Honeywell 53034 User Manual

Page 1
ONYX®FIRSTVISION
Installation and Operation Manual
Document 53034 10/29/07 Rev:
P/N: 53034:A2 ECN: 07-706
A2
Page 2

Fire Alarm System Limitations

An automatic fire alarm system—typically made up of smoke detec­tors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommenda­tions of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warn­ing against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limita­tions. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visi­ble smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escap­ing gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of­rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connec­tion of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause tempo­rary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly main­tained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily dis­abled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent work­ing order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be sched­uled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
2 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 3

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power
before servicing. The control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or intercon­necting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes.
To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper sys­tem operation verified.
This system meets NFPA requirements for operation at 0°C to 49°C (32°F to 120°F) and at a relative humidity 93% ± 2% RH (noncon­densing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15­27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibil­ity. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, ream­ing, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static­suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and program­ming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

FCC Warning

WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interfer­ence to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™ and NOTIFER Intergrated Systems™ are trademarks, and ONYX®, ONYXWorks®, FlashScan®, UniNet®, VIEW® and NOTIFIER® are registered trademarks of Honeywell. Windows® is a registered trademark of the Microsoft Corporation.
©11/7/07 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Canadian Requirements: This digital apparatus does not
exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regula­tions of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radio­electriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
3FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 4
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments, you can email us.
Please include the following information:
Product name and version number (if applicable)
Manual page number
Your comment
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 5
Table of Contents
Section 1 Introduction..............................................................................................................3
1.1: FIRSTVISION Specifications ...........................................................................................................................3
Table 1.1 F Table 1.2 F
1.2: F
IRSTVISION Descriptions..............................................................................................................................5
1.2.1: Product Overview................................................................................................................................5
Events that F
Compatibility..........................................................................................................................................6
Table 1.3 F
1.2.2: Networking ..........................................................................................................................................7
Figure 1.1 Example F
1.2.3: Ordering Information...........................................................................................................................8
1.3: Agency Approvals .........................................................................................................................................8
NFPA Standards .....................................................................................................................................8
Underwriters Laboratories U.S. Documents ..........................................................................................8
Underwriters Laboratories Canada Documents......................................................................................8
Other......................................................................................................................................................8
1.3.1: Environmental Conditions...................................................................................................................8
1.4: Conventions Used in this Manual..................................................................................................................9
1.4.1: Notes, Cautions, and Warnings ...........................................................................................................9
1.4.2: Procedures ...........................................................................................................................................9
Figure 1.2 Example for Procedure Explanation .....................................................................................9
1.4.3: Referencing Other Manuals.................................................................................................................9
1.5: Software Download Notice............................................................................................................................9
1.6: Related Manuals ............................................................................................................................................9
IRSTVISION Cabinet Specifications ......................................................................................3
IRSTVISION LCD Specifications...........................................................................................4
IRSTVISION Processes and Annunciates ............................................................................5
IRSTVISION Node Compatibility Table ................................................................................6
IRSTVISION Network............................................................................................7
Section 2 FIRSTVISION Installation Instructions ....................................................................11
2.1: Power Sources and Outputs Overview ........................................................................................................11
Table 2.1 Power Supply Required Ranges ...........................................................................................11
2.2: Enclosure Installation ..................................................................................................................................12
Figure 2.1 F Figure 2.2 F
IRSTVISION Dimensions (inches) ......................................................................................13
IRSTVISION Power Wiring Diagram..................................................................................14
2.3: LCD Installation ..........................................................................................................................................14
Section 3 Enabling FIRSTVISION to Monitor Your Building...................................................15
3.1: Process Overview ........................................................................................................................................15
Process Steps to Enable F
3.2: Make Connections to F
3.2.1: What To Connect and How To Make the Connections.....................................................................15
Figure 3.1 F Figure 3.2 F Figure 3.3 F
IRSTVISION USB Keyboard and Mouse Connections.......................................................15
IRSTVISION Standard Keyboard and Mouse Connections ................................................16
IRSTVISION LAN Connector Location..............................................................................16
Figure 3.4 Example NFN Gateway Embedded System Connections ..................................................17
Figure 3.5 Example NFN Gateway PC System Connections...............................................................18
3.3: Turn on Power to F
IRSTVISION ....................................................................................................................19
3.3.1: What Displays After the Initial Power Up of F
3.3.2: What You Should Know about F
3.3.3: What You Should Know about F
Windows Administrator Settings .........................................................................................................19
Screen Saver Settings ...........................................................................................................................19
Monitor Power 19 Screen Saver 20
Figure 3.6 Display Properties - Screen Saver Tab Window.................................................................20
3.4: Set the F
IRSTVISION Clock and Time Zone.................................................................................................21
Figure 3.7 System Clock ......................................................................................................................21
IRSTVISION ..................................................................................................15
IRSTVISION..............................................................................................................15
IRSTVISION...............................................................19
IRSTVISION IP Addresses ..............................................................19
IRSTVISION Windows Settings......................................................19
1FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 6
Table of Contents
Figure 3.8 Date and Time Properties....................................................................................................21
Figure 3.9 Time Zone Tab....................................................................................................................21
3.5: Establish Communication Between Your LAN and F
IRSTVISION ...............................................................22
Figure 3.10 Windows LAN Connection...............................................................................................22
Figure 3.11 Windows LAN Connection Properties..............................................................................22
Figure 3.12 Windows Internet Protocol Properties ..............................................................................23
Figure 3.13 Command Prompt .............................................................................................................23
3.6: Establish Gateway Communication.............................................................................................................23
How To Add a Gateway Using the Configuration Tool.......................................................................24
Figure 3.14 Gateway Configuration .....................................................................................................24
3.7: Copy Your Exported Building Design to F Figure 3.15 F
IRSTVISION USB Connector Locations...........................................................................25
3.7.1: How To Copy Your Exported Building Design to F
IRSTVISION................................................................................25
IRSTVISION.......................................................25
Figure 3.16 XML File and Floorplans Folder ......................................................................................25
3.8: Display Your Building Design on F
3.9: Test Your Building Design on F
IRSTVISION...........................................................................................26
IRSTVISION ................................................................................................27
3.10: Touch Screen Calibration...........................................................................................................................27
3.10.1: How to Calibrate F
IRSTVISION’s Touch Screen ..............................................................................27
Section 4 Operating Basics of FIRSTVISION ........................................................................... 29
4.1: Normal Operation (No Events Being Reported)..........................................................................................29
Figure 4.1 F Figure 4.2 F Figure 4.3 F Figure 4.4 F Figure 4.5 F Figure 4.6 F
4.2: Investigating Gateway Disconnection .........................................................................................................34
4.3: Operation When a Fire Alarm is Received ..................................................................................................35
Figure 4.7 F Figure 4.8 F Figure 4.9 F
4.4: Operation After a Fire Alarm Has Been Cleared.........................................................................................37
4.5: Accessing the Log File.................................................................................................................................38
Figure 4.10 Log File .............................................................................................................................38
IRSTVISION Display Example: No Alarms........................................................................30
IRSTVISION Display Example: Floor Number Button.......................................................30
IRSTVISION Display Example: Building Information .......................................................31
IRSTVISION Display Example: Zoomed Floor Plan ..........................................................32
IRSTVISION Display Example: Moving Through a Zoomed Floor Plan ...........................33
IRSTVISION Display Example: HAZMAT Information ....................................................34
IRSTVISION Display Example: Alarms..............................................................................35
IRSTVISION Display Example: Alarm Zoomed Floor Plan ...............................................36
IRSTVISION Display Example: Event List.........................................................................37
Section 5 The Development of FIRSTVISION .......................................................................... 39
5.1: The Current Situation for a Firefighter ........................................................................................................39
5.2: The Technology of F
5.2.1: Making Commissioning Easier..........................................................................................................39
5.3: Expected Firefighter Interaction with the F
5.3.1: Example Emergency Situations.........................................................................................................40
Fire Scene 1 ..........................................................................................................................................40
Figure 5.1 Fire Scene Scenario Floor Plan Information.......................................................................40
Figure 5.2 Fire Scene Scenario Roof Plan Information........................................................................41
Figure 5.3 Fire Scene Scenario HAZMAT Information.......................................................................41
Figure 5.4 Fire Scene Scenario Building Information..........................................................................42
Fire Scene 2 ..........................................................................................................................................43
Figure 5.5 Example Building Site Plan Information ............................................................................43
Figure 5.6 Example HAZMAT Information ........................................................................................44
Figure 5.7 Example Contact Information .............................................................................................45
2 FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
IRSTVISION..................................................................................................................39
IRSTVISION...............................................................................40
Page 7

Section 1 Introduction

The contents of this manual are important and must be kept in close proximity to the hardware. If building ownership is changed, this manual and all other testing and maintenance information must also be passed to the current owner of the facility. A copy of this manual was shipped with the equipment and is also available from the manufacturer.
WARNING: Improper Installation
!
Improper installation, maintenance, or lack of routine testing could result in system malfunction.
CAUTION: Servicing FIRSTVISION
!
This product can only be serviced by authorized personnel. Only authorized personnel can remove this product’s CPU back-cover or replace parts in this product. Unauthorized servicing personnel performing product services is strictly prohibited and can void your warranty

1.1 FIRSTVISION Specifications

NOTE: ONYX®FIRSTVISION™ is for Ancillary Use Only.

Table 1.1 FIRSTVISION Cabinet Specifications

Part Number FIRSTVISION-ENC
General:
Rough Opening Dimensions 18" W x 17.75" H x 3.5” D
Material Aluminum
Finish Black epoxy powder coat finish, fine texture
Mounting Panel
Enclosure:
Door Dimensions 20" W x 18.5" H x 0.4" D
Material 0.060 Galvaneal
Door Finish Black epoxy powder coat finish, fine texture – Door only
Door Plex shield 0.125 scratch resistant acrylic
Conduit punch outs (2) ½" and (2) ¾" on the top and bottom of the enclosure (8) total
Mounting (6) mounting holes for screw mtg. #10/12
Lock CFE – NOTIFIER® Standard Lock
Magnetic Latch Power Off/Command Latch release
3FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 8
Introduction FIRSTVISION Specifications

Table 1.2 FIRSTVISION LCD Specifications

Part Number FIRSTVISION-LCD
Product 17" Interactive Graphic Display
Display:
Size 17"
Resolution 1280 x 1024, 75 Hz, 32 Bit colors
Surface acoustic wave touchscreen USB TS controller
CPU:
Digital I/O (1) DO – Lock control, (3) DO – Brightness control
ACPI Compliant Not required
Processor Low Power VIA Fanless CPU
Speed 733MHz
Form factor Embedded
Slots NONE REQUIRED
Video Integral
Serial ports (1) RS-232
USB ports TWO
System RAM 512 MB
LAN One 10/100 Base-T interface
Peripherals:
Compact Flash Disk 2GB
Connectors (1) DB9 COM1
Operating System Windows® XP® Embedded
Other:
(1) DIN - KYBD (1) RJ-45 10/100BT (2) USB Ports on the front panel (2) Speakers (2 Watts)
Motherboard Lithium Battery Battery is not field replaceable. Contact Technical Services for information.
DC to DC Converter Fuse Fuse is only replaceable by authorized personnel. Contact Technical Services for
information. Fuse:10A, 250V, SLO BLO, 5x20mm.
4 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 9
FIRSTVISION Descriptions Introduction

1.2 FIRSTVISION Descriptions

1.2.1 Product Overview

FIRSTVISION uses a graphical user interface (GUI) approach to life safety monitoring for your building. The GUI's display method enables an authorized event responder (e.g. firefighter) to view an event in the context of the building's floor layouts. This allows planning of routes and methods for responding to the event.
Before it can be used by an event responder, F
IRSTVISION must be configured with information
about the building into which it is installed. Those configuration tasks are performed with the ONYX® F
IRSTVISION™ Configuration Tool (refer to 53035ONYX® FIRSTVISION
Configuration Tool manual). The Configuration Tool tasks include entering meaningful information about the layout of all floors in the building (drawing background), the locations of all sensing devices that communicate with F
IRSTVISION, building features (such as water supplies),
and hazards (such as flammable or reactive chemicals).
F
IRSTVISION should be installed in the authorized event responder’s preferred building entry
location.
Refer to “The Development of F
IRSTVISION” on page 39 for more information about this product.
Events that FIRSTVISION Processes and Annunciates
FIRSTVISION only supports SLC loop modules and devices. Only device or module events that use formats of LxxDyyy and LxxMyyy (respectively) that are reported by the types of devices listed below; are processed and annunciated by F
Fire Alarms
Supervisory
Medical
Security
NOTE: FIRSTVISION can simultaneously process up to 3000 events (alrms/supervisory/water/..).
IRSTVISION:
5FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 10
Introduction FIRSTVISION Descriptions
Compatibility
NOTE: FIRSTVISION1.5 (and above) must be used with gateway versions 3.x and above.
FIRSTVISION is compatible with the node types listed in the following table.
Table 1.3 FIRSTVISION Node Compatibility Table
NOTI•FIRE•NET™ Node Type
AFP-200 NAM
AFP-300/400 NAM
AFP-1010 SIB-NET
AM2020 SIB-NET
NFS-320 NCM-W/F
NFS-640 NCM-W/F
NFS2-640 NCM-W/F
NFS-3030 NCM-W/F
NFS2-3030 NCM-W/F
Network Board Used
Relative information about existing nodes (its device ID and custom label) can be imported into the Configuration Tool. Refer to the ONYX®F
IRSTVISION Configuration Tool Programming
Manual (P/N: 53035) for more information.
6 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 11
FIRSTVISION Descriptions Introduction

1.2.2 Networking

The following figure illustrates a possible NOTI•FIRE•NET™ network that includes FIRSTVISION. Refer to “Make Connections to F
IRSTVISION” on page 15 for more information.
FIRSTVISION
NFN Gateway PC
Figure 1.1 Example F
Ethernet (TCP/IP)
Network
OR
NFN Network
FACP FACP
FACP
IRSTVISION Network
NFN Gateway
NOTE: If you are connecting FIRSTVISION to an NFN Gateway PC and plan on running the ONYXWorks Workstation software application also, the Workstation must be set to Supervising Station Mode (refer to the Workstation manual).
7FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 12
Introduction Agency Approvals

1.2.3 Ordering Information

Please verify part numbers with your sales representative before and when you are ordering.
Part Number Description
FIRSTVISION-ENC Enclosure
FIRSTVISION-LCD Liquid Crystal Display (LCD)

1.3 Agency Approvals

FIRSTVISION has been designed to comply with standards set forth by the following regulatory agencies. Before proceeding, the installer should be familiar with the following documents:
NFPA Standards
• National Fire Protection Association Standards 72.
• National Electric Code (NFPA 70).
Underwriters Laboratories U.S. Documents
• UL-864 Control Units and Accessories for Fire Alarm Systems.
Underwriters Laboratories Canada Documents
• CAN/ULC-S524-91 Standard for Installation of Fire Alarm Systems.
• CAN/ULC-S527-99 Standard for Control Units for Fire Alarm Systems.
Other
• Requirements of the Local Authority Having Jurisdiction (LAHJ).
WARNING:
!
Improper installation, maintenance, and lack of routine testing could result in system malfunction.
WARNING: Wiring
!
It is recommended that the installer conform to local code requirements when installing all wiring. All power connections must be non-resettable.

1.3.1 Environmental Conditions

FIRSTVISION must be installed in the following environmental conditions:
Temperature range of 0ºC - 50ºC (32ºF - 120ºF).
10-95% humidity non-condensing at 30ºC (86ºF).
8 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 13
Conventions Used in this Manual Introduction

1.4 Conventions Used in this Manual

1.4.1 Notes, Cautions, and Warnings

This manual contains notes, cautions, and warnings to alert the reader as follows:
NOTE: Supplemental information for a topic, such as tips and references.
CAUTION: Summary in bold
!
Information about procedures that could cause programming errors, runtime errors, or equipment damage.
WARNING: Summary in bold
!
Indicates information about procedures that could cause irreversible equipment damage, irreversible loss of programming data or personal injury.

1.4.2 Procedures

Figure 1.2 Example for Procedure Explanation
Example Text: Main Menu select Graphics >Add Floor.
The graphic above is represented in the Example Text. All selections, fields, buttons, and screen titles are spelled (upper/lower case) exactly as they appear on the display.

1.4.3 Referencing Other Manuals

Example: Refer to the ONYX®FIRSTVISION™ Configuration Tool Programming Manual.
Italic text is used to reference a manual by its specific name.

1.5 Software Download Notice

In order to supply the latest features and functionality in fire alarm and life safety technology to our distributors and their customers, NOTIFIER makes frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, NOTIFIER strongly recommends that you visit the Magni-Fire website on a regular basis and download the most current version of software for each product prior to commissioning any system. Contact NOTIFIER Technical Support with any questions about NOTIFIER software and the appropriate version for a specific application.

1.6 Related Manuals

Here are some related hardware and applications documents:
•ONYX®F
IRSTVISION™ Configuration Tool Manual - 53035
9FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 14
Introduction Related Manuals
•ONYX®FIRSTVISION™ Cabinet Installation Instructions PID - 53105
AMPS-24/E Power Supply Manual - 51907
NOTI•FIRE•NET™ Manual (Version 4.0 & Higher) - 51584
NFS-320 Installation/Operation/Programming manuals - 52745/52746/52747
NFS-640 Installation/Operation/Programming manuals - 51332/51334/51333
NFS2-640 Installation/Operation/Programming manuals - 52741/52742/52743
NFS-3030 Installation/Operation/Programming manuals - 51330/51344/51345
NFS2-3030 Installation/Operation/Programming manuals - 52544/52545/52546
AFP-200 Instruction manual - 15511
AFP-300/400 Installation/Operation/Programming manuals - 50253/50260/50259
AM2020/AFP1010 Installation/Operation/Programming manual - 15088
ONYXWorks® NFN GW Embedded - 52306
ONYXWorks® NFN GW PC - 52307
10 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 15

Section 2 FIRSTVISION Installation Instructions

NOTE: You can use this information to install the FIRSTVISION enclosure (“Enclosure Installation”
on page 12) and to make power supply connections to the enclosure’s control board, or you can refer to the ONYX®FIRSTVISION™ Enclosure Installation Instructions (P/N 53105).

2.1 Power Sources and Outputs Overview

Complete all mounting procedures and check all wiring before applying power.
Electrical connections include the following:
• Primary Power Source: +24VDC, delivered through a power supply listed for fire protection services.
• Secondary Power Source: +24VDC, delivered from batteries.

Table 2.1 Power Supply Required Ranges

TYPICAL
Input Voltage 24V
Input Current @24V 3A
WARNING: Power Sources
!
Remove all power sources to equipment while connecting electrical components. Leave the external, main power breaker OFF until installation of the LCD is complete.
NOTE: FIRSTVISION LCD requires +24VDC @3A nominal and supervised battery backup in accordance with local code requirements. It can be powered by any regulated, power limited source that is approved for use with fire protective signaling units by a regulatory agency.
11FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 16
FIRSTVISION Installation Instructions Enclosure Installation

2.2 Enclosure Installation

Refer to “LCD Installation” on page 14 if the enclosure is already installed.
NOTE: You can use this information to install the FIRSTVISION enclosure and to make power supply connections to the enclosure’s control board or you can refer to the ONYX®FIRSTVISION Enclosure Installation Instructions (P/N 53105).
Use the following information as a guideline to accomplish the installation of the F enclosure and prepare the power supply components/connections for the F
IRSTVISION LCD.
IRSTVISION
Perform all installations in accordance with building construction, local code requirements, and/or as described in the manufacturer’s documentation.
Step 1. Mount the F
Step 1a.Prepare a rough opening in the wall at the location F
IRSTVISION enclosure on an inside wall of the building.
IRSTVISION will be mounted
according to the enclosure’s dimensions specified in Figure 2.1 on page 13).
NOTE: The dimensions shown are the exact measurement of the enclosure. Make the enclosure hole slightly larger (approximately 1/8”) than the enclosure’s dimensions for an easier fit.
Step 1b.Remove the enclosure’s knockout(s) that will be used to route your LAN cable and
power supply’s cable through.
Step 1c.Place the enclosure inside of the rough opening (with the LCD hinges on the left).
Step 1d.Attach the enclosure to the wall at the six locations provided using field supplied
fasteners.
NOTE: Make sure the enclosure is level before fastening it to the wall.
Mounting Hole (6 places)
Step 2. Mount the external power supply according to the manufacturer’s instructions.
Step 3. Route the external power supply wiring into the enclosure through one of the available
knockouts, and then connect it to the control board as shown in Figure 2.2 on page 14.
WARNING: Electrical Panel Breaker Lockout Procedures
!
Leave electrical panel breaker lockout safety procedures in place until you are ready to install and connect the FIRSTVISION LCD.
NOTE: Adhere to electrical panel breaker lockout safety procedures.
12 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 17
Enclosure Installation FIRSTVISION Installation Instructions
Step 4. Route the LAN cable into the enclosure through one of the available knockouts.
NOTE: The power supplies for FIRSTVISION and the gateway should use:
- a common ground.
- the same earth ground.
Figure 2.1 F
IRSTVISION Dimensions (inches)
13FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 18
FIRSTVISION Installation Instructions LCD Installation
b
b
a
a
c
c
k
k
o
f
o
L
f
C
L
D
C
D
d
i
s
p
l
a
y
Power Cable from LCD
J1
The FIRSTVISION enclosure is factory assembled and wired to install/connect the LCD.
P1
Enclosure’s Control Board
LCD Power Cable
WARNING: Electrical Connections
!
If power is applied to F FIRSTVISION’s Windows® operating system before turning off the power. See “Make Connections to FIRSTVISION” on page 15 for instructions on using FIRSTVISION like a personal computer, and then follow standard Windows shut-down procedures.

2.3 LCD Installation

Step 1. Install the FIRSTVISION LCD onto the enclosure’s factory installed hinges (LCD hinges on
the left).
Step 2. Connect the LCD’s power cable to the enclosure’s control board as shown in Figure 2.2 on
page 14.
Step 3. Connect the customer supplied LAN cable to the LAN port as shown in Figure 3.3 on
page 16.
Step 4. Swing the LCD closed and fasten it closed by using the 2 factory supplied black pan head
machined screws.
Step 5. Close the LCD’s glass paneled door.
Step 6. Use the factory supplied door key to lock the closed door.
Step 7. Verify the door locks and unlocks with each turn of the key.
Step 8. You are now ready to perform “Enabling F
page 15.
+24VDC/3A
Common GND
Enclosure’s Control Board
From Power Supply

Figure 2.2 FIRSTVISION Power Wiring Diagram

IRSTVISION for testing your electrical connections, you MUST shut down
IRSTVISION to Monitor Your Building” on
14 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 19
Section 3 Enabling FIRSTVISION to Monitor Your
Building

3.1 Process Overview

The procedures documented in the section should be performed after your building’s life safety monitoring system has been customized to F Configuration Tool (refer to ONYX® F for information).
Process Steps to Enable FIRSTVISION
Step 1. "Make Connections to FIRSTVISION".
Step 2. "Turn on Power to F
Step 3. "Establish Communication Between Your LAN and F
Step 4. "Establish Gateway Communication".
Step 5. "Copy Your Exported Building Design to F
Step 6. "Test Your Building Design on F
IRSTVISION".

3.2 Make Connections to FIRSTVISION

All of the procedures in this section require you to operate FIRSTVISION like a personal computer. Because of that operation usage scenario, you MUST connect an external keyboard and a mouse to F
IRSTVISION.
IRSTVISION using the ONYX® FIRSTVISION
IRSTVISION™ Configuration Tool Programming Manual
IRSTVISION".
IRSTVISION".
IRSTVISION".

3.2.1 What To Connect and How To Make the Connections

Step 1. Connect a keyboard and mouse to the either of these connectors.
• USB ports on the front of F port (for the mouse) is ideal for connecting to F
• PS/2 connectors located on the bottom of the LCD (Figure 3.2).
NOTE: You must unlock the front door of FIRSTVISION to gain access to the USB ports.
.
Figure 3.1 FIRSTVISION USB Keyboard and Mouse Connections
NOTE: To gain access to the PS/2 connectors, you must remove the screws holding the LCD
closed and then you must swing the LCD out.
IRSTVISION LCD (recommended). A keyboard with a USB
IRSTVISION (Figure 3.1).
15FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 20
Enabling FIRSTVISION to Monitor Your Building Make Connections to FIRSTVISION
.
Figure 3.2 FIRSTVISION Standard Keyboard and Mouse Connections
WARNING: Connector Damage Possible
!
Do not attempt to close the LCD with the keyboard and mouse connected because their cables will make contact with the enclosure’s wiring tray; possibly damaging the connectors.
Step 2. If not already connected; connect F
supplied CAT-5 ethernet cable to the LAN (Local Area Network) port.
Figure 3.3 F
IRSTVISION LAN Connector Location
IRSTVISION to your IP Network by attaching customer
16 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 21
Make Connections to FIRSTVISION Enabling FIRSTVISION to Monitor Your Building
FIRSTVISION
Three options: * Direct connection using a crossover
Ethernet cable
* Connection using 2 standard CAT-5
Ethernet cables and a UL-listed hub
* Connection to the customer supplied
Ethernet (TCP/IP) Network.
Ethernet (TCP/IP)
Network
NFN Gateway Embedded
NFN Network (v5.0 or later)
NOTE: For all connection details, see ONYXWorks®
NFN Gateway Embedded Installation & Operation Manual- 52306.
FACP FACP
FACP
Figure 3.4 Example NFN Gateway Embedded System Connections
17FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 22
Enabling FIRSTVISION to Monitor Your Building Make Connections to FIRSTVISION
FIRSTVISION
Three options: * Direct connection using a crossover
Ethernet cable
* Connection using 2 standard CAT-5
Ethernet cables and a UL-listed hub
* Connection to the customer supplied
Ethernet (TCP/IP) Network.
Ethernet (TCP/IP)
Network
NOTE: For all connection details, see ONYXWorks®
NFN Gateway PC Installation & Operation Manual- 52307.
Network Card
NFN Gateway PC
NFN Network (v5.0 or later)
TX A
RX A
TX B
RX B
NFN Gateway PC (Fiber Shown)
FACP FACP
FACP
Figure 3.5 Example NFN Gateway PC System Connections
18 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 23
Turn on Power to FIRSTVISION Enabling FIRSTVISION to Monitor Your Building

3.3 Turn on Power to FIRSTVISION

Turn-on the power supply connected to FIRSTVISION. Refer to “FIRSTVISION Installation Instructions” on page 11 for installation information.

3.3.1 What Displays After the Initial Power Up of FIRSTVISION

1. Windows® XP Embedded will start and display.
2. The software application "progress bar" will display and remain displayed until the loading of the software application and its components are complete.
NOTE: Do NOT attempt to stop this loading.
3. After the progress bar disappears; the software application will automatically start because a shortcut to the application has been placed in the product’s Startup folder.
NOTE: Do NOT remove this shortcut.

3.3.2 What You Should Know about FIRSTVISION IP Addresses

Your LAN IP address (setup with Windows Internet Protocol (TCP/IP) Properties) has a default of:
192.168.0.4.
• If it is necessary to change the factory LAN IP address; refer to
Between Your LAN and F
The gateway that F setting of 192.168.0.3.
• If it is necessary to change this factory setting; refer to
on page 23
• If it is necessary to change a gateway’s IP address, refer to the gateway’s respective
installation manual.
IRSTVISION monitors (setup with Add Gateway Connection) has a factory
for information.
IRSTVISION” on page 22 for information.
“Establish Gateway Communication”
“Establish Communication

3.3.3 What You Should Know about FIRSTVISION Windows Settings

Windows Administrator Settings
NOTE: Do NOT change the factory boot setup for FIRSTVISION’s host computer (that is,
administrator is automatically logged in at startup), or add any user accounts.
It is essential that the FIRSTVISION host computer remain configured to automatically log in the administrator account at startup, without asking for a password.
Screen Saver Settings
Monitor Power
A Monitor Power selection should NOT be changed from the factory default settings, which all are set to Never (always on), because any setting will prevent the software application from starting automatically after a power loss.
19FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 24
Enabling FIRSTVISION to Monitor Your Building Turn on Power to FIRSTVISION
Screen Saver
F
IRSTVISION supports Windows Screen Saver settings that extend the display’s life and prevent
screen image burn in. Only Windows screen saver application is supported, do NOT use a third­party screen saver application.
NOTE: A Screen Saver selection has been made at the factory. Those factory settings use a predetermined screen saver image and "Wait" setting of 10 minutes.
F
IRSTVISION’s screen saver will be displayed when its Wait setting is reached only if:
There are no events that F
IRSTVISION processes are being reported to FIRSTVISION.
The gateway connection is present.
If events that F is lost; F screen saver will remain disabled as long as there is an event that F reported. After all the events that F
IRSTVISION processes are being reported to FIRSTVISION or the gateway connection
IRSTVISION’s screen saver will disable and the software application will display. The
IRSTVISION processes being
IRSTVISION processes have been remedied (cleared/restored);
the screen saver will be automatically enabled after its Wait setting is reached.
Windows Screen Saver and Wait settings are made on the Display Properties window (i.e. Screen Saver tab). The Screen saver field options are "None" and "My Picture Slideshow". You can load and use your own screen saver images but they can NOT be of the 3D type.
CAUTION: 3D Type Animation
!
If you choose to use your own Screen-Saver file, do NOT use 3D type animation files because it may NOT disable when an event that FIRSTVISION processes occurred in the monitored network.
Consult Windows information for details about making Display Properties settings.
Figure 3.6 Display Properties - Screen Saver Tab Window
20 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 25
Set the FIRSTVISION Clock and Time Zone Enabling FIRSTVISION to Monitor Your Building

3.4 Set the FIRSTVISION Clock and Time Zone

The FIRSTVISION system clock is set at the factory, based on the factory time zone. Follow these steps to configure the clock for your local time zone:
NOTE: Correct time and date settings ensure times shown on FIRSTVISION display and in event
logs are accurate—crucial information for responding Firefighters.
Step 1. Double click the digital clock on the right side of the Windows taskbar.

Figure 3.7 System Clock

Step 2. Verify the time and date are shown correctly in the the dialogue that appears, and then
click the Time Zone tab.

Figure 3.8 Date and Time Properties

Step 3. Check the box next to “Automatically adjust clock for daylight saving changes.”
Step 4. Select your local time zone from the drop menu.
Step 5. Click OK.

Figure 3.9 Time Zone Tab

21FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 26
Enabling FIRSTVISION to Monitor Your Building Establish Communication Between Your LAN and FIRSTVISION
3.5 Establish Communication Between Your LAN and F
IRSTVISION
NOTE: A factory default IP address setting is set to: 192.168.0.4. If you need to change those
settings, then use the following information.
The following steps are performed using Windows operations on FIRSTVISION.
Step 1. If F
Step 2. Click Start >Control Panel. The Control Panel window displays.
Step 3. Double click on Network Connections. The Network Connections window displays.
Step 4. Right click on Local Area Connections 2 in the Network Connections window and select
Step 5. On the General tab click on "Internet Protocol (TCP/IP)", then click on the Properties
IRSTVISION application is running, shut it down (ESC key on direct connect keyboard).

Figure 3.10 Windows LAN Connection

Properties from the list of choices. The Local Area Connection Properties window displays.
button. The Internet Protocol (TCP/IP) Properties window displays.

Figure 3.11 Windows LAN Connection Properties

22 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 27
Establish Gateway Communication Enabling FIRSTVISION to Monitor Your Building
Step 6. Select the “Use the following IP address” radio button.
The “Obtain an IP address automatically” can NOT be used.
Step 7. Type in your IP address information on the Internet Protocol (TCP/IP) Properties window
(example only shown, the address is dependent on your network).

Figure 3.12 Windows Internet Protocol Properties

Step 8. Confirm that is 255.255.255.0 in the Subnet Mask field to choose the internal network (the
address is dependent on your network).
Step 9. Complete your entry by clicking on OK.
Step 10. Restart Windows. F
F
IRSTVISION and your LAN should be established.
IRSTVISION will automatically start. Communication between
Step 11. Verify the connection by doing either of the following:
• Check the Gateway icon in the upper left corner of the display (no X over icon means connected).
• Ping the gateway:
• Shut down F
IRSTVISION
• Select Start >Command Prompt to display a command prompt window.
• Type in "Ping <Gateway IP Address>". If the response to the Ping is returned from the Gateway, then the connection is established.

Figure 3.13 Command Prompt

Step 12. Close any remaining windows.
Step 13. You should now "Establish Gateway Communication"

3.6 Establish Gateway Communication

NOTE: FIRSTVISION1.5 (and above) must be used with gateway versions 3.x and above.
.
23FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 28
Enabling FIRSTVISION to Monitor Your Building Establish Gateway Communication
It is anticipated that the factory settings for a gateway may probably work for your application and it is recommended you use them, if possible, instead of setting up new settings. If you want to change the factory settings use the following information
NOTE: Your LAN connection must be established before you add a gateway.
How To Add a Gateway Using the Configuration Tool
The gateway can be changed here, but FIRSTVISION can monitor only one gateway.
NOTE: If you change the gateway IP address, you must re-export your building design to XML. See “How to Export Your Building Design for Copying to FIRSTVISION” in ONYX®FIRSTVISION
Configuration Tool Manual - 53035.
NOTE: The factory default Gateway IP address setting is: 192.168.0.3. If you need to change this setting, then use the following information.
Step 1. Start the Configuration Tool.
Step 2. Select Tools > Gateway Configuration.
Step 3. Enter the Gateway IP address.
Step 4. Click OK.

Figure 3.14 Gateway Configuration

Step 5. Close the Configuration Tool.
Step 6. You should now "Copy Your Exported Building Design to F
24 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
IRSTVISION".
Page 29
Copy Your Exported Building Design to FIRSTVISION Enabling FIRSTVISION to Monitor Your Building

3.7 Copy Your Exported Building Design to FIRSTVISION

This copying task can be accomplished using various methods. The copying method will be contingent on your connection to F your building design Site.xml file and Floor plan folder are stored) as part of a TCP/IP network, you can copy your building design to F connector, located inside the locking door, on F
IRSTVISION. With FIRSTVISION and your PC both (i.e. where
IRSTVISION over the network. You can also use a USB
IRSTVISION as the connection point.
Figure 3.15 F
IRSTVISION USB Connector Locations

3.7.1 How To Copy Your Exported Building Design to FIRSTVISION

Step 1. Establish a physical connection between your PC or storage device (i.e. where your
building design Site.xml file and Floorplan folder are stored) and F
Step 2. Use Window Explorer on F
"Floorplans" folder to the following folder on F
NOTE: Overwrite the folder and files, do NOT delete the existing site.xml and Floorplans folder. prior to this step.
IRSTVISION to find, select, and copy the Site.xml file and
IRSTVISION: C:/Facilities Monitoring/FIT.
Figure 3.16 XML File and Floorplans Folder
Step 3. You should now restart F
IRSTVISION and wait until Windows is displayed.
Step 4. You should now peform “Display Your Building Design on F
IRSTVISION.
IRSTVISION” on page 26.
25FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 30
Enabling FIRSTVISION to Monitor Your Building Display Your Building Design on FIRSTVISION

3.8 Display Your Building Design on FIRSTVISION

Step 1. Locate the FIRSTVISION icon displayed on the Desktop.
Step 2. Double click on the icon to load the Site.xml file.
NOTE: An application is loading message will display. It may take some time to load the file depending upon the components of the building (number of floors and icons). If the message is displayed; do NOT attempt to double click the icon again.
Step 3. You should now "Test Your Building Design on F
IRSTVISION".
26 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 31
Test Your Building Design on FIRSTVISION Enabling FIRSTVISION to Monitor Your Building

3.9 Test Your Building Design on FIRSTVISION

It is recommended that you simulate an event that FIRSTVISION processes that will test the interaction between your building design and F are some items to verify that they are functioning correctly:
• Battery-backup system is functioning correctly.
•F
IRSTVISION starts monitoring your building life safety system when started.
• The floor plan background images are correctly displayed on F
• Auto unlock of F received by F
• Activated device icons are shown in their correct locations over the floor plan background on F
IRSTVISION.
IRSTVISION enclosure when an event that FIRSTVISION processes is
IRSTVISION.
IRSTVISION response to that event. The following
IRSTVISION.

3.10 Touch Screen Calibration

FIRSTVISION’s touch screen was calibrated in the factory and you should not have to perform this procedure.
If you have determined that the cursor is not correctly tracking to the position of your finger then you can use the GenCalb function to calibrate the touch screen.

3.10.1 How to Calibrate FIRSTVISION’s Touch Screen

Step 1. Unlock and open the product’s glass paneled door using the factory supplied key.
Step 2. Connect the external keyboard and mouse to the product to the appropriate connectors.
Refer to “What To Connect and How To Make the Connections” on page 15.
Step 3. Press the ESC key on the keyboard to shutdown the software application.
Step 4. Locate and click on the Desktop icon for touchscreen calibration.
Step 5. Follow the displayed instructions to calibrate the touch screen.
Step 6. Restart the software application by clicking on F
Desktop shortcut.
Step 7. Remove the external connected components.
IRSTVISION’s software application
27FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 32
Enabling FIRSTVISION to Monitor Your Building Touch Screen Calibration
28 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 33

Section 4 Operating Basics of FIRSTVISION

Experiment with FIRSTVISION to gain a basic familiarity with its operation. This helps you ensure F
IRSTVISION is set up and configured correctly.

4.1 Normal Operation (No Events Being Reported)

When FIRSTVISION software application is started take note of some of the user interface characteristics, some of the displayed elements are a result of information defined using the Configuration Tool.
The Gateway Connection Icon in the upper left corner of the user interface indicates whether F
IRSTVISION is connected to your gateway (a red X displayed inside the icon means that
F
IRSTVISION is not connected).
WARNING: Gateway Connection Icon with a Red X
!
When you see that the gateway disconnected (red x in icon), FIRSTVISION will not receive events. So it is absolutely necessary to restore connectivity to the gateway to ensure the most accurate and up to date information is being displayed. Refer to “Investigating Gateway Disconnection” on page 34 for more information.
Corresponding to each floor in the building a Floor button (inverted style means it is selected).
The floor chosen as the lowest floor in the Configuration Tool’s Building Layout tree hierarchy is displayed with icons and its floor plan background. Also if applicable displayed on that floor are icons defined for elevators, stairs (Multi-Level icons) and HAZMAT area or sprinkler shutoff (Other icon).
A row of larger miscellaneous buttons across the top; more information about them later in this section.
3:41:05 PM
29FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 34
Operating Basics of FIRSTVISION Normal Operation (No Events Being Reported)

Figure 4.1 FIRSTVISION Display Example: No Alarms

NOTE: Device icons that use a device id’s are displayed on FIRSTVISION only when they
experience an event type that FIRSTVISION processes.
With the front door open; touching a floor number button displays the corresponding floor in the building layout.
3:41:05 PM
Figure 4.2 F
30 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
IRSTVISION Display Example: Floor Number Button
Page 35
Normal Operation (No Events Being Reported) Operating Basics of FIRSTVISION
With the front door open; touching one of the miscellaneous buttons will display an information window or site plan.
3:41:05 PM
Figure 4.3 F
IRSTVISION Display Example: Building Information
31FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 36
Operating Basics of FIRSTVISION Normal Operation (No Events Being Reported)
With the front door open; touching a place on the floor will open a window that displays an enlarged or zoomed view.
3:41:05 PM
Figure 4.4 F
32 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
IRSTVISION Display Example: Zoomed Floor Plan
Page 37
Normal Operation (No Events Being Reported) Operating Basics of FIRSTVISION
With the front door open; touching inside the Zoomed Floor Plan window near the left side, right side, top, or bottom changes the point of reference of the zoomed area. Touching near a corner of the window will navigate your zoomed view in a combined direction, like down and right.
3:41:05 PM
Figure 4.5 F
IRSTVISION Display Example: Moving Through a Zoomed Floor Plan
33FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 38
Operating Basics of FIRSTVISION Investigating Gateway Disconnection
With the front door open; touching an icon will display information about the image.
Figure 4.6 F
IRSTVISION Display Example: HAZMAT Information

4.2 Investigating Gateway Disconnection

The Gateway Connection Icon in the upper left corner of the user interface indicates whether F
IRSTVISION is connected to your gateway (a red X displayed inside the icon means that
F
IRSTVISION is not connected).
When you see that the gateway disconnected (red X in icon), F It is absolutely necessary to restore connectivity to the gateway to ensure the most accurate and up to date information is being displayed. In order to investigate connectivity issues, you need to operate F
Step 1. Follow the steps in “Make Connections to F
Step 2. Shut down the F
IRSTVISION like a personal computer. To do this:
IRSTVISION” on page 15 to attach a keyboard
and mouse to F
IRSTVISION.
IRSTVISION software application by pressing the Esc key.
See “Establish Communication Between Your LAN and F
Gateway Communication” on page 23 for information about gateway connectivity.
34 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
IRSTVISION will not receive events.
IRSTVISION” on page 22 and “Establish
Page 39
Operation When a Fire Alarm is Received Operating Basics of FIRSTVISION

4.3 Operation When a Fire Alarm is Received

When FIRSTVISION receives a fire alarm from a panel it is monitoring, its front door unlocks and a display change in the floor number button takes place indicating which floor the fire alarm is on. If multiple fire alarms have been reported, the device icons on that floor blink in a sequence that indicates the order in which they registered trouble.
3:41:05 PM
Figure 4.7 F
IRSTVISION Display Example: Alarms
35FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 40
Operating Basics of FIRSTVISION Operation When a Fire Alarm is Received
With the front door open; touching the display near the device icons being displayed will zoom to the area.
3:41:05 PM
Figure 4.8 F
IRSTVISION Display Example: Alarm Zoomed Floor Plan
36 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 41
Operation After a Fire Alarm Has Been Cleared Operating Basics of FIRSTVISION
With the front door open; touching the Event List button will display a listing of the current alarms.
3:41:05 PM
Figure 4.9 F
IRSTVISION Display Example: Event List

4.4 Operation After a Fire Alarm Has Been Cleared

If fire alarm was the only event being reported; then after a fire alarm has been cleared from the panel that F
The fire alarm is cleared from the Event List.
Any flashing fire alarm related device icons will no longer be displayed.
If a screen saver is being used; the screen saver will automatically start when the screen saver’s
•F
NOTE: Remember to go to FIRSTVISION after a fire alarm has been cleared from the monitored network because FIRSTVISION’s door will need to be latched closed.
IRSTVISION monitors; the following takes place on FIRSTVISION:
Wait setting is reached.
IRSTVISION returns to normal monitoring operation.
37FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 42
Operating Basics of FIRSTVISION Accessing the Log File

4.5 Accessing the Log File

FIRSTVISION maintains a log of the most recent 1,000 events from attached devices. Each log entry contains an event number, a time and date stamp, information identifying the device involved, and the state of the device during the event. How you access the log file depends on your connection to F
IRSTVISION.
With F
IRSTVISION and your PC connected over a TCP/IP network, you can browse across the
network to C:/Facilities Monitoring/FIT/Event-log.txt on the F
IRSTVISION machine.
You can also use a USB connector, located inside the locking door, on F connection point. To access the log file by using F
IRSTVISION like a personal computer:
IRSTVISION as the
Step 1. Connect a USB mouse and keyboard. Refer to “What To Connect and How To Make the
Connections” on page 15.
Step 2. Hold down the Ctrl key, and press the Esc key to open the Windows Start Menu.
Step 3. Use Window Explorer to browse to the file C:/Facilities Monitoring/FIT/Event-log.txt.

Figure 4.10 Log File

38 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 43

Section 5 The Development of FIRSTVISION

5.1 The Current Situation for a Firefighter

When Firefighters arrive on the scene of a building fire emergency, they must gather information to accurately assess the situation and plan their attack on the fire. Prompt assessment is essential—the sooner the seat of the fire and its progression are identified, the sooner the attack on the fire can be planned and launched. With speed and accuracy of response comes a reduction in loss of property and life.
Current fire annunciation panels used in commercial buildings provide the primary source of information for Firefighters arriving on the scene. This is particularly true at night when building occupants may not be available to report their observations. However, current alarm panels provide sensor/detector information in formats that are not always easily interpreted. Typically, these panels present activated smoke/heat detectors as items in a scrolling alphanumeric Event List. Each activated smoke or heat detector is described only by an alphanumeric location code and an activation time.

5.2 The Technology of FIRSTVISION

FIRSTVISION is simple and intuitive because it cannot be assumed that the Firefighters have either computer experience or training in its use. It enables the Firefighter to reduce the time to understand the situation.
F
IRSTVISION has an interactive display that orients Firefighters to the building using floor by floor
layouts. It decreases situation assessment time by showing the location of water supplies, evacuation routes, access routes and points, fire barriers, shutoffs for gas and power. F also shows structural hazards.
During installation F sensors, hazards, water supplies, and other important devices and information about building configuration. F building when responding to an event.
IRSTVISION is set up with the layouts for each floor that show the locations of
IRSTVISION is installed in a location where Firefighters are expected to enter the

5.2.1 Making Commissioning Easier

To customize FIRSTVISION for a building—making it possible to pinpoint fires and their progress, to see where important building features and hazardous materials are located, and so on—the building manager must commission the system with building-specific data.
Data to drive F of building floor and site plans from CAD files, sensor data from building fire panels, location data for objects such as standpipes, and textual data associated with hazardous materials documentation. One of Honeywell’s goals was to design a software application that gave the building manager the flexibility to pull in the best data available from different but existing sources. The resulting Configuration Tool provides an interface into which building managers enter or add fire detection information that customizes F
IRSTVISION display comes from a wide range of sources. Sources include drawings
IRSTVISION to the building.
IRSTVISION
39FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 44
The Development of FIRSTVISION Expected Firefighter Interaction with the FIRSTVISION

5.3 Expected Firefighter Interaction with the FIRSTVISION

FIRSTVISION supports tasks that help Firefighters determine whether a fire is occurring. To illustrate how F
"Fire Scene 2", provide a fire scene scenario and a description of the how Firefighters might use
F
IRSTVISION in that fire scene emergency.

5.3.1 Example Emergency Situations

Fire Scene 1
A fire has started in a second floor office near the front (above the lobby) of a building with a two­level roof. That is, part of the building has three floors above ground and the other part only two. The office that contains the fire is directly under the roof on the shorter side of the building. The building roof is reinforced with high-tension steel cable.
The Fire Department arrives at the building in less than five minutes after the department receives the alarm. Possible Firefighter responses to this fire scene are described in the following information.
IRSTVISION helps the Firefighter, example emergency situations, "Fire Scene 1" and
0 seconds
0 seconds
5 seconds
3:41:05 PM
1. The enclosure unlocks and the touch screen displays the floor on which the alarm activated.
2. The Incident Commander enters the building at the main entrance, goes to F and opens the enclosure to view the screen.
3. The Commander: – Verifies that the address is for the building that sent the alarm. (as shown in the
example in Figure 5.1)
– Sees the floors where the detector activations have occurred.
IRSTVISION
Figure 5.1 Fire Scene Scenario Floor Plan Information
40 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 45
Expected Firefighter Interaction with the FIRSTVISION The Development of FIRSTVISION
10
seconds
3:41:05 PM
4. After verifying the building and seeing fire location, the Commander radios firefighting team. As he calls, he continues observation: – Checks layouts of other floors and the roof (as shown in the example in Figure 5.2) to
be sure the fire is contained on only those levels.
– Checks which detector(s) is activated. If multiple detectors are activated he can
determine the progression of the fire by interpreting the blinking rate of the detectors and base his assessment of the situation on that displayed information.
– Checks for presence of hazardous materials near the fire on its respective floor. (as
shown in the example in Figure 5.3)
– Checks for the location of elevators, stairways, water supplies, and entry and exit
routes. Note: Notice the Caution on this background. It was added when the background was developed in the graphics software application. It was not added with the Annotation because an Annotation can only be added to a Building Site Plan.
Caution: Tensioned Concrete Roof
Figure 5.2 Fire Scene Scenario Roof Plan Information
Figure 5.3 Fire Scene Scenario HAZMAT Information
41FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 46
The Development of FIRSTVISION Expected Firefighter Interaction with the FIRSTVISION
20
seconds
5. The Commander begins directing the team how to attack the fire: where to enter the
building, how to approach the fire area, where to get water, how to vent the fire.
6. The Commander notes that no windows have blown out. Since the room with the fire is
directly under the roof, it seems best to vent the smoke through the roof. He touches the Building Information button to be sure there are no structural details that could cause problems. (as shown in the example in Figure 5.4) Here, he sees that the roof is tensioned concrete and tells the team that they will have to knock out a window from the outside of the building for venting.
Figure 5.4 Fire Scene Scenario Building Information
30-60
seconds
42 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
7. The Incident Commander has gathered the data required to plan the attack and relayed
the information to the team. Within two minutes of arrival, the team is containing and putting out the fire.
Page 47
Expected Firefighter Interaction with the FIRSTVISION The Development of FIRSTVISION
Fire Scene 2
In this scenario, the fire is near the front of the building and the main entrance drive, so trucks can be positioned easily. If the fire occurred in a back corner or the far side of the building, the Incident Commander would use the Building Site plan to see safe routes for driving the trucks closer to the fire (as shown in the example in Figure 5.5).
Figure 5.5 Example Building Site Plan Information
43FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 48
The Development of FIRSTVISION Expected Firefighter Interaction with the FIRSTVISION
If hazardous materials were stored near the fire, the Commander would touch the Hazard icon to see what the materials were and how to handle fire in the area (as shown in the example in Figure 5.6).
Figure 5.6 Example HAZMAT Information
44 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 49
Expected Firefighter Interaction with the FIRSTVISION The Development of FIRSTVISION
If the materials were unfamiliar, the Commander could touch the Contact button to see the on call number for the State Hazardous Material expert (as shown in the example in Figure 5.7). That expert would advise the team of dangers, or come personally to the scene.
Figure 5.7 Example Contact Information
45FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 50
The Development of FIRSTVISION Expected Firefighter Interaction with the FIRSTVISION
46 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 51
B
Building Design
Copy to Terminal
25
C
Commissioning 39 Computer Specifications
3, 4
D
Display Properties
power
19
F
FFD Node Compatibility Table 6
L
LAN 16
M
manual conventions 9 manuals
related
9
Monitor Power
19

Index

N
Node Compatibility 6
S
Specifications 3
Touchscreen, PC
3, 4
T
Test
Building Design
Touchscreen Specifications
27
W
Windows Screen Saver 20
3, 4
1FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 52
Index
2 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 53
Limited Warranty
Honeywell International Inc. warrants products manufactured by
it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of Honeywell International Inc. is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. Honeywell International Inc. does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than Honeywell International Inc. or as expressly authorized by Honeywell International Inc. in writing, or is serviced by anyone other than Honeywell International Inc. or its authorized distributors. This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products. Honeywell International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Honeywell International Inc., is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE HONEYWELL INTERNATIONAL INC.’S PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.
3FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Page 54
World Headquarters 12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118
www.notifier.com
Loading...