For Use With Control/Communicators Supporting V-Plex® Loop Devices
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The ADEMCO 4297 V-Plex® loop extender module is an
accessory for use with Ademco control panels that support
V-Plex (polling loop) devices. The 4297 module receives
signals from the control panel via its "input" loop, and then
re-transmits boosted copies of these signals via its
"extension" loop.
●
The 4297 draws power for its internal circuitry and its
extension loop from a supplementary power supply such as
the control panel’s auxiliary power output.
Also, the 4297 isolates open and short circuit faults
occurring on its extension loop from its input
loop. These characteristics allow the 4297 module to be
used to extend the control panel's polling loop, to provide
additional polling loop current, and to provideelectrically
isolated branch loops.
●
The 4297 module is fully supervised and causes the control
panel to trigger supervision fault indications for devices
wired to the extension loop when operating power to the
module fails, or when an open or short circuit occurs on the
extension loop. Refer to the control panel's installation
instructions for the type of supervision fault indication
provided.
Important Notes:
The 4297 cannot be used to increase the number of
*
polling loop zones supported by the control panel.
The 4297 is not designed to be used in a Class A
*
wiring configuration.
MOUNTING
For UL burglary and all fire installations:
Mount the 4297 module inside a UL Listed enclosure such as
the control panel's enclosure. Note that the enclosure must
be UL Listed for the desired application; i.e., use an attackresistant enclosure with a tamper switch for commercial
burglary applications.
For non-UL certified installations:
Mount the 4297 module directly on a surface using the
slotted holes located on the back of its housing (mounting
screws provided). Feed the wires through the slot on the side
or through the breakout located on the back of the housing.
Affix the connections label provided to the inside of the 4297
module's cover or in the control panel cabinet, if used.
WIRING CONNECTIONS
The 4297 module provides a 9-position terminal block for
making power, earth ground and polling loop connections.
The screw terminal assignments on this terminal block are
described in Figure 1.
UL NOTE: Use only 14-22 gauge wire.
For ULC fire installations, the 4297 can be used to
ULC
connect the fire alarm control panel to the Vista fire
transmitter. It is not to be used to connect fire alarm
detectors to the ADEMCO (Vista) fire transmitter.
EXTENSION POLLING LOOP
+
(CLASS B, STYLE 3)
}
–
MAX LINE IMPEDANCE 20
–
INPUT POLLING LOOP
}
(FROM CONTROL) (CLASS B,
+
STYLE 3)
(NO CONNECTION)
}
12VDC POWER INPUT (FROM
–
CONTROL PANEL OR A SUP-
}
PLEMENTAL POWER SUPPLY
+
LISTED FOR THE APPLICATION)
POLLING LOOP VOLTAGE: 8-11 VDC
INPUT POWER VOLTAGE: 12 VDC
INPUT POWER CURRENT: 180MA
:400MA (LOOP SHORTED)
FOR IMPEDANCES BELOW WHICH
GROUND FAULTS WILL BE
ANNUNCIATED, REFER TO THE
"SUMMARY OF CONNECTIONS"
LABEL FOR THE CONTROL PANEL.
FOR CE INSTALLATIONS
*
TERMINAL 3 MUST BE
CONNECTED TO
EARTH GROUND
Figure 1. 4297 Wiring Connections
9
8
7
6
5
TB1
4
3
*
2
1
NOTES:
1.
WHEN A SUPPLEMENTARY POWER SUPPLY IS USED, CONNECT IT TO
TERMINALS 1 & 2. CONNECT THE POWER SUPPLY (-) TO AUX POWER (-)
ON THE CONTROL PANEL. USE A CLASS II (POWER LIMITED) SUPPLY.
2.
WHEN USING AN EXTERNAL POWER SOURCE, CONNECTIONS MUST
BE MADE TO A UL864/UL1481 REGULATED POWER SUPPLY.
3.
ALL CIRCUITS ARE SUPERVISED AND POWER LIMITED.
ELECTRICAL SPECIFICATIONS:
4.
USE ONLY 14-22 GAUGE WIRE.
Power Supply Connections
The 4297 module can draw power for its internal circuitry
and its extension loop from a supplementary power supply
such as the control panel's auxiliary power output. See
Figure 2.
• All power-limited wiring must be separated from non-power
U
L
limited and high-voltage wiring by 1/4" (6.4 mm).
• Refer to the control panel installation instructions for
programming / installation requirements.
When Using One 4297
Use one 4297 to extend the polling loop, to provide additional
polling loop current, or to provide an extension loop which is
electrically isolated from the input loop.
Make the connections shown in Figure 3 when only one 4297
module is used. Make sure that the wire run length limits
indicated in Table 1 are not exceeded.
When Using Multiple 4297s
Use multiple 4297s to provide up to eight extension loops
which are electrically isolated from each other, or to provide
more current than one 4297 can supply.
Make the connections shown in Figure 4 when multiple 4297
modules are used. Do not wire 4297 modules in series (i.e.,
do not wire one module’s extension loop to another module’s
input loop). Do not use more than eight 4297 modules in
parallel unless otherwise stated in the control panel's
installation instructions. Make sure that the wire run length
limits indicated are not exceeded.
Important Notes:
* Twisted pair is recommended for all polling loop wire runs.
* If an intercom system is being used, keep the polling loop
wiring as far from the intercom wiring as possible
(minimum 6 inches). If this spacing cannot be achieved, use
shielded wire. Note that use of shielded wire reduces the
maximum permissible polling loop wire run length, as
indicated in Table 1 on page 2.
Ω
4297-003-V1
Page 2
WIRE RUN LENGTH
MUST NOT EXCEED:
GAUGE LENGTH
#22 100 FT
#20 150 FT
9
8
7
6
5
TB1
4
3
2
1
4297
Note: See the Installation & Setup Guide for the control panel being used for specific power and wiring requirements.
INPUT POLLING LOOP (FROM CONTROL).
WHEN USING SUPPLEMENTARY POWER, ON
COMMERCIAL FIRE PANELS, DO NOT CONNECT
THE INPUT POLLING LOOP GROUND ON TERMINAL 7.
NO CONNECTION
CURRENT DRAW:
• 50 mA + EXTENSION LOOP DRAW
DURING ACTUAL OPERATION.
• INCREASES TO 400 mA WHEN
+12VDC
POWER
EXTENTION LOOP SHORTENED
#18 225 FT
#16 375 FT
USE A CLASS II (POWER LIMITED) POWER
SUPPLY WHICH IS UL LISTED FOR THE
DESIRED FIRE AND/OR BURGLARY
APPLICATION. FOLLOW THE POWER SUPPLY'S
INSTRUCTIONS REGARDING BACKUP
BATTERY AND AC/BATTERY SUPERVISION
SIGNAL CONNECTIONS THAT APPLY TO THE
DESIRED APPLICATION.
TAKE CARE TO OBSERVE
POWER SUPPLY RATINGS.
–
SUPPLEMENTARY
+
USE CONTROL PANEL’S
AUXILIARY POWER OR USE
A SEPARATE POWER SUPPLY
Figure 2. Typical Supplementary Power Supply Connections
EXTENSION POLLING LOOP
4297
V-PLEX
DEVICE
CONTROL PANEL
INPUT POLLING LOOP
V-PLEX
DEVICE
V-PLEX
DEVICE
Figure 3. Connections Using One 4297 Module
•
DO NOT CONNECT 4297 MODULES IN SERIES
(i.e., DO NOT CONNECT ONE MODULE'S EXTENSION
LOOP TO ANOTHER MODULE'S INPUT LOOP.)
DO NOT CONNECT MORE THAN EIGHT
•
4297 MODULES IN PARALLEL.
EXTENSION POLLING LOOP #1
4297
POWER SUPPLY
V-PLEX
DEVICE
V-PLEX
DEVICE
NOTE
4297-001-V0
TO
OTHER
RPMS
polling_loop_005-V0
CONTROL PANEL
Figure 4. Typical Connections Using Multiple 4297 Modules
INPUT POLLING LOOP
4297
EXTENSION POLLING LOOP #2
V-PLEX
DEVICE
polling_loop-006-V1
CONFIGURATION GUIDELINES
These guidelines apply to control panels that support V-Plex polling loop devices. Some of these control panels
may have additional limitations; refer to the control panel's Installation & Setup Guide for specific power and
wiring requirements.
Maximum number of devices:
• All input loops (combined) = 64 devices max.
• All input loops (combined) plus 1 output loop = 119 devices max.
Maximum wire length limits:
Refer to Table 1 (at right) for wire length per gauge,
#22
#20
#18
#16
Table 1
Wire Length
650 ft.
950 ft.
1500 ft.
2400 ft.
and observe the maximum wire length limits.
• No individual wire run can exceed 2400 ft. max.
• 1 input loop plus 1 output loop (combined) = 4000 ft. max
• All input loops (combined) plus 1 output loop = 6400 ft. max
Note: Reduce wire length by ½ if using unshielded
wire in conduit, or if using shielded wire.
Wire Gauge
Maximum Current:
• All input loops (combined) = 128mA maximum current limit.
during normal operation. Increases to 400mA
when extension loop shorted.
Float Voltage: 13.65VDC
Standby Time: Exceeds 4 hrs with 1.2AH or larger battery
Recharge Time: Up to 48 hours
Miscellaneous: PTC thermistor provides reverse battery
connection protection
Extension Polling Loop Rating:
Output Current:128mA max. Do not draw more than
128mA on any individual extension loop
SEE THE CONTROL PANEL'S INSTALLATION INSTRUCTIONS FOR
COMPLETE INFORMATION REGARDING THE LIMITATIONS OF
THE ENTIRE SECURITY SYSTEM.
Regulatory Agency Listings
UL 609 commercial burglary, UL864 commercial fire,
UL985 household fire, and UL1023 household burglary.
NFPA-72 Compliant
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa
wire run.
Maximum line impedance: 20 ohms.
Miscellaneous: Refer to Table 1, for limits on polling loop
wire run length. The extension loop is power
limited.
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation
Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the
equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the
following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict
accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been
type tested and found to comply with the limits for a Class B computing device in accordance with the specifications in
Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential
installation. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch
circuits.
• Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA CLASS B STATEMENT
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules, and RSS210 of Industry Canada. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any
interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement
est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit
accepter toute interférence reçue y compris les interférences causant une réception indésirable.
– 3 –
Page 4
ÊN7571V4lŠ
N7571V4 11/13 Rev. A
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright 2009 Honeywell International Inc.
www.honeywell.com/security
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.