Honeywell 19546GM1, GM-1 User Manual

Page 1
Gas Monitoring Alarm System
Manning GM-1
Instruction and Installation Manual
07/09
Release D Draft
Honeywell Confidential & Proprietary
This work contains valuable, confidential, and proprietary information. Disclosure, use
or reproduction outside of Honeywell Inc. is prohibited except as authorized in writing.
This unpublished work is protected by the laws of the United States and other countries.
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 1
Page 2
Notices and Trademarks
Copyright 2009 by Honeywell International Inc.
Release D July 2009
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Manning is a registered trademark of Honeywell International Inc.
Other brand or product names are trademarks of their respective owners.
Honeywell Analytics 405 Barclay Blvd. Lincolnshire, IL 60069 USA
1-800-538-0363
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 2
Page 3
About This Document
World Wide Web
The following Honeywell web sites may be of interest.
Honeywell Organization WWW Address (URL)
Corporate www.honeywell.com
Honeywell Analytics www.honeywellanalytics.com
Manning Gas Detection www.manningsystems.com
Telephone
Contact us by telephone at the numbers listed below.
Organization Phone Number
United States Honeywell Analytics Inc. 1-800-538-0363 1-913-712-5576 1-913-712-5580 Fax
Canada Honeywell Analytics Inc. 1-888-749-8878
Europe Honeywell PACE +44 (0)1202 676161
Asia Pacific Honeywell Asia Pacific Inc. +82 (0)2 2025 0307
Middle East Honeywell Analytics Inc. +971 4 3458 338
Sales Information
Contact us at detectgas@honeywell.com
Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol Definition
ATTENTION: Identifies information that requires special consideration.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. CAUTION symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
WARNING: Indicates a potentially hazardous situation, which, if not avoided, could result in serious injury or death. WARNING symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
CAUTION
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 3
indicates a situation which, if not avoided, may result in equipment or work (data) on the system being damaged or lost, or may result in the inability to properly operate the process.
Page 4
Contents Serial number:
Section Title Page
1 System Description 5
2 Installation 7
3 Operation 10
4 Limited Warranty 13
Introduction
This manual has been prepared to help in the use and installation of the Manning GM-1 Gas Monitoring Alarm System. This manual will convey the operating details of the alarm system, ensure proper installation, and demonstrate start-up and routine maintenance procedures.
ATTENTION: This manual must be carefully followed by all individuals who have or will have the responsibility for using or servicing the Manning GM-1 alarm system. Warranties made by Honeywell
Analytics with respect to this equipment will be voided if the equipment is not used and serviced in accordance with the instructions in this manual. If in doubt about a procedure, please contact Honeywell Analytics before proceeding.
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 4
Page 5
1 System Description
The Manning GM-1 is designed to accept a single 4/20 mA current input signal, plus provide a regulated 24 VDC supply to operate all sensors manufactured by Honeywell Analytics.
The Manning GM-1 is housed in a rugged 14 gauge gasketed steel enclosure. Behind the clear plexiglass window is a 20-segment vertical LED bargraph display which gives a visual indication of the gas concentration.
The unit has warning and alarm level indications on the front panel, and warning and alarm relays allowing the user to incorporate functions such as ventilation control, remote horns, security system monitoring, and automatic shutdown.
Designed to be highly reliable when properly installed, all relays are energized during normal operation, and a sensor fault monitoring circuit will indicate a fault and trip a dedicated fault relay if the signal falls below
1.4 mA.
The unit has an audible horn which will sound if an alarm or fault condition is detected. The silence switch will silence the horn until the next event. If an alarm condition initiates the horn, the horn will clear automatically when the alarm relay clears.
The unit has a power-up delay feature that places all outputs in normal conditions for one minute to allow for sensor stabilization.
The Manning GM-1 will support all of Manning sensors, including oxygen, which requires a down­scale alarm.
All components that are in contact with voltages above 40 volts are UL listed, including the enclosure.
Note: The Manning GM-1 is for use in non-classified areas only.
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 5
Page 6
1 System Description continued
System Specifications
Electrical Power: 120 VAC, 50/60 Hz at 0.35 amp
(230 VAC 50/60 Hz is available as an option)
Signal input: 4/20 mA
DC Power available for sensors: Heavy-duty
internal 24 VDC, 1 amp maximum regulated supply
Display: 20-segment LED bargraph
Light Outputs and Relays:
Alarm Light and Relay
• Setpoint field adjustable
Alarm Light and Relay independently latchable by board mounted DIP switch
10 second on delay, 2 second off delay
Warning Light and Relay
• Setpoint field adjustable
Warning Light and Relay are NOT latchable
10 second on delay, 2 second off delay
Fault Light and Relay
Setpoint NOT adjustable — all mA signals below
1.4 mA will initiate fault output
Fault Light and Relay always latch
10 second on delay
Note: All relays are normally energized and monitored by individual LEDs for
ease of troubleshooting
Relay Ratings: 3 amps at 24 VDC or 120 VAC
Form C providing NO (normally open) or NC (normally closed) option
Enclosure: 14 gauge steel, gasketed, 10" high x 8" wide x 4" deep, NEMA 1 rated enclosure with plexiglass window
Weight: 11 lbs.
o
Operating Ambient Temperature range: 0
o
F
+120
Operating Humidity: 5-95% Relative Humidity, non­condensing
Options: Down-scale Alarm for oxygen
Push-button Controls:
Silence
Note: The Manning GM-1 is for use only in non-classified areas.
— Silences internal horn
Reset
— Clears signal, latched functions, and relays. If warning, alarm, or fault condition exists, indications will return after a short time delay.
F to
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 6
Page 7
2 Installation
A
Locating the Manning GM-1
When unpacking the unit, inspect all boxes and contents for shipping damage. If any screws or other metal parts are missing, these must be found to ensure that the printed circuit boards will not be damaged when power is applied.
Figure 1: Mounting dimensions for the Manning GM-1 Gas Monitoring Alarm System
5/16"
6"
The control unit is designed to be mounted on a solid (non-vibrating) wall through four holes in the two mounting flanges. While the physical location must be determined in part by local conditions, it is important to consider the following:
CAUTION
Protect the Manning GM-1 from rain, snow, water sprays, cleaning crews, and physical damage.
Mount the unit on a solid wall (non­vibrating) at eye level for convenience in taking readings, servicing, etc.
The Manning GM-1 is NOT explosion proof. DO NOT MOUNT in a hazardous atmosphere.
Operating temperature for the Manning GM-1 is 0
Pre-punched holes are provided in the bottom of the enclosure for cable access. DO NOT drill holes in the top of the cabinet as this will void the warranty.
o
F to +120o F.
Gas Monitor
Manning GM-1
10 3/4"
Reset
24 1/4"
Silence
If hole drilling is required, be sure to remove all metal filings.
Mounting dimensions are included in Figure 1.
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 7
Page 8
2 Installation continued
B Wiring
Electrical wiring must comply with all applicable codes. Plant equipment that may be involved and operating conditions should be discussed with local operating personnel to determine if any special needs should be taken into account.
Nearly all start-up problems are due to improper wiring or monitor configuration. Please follow these guidelines carefully. Figure 2 presents a wiring diagram for the Manning GM-1.
AC Power Wiring:
Use only stranded cable for AC power, relay outputs, and sensor input cables.
The units must have a proper third wire ground for safety and sensor shielding. Be sure to follow local codes.
All AC cables must be kept away from the incoming sensor cables, i.e., do not put AC cables inside conduit containing sensor cables.
Keep all wiring away from variable speed drives and SCR control units to minimize electrical noise exposure.
Electrical Power: 120 VAC, 50/60 Hz, 0.35 amps.
Relay Wiring:
All three relays have Form C, dry contacts. Any required power source must be within the 3 amp rating and fused or current limited to keep from damaging the contacts.
Relay wiring must be run in separate conduit from the sensor cable if the relay circuit is AC.
Sensor Wiring:
See sensor manual for proper sensor cable.
See sensor manual for proper sensor location.
Never run AC circuits in the same conduit as the sensor cable.
Note: Relays are energized in a non-alarmed condition so that a power loss in the Manning GM­1 will result in an alarm.
Electrical power ground: The unit must be properly grounded.
Risk of electric shock.
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 8
Page 9
2 Installation continued
Figure 2: Wiring diagram for the Manning GM-1 Gas Monitoring Alarm System
TP
WARNING
ADJUST
ALARM
ADJUST
GNDTP+20V
7
16
FUSE RATING 250V 1.0 AMP
NO NCC NO NCC NO NCCLN
120 VAC
MODEL G/M MAINBOARD REV D
WARNING
WARNING
RELAY*
TP
WARNING
RELAY
TP
ALARM
C11
+ + +
ALARM RELAY*
*Relay rating 3 amp. User must fuse to protect.
Note: Green wire earth ground must be connected to grounding stud marked
TP
SIG
ALARM RELAY
FAULT
RELAY*
BOT TOP
FAULT RELAY
SHLD GND+24 SIG
TP CURRENT DRAW
Bare wrap— to "SHLD" terminal of sensor
Black— to "GND" terminal of sensor
Risk of electrical shock.
Red— to "+24" terminal of sensor
White— to "SIG" terminal of sensor
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 9
Potential hazard.
Page 10
3 Operation
A Display Panel C DIP Switch Setting
A 20-segment Bargraph Display indicates the gas concentration level. The bottom LED is always lit to indicate power to the display.
The Warning LED indicates the warning level as determined by the warning setpoint has been exceeded. The Warning LED and Warning Relay operate together and never latch.
The Alarm LED indicates the alarm level as determined by the alarm setpoint has been exceeded. The Alarm LED and Alarm Relay are independently latchable or non-latchable as determined by the DIP switch on the main board. Standard factory settings are to latch the LED and not latch the relay.
The Power LED indicates power to the monitoring unit. This LED will flash during the one minute power up delay indicating that all relays are held in the normal condition to allow for sensor stabilization during power up.
The Fault LED indicates a signal input of less than
1.4 mA (0.14 volts) at TP Sig. The Fault LED and
Fault Relay always latch.
B
Reset and Silence Switches
Pushing the Reset switch will reset the fault light, fault relay, alarm light, and alarm relay. If either condition still exists, the appropriate light and relay will return to its tripped state after a time delay.
Pushing the Silence switch will silence the horn on the bottom of the Manning GM-1 until the next event occurs. The horn is triggered by a fault or an alarm condition. The horn will clear itself if the alarm and fault relay clear. A warning condition does not trigger the horn.
The two position DIP switch in the center of the bottom board controls the latching of the alarm light and alarm relay. Switch 1 (left) controls the alarm relay. Switch 2 (right) controls the alarm light. Putting the switch in the on (up) position will latch the corresponding function. Putting the switch in the off (down) position will cause the corresponding function to be not latched (see Figure 3).
This allows the alarm condition to remain activated if desired even if the gas concentration goes back to below the setpoint.
Figure 3: Warning adjustment and DIP switch settings
WARNING
7
TP
GNDTP+20V
ADJUST
WARNING
ALARM ADJUST
TP
WARNING
TP
ALARMTPSIG
RELAY
SW1
1 2
BOT TOP
AA
ALARM
FAULT
RELAY
RELAY
16
FUSE RATING 250V 1.0 AMP
NO NCC NO NCC NO NCCLN
120 VAC
MODEL G/M MAINBOARD REV D
WARNING
RELAY*
+ + +
ALARM RELAY*
C11
SHLD GND+24 SIG
FAULT
RELAY*
TP CURRENT DRAW
0.4 - 2.0 V
VDC
Warning adjust pot
DIP switches on bottom of board
Black-Red
+
Factory set pots
Risk of electrical shock.
Potential hazard.
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 10
Do Not Adjust!
Page 11
3 Operation continued
D Signal and Setpoints
The voltage between TP Gnd and TP Sig indicates the current signal received from the sensor. The normal range is 0.4 volts to 2.0 volts, which corresponds with 4/20 mA. This manual will use the voltage at TP Sig to describe the input signal. When this signal exceeds the voltage at TP Warning or TP Alarm, the warning or alarm function will take place. The warning setpoint is user adjustable by looking at the voltage on TP Warning and adjusting the warning adjust pot until the desired setpoint is reached (see Figure 3). The alarm adjust pot and TP Alarm function the same way.
The warning and alarm setpoints are factory adjusted as indicated on the data sheet included with your GM-1. Never adjust these setpoints outside the range of 0.4 to 2.0 volts. Contact Honeywell Analytics if you have any questions or want help in determining setpoints for your particular sensor and application.
After setpoint adjustment always expose sensor to the gas being monitored and verify that the warning and alarm lights trigger at the desired concentration as displayed by the bargraph.
E Start-Up Procedures
F Troubleshooting
The Fault Light and Fault Relay always latch when a fault condition is detected. After the condition is corrected the Reset switch must be pressed to clear the Fault Light and Fault relay.
The unit will indicate a fault if the signal is less than
0.14 volts at TP Sig.
Some Manning sensors are configured to send a signal of 0.05 volts at TP Sig if a sensor fault exists. If TP Sig = 0.05 volts, this indicates a properly wired sensor is in a fault condition. Proceed to investigate the sensor.
If TP Sig = 0.00 volts, this indicates no signal from the sensor. Check for correct wiring or loose connections between the sensor and monitoring unit.
Each relay has a green LED in series with its coil. If this LED is on, this indicates that the relay is energized and contacts will be in the normal position. If this LED is off, the contacts will be in the tripped condition.
Power supply voltages should be checked at TP +20V on the display board and at +24 on the sensor input terminal block (see Figure 4). Both points should be DC Volts as labeled.
Before applying power, make a final check of all wiring for continuity, shorts, grounds, etc. It is usually best to disconnect external alarms and other equipment from the unit until the initial start-up procedures are completed.
After power-up, allow 24 hours for the system to stabilize before testing the sensor. Because sensors are normally located at a distance from the monitoring unit, the test time required and accuracy of the response checks will be improved if two people perform the start-up procedures and use radio contact.
Start-Up Test: One person exposes the sensor to a small amount of the gas that is being monitored. The second person stays at the monitoring unit to determine that the sensor, when exposed to the target gas, is connected to the proper input, responds, and causes appropriate alarm functions.
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 11
The total sensor current draw can be checked by looking at the voltage between the two TP Current Draw test points. 1.0mV corresponds to 10 mA, and
50.0mV corresponds to 500mA, etc. Compare this reading with the current draw expected for the sensor you are using (see appropriate sensor manual).
If questions arise, call Honeywell Analytics.
Page 12
3 Operation continued
G Maintenance
The Manning GM-1 is designed for long life and high reliability. Honeywell Analytics recommends checking signal voltages monthly and logging them on the data sheet included with your Manning GM-1. Additionally, the sensor being monitored should be exposed to the target gas on a monthly basis while all alarm functions are verified at the Manning GM-1. This will test the sensor and any equipment con-
H Replacement Parts
For replacement parts, contact Honeywell Analytics. Be sure to give serial number and model number of unit.
nected to the relays in addition to the Manning GM-1.
Figure 4: Troubleshooting the Manning GM-1 Gas Monitoring Alarm System
Display power supply voltage
+20V
VDC
Sensor current draw
(1mV per 10 mA)
SENSOR DEPENDENT
mVDC
Black
-
Red
+
0.4 - 2.0 V
VDC
Black
-
Signal from sensor
Red
+
Risk of electrical shock.
7
TP
GNDTP+20V
WARNING
ADJUST
WARNING
TP
WARNING
RELAY
ALARM
ADJUST
ALARM
AC fuse
16
C11
+ + +
ALARM
RELAY*
120 VAC
MODEL G/M MAINBOARD REV D
FUSE RATING 250V 1.0 AMP
NO NCC NO NCC NO NCCLN
WARNING
RELAY*
Potential hazard.
Black
-
TP
TP
SIG
ALARM RELAY
BOT TOP
FAULT RELAY
Red
+
+24V
Black
-
VDC
Red
+
FAULT
RELAY*
TP CURRENT DRAW
SHLD GND+24 SIG
Power supply voltage to sensor
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 12
Page 13
4 Limited Warranty
1. Limited Warranty Honeywell Analytics, Inc. warrants to the original purchaser and/or ultimate customer (“Purchaser”) of Manning products (“Product”) that if any part thereof proves to be defective in material or workmanship within eighteen (18) months of the date of shipment by Honeywell Analytics or twelve (12) months from the date of first use by the purchaser, whichever comes first, such defective part will be repaired or replaced, free of charge, at Honeywell Analytics’ discretion if shipped prepaid to Honeywell Analytics at 405 Barclay Blvd., Lincolnshire, IL 60069, in a package equal to or in the original container. The Product will be returned freight prepaid and repaired or replaced if it is determined by Honeywell Analytics that the part failed due to defective materials or workmanship. The repair or replacement of any such defective part shall be Honeywell Analytics’ sole and exclusive responsibility and liability under this limited warranty.
2. Exclusions
A. If gas sensors are part of the Product, the
gas sensor is covered by a twelve (12) month limited warranty of the manufacturer.
B. If gas sensors are covered by this limited
warranty, the gas sensor is subject to inspection by Honeywell Analytics for extended exposure to excessive gas con­centrations if a claim by the Purchaser is made under this limited warranty. Should such inspection indicate that the gas sensor has been expended rather than failed prematurely, this limited warranty shall not apply to the Product.
C. This limited warranty does not cover consum-
able items, such as batteries, or items subject to wear or periodic replacement, including lamps, fuses, valves, vanes, sensor elements, cartridges, or filter elements.
3. Warranty Limitation and Exclusion
Honeywell Analytics will have no further obligation under this limited warranty. All warranty obligations of Honeywell Analytics are extinguishable if the Product has been subject to abuse, misuse, negligence, or accident or if the Purchaser fails to perform any of the duties set forth in this limited warranty or if the Product has not been operated in accordance with instructions, or if the Product serial number has been removed or altered.
4. Disclaimer of Unstated Warranties
THE WARRANTY PRINTED ABOVE IS THE ONLY WARRANTY APPLICABLE TO THIS PURCHASE. ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
5. Limitation of Liability
IT IS UNDERSTOOD AND AGREED THAT HONEYWELL ANALYTIC’S LIABILITY, WHETHER IN CONTRACT, IN TORT, UNDER
ANY WARRANTY, IN NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE AMOUNT OF THE PURCHASE PRICE PAID BY
THE PURCHASER FOR THE PRODUCT AND UNDER NO CIRCUMSTANCES SHALL HONEYWELL ANALYTICS BE LIABLE FOR
SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES. THE PRICE STATED FOR THE PRODUCT IS A CONSIDERATION LIMITING
HONEYWELL ANALYTICS’ LIABILITY. NO ACTION, REGARDLESS OF FORM, ARISING OUT OF THE TRANSACTIONS UNDER THIS
WARRANTY MAY BE BROUGHT BY THE PURCHASER MORE THAN ONE YEAR AFTER THE CAUSE OF ACTIONS HAS OCCURRED.
Manning GM-1 Gas Monitoring Alarm System 19546 GM1 07/09 REVD Copyright © 2009 Honeywell Analytics. All Rights Reserved. 13
Loading...