Hobart WS-500 Installation Manual

INSTALLATION
INSTRUCTIONS & PARTS
HOBART
WATER SOFTENING
SYSTEM
WS-500
A product of HOBART TROY, OHIO 45374
F25405 (March 2011)
INSTALLATION ............................................................................ 2
DISC SELECTION ......................................................................... 15
REPLACEMENT PARTS .................................................................... 15
© HOBART 2011
INSTALLATION
SAVE THESE INSTRUCTIONS
1. Determine location to install equipment. Make sure the unit will be on a flat surface.
2. If sand, silt, or turbidity is present, install a separate prefilter.
NOTE: Sediment filtration is recommended before the water softener, particularly in areas with known sediment issues or on a private water supplies.
NOTE: If the peak flow rate required is unknown, a prefilter with a minimum of 1.25" connections should be used. Filters with 5 micron nominal ratings should be considered the standard in food service applications.
By-Pass Valve Kit Installation
3. If the optional by-pass valve kit is being installed, continue with steps listed below. If by­pass valve kit is not being installed - proceed to step 24.
4. To install by-pass valve determine which port on the by-pass valve (Port A or Port B) to plumb the raw water connection to.
5. Determine which port on the by-pass valve (Port C or Port D) to connect the softener.
F25405 (March 2011) Page 2 of 20
6. Verify the by-pass valve is in the by-pass position. Turn by-pass handle to reveal yellow by-pass segment.
7. Remove the by-pass valve handle by pulling it away from the by-pass valve body.
9. Locate patch decal provided with by-pass valve kit.
10. Remove patch decal from paper lining and apply to body of the by-pass valve based on the specific installation using Table 1.
NOTE: For use in A-D or B-D configuration, it will be necessary to cut patch.
8. The five position valve has two installation configuration options. Photo below shows the crossover and parallel configurations as the valve is shipped.
F25405 (March 2011)Page 3 of 20
Table 1
MODE RAW
INLET
A-C A C PARALLEL 2
B-C B C CROSSOVER 3
A-D A D CROSSOVER 4
B-D B D PARALLEL 5
SOFTENER
INLET
INSTALL CONFIGURATION
FIG
F25405 (March 2011) Page 4 of 20
11. Align the handle with the shaft until handle slides onto shaft. Push down on handle until it snaps into place.
NOTE: The handle is keyed allowing it to go on the shaft only one way. Failing to perform above procedure can result in breaking the shaft inside the handle. Do not force handle onto shaft.
17. Apply a liberal amount of silicone to the four O­rings and install on the two end spaces on both Port C and Port D.
NOTE: When installing a plastic component in line, it is recommended that grounding straps be put in place before the lines are actually cut to ensure the ground is never broken.
12. Prepare plumbing by roughing in.
13. Connect the inlet/outlet adapters to the plumbing. Solder or glue adapters to pipe as applicable.
NOTE: Do not solder adapters while in the by-pass valve.
NOTE: Care should be taken during the installation process to assure that solder flux does not come in contact with the media tanks, the control module, and related components.
14. After all plumbing is completed and before connecting any equipment, flush both inlet and outlet lines by opening the raw water inlet valve and allowing water to rinse out and debris in the line.
15. Close the raw water line when complete.
16. Locate from the by-pass kit the two elbows, four O-rings, two E-Clips and silicone packet.
18. Insert mesh screens into left and right elbows.
19. Locate from the by pass kit the four O-rings, two E-Clips and silicone packet
F25405 (March 2011)Page 5 of 20
20. Apply a liberal amount of silicone to the four O­rings and install them on the two outermost groves on both elbows
NOTE: Elbows are marked left (L) and right (R). When applying to by-pass valve be certain to install in correct location based on left/right orientation.
By-Pass Valving Installation NOTE: If optional by-pass valve kit is not installed - it
is recommended that by-pass valving be installed. To install by-pass valving - follow steps listed below.
24. Determine location to install equipment. Make sure the unit will be on a flat surface.
25. If sand, silt, or turbidity is present, install a separate prefilter.
NOTE: Sediment filtration is recommended before the water softener, particularly in areas with known sediment issues or on a private water supplies.
NOTE: If the peak flow rate required is unknown, a prefilter with a minimum of 1.25" connections should be used. Filters with 5 micron nominal ratings should be considered the standard in food service applications.
26. Install by-pass valving. Be certain to note the inlet and outlet arrows on the valve head.
27. Connect the inlet/outlet adapters leading to the softener using the proper size plumbing.
28. Plumb as necessary to accommodate the by­pass valving and to complete the installation.
NOTE: Make sure to align the center slot (the slot with the small triangle underneath it) with the outside of the by pass valve.
21. Connect elbows from the by-pass valve to softener using E-clips. Press E-clips until they securely snap in place.
22. Connect the by-pass valve to the inlet/outlet adapters. Press E-clips until they securely snap in place.
23. Plumb as necessary to accommodate the by­pass valve and to complete the installation. Proceed to step 31.
NOTE: Actual installation of by-pass valving may vary from installation to installation. Be sure to follow state and local codes.
NOTE: When installing a plastic component in line, it is recommended that grounding straps be put in place before the lines are actually cut to ensure the ground is never broken.
NOTE: Do not solder brass adapters while inserted in the module base. Damage to plastic and ruber parts may result due to the heat. In addition, the materials used in the soldering process may attack certain types of plastics.
NOTE: Care should be taken during the installation process to assure that solder flux do not come in contact with the media tanks, the control module, and related components.
F25405 (March 2011) Page 6 of 20
29. After all plumbing is completed, but before connecting equipment, flush both the inlet and outlet lines by opening the by-pass valve and allowing water to rinse out any debris in the lines.
30. Connect the main tank with softener valve to the inlet/outlet adapter. The inlet/outlet adapter is inserted into the control valve and locked in place by the plastic E-clips.
31. Locate enclosed kit containing four O-rings, two pipes with O-rings, and the silicone packet. Apply a liberal amount of silicone to the four O­rings and the O-rings in the two pipes. Install the four O-rings to the inlet/outlet adapters.
32. NOTE: Be certain the E-clips are fully inserted into the valve. Check to make sure that all three tabs on the E-clips are fully inserted.
F25405 (March 2011)Page 7 of 20
F25405 (March 2011) Page 8 of 20
F25405 (March 2011)Page 9 of 20
Tank Connection
Brine Drum
33. Connect the remote tank to the main tank using connector pipes, connector links and connector pins.
NOTE: Always use both links and pins.
34. Run a drain line to the discharge point.
NOTE: Follow state and local codes.
35. Before connecting unit, check for obstructions or kinks. Apply Teflon tape to pipe threads on side of softener valve, and install the two fittings supplied. Connect drain line to valve.
36. Position the brine drum. NOTE: Brine drum should be conveniently
positioned to allow salt to be added.
NOTE: An air gap must be provided for all drain lines. Check state and local plumbing codes for proper setup of drain line air gaps.
NOTE: On drain lines that must travel more than 8 feet up and 30 feet over, it is best to take the 5/8" drain line that fits the valve and attach it in a larger diameter line or pipe.
NOTE: In Hobart Softeners, the brine drum mixes and stores a solution of salt for regeneration of the softener media. During the brine rinse cycle, this solution is drawn from the brine drum and through the media to regenerate it.
The brine drum contains an adjustment to draw the correct amount of salt (brine) solution for each cycle. This adjustment is made in two places, the adjuster tube and the float cup.
NOTE: The adjuster tube measures the amount of solution that is drawn from the brine drum into the softener during the brine rinse cycle. The float cup height determines how much softened water flows back into the brine drum to prepare for the next regeneration.
The adjuster tube is set by cutting and removing tabs on both sides of the tube. Cut across each tab horizontally, following the channel in the plastic. Break off each tab individually until the proper setting is reached. The remaining number or letter imprinted on the tab determines the correct setting.
F25405 (March 2011) Page 10 of 20
NOTE: The float cup height determines how much softened water flows back into the brine drum to prepare for the next regeneration.
The float cup is set by adjusting its height above the bottom of the Brine Valve Assembly. By removing the brine valve assembly and resting it on a flat surface, the height of the float cup can be measured with a ruler.
The height is measured from the base of the brine valve assembly to the top of the float cup.
NOTE: Standard settings are defined by markings on the rod of the brine valve assembly. Where the predefined settings are not adequate, the actual float cup height must be measured and the setting must be measured and set according to the measured float cup height.
Determining the correct brine valve setting for a particular application is a three step process:
1. Determine the compensated hardness. This requires a hardness test and an iron test on raw water at the application site. Compensated hardness is calculated by multiplying the ferrous iron (in ppm) by 3 and adding it to the grains of hardness.
F25405 (March 2011)Page 11 of 20
2. To test the water supply, use the water analysis test kit available through Pro Products Inc. The recommended kit is #2404 Deluxe Field Analysis Kit. To order the test kit contact Pro Products at 800-285-9176 or visit www.ProProducts.com.
3. Set the adjuster tube and float cup. Use the brine drum specifications for the WS-500 to determine the correct settings for both the adjuster tube and the float cup height.
Brine Valve Settings for WS-500 24 x 40 Brine Valve Adjustment
Salt Setting
Adjuster Tube
Float Cup
NOTE: Do not drop the brine valve into the drum.
Dropping may lower the float cup, resulting in an improper setting.
After the adjustments have been made to the adjuster tube and the float cup, the brine valve assembly must be installed in the brine drum. Locate the brine valve in the brine well so the 3/8" bent tube is along the back of the brine well away from the brine drum wall. The 3/8" bent tube snaps into a notch and extends from the brine drum about 1 inch.
NOTE: The WS-500 comes with a #4 meter disc installed at the factory. If this is not the correct disc for a given application, locate the meter disc kit and install the correct disc.
Disc Selection
36. To change disc, remove screws and cap cover from level one.
25 lbs.
K
12"
38. Remove balance piston o-ring and balance piston spring.
39. Remove meter drive pawl.
37. Remove balance piston.
F25405 (March 2011) Page 12 of 20
40. Remove meter disc.
41. Install correct meter disc and reassemble in reverse order.
NOTE: Make certain all components are correctly installed.
NOTE: Be certain to start cap screws by hand rotating backwards until screw drops into thread then tighten. An alternating, crossing pattern should be used while tightening cap screws to ensure correct cap fit.
Salt Alarm Installation
47. To install salt alarm system - remove paper lining from back of salt alarm sensor.
Add a clean grade of salt at this time. Higher grades of Pelletized Salt for impurities and solubility should be used.
NOTE: Do not use rock salt or solar salt. NOTE: On iron-bearing water, a salt that contains
resin cleaning additives is recommended.
42. Open the inlet valve slowly and allow the tanks to fill slowly with water. Water will run at the drain until unit is full and pressurized.
43. With the unit in service and under pressure, allow the brine drum to fill with water until the brine valve shuts off.
44. After the unit is fully pressurized, purge air form the lines by opening soft water outlet.
NOTE: When brine drum overflow could cause damage, a ½" I.D. overflow line must be installed on the barbed overflow fitting on drum and connected to a drain. Make sure drain is not higher than barbed fitting. FOLLOW STATE AND LOCAL CODES.
45. Check for plumbing leaks.
46. Check unit for proper operation.
48. Remove plastic lining from Velcro
®
backing
located on back of salt alarm controller.
49. Remove four screws securing back cover to salt alarm controller.
F25405 (March 2011)Page 13 of 20
50. Install three (3) AA batteries into salt alarm controller.
NOTE: When installing batteries - be certain to inspect connector to ensure it is secure.
51. Re-install back cover to salt alarm controller.
52. Using the adhesive backing on both devices ­place alarm controller and salt alarm sensor in a position that will allow salt alarm controller to be seen and heard when it is activated.
54. Check for proper operation by pressing the recessed red button on bottom of salt alarm controller. If controller is operating properly ­the indicator light will flash and an audible tone will be heard.
53. Insert phone cable into salt alarm sensor and salt alarm controller.
NOTE: Salt alarm controller can be mounted up to 100 feet from salt alarm connector box using standard phone cable from local retailers (7 foot cable is provide with kit).
F25405 (March 2011) Page 14 of 20
DISC SELECTION
Using the full louver nozzle, the amount of hardness removed (in compensated gpg) will be based on the amount of brine and the meter disc selected.
OVERDRIVE OPERATION
Setting Capacity Efficiency Dosing Meter
Disc
3
3
1234567 8
Disc
7 142128344045 51
20 20 20 20 15.7 12.4 10.0 8.3
*Compensated hardness in gpg = Hardness + (3 x Fe in mg/l)
25 lbs. 70,000 grains 2,800 gr./lb. 10.0 lbs./ft
Peak flow during regeneration:
ALTERNATING OPERATION
Setting Capacity Efficiency Dosing Meter
25 lbs. 70,000 grains 2,800gr./lb. 10.0 lbs./ft
Flow during regeneration (@ 15 psig)
Gallons/Regeneration: 8,922 4,461 2,974 2,231 1,784 1,487 1,275 1,115
REPLACEMENT PARTS
Disc Selection
(Compensated Hardness*)
1 2 3 4 5678
6 12 16 20 24303540
28.0 28.0 28.0 20.7 15.7 12.4 10.0 8.3
*Compensated hardness in gpg = Hardness + (3 x Fe in mg/l)
Disc Selection
(Compensated Hardness*)
Item
Number
1 00-913091-130 Cord Phone 7ft. 1 2 00-913091-129 Sensor Salt Alarm 1 3 00-913091-128 Salt Alarm Assy. 1
Part Number Description Qty.
F25405 (March 2011)Page 15 of 20
F25405 (March 2011) Page 16 of 20
Item
Number
1 00-913091-00067 Cap Screw 8 2 00-913091-00068 Cap 1 3 00-913091-00069 O-Ring (Actuator) 1 4 00-913091-00071 Seal - Cap 1 5 00-913091-00070 Actuator 1 6 00-913091-00072 Meter Disc 1 1 7 00-913091-00073 Meter Disc 2 1 8 00-913091-00074 Meter Disc 3 1
9 00-913091-00075 Meter Disc 4 1 10 00-913091-00076 Meter Disc 5 1 11 00-913091-00077 Meter Disc 6 1 12 00-913091-00078 Meter Disc 7 1 13 00-913091-00079 Meter Disc 8 1 14 00-913091-00048 O-Ring (Balance Piston) 1 15 00-913091-00008 Piston - Balance 1 16 00-913091-00010 Spring (Balance Piston) 1 17 00-913091-00049 Control Disc (Tan) 1 18 00-913091-00012 Pawl (No Back) 1 19 00-913091-00013 Pawl - Meter Drive 1 20 00-913091-00014 Spring (Meter Drive Pawl) 1 21 00-913091-00015 Pawl - Regen Start 1 22 00-913091-00081 Eccentric Pin 1 23 00-913091-00061 Filter 1 24 00-913091-00016 Pawl - Regen Drive 1 25 00-913091-00081 Eccentric Pin 1 26 00-913091-00084 O-Ring (Regen) 1 27 00-913091-00083 Pin - Support 1 28 00-913091-00085 Screw (Level 1) 8 29 00-913091-00017 Seal - Red (Level 1) 1 30 00-913091-00047 Level 1 Assy. (Incls. Items 1 thru 29) 1 31 00-913091-00020 Level 2 1 32 00-913091-00100 Tube - Vent 1 33 00-913091-00050 Brine Flow Control (0.7 GPM) 1 34 00-913091-00023 Seal - Red (Level 2) 1 35 00-913091-00051 Level 3 Assy. 1 36 00-913091-00087 Elbow - Brine 1 37 00-913091-00086 Elbow - Drain 1 38 00-913091-00097 Regeneration Flow Control 1 39 00-913091-00025 Seal - Red (Level 3) 1 40 00-913091-00052 Venturi Throat (Yellow) 1 41 00-913091-00055 Control Valve (With Quad Ring) 1 42 00-913091-00102 Quad Ring (Control Valve) 1 43 00-913091-00094 Main Piston (Incls. Item 44) 4 44 00-913091-00095 Quad Ring (Main Piston) 4 45 00-913091-00096 Valve Seat - Main (Incls. Item 46) 4 46 00-913091-00093 Seal - Main Valve 4 47 00-913091-00056 Backwash Flow Control 1 48 00-913091-00103 Seal - Control Valve 1
Part Number Description Qty.
Page 17 of 20
F25405 (March 2011)
Item
Number
49 00-913091-00054 Level 4 1 50 00-913091-00053 Level 4 Assy. (Incls. Items 41 thru 49 & 51) 1 51 00-913091-00031 Seal - Red (Level 4) 1 52 00-913091-00058 Drain Valve (With Quad Ring) 1 53 00-913091-00035 Interlock 1 54 00-913091-00057 Level 5 1 55 00-913091-00059 Seal - Drain Valve 1 56 00-913091-00039 Seal - Main Base (Level 6) 1 57 00-913091-00040 Check Stems 2 58 00-913091-00060 Level 6 1 59 00-913091-00101 Ring - Main Base 1 60 00-913091-00062 Upper Distributor 1 61 00-913091-00063 Brine Valve Assy. 1 62 00-913091-00064 E-Clip (In/Out) 2 63 00-913091-00110 Nozzle (Full Louver) 1 64 00-913091-00111 Pin - Connector 2 65 00-913091-00112 O-Ring (Connector) 4 66 00-913091-00113 Pipe - Connector 2 67 00-913091-00114 Link - Connector 2
---- 00-0913091-00046 Complete Head Assy. (WS-500) 1
---- 00-913091-00098 Drain Tube AR
---- 00-913091-00099 Brine Tube AR
Part Number Description Qty.
F25405 (March 2011)
Page 18 of 20
Item
Number
1 00-913091-127 Kit, Bypass Valve with Install Elbow 1
2 00-913091-132 Screens for In/Out 20 Mesh 1
3 00-913091-131 Kit, Elbow 1.25" 2
Part Number Description Qty.
F25405 (March 2011)Page 19 of 20
- N O T E S -
F25405 (March 2011) Printed in U.S.A.Page 20 of 20
Loading...