Honeywell 53034 User Manual

ONYX®FIRSTVISION
Installation and Operation Manual
Document 53034 10/29/07 Rev:
P/N: 53034:A2 ECN: 07-706
A2

Fire Alarm System Limitations

An automatic fire alarm system—typically made up of smoke detec­tors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommenda­tions of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warn­ing against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limita­tions. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visi­ble smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escap­ing gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of­rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connec­tion of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause tempo­rary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly main­tained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily dis­abled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent work­ing order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be sched­uled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
2 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power
before servicing. The control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or intercon­necting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes.
To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper sys­tem operation verified.
This system meets NFPA requirements for operation at 0°C to 49°C (32°F to 120°F) and at a relative humidity 93% ± 2% RH (noncon­densing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15­27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibil­ity. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, ream­ing, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static­suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and program­ming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

FCC Warning

WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interfer­ence to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™ and NOTIFER Intergrated Systems™ are trademarks, and ONYX®, ONYXWorks®, FlashScan®, UniNet®, VIEW® and NOTIFIER® are registered trademarks of Honeywell. Windows® is a registered trademark of the Microsoft Corporation.
©11/7/07 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Canadian Requirements: This digital apparatus does not
exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regula­tions of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radio­electriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
3FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments, you can email us.
Please include the following information:
Product name and version number (if applicable)
Manual page number
Your comment
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Table of Contents
Section 1 Introduction..............................................................................................................3
1.1: FIRSTVISION Specifications ...........................................................................................................................3
Table 1.1 F Table 1.2 F
1.2: F
IRSTVISION Descriptions..............................................................................................................................5
1.2.1: Product Overview................................................................................................................................5
Events that F
Compatibility..........................................................................................................................................6
Table 1.3 F
1.2.2: Networking ..........................................................................................................................................7
Figure 1.1 Example F
1.2.3: Ordering Information...........................................................................................................................8
1.3: Agency Approvals .........................................................................................................................................8
NFPA Standards .....................................................................................................................................8
Underwriters Laboratories U.S. Documents ..........................................................................................8
Underwriters Laboratories Canada Documents......................................................................................8
Other......................................................................................................................................................8
1.3.1: Environmental Conditions...................................................................................................................8
1.4: Conventions Used in this Manual..................................................................................................................9
1.4.1: Notes, Cautions, and Warnings ...........................................................................................................9
1.4.2: Procedures ...........................................................................................................................................9
Figure 1.2 Example for Procedure Explanation .....................................................................................9
1.4.3: Referencing Other Manuals.................................................................................................................9
1.5: Software Download Notice............................................................................................................................9
1.6: Related Manuals ............................................................................................................................................9
IRSTVISION Cabinet Specifications ......................................................................................3
IRSTVISION LCD Specifications...........................................................................................4
IRSTVISION Processes and Annunciates ............................................................................5
IRSTVISION Node Compatibility Table ................................................................................6
IRSTVISION Network............................................................................................7
Section 2 FIRSTVISION Installation Instructions ....................................................................11
2.1: Power Sources and Outputs Overview ........................................................................................................11
Table 2.1 Power Supply Required Ranges ...........................................................................................11
2.2: Enclosure Installation ..................................................................................................................................12
Figure 2.1 F Figure 2.2 F
IRSTVISION Dimensions (inches) ......................................................................................13
IRSTVISION Power Wiring Diagram..................................................................................14
2.3: LCD Installation ..........................................................................................................................................14
Section 3 Enabling FIRSTVISION to Monitor Your Building...................................................15
3.1: Process Overview ........................................................................................................................................15
Process Steps to Enable F
3.2: Make Connections to F
3.2.1: What To Connect and How To Make the Connections.....................................................................15
Figure 3.1 F Figure 3.2 F Figure 3.3 F
IRSTVISION USB Keyboard and Mouse Connections.......................................................15
IRSTVISION Standard Keyboard and Mouse Connections ................................................16
IRSTVISION LAN Connector Location..............................................................................16
Figure 3.4 Example NFN Gateway Embedded System Connections ..................................................17
Figure 3.5 Example NFN Gateway PC System Connections...............................................................18
3.3: Turn on Power to F
IRSTVISION ....................................................................................................................19
3.3.1: What Displays After the Initial Power Up of F
3.3.2: What You Should Know about F
3.3.3: What You Should Know about F
Windows Administrator Settings .........................................................................................................19
Screen Saver Settings ...........................................................................................................................19
Monitor Power 19 Screen Saver 20
Figure 3.6 Display Properties - Screen Saver Tab Window.................................................................20
3.4: Set the F
IRSTVISION Clock and Time Zone.................................................................................................21
Figure 3.7 System Clock ......................................................................................................................21
IRSTVISION ..................................................................................................15
IRSTVISION..............................................................................................................15
IRSTVISION...............................................................19
IRSTVISION IP Addresses ..............................................................19
IRSTVISION Windows Settings......................................................19
1FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Table of Contents
Figure 3.8 Date and Time Properties....................................................................................................21
Figure 3.9 Time Zone Tab....................................................................................................................21
3.5: Establish Communication Between Your LAN and F
IRSTVISION ...............................................................22
Figure 3.10 Windows LAN Connection...............................................................................................22
Figure 3.11 Windows LAN Connection Properties..............................................................................22
Figure 3.12 Windows Internet Protocol Properties ..............................................................................23
Figure 3.13 Command Prompt .............................................................................................................23
3.6: Establish Gateway Communication.............................................................................................................23
How To Add a Gateway Using the Configuration Tool.......................................................................24
Figure 3.14 Gateway Configuration .....................................................................................................24
3.7: Copy Your Exported Building Design to F Figure 3.15 F
IRSTVISION USB Connector Locations...........................................................................25
3.7.1: How To Copy Your Exported Building Design to F
IRSTVISION................................................................................25
IRSTVISION.......................................................25
Figure 3.16 XML File and Floorplans Folder ......................................................................................25
3.8: Display Your Building Design on F
3.9: Test Your Building Design on F
IRSTVISION...........................................................................................26
IRSTVISION ................................................................................................27
3.10: Touch Screen Calibration...........................................................................................................................27
3.10.1: How to Calibrate F
IRSTVISION’s Touch Screen ..............................................................................27
Section 4 Operating Basics of FIRSTVISION ........................................................................... 29
4.1: Normal Operation (No Events Being Reported)..........................................................................................29
Figure 4.1 F Figure 4.2 F Figure 4.3 F Figure 4.4 F Figure 4.5 F Figure 4.6 F
4.2: Investigating Gateway Disconnection .........................................................................................................34
4.3: Operation When a Fire Alarm is Received ..................................................................................................35
Figure 4.7 F Figure 4.8 F Figure 4.9 F
4.4: Operation After a Fire Alarm Has Been Cleared.........................................................................................37
4.5: Accessing the Log File.................................................................................................................................38
Figure 4.10 Log File .............................................................................................................................38
IRSTVISION Display Example: No Alarms........................................................................30
IRSTVISION Display Example: Floor Number Button.......................................................30
IRSTVISION Display Example: Building Information .......................................................31
IRSTVISION Display Example: Zoomed Floor Plan ..........................................................32
IRSTVISION Display Example: Moving Through a Zoomed Floor Plan ...........................33
IRSTVISION Display Example: HAZMAT Information ....................................................34
IRSTVISION Display Example: Alarms..............................................................................35
IRSTVISION Display Example: Alarm Zoomed Floor Plan ...............................................36
IRSTVISION Display Example: Event List.........................................................................37
Section 5 The Development of FIRSTVISION .......................................................................... 39
5.1: The Current Situation for a Firefighter ........................................................................................................39
5.2: The Technology of F
5.2.1: Making Commissioning Easier..........................................................................................................39
5.3: Expected Firefighter Interaction with the F
5.3.1: Example Emergency Situations.........................................................................................................40
Fire Scene 1 ..........................................................................................................................................40
Figure 5.1 Fire Scene Scenario Floor Plan Information.......................................................................40
Figure 5.2 Fire Scene Scenario Roof Plan Information........................................................................41
Figure 5.3 Fire Scene Scenario HAZMAT Information.......................................................................41
Figure 5.4 Fire Scene Scenario Building Information..........................................................................42
Fire Scene 2 ..........................................................................................................................................43
Figure 5.5 Example Building Site Plan Information ............................................................................43
Figure 5.6 Example HAZMAT Information ........................................................................................44
Figure 5.7 Example Contact Information .............................................................................................45
2 FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
IRSTVISION..................................................................................................................39
IRSTVISION...............................................................................40

Section 1 Introduction

The contents of this manual are important and must be kept in close proximity to the hardware. If building ownership is changed, this manual and all other testing and maintenance information must also be passed to the current owner of the facility. A copy of this manual was shipped with the equipment and is also available from the manufacturer.
WARNING: Improper Installation
!
Improper installation, maintenance, or lack of routine testing could result in system malfunction.
CAUTION: Servicing FIRSTVISION
!
This product can only be serviced by authorized personnel. Only authorized personnel can remove this product’s CPU back-cover or replace parts in this product. Unauthorized servicing personnel performing product services is strictly prohibited and can void your warranty

1.1 FIRSTVISION Specifications

NOTE: ONYX®FIRSTVISION™ is for Ancillary Use Only.

Table 1.1 FIRSTVISION Cabinet Specifications

Part Number FIRSTVISION-ENC
General:
Rough Opening Dimensions 18" W x 17.75" H x 3.5” D
Material Aluminum
Finish Black epoxy powder coat finish, fine texture
Mounting Panel
Enclosure:
Door Dimensions 20" W x 18.5" H x 0.4" D
Material 0.060 Galvaneal
Door Finish Black epoxy powder coat finish, fine texture – Door only
Door Plex shield 0.125 scratch resistant acrylic
Conduit punch outs (2) ½" and (2) ¾" on the top and bottom of the enclosure (8) total
Mounting (6) mounting holes for screw mtg. #10/12
Lock CFE – NOTIFIER® Standard Lock
Magnetic Latch Power Off/Command Latch release
3FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Introduction FIRSTVISION Specifications

Table 1.2 FIRSTVISION LCD Specifications

Part Number FIRSTVISION-LCD
Product 17" Interactive Graphic Display
Display:
Size 17"
Resolution 1280 x 1024, 75 Hz, 32 Bit colors
Surface acoustic wave touchscreen USB TS controller
CPU:
Digital I/O (1) DO – Lock control, (3) DO – Brightness control
ACPI Compliant Not required
Processor Low Power VIA Fanless CPU
Speed 733MHz
Form factor Embedded
Slots NONE REQUIRED
Video Integral
Serial ports (1) RS-232
USB ports TWO
System RAM 512 MB
LAN One 10/100 Base-T interface
Peripherals:
Compact Flash Disk 2GB
Connectors (1) DB9 COM1
Operating System Windows® XP® Embedded
Other:
(1) DIN - KYBD (1) RJ-45 10/100BT (2) USB Ports on the front panel (2) Speakers (2 Watts)
Motherboard Lithium Battery Battery is not field replaceable. Contact Technical Services for information.
DC to DC Converter Fuse Fuse is only replaceable by authorized personnel. Contact Technical Services for
information. Fuse:10A, 250V, SLO BLO, 5x20mm.
4 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
FIRSTVISION Descriptions Introduction

1.2 FIRSTVISION Descriptions

1.2.1 Product Overview

FIRSTVISION uses a graphical user interface (GUI) approach to life safety monitoring for your building. The GUI's display method enables an authorized event responder (e.g. firefighter) to view an event in the context of the building's floor layouts. This allows planning of routes and methods for responding to the event.
Before it can be used by an event responder, F
IRSTVISION must be configured with information
about the building into which it is installed. Those configuration tasks are performed with the ONYX® F
IRSTVISION™ Configuration Tool (refer to 53035ONYX® FIRSTVISION
Configuration Tool manual). The Configuration Tool tasks include entering meaningful information about the layout of all floors in the building (drawing background), the locations of all sensing devices that communicate with F
IRSTVISION, building features (such as water supplies),
and hazards (such as flammable or reactive chemicals).
F
IRSTVISION should be installed in the authorized event responder’s preferred building entry
location.
Refer to “The Development of F
IRSTVISION” on page 39 for more information about this product.
Events that FIRSTVISION Processes and Annunciates
FIRSTVISION only supports SLC loop modules and devices. Only device or module events that use formats of LxxDyyy and LxxMyyy (respectively) that are reported by the types of devices listed below; are processed and annunciated by F
Fire Alarms
Supervisory
Medical
Security
NOTE: FIRSTVISION can simultaneously process up to 3000 events (alrms/supervisory/water/..).
IRSTVISION:
5FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Introduction FIRSTVISION Descriptions
Compatibility
NOTE: FIRSTVISION1.5 (and above) must be used with gateway versions 3.x and above.
FIRSTVISION is compatible with the node types listed in the following table.
Table 1.3 FIRSTVISION Node Compatibility Table
NOTI•FIRE•NET™ Node Type
AFP-200 NAM
AFP-300/400 NAM
AFP-1010 SIB-NET
AM2020 SIB-NET
NFS-320 NCM-W/F
NFS-640 NCM-W/F
NFS2-640 NCM-W/F
NFS-3030 NCM-W/F
NFS2-3030 NCM-W/F
Network Board Used
Relative information about existing nodes (its device ID and custom label) can be imported into the Configuration Tool. Refer to the ONYX®F
IRSTVISION Configuration Tool Programming
Manual (P/N: 53035) for more information.
6 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
FIRSTVISION Descriptions Introduction

1.2.2 Networking

The following figure illustrates a possible NOTI•FIRE•NET™ network that includes FIRSTVISION. Refer to “Make Connections to F
IRSTVISION” on page 15 for more information.
FIRSTVISION
NFN Gateway PC
Figure 1.1 Example F
Ethernet (TCP/IP)
Network
OR
NFN Network
FACP FACP
FACP
IRSTVISION Network
NFN Gateway
NOTE: If you are connecting FIRSTVISION to an NFN Gateway PC and plan on running the ONYXWorks Workstation software application also, the Workstation must be set to Supervising Station Mode (refer to the Workstation manual).
7FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Introduction Agency Approvals

1.2.3 Ordering Information

Please verify part numbers with your sales representative before and when you are ordering.
Part Number Description
FIRSTVISION-ENC Enclosure
FIRSTVISION-LCD Liquid Crystal Display (LCD)

1.3 Agency Approvals

FIRSTVISION has been designed to comply with standards set forth by the following regulatory agencies. Before proceeding, the installer should be familiar with the following documents:
NFPA Standards
• National Fire Protection Association Standards 72.
• National Electric Code (NFPA 70).
Underwriters Laboratories U.S. Documents
• UL-864 Control Units and Accessories for Fire Alarm Systems.
Underwriters Laboratories Canada Documents
• CAN/ULC-S524-91 Standard for Installation of Fire Alarm Systems.
• CAN/ULC-S527-99 Standard for Control Units for Fire Alarm Systems.
Other
• Requirements of the Local Authority Having Jurisdiction (LAHJ).
WARNING:
!
Improper installation, maintenance, and lack of routine testing could result in system malfunction.
WARNING: Wiring
!
It is recommended that the installer conform to local code requirements when installing all wiring. All power connections must be non-resettable.

1.3.1 Environmental Conditions

FIRSTVISION must be installed in the following environmental conditions:
Temperature range of 0ºC - 50ºC (32ºF - 120ºF).
10-95% humidity non-condensing at 30ºC (86ºF).
8 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Conventions Used in this Manual Introduction

1.4 Conventions Used in this Manual

1.4.1 Notes, Cautions, and Warnings

This manual contains notes, cautions, and warnings to alert the reader as follows:
NOTE: Supplemental information for a topic, such as tips and references.
CAUTION: Summary in bold
!
Information about procedures that could cause programming errors, runtime errors, or equipment damage.
WARNING: Summary in bold
!
Indicates information about procedures that could cause irreversible equipment damage, irreversible loss of programming data or personal injury.

1.4.2 Procedures

Figure 1.2 Example for Procedure Explanation
Example Text: Main Menu select Graphics >Add Floor.
The graphic above is represented in the Example Text. All selections, fields, buttons, and screen titles are spelled (upper/lower case) exactly as they appear on the display.

1.4.3 Referencing Other Manuals

Example: Refer to the ONYX®FIRSTVISION™ Configuration Tool Programming Manual.
Italic text is used to reference a manual by its specific name.

1.5 Software Download Notice

In order to supply the latest features and functionality in fire alarm and life safety technology to our distributors and their customers, NOTIFIER makes frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, NOTIFIER strongly recommends that you visit the Magni-Fire website on a regular basis and download the most current version of software for each product prior to commissioning any system. Contact NOTIFIER Technical Support with any questions about NOTIFIER software and the appropriate version for a specific application.

1.6 Related Manuals

Here are some related hardware and applications documents:
•ONYX®F
IRSTVISION™ Configuration Tool Manual - 53035
9FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Introduction Related Manuals
•ONYX®FIRSTVISION™ Cabinet Installation Instructions PID - 53105
AMPS-24/E Power Supply Manual - 51907
NOTI•FIRE•NET™ Manual (Version 4.0 & Higher) - 51584
NFS-320 Installation/Operation/Programming manuals - 52745/52746/52747
NFS-640 Installation/Operation/Programming manuals - 51332/51334/51333
NFS2-640 Installation/Operation/Programming manuals - 52741/52742/52743
NFS-3030 Installation/Operation/Programming manuals - 51330/51344/51345
NFS2-3030 Installation/Operation/Programming manuals - 52544/52545/52546
AFP-200 Instruction manual - 15511
AFP-300/400 Installation/Operation/Programming manuals - 50253/50260/50259
AM2020/AFP1010 Installation/Operation/Programming manual - 15088
ONYXWorks® NFN GW Embedded - 52306
ONYXWorks® NFN GW PC - 52307
10 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07

Section 2 FIRSTVISION Installation Instructions

NOTE: You can use this information to install the FIRSTVISION enclosure (“Enclosure Installation”
on page 12) and to make power supply connections to the enclosure’s control board, or you can refer to the ONYX®FIRSTVISION™ Enclosure Installation Instructions (P/N 53105).

2.1 Power Sources and Outputs Overview

Complete all mounting procedures and check all wiring before applying power.
Electrical connections include the following:
• Primary Power Source: +24VDC, delivered through a power supply listed for fire protection services.
• Secondary Power Source: +24VDC, delivered from batteries.

Table 2.1 Power Supply Required Ranges

TYPICAL
Input Voltage 24V
Input Current @24V 3A
WARNING: Power Sources
!
Remove all power sources to equipment while connecting electrical components. Leave the external, main power breaker OFF until installation of the LCD is complete.
NOTE: FIRSTVISION LCD requires +24VDC @3A nominal and supervised battery backup in accordance with local code requirements. It can be powered by any regulated, power limited source that is approved for use with fire protective signaling units by a regulatory agency.
11FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
FIRSTVISION Installation Instructions Enclosure Installation

2.2 Enclosure Installation

Refer to “LCD Installation” on page 14 if the enclosure is already installed.
NOTE: You can use this information to install the FIRSTVISION enclosure and to make power supply connections to the enclosure’s control board or you can refer to the ONYX®FIRSTVISION Enclosure Installation Instructions (P/N 53105).
Use the following information as a guideline to accomplish the installation of the F enclosure and prepare the power supply components/connections for the F
IRSTVISION LCD.
IRSTVISION
Perform all installations in accordance with building construction, local code requirements, and/or as described in the manufacturer’s documentation.
Step 1. Mount the F
Step 1a.Prepare a rough opening in the wall at the location F
IRSTVISION enclosure on an inside wall of the building.
IRSTVISION will be mounted
according to the enclosure’s dimensions specified in Figure 2.1 on page 13).
NOTE: The dimensions shown are the exact measurement of the enclosure. Make the enclosure hole slightly larger (approximately 1/8”) than the enclosure’s dimensions for an easier fit.
Step 1b.Remove the enclosure’s knockout(s) that will be used to route your LAN cable and
power supply’s cable through.
Step 1c.Place the enclosure inside of the rough opening (with the LCD hinges on the left).
Step 1d.Attach the enclosure to the wall at the six locations provided using field supplied
fasteners.
NOTE: Make sure the enclosure is level before fastening it to the wall.
Mounting Hole (6 places)
Step 2. Mount the external power supply according to the manufacturer’s instructions.
Step 3. Route the external power supply wiring into the enclosure through one of the available
knockouts, and then connect it to the control board as shown in Figure 2.2 on page 14.
WARNING: Electrical Panel Breaker Lockout Procedures
!
Leave electrical panel breaker lockout safety procedures in place until you are ready to install and connect the FIRSTVISION LCD.
NOTE: Adhere to electrical panel breaker lockout safety procedures.
12 FIRSTVISION Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Enclosure Installation FIRSTVISION Installation Instructions
Step 4. Route the LAN cable into the enclosure through one of the available knockouts.
NOTE: The power supplies for FIRSTVISION and the gateway should use:
- a common ground.
- the same earth ground.
Figure 2.1 F
IRSTVISION Dimensions (inches)
13FIRSTVISION™ Installation and Operation Manual - P/N: 53034:Rev: A2 10/29/07
Loading...
+ 37 hidden pages