Honeywell CT2700 User Manual

Low Voltage (20 to 30 Vac) Thermostat and Wallplate
Congratulations on the purchase of your new thermostat! Over 100 years of Honeywell engineering expertise went into the making of this thermostat in an effort to provide you with a more comfortable and convenient living environment.
Your new thermostat will automatically control the tem­perature in your home, keeping you comfortable while saving energy when programmed according to the instructions in this manual.
Direct any questions concerning the application of this thermostat to Honeywell Customer Assistance at 1-800-468-1502, Monday - Friday 7:00 a.m. - 5:30 p.m., Central time.
Programmable Heat and/or Cool
Model CT2700
CT2700
An Electronic Round
USER’S GUIDE
MERCURY SWITCH
TYPICAL LOCATION OF A MERCURY SWITCH IN A THERMOSTAT
RECYCLING THERMOSTAT
If this thermostat is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube.
If you have questions, call Honeywell, Inc. at 1-800-468-1502.
1 PREPARE FOR INSTALLATION
Check Table 1 to make sure this thermostat is
compatible with your system. If not, return to the retailer. For more information, call Honeywell, Inc. at 1-800-468-1502.
M10614
®U.S. Registered Trademark Copyright © 1997 Honeywell Inc. • • All Rights Reserved
X-XX UL
69-1085
CT2700 AN ELECTRONIC ROUND ™ PROGRAMMABLE THERMOSTAT
Table 1. Compatibility Chart
System Type Compatible With CT2700
Gas—Standing Pilot Yes Gas—Electronic Ignition Ye s Gas-Fired Boilers Yes
Gas—Millivolt No
Oil-Fired Boilers Yes Oil-Fired Furnace Ye s Electric Furnace Yes Electric Air Conditioning Ye s
Baseboard Electric (120/240 Line Volt) No Heat Pumps/Multistage Equipment No
Not compatible with any 120/240 volt circuit. Not compatible with 2-wire White-Rodgers no. 1361 zone valves.
a
Not compatible with millivolt systems.
b
Compatible with 2-wire Honeywell zone valves. Isolating relay required for 3-wire thermostats zone valves
a
a,b
b
Acquire tools and items as needed. See Fig. 1.
CROSS-RECESSED SCREWDRIVER
WIRE CUTTER/STRIPPER OR SHARP KNIFE, IF NEEDED TO STRIP WIRES
LEVEL, IF NEEDED TO LEVEL THERMOSTAT FOR APPEARANCE
HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED TO DRILL HOLES IN WALL
MASKING TAPE, IF NEEDED TO LABEL WIRES AS DISCONNECTED FROM OLD THERMOSTAT
M878B
Fig. 1. Required installation tools/supplies.
2 REMOVE OLD THERMOSTAT
Test to make certain that your heating and air
conditioning systems (where applicable) are working properly. If either does not work, contact your local heating/air conditioning dealer. To avoid compressor damage, do not operate the cooling system when outdoor temperature is below 50°F (10°C).
CAUTION
Be careful when handling wires during installation. Damage to heating/cooling system possible.
Disconnect power at furnace or at main breaker/ fuse box before starting operation.
Carefully unpack your new thermostat, wallplate,
and decorator cover plate; save package of screws, instructions and receipt.
Remove the cover from the old thermostat. If it does
not snap off when pulled firmly from the bottom, check for a screw used to lock on the cover.
Loosen screws holding thermostat to subbase, wallplate, to wall and lift away.
Disconnect wires from old thermostat or subbase.
As you disconnect each wire, use masking tape to label it with the old terminal designation. If there are only two wires, they do not need labeling. Wrap wires around a pencil to keep them from falling back into the wall as shown in Fig. 2.
WIRES THROUGH WALL OPENING
M5136
Fig. 2. Wrapping wires around pencil.
Replacing Clock With C or C1 Clock Terminals
If you are replacing a Honeywell Chronotherm® Thermo­stat, you may find one or two wires that go to the C or C1 clock terminals on the Chronotherm® wallplate. Do not allow them to touch, or you can damage your transformer. Disconnect the wires and wrap them separately using electrical tape; do not wrap them together. Place the wires to avoid interfering with the new thermostat operation. Record the colors and terminal designation labels of the remaining wires.
Thermostat wiring
Six or More Wires
If there are six or more wires connected to the thermostat (excluding clock wires attached to terminals), you probably have a variation of a multistage heat pump or other multistage system. The thermostat is not compatible with such systems so return the product to your retailer. If you would like information about which programmable thermostats work with your system, call Honeywell Customer Assistance Center at 1-800-468-1502.
69-1085
2
CT2700 AN ELECTRONIC ROUND ™ PROGRAMMABLE THERMOSTAT
1
1
W
Y
G
R
HEATING RELAY AND FAN COIL
24V
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M12543
T8700
L1 (HOT)
L2
1
1
W
Y
G
R
FAN COIL
COOLING CONTACTOR COIL
24V
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M12544
T8700
Three Thermostat Wires
If you have three wires for heating only and can operate the fan using the FAN ON switch, this thermostat works with your system. However, some hot water (zoned) heating systems have three thermostat wires. The thermostat will work only if you install an isolating relay on these systems. For details, call Honeywell Customer Assistance Center at 1-800-468-1502.
3 MOUNT WALLPLATE
IMPORTANT
Level for appearance only. The thermostat functions normally even when not mounted level.
Position the decorator cover plate and wallplate on
the wall. Level the wallplate for appearance if desired. Use a pencil to mark the two mounting holes that best fit the application. See Fig. 3.
WALL
DECORATOR COVER PLATE
WALLPLATE
E
A
H
T
F
F
O
L
O
O
C
F
A
N
O
N
A
U
T
O
PLASTIC SCREW ANCHOR (2)
4 WIRE WALLPLATE TERMINALS
The CT2700 Thermostat is powered through the heating/ cooling system and is adaptable to most 4-wire, 18 to 30 Vac heating-cooling systems. Refer to Figs. 4 through 6 for some typical system wiring diagrams.
T8700 R G
Y
W
HEATING
1
L1 (HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
Fig. 4. CT2700 wiring diagram,
Fig. 5. CT2700 wiring diagram,
PRIMARY CONTROL
24V
4-wire heat/cool system.
2-wire, heat-only system.
FAN RELAY
COOLING CONTACTOR
M12525
Fig. 3. Mounting decorator cover plate and
Remove the decorator cover plate and wallplate
from the wall, and drill two 3/16-inch holes in the wall (if drywall). For firmer wall material such as plaster or wood, drill 7/32-inch holes. Gently tap provided anchors into the drilled holes until flush with the wall.
Reposition the decorator cover plate and wallplate,
pulling wires through the wiring opening. Loosely insert the mounting screws into the holes.
Level for appearance only; the thermostat functions
properly even when not level. Tighten the mounting screws.
wallplate to wall.
M12532
IMPORTANT
3
Fig. 6. CT2700 wiring diagram,
3-wire, cool-only system.
Use 18-gauge maximum wire to wire the thermostat.
69-1085
CT2700 AN ELECTRONIC ROUND ™ PROGRAMMABLE THERMOSTAT
All wiring must comply with local electrical codes and ordinances. If unsure about household wiring procedures, call your local heating and air conditioning contractor.
Refer to the masking tape labels you placed on wires when you removed your old thermostat.
Match the letter of your old thermostat wire with the
terminal of the corresponding letter on your new thermostat. Refer to Fig. 7.
ROUTE WIRING AS SHOWN THROUGH ENTRANCE HOLE
F
O
L
O
O
C
T
A
E
H
F
R
G
Y
W
ALTERNATE MOUNTING
SCREW HOLE
F
A
MOUNTING
N
O
SCREW
N
A
U
T
O
HOLE
5 ADJUST FAN OPERATION SWITCH
The thermostat fan operation switch, labeled fuel switch in Fig. 9, is set at the factory in the F (gas/oil fuel) position. This is the correct setting for most systems. If this system is an electric heat system, set the switch to the E (electric) position. The E setting allows the fan to turn on immedi­ately with the heating or cooling equipment in a system where the G terminal is connected.
F
FUEL SWITCH
E
ALTERNATE
MOUNTING
MOUNTING SCREW HOLE
WIRING ENTRANCE HOLE
SCREW HOLE
M12529
Fig. 7. CT2700 wallplate wiring connections.
NOTE: To ensure proper mounting of the thermostat,
restrict all wiring to the left side of the terminals.
Loosen the terminal screws and slip each wire
beneath its matching terminal. The shape of the terminals permit insertion of straight or wraparound connections. See Fig. 8. Tighten the terminals.
FOR WRAPAROUND, STRIP 7/16 INCHES (11 mm)
FOR STRAIGHT INSERTION, STRIP 5/16 INCHES (8 mm)
Fig. 8. CT2700 methods for wiring connection.
Plug the hole in the wall with insulation to help
prevent drafts from adversely affecting thermostat operation.
Fig. 9. Fuel switch, rear view of thermostat.
6 MOUNT THERMOSTAT TO
WALLPLATE
Align the tab and connector pins at the top of the thermostat with the wallplate. See Fig. 10.
DASHED LINES
M12537
INDICATE TABS ON BACK OF THERMOSTAT
A
ALIGN TABS/PINS A T T OP OF THERMOSTAT WITH WALLPLATE CONNECTOR.
M12530
Fig. 10. Mounting thermostat to wallplate.
F
F
O
L
O
O
C
Set
M12531
T
A
F
E
A
H
N
O
N
A
U
T
O
T
A
F
E
A
H
F
F
O
L
O
O
C
PRESS THERMOSTAT CASE
B
STRAIGHT ON TO LATCH.
N
O
N
A
U
T
O
Set
69-1085
4
CT2700 AN ELECTRONIC ROUND ™ PROGRAMMABLE THERMOSTAT
AM
SET
Press the thermostat straight on to the wallplate to
latch.
NOTE: To remove the thermostat from the wallplate,
grasp the thermostat on both sides and pull the thermostat straight out.
Restore power to the heating/cooling system.
7 PROGRAM YOUR THERMOSTAT
The thermostat is preprogrammed for your convenience with the following time and temperature settings, see Table 2.
Table 2. Preprogrammed Time/Temperature Settings.
Period
Start Time
WAKE 6:00 AM 70°F (21°C) 78°F (25.5°C) SLEEP 10:00 PM 62°F (16.5°C) 82°F (28°C)
WAKE is the time period you want the house at a comfort­able temperature during the day.
SLEEP is the time period you can set for an energy­savings temperature while you are sleeping.
NOTE: The heating and cooling program times are the
same. Changing your cooling WAKE time also changes your heating WAKE time.
The following sequence uses the heating program as an example; the System switch is in the HEAT position. To change to the cooling program, move the System switch to the COOL position and enter the cooling temperature settings.
NOTE: To exit the sequence at any time, press
until End is displayed.
1. Set Current Time a. Press . b. Press or
to set current time.
If you wish to change the preprogrammed time/ tempera­ture settings, follow steps 2 through 6. If not, press the
key until End is displayed or the thermostat will automatically return to normal operational mode within five minutes.
2. Set WAKE Time a. Press . b. Press or
to set desired WAKE time.
Heating
Setpoint
PM
AM
Cooling
Setpoint
3. Set WAKE Temperature
a. Press . b. Press or
to set desired WAKE temperature.
4. Set SLEEP Time
a. Press . b. Press or
to set desired SLEEP time.
5. Set SLEEP Temperature
a. Press . b. Press or
to set desired SLEEP temperature.
PM
SET
PM
6. Run Program Press . End is
displayed for five seconds indicating the end of programming. The thermostat then displays the current time and room temperature.
PM
8 OPERATE YOUR THERMOSTAT
Display Temperature Setting
a. Press or once
to display present temperature setting. After approximately five seconds, the thermostat displays the current time and room temperature.
Temporary Change
a. Press or until
the desired tempera­ture is displayed.
b. TEMPORARY is
displayed. The TEMPORARY change is in effect until the next program period.
NOTE: To cancel your TEMPORARY change, press
until End is displayed.
SET
SET
TEMPORARY
AM
AM
AM
5
69-1085
CT2700 AN ELECTRONIC ROUND ™ PROGRAMMABLE THERMOSTAT
Hold Function
To hold the thermostat at one temperature indefinitely, program both WAKE and SLEEP to the same temperature.
9 SET FAN AND SYSTEM SWITCHES
Manually control fan and system settings using the switches located at the top of the thermostat case. See Fig. 11 for switch locations.
TEMPERATURE DISPLAY
T
A
E
H
F
F
O
L
O
O
C
PM
Set
DECREASE SETTING
Fig. 11. CT2700 time/temperature display and
system/fan switches.
Fan Switch
The FAN switch settings are: ON: The fan runs continuously. Use for improved air
circulation.
AUTO: Normal setting for most homes. In cooling,
the fan starts and stops with the cooling equip­ment. In heating, the fan is controlled directly by the heating equipment and starts a few minutes after the heating equipment turns on (on most systems). When the thermostat fuel switch is set to the E position for electric heat, the fan starts and stops with the heating equipment.
Slide the switch on the thermostat to the desired fan setting.
System Switch
The System switch settings control thermostat operation as follows: COOL: The thermostat controls the cooling system. OFF: Both heating and cooling are off. HEAT: The thermostat controls the heating system.
Slide the System switch on the thermostat to the desired system setting.
69-1085
FAN SWITCHSYSTEM SWITCH
F
A
N
O
N
A
U
T
O
INCREASE SETTING
M12523
10 CHECK OPERATION AFTER
INSTALLATION/PROGRAMMING
Heating System
Slide the System switch to HEAT and the Fan switch to AUTO.
Press and hold the key to raise the temperature several degrees above the room temperature to start the heating equipment. When using the thermostat with the fuel switch set to the E position for electric heat, the fan starts immediately.
Press the key to lower the temperature setting below the room temperature. The heating equipment
should stop.
Cooling System
CAUTION
Operating at too low of an outdoor temperature may cause compressor damage Damage to compressor possible.
Do not operate cooling system if outdoor tempera­ture is below 50°F (10°C). Refer to manufacturer recommendations.
IMPORTANT
Temporary protection delay protects compressor; the thermostat allows the compressor to remain off for five minutes before restarting.
Slide the System switch to COOL and the Fan switch to AUTO.
Press the key to lower the temperature setting several degrees below the room temperature to start the cooling equipment.
Press the key to raise the temperature setting above the room temperature. The cooling equipment
should shut down.
Fan
Slide the System switch to OFF and the Fan switch to ON. The fan should run continuously.
CUSTOMIZE YOUR THERMOSTAT
The following instructions provide the information neces­sary to change the heating cycle rate to match your heating equipment; choose Fahrenheit (°F) or Celsius (°C); and 12- or 24-hour clock.
To exit at any time, press until End is displayed.
1. Enter Installer Setup
a. Slide System switch to OFF position.
b. Use the or
keys to
the temperature setpoint to 52°F (11°C).
6
set
SET
AM
CT2700 AN ELECTRONIC ROUND ™ PROGRAMMABLE THERMOSTAT
c. After the
thermostat reverts back to displaying room temperature (approximately five seconds), simultaneously press and keys and hold for three seconds. Release the keys after the display changes.
d. Press within
five seconds. The display changes to show current cycle rate setting.
TEMPORARY
AM
2. Cycles Per Hour a. Use or to select 1, 3, 6, or 9 cycles per
hour (cph). Refer to Table 3.
Table 3. Heating Cycle Rates
System Program Setting (cph)
Gas or oil forced air 6
b. Press to
display the current °F or °C setting.
3. Fahrenheit - Celsius Temperature
a. Use or to choose between °C and °F. b. Press to
display the current 12- or 24-hour clock setting.
4. Clock Format a. Use or to choose either
hour clock format.
Press once to exit the Installer Setup. Upon exiting, the temperature setting will be at 52°F (11°C). Pressing
six times returns the thermostat to the normal operational mode. End appears in the display.
5. Slide system switch to desired position.
Electric furnace 9 Hotwater baseboard, High
efficiency (90+) gas furnace Steam, radiant floor heat,
gravity
3
1
TROUBLESHOOT YOUR THERMOSTAT
Symptom Possible Cause Corrective Action
Heating/cooling equipment will not operate
Partial display Inoperative thermostat. Replace thermostat.
No display No power to thermostat. Check power to thermostat.
Temperature display is incorrect
Cannot change temperature setting
No AC power to thermostat.
Check power to heating/cooling equipment: — On/Off switch — Fuse or circuit breaker — Loose 24V connection: At thermostat; at furnace/air
conditioner
— Incorrect wiring: check appropriate wiring diagram. Thermostat inoperative. See checkout section. System switch on
thermostat in wrong position.
Thermostat minimum-off times operating for cooling.
Reset System switch.
Wait five minutes or follow steps in Checkout section.
Incorrect wiring. Check wiring. Heating/cooling
equipment inoperative.
Still in installer setup mode.
Thermostat mounted incorrectly on wallplate.
Thermostat is configured for °F or °C.
The upper or lower temperature limits were reached.
Consult equipment manufacturer instructions.
See Installer Setup section for exit instructions.
See installation instructions for correct mounting.
Reconfigure the display. See Installer Setup section for
instructions to change the display.
Check the temperature setpoints; temperature setting
range is 40°F (4°C) to 99°F (37°C).
7
a 12- or 24-
69-1085
CT2700 AN ELECTRONIC ROUND ™ PROGRAMMABLE THERMOSTAT
PERCENT OF HEATING COSTS YOU CAN SAVE
SAVINGS FOR ONCE-A-DAY 10°F (5°C) DECREASE*
6TO 8%
9 TO 11% 12 TO 13% 14 TO 15% 16 TO 18%
PERCENT OF COOLING
COSTS YOU CAN SAVE
SAVINGS FOR ONCE-A-DAY 10°F (5°C) INCREASE*
7TO 9% 10 TO 11% 12 TO 14% 14 TO 19%
*
YOUR SAVINGS DEPENDS ON HOME SIZE AND ACTUAL HEAT LOSS OR GAIN, GEOGRAPHIC LOCATION, FREQUENCY OF TEMPERATURES CHANGE, AND RANGE IN DEGREES OF CHANGE.
HEAT
COOL
M12545
Limited One-Year Warranty
Honeywell warrants this product to be free from defects in the workmanship or materials, under normal use and service, for a period of one (1) year from the date of the purchase by the consumer. if, at any time during the warranty period, the product is defective or malfunctions, Honeywell shall repair or replace it (at Honeywell’s option) within a reasonable period of time.
If the product is defective,
(i) return it , with a bill of sale or other dated proof of purchase, to the retailer from which you purchased it, or
(ii) package it carefully, along with proof of purchase (including date of purchase) and a short description of the malfunction, and
mail it, postage prepaid, to the following address:
Honeywell, Inc. in Canada: Honeywell, Limited/Honeywell Limitée Return Goods Department Product Services ON15-FFE 1050 Berkshire Lane 155 Gordon Baker Road Plymouth, MN 55441-4437 North York, Ontario M2H 3N7
This warranty does not cover removal of reinstallation costs. This warranty shall not apply if it is shown by Honeywell that the defect or malfunction was caused by damage which occurred while the product was in the possession of a consumer.
Honeywell’s sole responsibility shall be to repair or replace the product within the terms stated above. Honeywell shall not be liable for
any loss or damage of any kind, including any incidental or consequential damages resulting, directly or indirectly, from any breach of any warranty, expressed or implied, or any other failure of this product. Some states do not allow the exclusion or limitation or incidental
or consequential damages, so this limitation may not apply to you.
This warranty is the only expressed warranty Honeywell makes on this product. The duration of any implied warranties, including the warranties of merchantability and fitness for a particular purpose is hereby limited to the one year duration of this warranty. Some states
do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state.
If you have any questions concerning this warranty, please write our Customer Assistance Center, Honeywell, Inc., P.O. Box 524, Minneapolis, MN 55440-0524, Monday - Friday, 7:00 a.m. to 5:30 p.m., Central time. In Canada, write Retail Products ON15-02H, Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 3N7.
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
69-1085
69-1085 R.T. 8-97 Printed in U.S.A.
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7
8
Helping You Control Your World
®
Loading...