Honeywell 4074EYC Installation Instructions Manual

4074EYC
203219DCEB RESISTOR
INSTALLATION INSTRUCTIONS
APPLICATION
The 203219DCEB resistor is connected to the TACO zone valve to assure compatibility with powerstealing thermo­stats during a call for heat. The 203219DCEB is a 3240 ohms resistor.
INST ALLA TION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check the ratings on the resistor to make sure the resistor is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CA UTION
Disconnect power supply before installing the resistor to prevent electrical shock or equipment damage.
To Install the Resistor
1. Loosen the TACO zone valve terminal screws
marked 1 and 2. See Fig. 1.
2. Slide the resistor leads under the terminal screws and tighten the screws.
CA UTION
• Do not short the resistor leads to the zone valve or equipment damage can occur.
• Do not handle the resistor when the TACO zone valve has power. The resistor can be warm.
3. Turn the system power on.
THERMOSTAT
RW
1
L1 (HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
BEND THE RESISTOR AWAY FROM THE ZONE VALVE
2
CASE SO IT DOES NOT SHORT OUT.
Fig. 1. Connect resistor to the TACO zone valve
terminal numbers 1 and 2.
TACO ZONE VALVE
1
2
3
CHECKOUT
1. Set the thermostat heating setpoint to 10°F (6°C)
above the room temperature.
2. Watch the thermostat display for approximately 5 minutes to be sure the display does not go blank during the call for heat.
3. Reset the thermostat to a comfortable setpoint.
RESISTOR
2
M15401
®U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • All Rights Reserved
X-XX UL
X-XX UL
69-1158-2
XXXXXXXXXXXXXXXX
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
XX-XXXX—X
69-1158—2 F.M. Rev. 10-98
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
2
www.honeywell.com/yourhome
Loading...