 Us ing Join, Re peat and End Mark ers and Cy cling Pro grams 8-6
8.6 Ba sic Rules to Re mem ber 8-8
8.7 Ex it ing Pro gram De fine Mode 8-8
9 DE FIN ING THE CON TROL LER PA RAME TERS
(CON TROL LER DE FINE MODE) 9-1
9.1 Con trol ler Pa rame ters 9-2
9.2 Base Mode Dis plays 9-10
9.3 Loop Alarm And Loop Alarm Time 9-10
9.4 Ex it ing Con trol ler De fine Mode 9-11
Il lus tra tions
Fig ure 2-1 Front Panel Con trols 2-1
Fig ure 2-2 Front Panel In di ca tors 2-2
Fig ure 2-3 Front Panel Dis plays 2-3
Fig ure 2-4 Alarm Status Dis play 2-4
Fig ure 8-1 Guar an teed Soak Op era tion 8-4
Fig ure 9-1 Pro por tional Band and Dead band/Over lap 9-7
Fig ure 9-2 Alarm Op era tion 9-8
Fig ure 9-3 Alarm Hys tere sis Op era tion 9-9
(iv )
1 INTRODUCING THE DCP 100T
The DCP 100T Digital Controller Programmer is a powerful, easy-to-use
1
4
-DIN setpoint programmer with full PID control capability (complete with Self-Tune and Pre-Tune facilities). Its standard features are:
Up to eight programs of up to 16 free-format (e.g. dwell, ramp, join or
end) segments each.
Facility to join programs to one another in any sequence (maximum
program length 121 segments).
User can change currently-running program segment.
Delayed Start of Program facility.
End of Program relay output.
Universal input - thermocouple, RTD (Pt100) or DC linear
- user- selectable).
Universal power supply (90 - 264V ac 50/60Hz).
Configurable from front panel.
Comprehensive front panel displays.
Front panel sealing to NEMA 4 standard.
Behind-panel depth only 100mm.
Optional features include:
Remote control and selection of program (plug-in option).
Up to four Event relay outputs (plug-in option).
Second control output.
Recorder output (setpoint or process variable).
RS485 serial communications.
User-definable program tag names
Real Time Clock
1-1
Support software (Off-Line Configurator, On-Line Graphic Program Editor) -
operates via RS485 communications link.
The Digital Controller Programmer has four operating modes:
Base Mode: Day-to-day PID control operations with no program running. In this mode, a program may be selected to run.
Program Run Mode: A selected program is running, held or waiting for a pre-defined delay before starting. In this mode, the operator can view status and program information.
Program Define Mode 1: Used to view/create/edit programs. This mode is entered either from Base Mode (selected program may be edited/created) or from Program Run Mode (currently-running program may be edited).
Controller Define Mode 2: Used to define the Controller characteristics.
1 -2
1 Entry via Lock Code; also optional Program Lock prevents changing of program definitions
while a program is running.
2 Entry via a Lock Code.
2 FRONT PANEL CONTROLS,
INDICATORS AND DISPLAYS
2.1 CONTROLS
2-1
Figure 2-1 Front Panel Con trols
MODE key
Changes mode of instrument.
SET UP key
Displays the next parameter in sequence (indicated by Message display - see Subsection 2.3).
Up key
Increments displayed parameter value/cycles through options.
Down key
Decrements displayed parameter value/cycles through options.
Program key
Cycles through Program Numbers.
Run/Hold key:
Runs, holds or aborts current program.
Selects/de-selects Self-Tune and Pre-Tune (when Message Display shows appropriate message).
Jumps to next segment, when a program is running.
Selects/de-selects Manual Control (see Section 7).
Sets a segment to Soak when defining a program.
2.2 INDICATORS
2.2.1 Control Status Indicators
AT ON - Self-Tune active; flashing - Pre-Tune active ALM Flashes when any alarm active OUT1 ON when primary control outputis active OUT2 ON when secondary control output (if fitted) is active. MAN ON when Manual Control is selected.
2.2.2 Run Status Indicators
RUN ON - Program running or (if HLD ON also) program held
Flashing - Program in Delayed state.
HLD ON - Program Held
Flashing - Program in Guaranteed Soak
x60 OFF - Timebase = hours/minutes
ON - Timebase = minutes/seconds
2.2.3 Event Indicators
Each indicates the status (active or inactive) of a user-defined event (OFF = inactive, ON = active).
2.2.4 Mode Indicators
SET ON when Controller Define Mode or Program Define Mode
is entered; flashes when viewing parameters in Controller Define Mode or Program Define Mode after entry from Base Mode
PRG ON when Program Define Mode is entered.
2-2
2.3 DISPLAYS
2-3
Figure 2-2 Front Panel Displays
2.4 ALARM STATUS INDICATION
When any alarm is active, the ALM indicator will flash. To view the alarm status in the Message Display, press the SET UP key until a display appears of the form:
2.5 VIEWING PROGRAM AND CONTROLLER PARAMETERS
In Base Mode (i.e. with no program currently running or held), the MODE key gives
“view only” access to Program Define Mode and Controller Define Mode:
2-4
Figure 2-3 Alarm Status Dis play
Appears only if the Loop Alarm is active
Appears only if Alarm 2 is active
Appears only if Alarm 1 is active
VIEW ONLY VIEW ONLY
See Section 8 See Section 9
3 PROGRAMS
3.1 SELECTING AND RUNNING A PROGRAM
With no program running, the Digital Controller Programmer is in Base Mode and
the RUN and HLD indicators are OFF. In this mode, select a program as follows:
1. Hold down the PROG key un til the re quired pro gram number is
dis played.
2. Press the Run/Hold key once to start the pro gram. The RUN in di ca tor will
then go ON; the instrument is now in Pro gram Run Mode.
3.2 CHANGING THE PROGRAM TIMEBASE
Whilst a program is running, the normal timebase is hours/minutes. To change to a timebase of minutes/seconds (i.e. select the x60 facility), press the Up key for more
than five seconds, whereupon the x60 indicator will go ON. To cancel operation
on the x60 timebase, press the Down key for more than five seconds, whereupon
the x60 indicator will go OFF.
3.3 HOLDING A PROGRAM MANUALLY
You may hold or freeze a program by momentarily pressing the Run/Hold key. The
HLD indicator will then go ON (the RUN indicator staying ON) and the program
will stop execution. The program may subsequently be restarted by momentarily pressing the Run/Hold key again.
HLD INDICATOR FLASHING: If, before the operator holds the program manually, the HLD indicator starts flashing, this indicates that the program
is currently subject to a Guaranteed Soak (see Subsection 8.3). If the
Run/Hold key is pressed (for a manual Hold), the HLD indicator will go ON
continuously. When the operator removes the manual Hold (by pressing the
Run/Hold key again), the HLD indicator will either flash (indicating that the
Guaranteed Soak conditions still prevail) or go OFF (indicating that the Guaranteed Soak conditions no longer exist).
RUN INDICATOR FLASHING: This indicates that the program is in a Delay
state i.e. is timed to start after a user-defined delay has elapsed. When the
delay period has elapsed, the program will run and the RUN indicator will
come on continuously.
3-1
3.4 JUMPING TO THE NEXT SEGMENT
At any time during a program’s execution, the operator may jump forward to the
next segment by simultaneously pressing the PROG and Up keys. Note that, since
pro grams may be joined or set to cy cle, jump ing past the last seg ment in a pro gram may re sult in changes in the Pro gram Num ber and Cy cle Count.
3.5 VIEWING PROGRAM PROGRESS/STATUS
In Program Run Mode, a number of displays are made available to the operator (in the Message Display area) which indicate program progress/status. Whilst the
current program is running, held or delayed, press the SET UP key to cycle
through a sequence of program status displays with the following legends in the Message Display:
In the case of Segment Time Remaining or Guaranteed Soak Time display, the
time is in hours/minutes (if the x60 indicator is OFF) or minutes/seconds (if the x60
indicator is ON). The Delay Time display is always in hours/minutes.
NOTE: If the SET UP key is held for two seconds or longer, the Digital
Controller Programmer will auto-scroll through the above display cycle (with the exception of the Self-Tune and Pre-Tune displays). To stop the
Auto-scroll, press any key other than the SET UP key.
Af ter all ap pli ca ble pro gram status/prog ress dis plays have been shown, press the
SET UP key to re turn to the Base Mode dis plays.
3 -2
3.6 ABORTING A PROGRAM
The operator may abort (i.e. terminate) the current program by holding down the Run/Hold key for more than five seconds. When the program is aborted, a return is made to the Base Mode and the Message Display will show:
This message will be removed by the next keypress.
3.7 “END OF PROGRAM” INDICATION
When the program has reached its End Marker, the Message Display shows:
and a return is made to Base Mode.
3.8 VIEWING PROGRAM AND CONTROLLER PARAMETERS
In Program Run Mode (i.e. with a program currently running or held), the MODE
key gives “view only” access to Program Define Mode and Controller Define Mode:
3-3
VIEW ONLY VIEW ONLY
See Section 8 See Section 9
4 ADJUSTING THE SETPOINT
With the Digital Controller Programmer in Base Mode (i.e. with the RUN, HLD, SET and PRG indicators OFF), the two main displays will show the process variable
value (upper display) and the setpoint value (lower display - Read Only). To change the setpoint value:
1. Press the SET UP key; the Mes sage Area will dis play one of:
whichever is appropriate to the input range used.
2. Use the Up and Down keys to change the set point value (in the lower dis play) as re quired.
3. When the set point value is set as de sired, press the SET UP key again to
re turn to the ini tial dis play.
4 -1
5 USING THE SELF-TUNE FACILITY
The Self-Tune facility is used to optimise tuning whilst the Controller part of the Digital Controller Programmer is operating. Self Tune may be activated as follows:
1. With the Digi tal Con trol ler Pro gram mer in Base Mode (with the RUN and HLD in di ca tors OFF), press the SET UP key un til the Mes sage Dis play
shows:
and the lower Main Dis play shows:
2. Press the MODE and Up keys to change the lower Main Dis play to:
in di cat ing that the Self- Tune fa cil ity is now ac ti vated.
To de-activate the Self-Tune facility, press the SET UP key to obtain the same Message Display as above; then press the MODE and Up keys simultaneously to change the lower Main Display from On to OFF.
5-1
6 USING THE PRE-TUNE FACILITY
The Pre-Tune facility is used to set the Digital Controller Programmer’s PID control parameters to values which are approximately correct in order to provide a base from which the Self-Tune facility may subsequently optimise tuning. Pre-Tune may be activated as follows:
1. With the Digi tal Con trol ler Pro gram mer in Base Mode (with the RUN and HLD in di ca tors OFF), press the SET UP key un til the Mes sage Dis play
shows:
and the lower Main Dis play shows:
2. Press the MODE and Up keys to change the lower Main Dis play to:
in di cat ing that the Pre- Tune fa cil ity is now ac ti vated.
NOTES
1. If the process variable is within 5% of the input span from the setpoint, the Pre-Tune facility cannot be activated and any attempt to do so will have no effect.
2. Since the Pre-Tune facility is a single-shot operation, it will automatically de-activate itself once the operation is complete.
To de-activate the Pre-Tune facility manually (with the Digital Controller
Programmer in Base Mode), press the SET UP key to obtain the same Message Display as above; then press the MODE and Up keys to change the lower Main Display from On to OFF.
6-1
7 MANUAL CONTROL
In any mode except Configuration Mode or Calibration Mode, the operator may
select manual control of the process by simultaneously pressing the SET UP and MODE keys. The Digital Controller Programmer will then enter Base Mode or (if a
program is currently running) Program Run Mode with the program held. The Message Display will show:
and the lower Main Display will show the power output value, which may then be adjusted using the Up and Down keys. Whilst manual control is being exercised, the power output display is included in the displays available in Base Mode and Program Run Mode.
To cancel manual control, press the SET UP and MODE keys simultaneously,
whereupon the power out value display and the Power Message Display will disappear and the Digital Controller Programmer will remain in whatever mode prevailed when manual control was cancelled (if this is Program Run Mode, the currently-running program will be resumed from the point at which it was held).
7-1
8 DEFINING AND VIEWING A PROGRAM
(PROGRAM DEFINE MODE)
The Digital Controller Programmer may be put into Program Define Mode from either Base Mode or Program Run Mode (i.e. with a program currently running).
8.1 ENTRY INTO PROGRAM DEFINE MODE
1. Press the SET UP and Up keys si mul ta ne ously. The lower Main Dis play will show 0 and the Mes sage Dis play will show:
2. Use the Up and Down keys to set the value in the lower Main Dis play to the Lock Value (de fined by the user in Con trol ler De fine Mode) and press
the SET UP key.
The Digital Controller Programmer will enter Program Define Mode, the SET and PRG indicators will go ON and the operator will be able to edit programs and segments. The MODE key can then be used (a) to switch to Controller Define
Mode (see Section 9), and then (b) to show a Message Display:
To return to Program Define Mode (and re-start the Program Define/Controller
Define/Exit? display cycle), press the MODE key; to return to Base Mode, press the SET UP key.
If an incorrect lock value is entered, a return is made to Base Mode.
Program parameters are divided into three categories:
(a) Those com mon to all pro grams - global pa rame ters (b) Those com mon to all se gments in a spe cific pro gram (c) Those rele vant to a spe cific seg ment in a spe cific pro gram
Upon entry into Program Define Mode, the operator will be presented with the first of a sequence of parameter displays (see following Subsections). The operator
may then step through the sequence, using the SET UP key. The displayed Program Number may be changed using the PROG key and the displayed
Segment Number may be changed using the Run/Hold key.
NOTE: If en try is made from Pro gram Run Mode and Pro gram Lock is On, only Con trol ler De fine Mode will be ac ces si ble.
8-1
8.2 PARAMETERS COMMON TO ALL PROGRAMS (GLOBAL)
Parameter
Message
Display
Function Available Settings (Lower Main Display)
Start On Defines setpoint value at the
start of each program.
Current setpoint value
Current process variable value
End On Defines setpoint value at the
end of each program.
Final SP value
1
Controller SP value
Delay Time Defines delay (in
hours/minutes) between initiating the program and the program actually starting.
Numerical value, with the decimal point acting as the de-limiter between the two units (hours.minutes)
Program Lock
Defines whether the operator is permitted to change program definitions whilst a program is running/held.
Not permitted
Permitted
Power Fail Recovery
Defines response to restoration of power after power failure.
0.00 or 1.00 if no Real Time Clock.
0.00 or Time (0.01 - 24.00) if Real Time Clock fitted.
0.00 = Cold Start
2
1.00 or Time = Warm Start
3
RTC Time
4
Defines Real Time Clock initial setting (hours.minutes).
0.10 - 24.00
RTC Day
4
Defines Real Time Clock initial setting (day of week)
Sun , Mon , tuE , Wed , thu , Fri or SAt
External Selection
Defines functions which may be controlled externally
No external selection
Program selection only
Only Run, Hold, Abort and x60 functions
All program selection and run control functions
Lock Code
5
Lock Code for Program Define Mode
0 - 9999. Default = 10.
8-2
Program Number = A Segment Number = Blank
1 The final setpoint value for the End Marker of each program - see Subsection 8.4 2 Cold Start = Base Mode with Program No. as when power failed and Segment No. blank 3 Warm Start = resumption from point when power failed (with RTC, if Time has not
expired, otherwise Cold Start.
4 Available only if Real Time Clock fitted. 5 Only applicable if instrument is configured to have two lock codes.
8.3 PARAMETERS WHICH APPLY TO A SPECIFIC PROGRAM
AS A WHOLE
Parameter
Message
Display
Function Available Settings (Lower Main Display)
Cycle Count Defines the number of
times a program will be repeated.
0 - 9999 Program will repeat
the set number of times
Program will repeat indefinitely
Guaranteed Soak
Selects operation of Guaranteed Soak facility (relative to setpoint) - see Figure 8-1.
No Guaranteed Soak
Above setpoint only
Below setpoint only
Above and below setpoint
Guaranteed Soak Band
Defines the width of the Guaranteed Soak Band
-see Figure 8-1.
Numerical value (0 to-span)
Guaranteed Soak On
Defines whether the Guaranteed Soak facility is used on ramps only, on soaks only or on both ramps and soaks.
On ramps and soaks
On soaks only
On ramps only
Pre-x60 Defines whether the
timebase for the program is pre-selected to be hours/minutes or minutes/seconds (NOTE: This parameter setting is over-ruled by the external “x60” input).
No pre-selection
Minutes/seconds
Hours/minutes
Timer (RTC only)
Selects/de-selects timer control of program.
Timer control selected
Timer control not selected
Start Hour (Timer On)
Defines start time for program.
24.00 (0.00) to 23.59
Start Day (Timer On)
Defines day(s) for program to run.
Sun, Mon, tue, Wed, thu, Fri, Sat, 5 dY (Mon - Fri), 6 dY (Mon - Sat) or ALL (all 7 days of the week)
This se quence may be viewed/ed ited for any pro gram by chang ing the Pro gram
Num ber with the PROG key, then step ping through the pa rame ters with the SET UP key.
8 -3
Program Number = 1 to 8 Segment Number = Blank
8-4
Figure 8-1 Guaranteed Soak Operation
8.4 PARAMETERS IN ANY/EACH SEGMENT IN A SPECIFIC
PROGRAM
Parameter
Message
Display
Function Available Settings (Lower Main Display)
Final Setpoint Value
Defines the final setpoint value for this segment, selects a Soak segment or indicates a Join, Repeat or End Marker.
Numeric value (limited by SPHi and SPLo) or (by pressing the Up and Down keys simultaneously) indicates a Soak segment with:
or, if the segment is already a Join, Repeat or End Marker, as shown below.
Segment Time or Ramp Rate, as selected in Configuration Mode (see Installation Manual)
or
as appropriate
Defines the duration or ramp rate of the segment or whether it is a Join Marker, Repeat Marker or End Marker.
1
Four-digit number in the form mm.nn (hours.minutes or minutes.seconds) or negative values as follows:
J01 Join to Program 1 J02 Join to Program 2 J03 Join to Program 3 J04 Join to Program 4 J05 Join to Program 5 J06 Join to Program 6 J07 Join to Program 7 J08 Join to Program 8 REP Repeat Marker End End Marker
Event
2
Defines the states of the four Event Outputs for this segment.
Four-bit binary number (0 = inactive, 1 = active):
8-5
Program Number = 1 to 8 Segment Number = 1 to 16
Event 1
Event 2
Event 3
Event 4
1 If a segment is set to be a Join Marker, a Repeat Marker or an End Marker, the next
depression of the SET UP key will set the segment number to A and the first parameter
common to the whole program (Cycle Count - see Subsection 8.3) will be displayed.
Otherwise, the next depression of the SET UP key will display the next segment
parameter - Event (for the current segment) if the Event Output hardware is fitted.
2 This parameter appears only if the Event Output hardware is fitted, in which case this
parameter will be followed by the Final Setpoint parameter for the next segment. If the Event Output hardware is not fitted, this parameter is omitted from the sequence and the segment number is advanced, causing the Final Setpoint Value parameter for the next segment to appear immediately.
CANCELLING JOIN, REPEAT OR END MARKERS
To cancel a Join, Repeat or End Marker:
(a) at the Fi nal Set point Value pa rame ter, press the Up and Down keys si mul ta ne ously to pro duce a Soak seg ment, or
(b) at the Seg ment Time/Ramp Rate pa rame ter, in cre ment the value to 0 or a posi tive value.
8.5 USING JOIN, REPEAT AND END MARKERS AND
CYCLING PROGRAMS
By default, the Digital Controller Programmer has eight programs, each 16 segments long (all 16 segments are active and, at the end of Segment 16 is an implicit End Marker). These programs can be made shorter (using End Markers) or longer (by creating program sequences with Join, Repeat and End Markers). The only limit to the size of a program sequence is a maximum length of 121 active segments plus seven Join Markers plus one End Marker (i.e. all eight programs joined to make one program sequence).
Segments follow a free format in that ramp or dwell can be followed by dwell or ramp, completely as desired.
Consider two example programs:
To join the two programs to form a program sequence, change the End Marker of Program 1 to a Join Marker (Segment Time/Ramp Rate set to J02 - Join Program
2):
8-6
PROGRAM 1
(5 active segments, 1 End Marker)
PROGRAM 2
(3 active segments, 1 End Marker)
PROGRAM 1
(5 active segments, 1 Join Marker)
PROGRAM 2
(3 active segments, 1 End Marker)
There are no restrictions on joining programs; several programs can be joined to one program (e.g. to provide user-selectable warm-up programs, depending upon which program is run first).
The Cycle feature can be used to make more complex program sequences. Consider the two simple example programs previously described:
and consider the case in which Program 1 is set to perform two cycles and is joined to Program 2. When Program 1 is run, the result would be:
If Program 2 were now set to perform ten cycles, the result would be:
Now, with Pro gram 2 set to per forn ten cy cles, if the End Marker of Pro gram 2 were
changed to a Re peat Marker (Seg ment Time/Ramp Rate set to REP), the re sult
would be:
8-7
PROGRAM 1
(5 active segments, 1 End Marker)
PROGRAM 2
(3 active segments, 1 End Marker)
PROGRAM 1 PROGRAM 2PROGRAM 1
PROGRAM 1 PROGRAM 2PROGRAM 1
10 cycles
At the end of the tenth cycle of Program 2, the program sequence would end.
8.6 BASIC RULES TO REMEMBER
In any program sequence:
A pro gram end ing in a Join Marker will per form the re quired number of
cy cles of it self be fore join ing the new pro gram.
A pro gram end ing in a Re peat Marker (hence, by defi ni tion, the last
pro gram in the se quence) will per form the re quired number of cy cles of it self be fore end ing the se quence.
A pro gram end ing in an End Marker (hence, by defi ni tion, the last
pro gram in the se quence) will per form its cy cle count on the en tire pro gram se quence be fore end ing that se quence.
8.7 EXITING PROGRAM DEFINE MODE
The operator may exit from Program Define Mode by pressing the MODE key until
the Exit ? prompt appears in the Message Display, then pressing the SET UP key,
which will cause a return to the mode from which entry was made.
NOTE: An auto matic re turn is made if there is no key ac tiv ity in Pro gram De fine Mode for five min utes.
8-8
PROGRAM 1 PROGRAM 2PROGRAM 1
10 cycles
9 DEFINING THE CONTROLLER
PARAMETERS (CONTROLLER DEFINE MODE)
Entry can be made into this mode from Program Define Mode, Program Run Mode or Base Mode.
To enter from Base Mode or Program Run Mode:
1. Press the SET UP and Up keys si mul ta ne ously. The lower Main Dis play will show 0 and the Mes sage Dis play will show:
2. Use the Up and Down keys to set the value in the lower Main Dis play to
the cor rect Lock Code Value (for Program De fine Mode) and press the SET UP key. The Digi tal Con trol ler Pro gram mer is now in Pro gram De fine Mode.
NOTE: If an in cor rect Lock Code Value is en tered, the Digi tal Con trol ler Pro gram mer will re turn to its origi nal mode (i.e. Base Mode or Pro gram Run Mode).
3. Press the MODE key. If the instrument has been configured to have only
one Lock Code, entry into Controller Define Mode is immediate and no further action is needed. If the instrument is configured to have two Lock Codes (one for Program Define Mode, one for Controller Define Mode), the
Lower Main Display will show 0 and the Message Display will show:
4. Use the Up and Down keys to set the value in the Lower Main Display to
the Lock Code value (for Controller Define Mode), then press the SET UP
key.
The Digital Controller Programmer is now in Controller Define Mode.
NOTE: If an in cor rect Lock Code Value is en tered, the Digi tal Con trol ler Pro gram mer will re turn to its origi nal mode (i.e. Base Mode, Pro gram Run Mode or Program Define Mode).
To enter from Program Define Mode, perform Step 3 and (if necessary) Step 4 above.
9-1
Upon en try into Con trol ler De fine Mode, the SET in di ca tor will come ON and the
first of the Con trol ler pa rame ters (In put Fil ter Time Con stant) will be pre sented for
ed it ing/view ing. Us ing the SET UP key, step through the se quence of Con trol ler
pa rame ters, ed it ing as re quired (us ing the Up/Down keys).
9.1 CONTROLLER PARAMETERS
The Controller parameters appear in the following sequence:
Parameter
Message
Display
Function
Available Settings/Values
(Lower Main Display)
Input Filter Time Constant
Defines the time constant for the input filter (removes extraneous pulses from the process variable input).
0.0 seconds (filter OFF) to 100.0 seconds on 0.5-second increments. Default = 2.0 seconds
Process Variable Offset
1
Modifies actual PV value: PV Offset + PV = PV value
For linear input, limited by Scale Range Maximum and Scale Range Minimum. Default = 0.
Output 1 Power Current Output 1 power
level
Read only - not adjustable
Output 2 Power
2
Current Output 2 power level
Read only - not adjustable
Proportional Band 1 (PB1)
Portion of input span in which Output 1 power level is proportional to the (offset) process variable value (see Figure 9-1)
0.0% (ON/OFF Control) to 999.9% of input span. Default = 10.0%.
Proportional Band 2 (PB2)
Portion of input span in which Output 2 power level is proportional to the (offset) process variable value (see Figure 9-1)
0.0% (ON/OFF Control) to 999.9% of input span. Default = 10.0%.
Reset
3
Integral Time Constant 1 second to 99 minutes 59
seconds.
Rate
3
Derivative Time Constant 00 seconds to 99 minutes 59
seconds
Overlap or Deadband
4
The portion of Proportional Band (PB1 + PB2) over which both outputs are active (Overlap) or over which neither output is active (Deadband) - see Figure 9-1
20% to + 20% (negative value =
deadband, positive value = overlap). Default = 0%.
Bias (Manual Reset)
3
Bias applied to output power, expressed as a percentage of output power
0% to 100% (Output 1 only)
100% to +100% (Outputs 1 & 2)
Default = 25%
9-2
Parameter
Message
Display
Function
Available Settings/Values
(Lower Main Display)
ON/OFF Differential
5
Switching differential for
one output (Diff 1 or Diff 2) or both outputs (Diff) set to ON/OFF
control (PB1, PB2 or both set to 0%)
0.1% to 10% of input span. Default = 0.5%.
Setpoint High Limit
6
Maximum limit for setpoint adjustment.
Should be set to a value which prevents setpoint values causing damage to the process.
Current setpoint value to Input Range Maximum. Default = Input Range Maximum
Setpoint Low Limit
6
Minimum limit for setpoint adjustment. Should be
set to a value which prevents setpoint values causing damage to the process.
Input Range Minimum to current setpoint value. Default = Input Range Minimum
Motor Travel Time
11
Time taken for valve to travel from one end stop to the other.
5 seconds to 5 minutes. Default = 1 minute
Minimum Motor ON Time
11
Minimum drive effort required to initiate movement in a stationary valve.
0.0 seconds to Motor Travel Time plus 10 seconds. Default = 1 minute.
Recorder Output Scale Maximum
7
The value of the process variable or setpoint (as applicable) for which the recorder output is at a maximum.
1999 to 9999 (decimal point as
for the process variable input range).
Default = Input Range Maximum
Recorder Output Scale Minimum
7
The value of the process variable or setpoint (as applicable) for which the recorder output is at a minimum.
1999 to 9999 (decimal point as
for the process variable input range).
Default = Input Range Minimum
Output Power Limit
3
Limits the power level of Output 1 (used to protect the process).
0% to 100%
Output 1 Cycle Time
8
Limits the frequency of operation of output relay to maximise relay life.
0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256 or 512 seconds. Default = 32 seconds
Output 2 Cycle Time
8
Limits the frequency of operation of output relay to maximise relay life.
0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256 or 512 seconds. Default = 32 seconds
Process High Alarm 1 Value
If Alarm 1 is a Process High Alarm, the value of the process variable at or above which Alarm 1 will become active (see Figure 9-2).
Input Range Maximum to Input Range Minimum. Default = Input Range Maximum.
9-3
Parameter
Message
Display
Function
Available Settings/Values
(Lower Main Display)
Process Low Alarm 1 Value
If Alarm 1 is a Process Low Alarm, the value of the process variable at or below which Alarm 1 will become active (see Figure 9-2).
Input Range Maximum to Input Range Minimum. Default = Input Range Minimum.
Band Alarm 1 Value
If Alarm 1 is a Band Alarm, the band of process variable values (centred on the setpoint) outside which the process variable will cause this alarm to be active.
±(input span) from setpoint.
Default = 5 input units.
Deviation (High/Low) Alarm 1 Value
If Alarm 1 is a Deviation High/Low alarm, gives a value above (positive value) or below (negative value) the setpoint. If the process variable deviates from the setpoint by a margin greater than this value, the alarm becomes active (see Figure 9-2).
±(input range) from setpoint.
Default = 5 input range units.
Alarm 1 Hysteresis Value
Defines a hysteresis band on the “safe” side of the Alarm 1 value (see Figure 9-3).
1 LSD to 10% of input span (0 is an invalid value).
Process High Alarm 2 Value
If Alarm 2 is a Process High Alarm, the value of the process variable at or above which Alarm 2 will become active (see Figure 9-2).
Input Range Maximum to Input Range Minimum. Default = Input Range Maximum.
Process Low Alarm 2 Value
If Alarm 2 is a Process Low Alarm, the value of the process variable at or below which Alarm 2 will become active (see Figure 9-2).
Input Range Maximum to Input Range Minimum. Default = Input Range Minimum.
Band Alarm 2 Value
If Alarm 2 is a Band Alarm, the band of process variable values (centred on the setpoint) outside which the process variable will cause this alarm to be active.
±(input span) from setpoint.
Default = 5 input units.
9-4
Parameter
Message
Display
Function
Available Settings/Values
(Lower Main Display)
Deviation (High/Low) Alarm 2 Value
If Alarm 2 is a Deviation High/Low alarm, gives a value above (positive value) or below (negative value) the setpoint. If the process variable deviates from the setpoint by a margin greater than this value, the alarm becomes active (see Figure 9-2).
±(input range) from setpoint.
Default = 5 input range units.
Alarm 2 Hysteresis Value
Defines a hysteresis band on the “safe” side of the Alarm 2 value (see Figure 9-3).
1 LSD to 10% of input span (0 is an invalid value).
Loop Alarm Enable
Enables/disables Loop Alarm (see Subsection
9.3)
0 = Disabled, 1 = Enabled. Default = 0 (Disabled)
Loop Alarm Time
If ON/OFF control is selected (i.e. PB1 = 0) and Loop Alarm is enabled, this defines the duration of the saturation condition after which the Loop Alarm is activated (see Subsection 9.3).
1 second to 99 minutes 59 seconds. Default = 99 minutes 59 seconds.
Scale Range Decimal Point
9
For linear inputs, defines the decimal point position.
0 = XXXX 1 = XXX.X (Default) 2 = XX.XX 3 = X.XXX
Scale Range Maximum
9
For linear inputs, defines the scaled input value when the process variable input is at its maximum value.
1999 to 9999 (decimal point
position as defined by Scale Range Decimal Point parameter (see above).
Default = 100.0
Scale Range Minimum
9
For linear inputs, defines the scaled input value when the process variable input is at its minimum value.
1999 to 9999 (decimal point
position as defined by Scale Range Decimal Point parameter (see above).
Default = 0.0
Auto Pre-Tune Enable/Disable
Determines whether the Pre-Tune facility is automatically activated on power-up.
OFF = Disabled, ON = Enabled. Default = OFF.
Manual Control Enable/Disable
Enables/disables operator selection of Manual Control mode.
OFF = Disabled, ON = Enabled. Default = OFF.
Comm­unications Write Enable/Disable
10
Enables/disables adjustment of parameter settings/value via the RS485 communications link.
OFF = Disabled, ON = Enabled. Default = OFF.
9-5
Parameter
Message
Display
Function
Available Settings/Values
(Lower Main Display)
Lock Value
or
Defines the four-digit code required to enter Controller Define Mode (and, if a common lock code is to be used, Program Define Mode).
0 to 9999. Default = 10.
NOTES ON CONTROLLER DEFINE MODE PARAMETERS
1. The Process Variable Offset value should be chosen with great care. Any adjustment to this parameter is, in effect, a calibration adjustment. Injudicious application of values to this parameter could lead to the displayed process variable value having no meaningful relationship to the actual process variable value. There is no front panel indication when
this parameter is in effect (i.e. has been set to a non-zero value).
2. These parameters are applicable only if the secondary control (COOL) output is fitted.
3. These parameters are not applicable if Proportional Band 1 has been set to 0 (i.e. ON/OFF control).
4. This parameter is not applicable if Proportional Band 1 is set to 0 or if Output 2 (COOL) is not fitted.
5. The Message Display will show Diff 1 for ON/OFF control on Output 1 only, Diff 2 for ON/OFF control on Output 2 only and Diff for ON/OFF control on both Output 1 and Output
2.
6. Internal software prevents (a) the Setpoint High Limit being given a value less than any setpoint value contained in the currently-resident programs, and (b) the Setpoint Low Limit being given a value greater than any setpoint value contained in the currently-resident programs.
7. These parameters are not applicable if the Recorder Output Option is not fitted.
8. Output 1 Cycle Time is not applicable if Proportional Band 1 is set to 0 or if Output 1 is a DC Linear output. Output 2 Cycle Time is not applicable if Proportional Band 1 is set to 0, if Proportional Band 2 is set to 0, If Output 2 is not fitted or if Output 2 is a DC Linear output.
9. These parameters are applicable only if a linear input is fitted
10. Applicable only if the RS485 Serial Communications Option is fitted.
11. Applicable to TPSC control only.
12. If the instrument is configured to have one lock code only (Message Display will show
Lock ), this value is used to enter Program Define Mode and Controller Define Mode. If two lock codes are to be used (Message Display will show Lock C), this value applies to
Controller Define Mode only.
9-6
9-7
Figure 9-1 Pro por tional Band and Dead band/Over lap
9-8
Figure 9-2 Alarm Operation
9-9
Figure 9-3 Alarm Hysteresis
Alarm Op era tion
Process
Alarm Value
Hysteresis Band
Alarm Inactive Alarm Active
Alarm Inactive
Process
Variable
Process
Alarm Value
Hysteresis Band
Process
Alarm Inactive Alarm Active
Alarm Inactive
Hysteresis Band
Hysteresis Band
Process
Alarm Value
Alarm
SetpointAlarm
Inactive
Alarm Inactive
Alarm Active
Alarm Active
Alarm Inactive
Band
Alarm
Deviation
Setpoint
Hysteresis Band Alarm Inactive Alarm Active
Alarm Inactive
Process
Alarm
Setpoint
Hysteresis
Alarm Value Alarm Inactive Alarm Active
Alarm Inactive
Process
Variable
9.2 BASE MODE DISPLAYS
Once the complete cycle of Controller Define Mode parameters has been displayed, the user may then step through the Base Mode displays (controller setpoint - alarm status - Self Tune - Pre-Tune), making adjustments where required, before re-starting the Controller Define Mode parameter cycle.
9.3 LOOP ALARM AND LOOP ALARM TIME
The Loop Alarm is a special alarm which detects faults in the control feedback loop by continuously monitoring process variable response to the control output(s).
The Loop Alarm facility, when enabled, repeatedly checks the control output(s) for saturation i.e. either or both outputs being at the maximum or minimum limit. If an output is found to be in saturation, the Loop Alarm facility starts a timer; thereafter, if the saturated output has not caused the process variable to be corrected by a pre-determined amount V after a time T has elapsed, the Loop Alarm goes active. Subsequently, the Loop Alarm facility repeatedly checks the process variable and the control output(s). When the process variable starts to change value in the correct sense or when the saturated output comes out of saturation, the Loop Alarm is de-activated.
For PID control, the Loop Alarm Time T is always set to twice the value of the Reset (Integral Time Constant) parameter. For On/Off control, the user-defined value of the Loop Alarm Time parameter is used.
The value of V is dependent upon the input type:
o
C ranges: 2oC or 2.0oC
o
F ranges: 3oF or 3.0oF
Lin ear ranges: 10 least sig nifi cant dis play units
For single output Controllers, the saturation limits are 0% and Output Power Limit. For dual output Controllers, the saturation limits are –100% and Output Power Limit.
NOTES
1. Correct operation of the Loop Alarm depends upon reasonably accurate PID tuning.
2. The Loop Alarm is automatically disabled during Manual Control Mode and during execution of the Pre-Tune facility. Upon exit from Manual Control Mode or after completion of the Pre-Tune routine, the Loop Alarm is automatically re-enabled.
9-10
When full ON/OFF con trol is se lected (i.e. Pro por tional Band 1 is set to 0) and Loop Alarm is en abled, the Loop Alarm Time pa rame ter de ter mines the du ra tion of the satu ra tion con di tion af ter which the Loop Alarm will be ac ti vated. It may be ad justed within the range 1 sec ond to 99minutes 59 sec onds. This pa rame ter is omit ted from the dis play se quence if ON/OFF con trol is not se lected or Loop Alarm is dis abled. The de fault set ting is 99:59.
9.4 EXITING CONTROLLER DEFINE MODE
The operator may exit from Controller Define Mode by pressing the MODE key until the Exit ? prompt appears in the Message Display, then pressing the SET UP
key, which will cause a return to the mode from which entry was made.
NOTE: An auto matic re turn is made if there is no key ac tiv ity in Con trol ler De fine Mode for five min utes.
9-11
Alphabetical Index
A
Aborted Program
Indication of 3-3 Alarm 1 Hysteresis Value 9-4 Alarm 1 Value
Band Alarm 9-4
Deviation (High/Low) Alarm
9-4 Process High Alarm 9-3 Process Low Alarm 9-4
Alarm 2 Hysteresis Value 9-5 Alarm 2 Value
Band Alarm 9-4 Deviation (High/Low) Alarm
9-5 Process High Alarm 9-4 Process Low Alarm 9-4
Alarm Status
Display of 2-4, 3-2
Auto Pre-Tune Enable/Disable 9-5 Auto-Scroll Feature 3-2
B
Bias 9-2
C
Communications Write Enable/Disable
9-5
Controller Define Mode
Automatic exit from 9-11 Entry from Base Mode or Program
Run Mode 9-1 Entry from Program Define Mode
9-1 Exit from 9-11 Indication of entry 9-2
Controller Define Mode Parameters
"Read Only" access from Base Mode 2-4
"Read Only" access from Program Run Mode 3-3
D
Deadband 9-2 Delay State
Indication of 3-1 Delay Time 8-2 Delay Time Remaining
Display of 3-2 Derivative Time Constant 9-2 Down key
Function 2-1
E
End Marker
Cancellation of 8-6 End of Program Sequence
Indication of 3-3 End On parameter 8-2 External Selection 8-2
F
Front Panel Displays
Functions 2-3 Front Panel Keys
Functions 2-1
G
Guaranteed Soak
Indication of 3-1 Guaranteed Soak Time
Display of 3-2
1
I
Input Filter Time Constant 9-2 Integral Time Constant 9-2
J
Join Marker
Cancellation of 8-6
L
Lock Code (Controller Define Mode)
Setting 9-6 Using 9-1
Lock Code (Program Define Mode)
Setting 8-2 Using 8-1, 9-1
Loop Alarm
Description 9-10 Loop Alarm Enable 9-5 Loop Alarm Time 9-5
Definition 9-10
M
Manual Control
Front panel display 7-1
Selection/de-selection 2-1,
7-1 Manual Control Enable/Disable 9-5 Manual Program Hold
Indication of 3-1 Manual Reset 9-2 Minimum Motor ON Time 9-3
MODE key
Function 2-1 Motor Travel Time 9-3
N
Next Segment
Jump to 2-1 - 3-2
Number of Cycles Completed
Display of 3-2
O
ON/OFF Differential 9-3 Output 1 Cycle Time 9-3 Output 1 Power 9-2 Output 2 Cycle Time 9-3 Output 2 Power 9-2 Output Power Limit 9-3 Overlap 9-2
P
Power Fail Recovery 8-2 Pre-Tune Facility
Limitations on use 6-1 Selection/de-selection 2-1,
6-1 Status display 3-2
Process Variable Offset 9-2
PROG key
Function 2-1
Program Define mode
Indication of 8-1
Program Define Mode
Automatic exit from 8-8 Entry into 8-1 Exit from 8-8 Global parameters 8-2 Parameters specific to
a segment 8-5
Program Define Mode Parameters
"Read Only" access from Base Mode 2-4
"Read Only" access from Program
Run Mode 3-3 Program Lock 8-2 Program Running 3-1
2
Program Selection 3-1 Program Tag
Display of 3-2
Program Timebase
Changing 3-1 Proportional Band 1 9-2 Proportional Band 2 9-2
R
Rate 9-2 Recorder Output Scale Maximum
9-3 Recorder Output
Scale Minimum 9-3 Repeat Marker
Cancellation of 8-6 Reset 9-2 RTC Day 8-2 RTC Time 8-2 Run/Hold key
Function 2-1
S
Scale Range Decimal Point 9-5 Scale Range Maximum 9-5 Scale Range Minimum 9-5 Segment Time Remaining
Display of 3-2 Self-Tune Facility
Selection/de-selection 2-1,
5-1
Status Display 3-2
SET UP key
Function 2-1 Setpoint
Adjustment of 4-1 Setpoint High Limit 9-3 Setpoint Low Limit 9-3 Soak Segment
Setting of 2-1 Start On parameter 8-2
U
Up key
Function 2-1
3
Loading...