System Features......................................................................................................................................................... 1-1
About Private Network Application .......................................................................................................................... 1-1
About AlarmNet-i Internet Application..................................................................................................................... 1-2
Modes of Operation................................................................................................................................................... 1-3
Zone Trigger Mode ..................................................................................................................................... 1-3
4204 Mode and Two-4204 Mode................................................................................................................ 1-3
Module Supervision Features .................................................................................................................................... 1-4
SECTION 2: Mounting and Wiring ......................................................................................................... 2-1
Mounting the 7847i/7847i-E...................................................................................................................................... 2-1
Wiring the 7847i/7847i-E.......................................................................................................................................... 2-2
Wiring for ECP, 4204 and Two-4204 Modes.............................................................................................. 2-2
Wiring for Zone Trigger Mode.................................................................................................................... 2-3
Power Connections and Options................................................................................................................................ 2-4
SECTION 3: Programming the 7847i/7847i-E ....................................................................................... 3-1
General Information .................................................................................................................................................. 3-1
Using the AlarmNet Direct Website............................................................................................................ 3-1
Using a 7720P Programming Tool.............................................................................................................. 3-1
Using the Control Panel Programming Mode ............................................................................................. 3-2
ECP Status Codes ................................................................................................................................................ 3-9
i
7847i/7847i-E Installation and Setup Guide
Alternative Modes (Zone Trigger, 4204 and Two-4204) .......................................................................................... 3-9
Zone Trigger Mode ..................................................................................................................................... 3-9
Alternative Mode Programming.............................................................................................................................. 3-10
Registering the 7847i/7847i-E................................................................................................................................... 4-1
Registering through AlarmNet Direct Website (does not apply if using Private LAN) .............................. 4-1
Using the Tamper Switch............................................................................................................................ 4-2
Using the Programming Tool...................................................................................................................... 4-2
Register by Phone........................................................................................................................................ 4-4
System Status Displays ............................................................................................................................... 5-2
Appendix A : Summary of LED Operation.............................................................................................................. A-1
Status Display Operation............................................................................................................................ A-1
Mode and Status LED Display................................................................................................................... A-4
Mode and Status Indicator Switch.............................................................................................................. A-4
Appendix B : Central Station Messages ....................................................................................................................B-1
Appendix C : IP Downloading ..................................................................................................................................C-1
General Information ....................................................................................................................................C-1
Direct Wire Setup........................................................................................................................................C-1
Appendix D : Glossary ............................................................................................................................................. D-1
Summary of Connections Diagram…………………………………………………………..……….Inside Back Cover
ii
SECTION 1
General Information
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
♦ Introduction
♦ System Features
♦ About Private Network Application
♦ About AlarmNet-i Internet Application
♦ Encryption
♦ Enterprise Related Encryption Functions
•••••••••••••••••••••••••••••••••••••••••••••••••
Introduction
AlarmNet’s 7847i Internet Communication Module and 7847i-E Internet/Intranet
Communication Module were developed to transport alarm signals via the Internet or
Private LAN (7847i-E only). These easy-to-install devices provide sophisticated data security
and communicate with all AlarmNet central stations through AlarmNet’s server, or directly
to a 7810iR-ent Internet/Intranet receiver in a private network application (7847i-E). In
addition to alarm reporting, the 7847i and 7847i-E provide upload/downloading capability
via the internet or a Private LAN (7847i-E only).
♦ Installation Key
♦ Recovery Mode
♦ Remote Services
♦ Modes of Operation
♦ Specifications
System Features
Basic features of the 7847i and 7847i-E include:
• Easy CAT-5 10 BaseT connection to a hub or router
• Installs behind firewalls without compromising network security
• Supports dynamic or static IP addressing
• Quick connection to compatible Honeywell series control panels
• Simple programming using a 7720P programming tool or AlarmNet Direct website
• Reports fire, burg, and status messages via the Internet (or Intranet for 7847i-E)
• Allows uploading and downloading of control panel data over the Internet (or Intranet for 7847i-E)
• Supports remote control of alarm systems via Remote Access feature, and email notification of
events via Multi-Mode feature (Web Service)
About Private Network Application
The 7847i-E may be configured to transmit signals within a private network application to a
7810iR-ent receiver. Up to 300 7847i-E Internet/Intranet Communication Modules may be
routed to a single 7810iR-ent receiver. In a private network application, the signals are not
routed to the AlarmNet Control Center (see Figure 1).
The 7847i/7847i-E module requires an AlarmNet–i account. For new installations, please obtain the
account information from the central station prior to programming this module. For replacement
installations, the AlarmNet-i account is created automatically when the module is registered (based on
the existing "C Series" account).
About AlarmNet-i Internet Application
AlarmNet-i is a fully encrypted, secure method of delivering alarm messages from a
protected premise to an AlarmNet equipped central station. An Internet Communicator
Module transmits status, supervisory, and alarm messages to the AlarmNet Control Center
using a broadband Internet connection (see Figure 1).
The AlarmNet Control Center identifies, validates, and forwards the messages to the
appropriate AlarmNet central station. An Internet receiver, 7810iR or 7810iR-ent, is
required when receiving Internet signals from the AlarmNet Control Center. AlarmNet-i
has an unlimited account capacity.
Encryption
The 7847i/7847i-E and 7810iR-ent support private key encryption. Private key encryption
means that both the sender and the receiver know the KEY used to encrypt the data. Each
device produced by Honeywell is loaded with a globally unique identifier called a MAC
number, and a large random number or KEY. This KEY and MAC number are also stored in
the AlarmNet servers. When a device contacts AlarmNet it sends the MAC number in the
clear followed by the message that is encrypted using the KEY data. The server looks up its
copy of the KEY based on the MAC number and uses that KEY to decrypt the message.
The communication devices use 256 bit AES (Rijndael) encryption (which is required for
certain government installations). The AlarmNet-i AES Encryption Software Module Version
1.0 contained in the Honeywell products has NIST approval. Listings for this approval can be
found at http://csrc.nist.gov/cryptval/aes/aesval.html
Enterprise Encryption Related Functions
The previous paragraph described general encryption, and how it functions with AlarmNet.
When used in a Private closed network or Enterprise installations, some additional processes
are required to support encryption. In an enterprise installation the 7810iR-ent takes on the
server function that exists in the AlarmNet Internet installation and has a process to learn
the MAC numbers and KEYs for which it will be responsible.
Installation Key (for Private LAN)
At installation a 10-digit installation key needs to be programmed into every device in the
network. This 10-digit key should be the same for all devices used in the Private LAN mode.
The purpose of this key is to encrypt the private KEY of each subscriber device as it is
registered to the 7810iR-ent so this sensitive data is never sent in the clear. This KEY is only
used for registration purposes and is not used for supervision or alarm transmission. Once a
device is registered the 7810iR-ent will have a copy of the 7847i-E’s factory KEY. From this
point on the unique factory key is used for communications.
Recovery Mode
Recovery Mode is only available when in Private LAN mode. In the event of a failure of the
7810iR-ent requiring the replacement of the hardware or the erasure of its memory, the
7810iR-ent supports a Recovery Mode. In Recovery Mode, the 7810iR-ent is programmed
with the same 10-digit installation key. When a 7847i-E communicates with the 7810iR-ent
and is found not to exist in its database, a special response is sent back to the 7847i-E
requesting it to re-register itself. The 7847i-E then registers using the 10-digit installation
key. When all accounts have been recovered, Recovery Mode can be turned off to provide
better control of registration.
Certification number 127.
1-2
Remote Services
Section 1: General Information
U
L
• Access their security system from a computer via a website (Remote Access feature)
• Receive email and text message notifications of system events (Multi-Mode feature)
• Perform system functions and receive confirmations using text messages (SMS feature)
Remote Access and Multi-Mode have not been evaluated by UL.
Honeywell now offers a new series of web based services that provides consumers with the
ability to communicate with their security system remotely in a number of ways. These new
web services will allow users to:
Dealers will initially enroll their customers for web services during account programming
through the AlarmNet Direct website. The features that can be enabled include Remote
Access and Multi-Mode. Once enabled, the specific programming fields associated with these
features can be programmed into the communications device either remotely using the
AlarmNet Direct website or locally using the 7720P local keypad programming tool.
Modes of Operation
The 7847i and 7847i-E provide four modes of operation so they can be used with various
types of control panels, as summarized below:
ECP Mode
• This mode is for use with Honeywell controls that support LRR-ECP communication
• The module connects to the control’s keypad terminals and provides 2-way communication with
the control using ECP messaging
•The control treats the module as a Long Range Radio (LRR) device, so program the control
accordingly, including setting the module’s proper LRR device address
• Panel-generated reports are sent in Contact ID format
• The module also supports two hardwire zone trigger inputs (zones 6 and 7) – these report in
Ademco High-Speed format
Zone Trigger Mode
•This mode is for use with controls that do not support LRR-ECP communication nor 4204 Relay
Modules
• The module provides six input zones
• Each zone can be configured for +V, -V, or EOLR triggering
• Each zone can be programmed for inverted operation, delayed reporting, and restoral reporting
• Zone 1 and 2 inputs can distinguish between pulsed and steady signals and report fire or burglary
alarms respectively
• Zone 1 and 2 inputs can also be programmed to report LYNX panic (if used with LYNX control)
• Reports are sent in ADEMCO High-Speed format
4204 Mode and Two-4204 Mode
•This mode is for use with Honeywell controls that do not support LRR-ECP communication, but
that do support 4204 Relay Modules
• The module connects to the control’s keypad terminals
• The control treats the module as 4204 Relay Module(s), so program the control accordingly,
including setting the module’s proper 4204 device address
•4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on options
programmed
•Two-4204 mode provides up to eight zone inputs, depending on options programmed
1-3
7847i/7847i-E Installation and Setup Guide
• Each 4204 zone can be programmed for delayed reporting and restoral reporting
• Reports are sent in ADEMCO High-Speed format
Module Supervision Features
The 7847i/7847i-E provides the following types of supervision and module fault detection:
•Network communication failure
message from the module within a specified time (“Supervision” option), AlarmNet notifies the
central station of a communication failure.
•Communication path failure
control panel can be notified of a trouble condition with the module after a specified time has
elapsed (“Notify Panel Of” option).
• Fault output
If used, the fault relay will trip when the following conditions occur: tamper*, loss of network
connectivity*, the device is not registered and the device is remotely disabled by AlarmNet.
: Terminal 11 can serve as a fail-safe trigger for module fault conditions.
: In the event the module detects a communication path failure, the
* Alarm reporting for the noted condition must be enabled for it to trigger the fault relay.
• Cover tamper condition (“Tamper Rpt” option).
Specifications
Mechanical
Dimensions: 8.4" x 8.0" x 1.5"
Weight: 1 lb.
: In the event the AlarmNet network does not hear a supervisory
Electrical
Input Power: 12VDC
Current Drain: 20mA average standby, 75mA peak transmit
Radio Fault Output: Open collector
Input Trigger Levels: (V+) 2V – 14V
(V-) 0V – 1V
Ethernet
Network Standard: IEEE 802.3u compliant
Data Rate: 10Base-T / 100Base-T with auto detect
Ethernet Cable: Cat. 5 (min.), MDI/MDI-X auto crossover
Environmental
Operating temperature: -20º to +55ºC
Storage temperature: -40º to +70ºC
Humidity: 0 to 95% relative humidity, non-condensing
Altitude: to 10,000 ft. operating, to 40,000 ft. storage
1-4
SECTION 2
Mounting and Wiring
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
♦ Mounting the 7847i/7847i-E
♦ Wiring the 7847i/7847i-E
♦ Power Connections and Options
♦ Ethernet Connections
•••••••••••••••••••••••••••••••••••••••••••••••••
Mounting the 7847i/7847i-E
The 7847i/7847i-E must be mounted indoors. To mount the unit, see Figure 2 and complete
the following steps:
1. Unpack the unit and detach the case back by pushing up into the two tabs located at the
bottom of the 7847i/7847i-E module with the blade of a screwdriver while pulling the
case back and case front apart.
2. Locate the case back over the mounting surface such that the opening in the case back is
aligned with the wire/cable access opening (in the mounting surface) while passing the
wires/cable through the opening in the case back, or through the removable knockouts
located on the bottom of the back cover.
3. Secure the case back to the mounting surface using four screws (supplied).
4. When all wiring is completed, attach the case front of the unit to the case back. Attach
the top first then press the bottom section inward until it snaps into place securely.
Secure bottom using cover securing screw (supplied) as shown below, (required for UL
installations).
5. Twist and remove cap from handle (supplied) and discard handle. Insert cap in top hole
of case back, as shown.
PRESS CAP
INTO PLACE
CASE
BACK
MOUNTING
SCREW (4)
(TYP)
CAP
(TWIST OFF)
OPTIONAL WIRING
KNOCKOUT
OPTIONAL WIRING
KNOCKOUTS
TAB
TAB
COVER SECURING SCREW
Figure 2. Mounting the 7847i/7847i-E
CASE
FRONT
7847i-E-022-V1
2-1
7847i/7847i-E Installation and Setup Guide
Wiring the 7847i/7847i-E
Unshielded, 22 AWG cable is recommended for 7847i/7847i-E power/data wires.
Wiring for ECP, 4204 and Two-4204 Modes
Most Honeywell ADEMCO control panels support LRR-ECP data communication, (e.g.,
VISTA-10P, VISTA-15P, VISTA-20P, LynxR-I, VISTA-128BP/250BP and
VISTA-128FBP/250FP). However, there are some panels that do not. Check the Installation
and Setup Guide for the control panel you are using to see if it supports ECP communication.
Connect the 7847i/7847i-E to a compatible Honeywell VISTA control panel's ECP terminals,
in parallel with keypads and other peripheral devices, VIP module, etc. Wire length/gauge
limitations are the same for the module as they are for keypads and other peripheral devices.
To wire the module for ECP communication, see Figure 3 and do the following:
Table 1. Wiring connections for ECP or 4204 modes
7847i/7847i-E Control
Terminal 3 V+ +12 V Aux
Terminal 4 GND Ground
Terminal 5 Data In Data Out
Terminal 6 Data Out Data In
TB1
+12 V
GND
DATA OUT
DATA IN
RED
BLK
YEL
GRN
V+
3
GND
4
5
ECP DATA IN
6
ECP DATA OUT
CONTROL PANEL
7847i / 7847i-E
7847i-E-019-V0
Figure 3. Wiring a Vista for ECP Mode or 4204 Modes
To install a 7847i/7847i-E with a LynxR-I Security System, wire the devices as shown in
Figure 4 below. Refer to LynxR-I Installation and Setup Guide.
2-2
Section 2: Mounting and Wiring
BLK
YEL
RED
GRN
NC
GND
DATA IN
+12 VDC
DATA OUT
LYNXR-I CONTROL PANEL
Figure 4. Wiring a LynxR-I for ECP Mode
Wiring for Zone Trigger Mode
To trip the zone on the 7847i/7847i-E in V+ trigger mode, the positive triggering voltage from
the control panel must be within 2.0V-14V.
Trigger levels above this range may cause permanent damage to the unit.
Trigger levels below this range result in unreliable operation.
To trip the zone on the 7847i/7847i-E in V- trigger mode, the negative triggering voltage
must be less than 1.0V.
NOTE:LynxR and LynxR-EN have a designated trigger for V- trigger.
Connect a wire from the triggering source (bell output, voltage trigger, etc.) of the control
panel to the zone input of the module, and connect a common ground between the module
and control panel.
4-WIRE CABLE (N4632-4)
RED
BLK
YEL
GRN
TB1
V+
3
GND
4
ECP DATA IN
5
6
ECP DATA OUT
7847i / 7847i-E
7847i-E-018-V0
UL
The configurations shown in Figures 5a and 5b have not been evaluated by UL.
Examples of zone connections are shown below:
TB1
+12 V
GND
BELL (+)
CONTROL PANEL
(+)
( )
V+
3
GND
4
5
ZONE INPUT Z1/Z2
7847i / 7847i-E
7847i-E-020-V0
Figure 5a. Wiring the 7847i/7847i-E Zone 1 Input for a Positive (+) Triggered Bell Output
TB1
+12 V
GND
BELL ( )
CONTROL PANEL
(+)
( )
V+
3
GND
4
ZONE INPUT Z1/Z2
5
Figure 5b. Wiring the 7847i/7847i-E Zone 1 Input for a Ground (-) Triggered Bell Output
7847i / 7847i-E
7847i-E-021-V0
2-3
7847i/7847i-E Installation and Setup Guide
TB1
1
2
NOT USED
NOT USED
9
LRR / AAV
TRIGGER
8
LYNXR/LYNXR-EN
CONTROL PANEL
2K EOL
RESISTOR
GND
4
ZONE INPUT Z1/Z2
5
7847i / 7847i-E
7847i-E-024-V0
Figure 6. Wiring the 7847i/7847i-E Zone 1 Input to a LynxR Trigger Output
TB1
NOT USED
1
NOT USED
2
ECP (+) VOLTAGE INPUT
3
GND
2K EOL
RESISTOR
Figure 7. Wiring the 7847i/7847i-E Zone 1 Input for EOL Supervised N.O./N.C. Triggers
N.O.
N.C.
4
ZONE INPUT Z1/Z2
5
7847i / 7847i-E
7847i-E-028-V0
Power Connections and Options
Primary power for the 7847i/7847i-E is provided by the auxiliary power output of the control
panel 9.6V –13.8V, typical, or other external power source.
When calculating the total load on the auxiliary power output of the control panel, 20mA
must be budgeted for the 7847i/7847i-E. Under normal operating conditions, the unit will
not pull more than 20mA; however, it will draw 75mA during a transmission.
Connect the wires from the (+) and (–) terminals of the DC power source to terminals V+ and
GND on TB1 of the 7847i/7847i-E. Observe Polarity!
If using an external power source, connect GND from power supply to GND of the control
panel.
Ethernet Connections
1. For UL installations, the Cat. 5 Ethernet connection between the 7847i/7847i-E and the
router cannot exceed 12 feet with both the 7847i/7847i-E and the router located within
UL
the same room.
2. Use a Listed cable/DSL router suited for the application.
•Connect one end of the Ethernet cable (Category 5) to the 7847i-E's RJ45 Ethernet
connector and the other end to the cable/DSL router.
2-4
ROUTER
TO
TAMPER
SWITCH/
IB SERVICE
TB1
Xmit
Shift
BS / ESC
/
N / Y
SpaceEnter
Shift
7
Section 2: Mounting and Wiring
7720PROGRAMMINGTOOL
A
B
123
DE
45
S
C
F
6
T
X
98
#0
7720P
PROGRAM
CONNECTOR
S TATU S
LED
DISPLAY
ETHERNET
PORT
NETWORK
CONNECTIVITY
LED DISPLAY
RJ45
MODE AND STATUS
INDICATOR SWITCH
MODE AND STATUS
LED DISPLAY
7847i-E-016-V0
Figure 8. Ethernet Connections
Initial Power-Up Sequence
Before connecting power, check that the following have been completed:
•Terminal block TB1 V+ and GND terminals are connected to the control panel's auxiliary
power output: 12 VDC nominal.
•Power up the control panel.
Initially, all 7847i/7847i-E programming options are set to the factory default settings.
NOTE: Refer to
Appendix A
for detailed information on LED functions.
2-5
7847i/7847i-E Installation and Setup Guide
2-6
SECTION 3
Programming the 7847i/7847i-E
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
♦
General Information
♦
ECP ModeProgramming
♦
Alternative Modes (Zone Trigger, 4204 and
Two-4204)
•••••••••••••••••••••••••••••••••••••••••••••••••
General Information
To the control panel, the 7847i/7847i-E Internet/Intranet Communication Modules, when in ECP Mode, is
treated as a long-range radio device.
The 7847i/7847i-E can be configured to deliver alarms via the Internet to an AlarmNet
central station or via a Private LAN (7847i-E only) directly to a 7810iR-ent receiver. Both
methods of communication are encrypted to ensure security. The 7847i and 7847i-E use 256bit AES (Rijndael) encryption (which is required for certain government installations).
♦ Alternative Mode Programming
♦ Exiting Programming Mode
The 7847i/7847i-E modules require an AlarmNet–i account, except when Private LAN is enabled on
• Through the AlarmNet Direct website
• Through use of a 7720P Programming Tool
• Through a programming mode in control panel, on panels that support this option (e.g., Vista-
Using the AlarmNet Direct Website
Using a 7720P Programming Tool
the 7847i-E. Obtain the account information from the central station prior to programming this module.
You can program a 7847i/7847i-E by one of the following methods:
128BP and FBP)
To program the module via the website (if you are already signed up for this service), go to:
If you are not signed up for this service, click on “Dealer Sign-Up".
Log in and follow the on-screen prompts.
Please have the following information available when programming the module:
1. Primary City ID (two-digit hexadecimal number)
2. Primary Central Station ID (two-digit number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on the outside of box and on label inside
module)
After programming is complete, you must transfer the data to the module and the module
must be registered. Refer to Section 4: Registration, for further instructions.
Connect the 7720P Programming Tool; refer to Figure 8 in Section 2. The 7847i and 7847i-E
power the 7720P Programming Tool via the programming jack, and automatically senses the
presence of the 7720P when it is plugged in.
.
3-1
7847i/7847i-E Installation and Setup Guide
Each key of the 7720P has two possible functions: a normal function and a Shift function.
To perform a normal key function, simply press the desired key. To perform a Shift function,
press the [shift] key, and then press the appropriate key.
The prompts in this document reflect use of the 7720P Programming Tool. Table 2 below lists
each normal and shift key function.
Table 2. 7720P Normal and Shift Key (shift LED lit) Functions
KEY NORMAL KEY FUNCTION SHIFT KEY FUNCTION
BS/ESC [BS]: Press to delete entry [ESC]: Press to quit program mode; also can reset
↓/↑ [↓]: Scroll down programming [↑]: Scroll up programming
N/Y [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer
SHIFT Press before pressing a SHIFT key function. Will light SHIFT LED. LED goes out once a key
is pressed. Press again for each SHIFT function desired.
1/A [1]: For entering the number 1 [A]: For entering letter A
2/B [2]: For entering the number 2 [B]: For entering letter B
3/C [3]: For entering the number 3 [C]: For entering letter C
4/D [4]: For entering the number 4 [D]: For entering letter D
5/E [5]: For entering the number 5 [E]: For entering letter E
6/F [6]: For entering the number 6 [F]: For entering letter F
7/S [7]: For entering the number 7 [S]: For entering letter S
8/T [8]: For entering the number 8 [T]: For entering letter T
9/X [9]: For entering the number 9 [X]: For entering letter X
SPACE [SPACE]: For scrolling option list No SHIFT function
0 [0]: For entering the number 0 No SHIFT function
#/ENTER [#/ENTER]: Press to accept entries No SHIFT function
* Active only when the "Exit Programming Mode" prompt is displayed.
Using the Control Panel Programming Mode
Some control panels support programming of the 7847i/7847i-E through the control
panel programming mode (e.g., Vista-128BP). If programming through the control
panel, only the ECP Mode programming options are available. The "mode" questions
will not be displayed, and the mode cannot be changed. For a description of key
functions on the control panel keypad, and how they map to the 7720P Programming
tool, refer to the control panel's Programming Guide.
Programming Conventions
Programming is accomplished by answering a series of prompts (questions). Most prompts
require only a [Y]es or [N]o response, while others require a numerical response (ID
numbers, etc.).
The current value is displayed on the second line in parentheses ( ). A "?" indicates an
invalid entry.
Use the [ENTER] key to accept the current entry and proceed to the next prompt. If the
current value is invalid, pressing [ENTER] re-displays the prompt; the next prompt is not
displayed until a valid answer is entered.
Use the up/down arrow keys to scroll through the programming questions without changing
any values. Press the [ESC] key to go to the end of the list of questions.
programming defaults*
ECP Mode Programming
Press the [ENTER] key to begin programming.
NOTE: The central station can remotely block access to local
device programming. If this has been done, the
following prompt appears:
3-2
Access to Prog
Mode Denied
Section 3: Programming the 7847i/7847i-E
NOTE: The default programming values for ECP mode are listed in each prompt below.
Table 3: Programming a 7847i-E for ECP mode only.
PROMPTS ENTRY OPTIONS DESCRIPTION
Strt Prog Mode?
1
(Y/N)_
Enter Password:
2
Program Device?
3
(Y/N)_
Create Password?
4
(Y/N)_
5
Change Password?
(Y/N)_
Enter Password
6
Verify Password
7
Exit Prog. Mode?
8
(Y/N)_
Device Mode
9
(ECP)_
Important Information Regarding Multi-Mode Options
Users can receive email notification of system events by using the Multi-Mode feature. In ECP mode, this is
accomplished through emulation of a 4204 relay module, or two 4204 relay modules. When “4204-Sourced” is
selected, the user can be notified of up to four events, plus two additional events if using the optional communication
device zones of 6 and 7. When “2-4204-Sourced” is selected, the user can be notified of up to eight system events.
[Y], [N]
Enters programming mode.
[0-9, A-F, N, S,
T, X, Y]
If a password has been previously assigned, this
prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
[Y], [N] To begin programming the module, press [Y] and go to
Prompt 9: "Device Mode."
To create a password if none has been assigned, press
[N] and go to Prompt 4: "Create Password."
To change an existing password, press [N] and go to
Prompt 5: "Change Password."
[Y], [N]
Passwords can be used to protect account and
programming information.
If no password has been assigned, this prompt appears
after pressing [N] at the "Program Device?" prompt.
If a password is desired, press [Y] and go to Prompt 6:
"Enter Password."
[Y], [N] If a password has already been assigned, this prompt
appears after pressing [N] at the "Program Device?"
prompt.
Press [Y] if you want to change the password.
NOTE: To clear an existing password, without entering
a new one, answer [Y] to the "Change Password?"
prompt, then press the [Enter] key when prompted for
the new password and its confirmation.
[0-9, A-F, N, S,
T, X, Y]
This prompt is displayed if [Y] was pressed in Prompt 4
or 5.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
[0-9, A-F, N, S,
T, X, Y]
Re-enter the password as confirmation.
If the password doesn't match the first entry, the
following is displayed followed by the "Exit Prog.
Mode?" prompt:
Verify Not OK
PSWD not created
Otherwise, the "Exit Prog. Mode?" prompt is displayed
directly.
[Y], [N]
[ESC]
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the Exiting Programming Mode paragraph in
this section.
• ECP
• Zone Triggers
• 4204 Emu
• Two 4204s
Press the [space] key to scroll through the modes of
operation. Press [ENTER] to select ECP mode.
See Table 5 if programming other modes.
3-3
7847i/7847i-E Installation and Setup Guide
The Multi-Mode address must match the address of a relay module enabled in the control panel (although you don’t
actually connect a module). If using “2-4204-Sourced,” the address of the second module is automatically assigned
the next device address after the first 4204. Make sure that address is also enabled in the control panel. Program
outputs to trigger on system events the user would like to be notified of through Output Device (Relay) programming
in the control panel. Outputs 1-4 on the first 4204 Device Address map to events 1-4. Outputs 1-4 on the second 4204
Device Address map to events 5-8.
For LynxR-I/ReadyGuardR-I series controls (when available), if "4204 Sourced" is selected, you must enable MultiMode Address 6 or 7 in the control panel. If "2-4204" Sourced is selected, you must enable both (program field *86.
These events are configured at the AlarmNet Total Connect website at: https://services.alarmnet.com/TotalConnect
Multi-Mode (email notification) is intended as a convenience for the user, and does not replace Central Station
reporting of critical events (alarms, troubles, etc.).
NOTE: The Multi-Mode option is not available, and will not be displayed, when Private LAN is enabled on the 7847i-E.
PROMPTS ENTRY OPTIONS DESCRIPTION
10
Multi Mode
(Disabled)_
• Disabled
• 4204 Sourced
• 2-4204 Sourced
Multi Mode Addr
11
(12)_
[01-30]
Important Information Regarding Private LAN mode (7847i-E only).
1. Prompts 13-20 apply only if Private LAN was selected in Prompt 12.
2. Prompts 16-18 apply only if Prompt 15: Alarm Delivery is set to “Fail to CS IP2".
En.Priv.LAN: Y/N
12
(N)
CS IP:
13
255.255.255.255
CS Port:
14
(80)
Alarm Delivery:
15
Only One CS IP_
Secondary CS IP:
16
255.255.255.255
[Y], [N]
12 digit:
xxx.xxx.xxx.xxx
[80] Enter the Central Station Port Number.
[Only One CS
IP]
[Fail to CS IP2]
12 digit:
xxx.xxx.xxx.xxx
Enable if you want specific events sent by email to the
user.
Select "4204 Sourced" to send up to four events or "24204 Sourced" to send eight events.
Disable for normal alarm processing and go to Prompt
21: "Primary City ID".
This address must be programmed if using the MultiMode feature. The device address must be unique from
the normal LRR Device Address (Prompt 28), and the
Keypad Address used for Remote Access or Direct Wire
downloading. The address used must also be enabled
as a 4204 relay module in Vista and First Alert control
panels. See Important Information above.
Applies only to 7847i-E. Press [Y] to enable alarm
delivery via a Private LAN to a 7810iR-ent receiver.
Press [N] to enable alarm delivery over the internet or if
you have a 7847i, and go to Prompt 21: Primary City ID.
Enter the four part primary CS IP address of the
7810iR-ent receiver at the reporting center to which
this device will report. The four parts of the address
must be separated by spaces.
NOTE: This entry CANNOT be left as 255.255.255.255”.
It MUST be programmed with a valid IP address.
NOTE: The CS Port number must match the "Listening
Port" question of the 7810iR-ent.
Select the "Only One CS IP" option, if only one Central
Station IP address is desired and go to Prompt 18:
Verify Inst. Key.
Select the "Fail to CS IP2" option, if a secondary
Central Station IP address is desired.
Enter the four part secondary CS IP address of the
7810iR-ent receiver at the reporting center to which this
device will report. The four parts of the address must be
separated by spaces.
NOTE: This entry CANNOT be left as “255.255.255.255”
if using the Secondary CS IP. It MUST be programmed
with a valid IP address.
3-4
Section 3: Programming the 7847i/7847i-E
PROMPTS ENTRY OPTIONS DESCRIPTION
Second CS Port:
17
(80)
IP2 Supervision
18
30 Day_
[80]
• 30 Day
• Daily
• Full Rate
• None
Installation Key:
19
**********_
Verify Inst. Key:
20
**********_
[0-9] Enter the 10-digit Installation Key necessary for
[0-9]
Important Information Regarding Primary and Secondary Accounts (Questions 21-27)
Account information is provided by the central station administrator. If the control supports secondary
account reporting, you will need secondary account information, unless using a Private LAN (7847i-E). The
City ID, CS ID or Subscriber ID of the secondary account must differ from that of the primary account. If
Private LAN (7847i-E) is enabled, Prompts 24-27 will not be displayed.
Primary City ID
21
(??)_
Primary CS ID
22
(??)
Primary Sub ID
23
[0001-9999]
[01-99]
[01-FE] Enter the 2-digit primary central station ID number,
(????)
En. 2nd CS Y/N
24
[Y], [N]
(N)_
2nd City ID
25
26
(??)_
2nd CS ID
[01-99]
[01-FE]
(??)_
2nd Sub ID
27
(????)_
Device Address
28
[01-30]
(03)_
[0001-9999] Enter the 4-digit subscriber account number for the
Enter the Central Station Port Number.
NOTE: The CS Port number must match the "Listening
Port" question of the 7810iR-ent.
Sets the supervision timing for the secondary internet
receiver to send a test alarm if set to Daily or 30 Day,
or to send a status message to the 7810iR-ent if the
interval is set to Full Rate. Selecting Full Rate means
secondary supervision will be the same as primary.
NOTE: The second 7810iR-ent must be programmed to
supervise subscribers in order to generate a
communication failure.
Press the [space] key to scroll through the choices.
communication with 7810iR-ent. If the key entry is
invalid, the prompt is repeated. See the Installation Key paragraph in Section 1 for more information.
Re-enter the 10-digit Installation Key to verify key.
If verification fails, “Verify NOT OK” will be displayed
for one second and the display will return to the entry
of the installation key.
Enter the 2-digit primary city ID, 01-99 (decimal).
01-FE (HEX).
Enter the 4-digit subscriber account number for the
primary central station, 0001-9999 (decimal).
Applicable only if control supports Central Station #1
and #2 Category Enable reporting for the LRR device
(e.g., VISTA-128BP, FA1660C, etc.).
Used if reporting to a second central station is desired.
Press [N], go to Prompt 28: "Device Address."
Enter the 2-digit secondary city ID, 01-99 (decimal).
Enter the 2-digit second central station's ID number,
01-FE (HEX).
second central station, 0001-9999.
In ECP mode, the 7847i/
7847i-E communicates with
the panel as a Long Range Radio (LRR) device. Enter
the appropriate ECP device address. For VISTA-10 and
VISTA-20 series control panels, use address 03. For
other controls, see the control panel’s Installation and
Setup Guide.
NOTES:
1. When programming the control, enable the LRR
output.
2. The device address must be unique from the "Keypad
Address" entered in Prompt 31, and the Multi-Mode
Address entered in Prompt 11.
3-5
7847i/7847i-E Installation and Setup Guide
NOTE: The Remote Access option is not available, and will not be displayed, when Private LAN is enabled on the 7847i-E.
PROMPTS ENTRY OPTIONS DESCRIPTION
Remote Access Y/N
29
(N)_
[Y], [N]
Press [Y] to allow the end user to access their system
via a website. Availability of this service is controlled
by the dealer via the web-based programming tool on
the AlarmNet Direct website.
Direct Wire Y/N
30
(N)_
[Y], [N]
Applies only to VISTA-128BP/250BP and FBP Series
controls, and FA1600C and FA1700C Series controls.
Enables Direct Wire Downloading over IP.
If [N], and if Prompt 29: Remote Access is disabled,
Keypad Address
31
(28)_
[01-30]
skip to Prompt 32: "Supervision."
Must be programmed if using either the Remote Access
feature or Direct Wire downloading. Enter the
appropriate device address.
NOTES:
1. This address must also be programmed as an alpha
keypad in the control panel or an AUI (Advanced
User Interface) type device, if a full enhanced graphic
interface to the system is desired and the control
panel supports it. DO NOT connect an actual
keypad (or any other device) assigned to this address.
2. If using a compatible LynxR-I series control (when
available), this address must be set to “1.”
3. This address must be unique from the "Device
Address" entered in Prompt 28.
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. (If the supervision period is changed after
registration, you must re-register the module.)
Press the [space] key to scroll through choices.
32
Supervision
(24 Hours)_
• 24 Hours
• 1 Hour
• US UL Line
(6 Min)
• CN UL Line
Lvl 3 (3 Min)
• US UL Line
(90 Sec)
• CN UL Line
Lvl 4 (90 Sec)
• CN UL Line
Lvl 5 (75 Sec)
• None
Old Alarm Time
33
10 Minutes_
• 30 Day
•10 Minutes
• 15 Minutes
• 30 Minutes
• 1 Hour
• 2 Hours
• 4 Hours
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
• 8 Hours
• 12 Hours
• 24 Hours
UL NOTE: Must be 10 minutes.
3-6
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.