Hitachi RAD-25NH4, RAC-25NH4, RAD-40NH4, RAC-50NH4 Service Manual

Page 1
NO. 0214E
SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT
ROOM AIR CONDITIONER
INDOOR UNIT + OUTDOOR UNIT
JUNE 2004
Refrigeration & Air-Conditioning Division
SERVICE MANUAL
REFER TO THE FOUNDATION MANUAL
TECHNICAL INFORMATION
FOR SERVICE PERSONNEL ONLY
(W)
(A)
(kW)
(B.T.U./h)
(W)
(A)
(kW)
(B.T.U./h)
W
H
D
(kg)
RAD-25NH4 RAC-25NH4
DC INVERTER (CEILING CASSETTE TYPE)
TYPE
MODEL
POWER SOURCE
TOTAL INPUT
TOTAL AMPERES
CAPACITY
TOTAL INPUT
TOTAL AMPERES
CAPACITY
DIMENSIONS (mm)
NET WEIGHT
SPECIFICATIONS
750
235
400
19
RAD-25NH4 RAD-40NH4
CONTENTS
SPECIFICATIONS ------------------------------------------------------------------- 4
HOW TO USE ------------------------------------------------------------------------ 6
CONSTRUCTION AND DIMENSIONAL DIAGRAM ---------------------- 25
MAIN PARTS COMPONENT --------------------------------------------------- 27
WIRING DIAGRAM -----------------------------------------------------------------29
CIRCUIT DIAGRAM ---------------------------------------------------------------- 31
PRINTED WIRING BOARD LOCATION DIAGRAM ---------------------- 37
BLOCK DIAGRAM ------------------------------------------------------------------ 39
BASIC MODE ------------------------------------------------------------------------ 41
REFRIGERATING CYCLE DIAGRAM ---------------------------------------- 55
AUTO SWING FUNCTION ------------------------------------------------------- 57
DESCRIPTION OF MAIN CIRCUIT OPERATION ------------------------ 58
SERVICE CALL Q & A ----------------------------------------------------------- 89
TROUBLE SHOOTING ------------------------------------------------------------ 92
PARTS LIST AND DIAGRAM ------------------------------------------------- 112
RAD-25NH4/RAC-25NH4 RAD-40NH4/RAC-50NH4
RAC-25NH4 RAC-50NH4
COOLING
HEATING
INDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
1 PHASE, 50 Hz, 220-240V
720 (220~980)
3.31-3.03
2.50 (1.00 ~ 3.00)
8,540
1,000 (210 ~ 1,280)
4.59-4.21
3.80 (1.10 ~ 4.80)
12,980
750
570
280
38
750
235
400
19
850
650
298
60
1 PHASE, 50 Hz, 220-240V
1,400 (220~1,560)
6.43-5.89
4.00 (1.00 ~ 4.50)
13,660
1,770 (210 ~ 1,920)
8.13-7.45
5.20 (1.10 ~ 5.80)
17,750
RAD-40NH4 RAC-50NH4
Page 2
SAFETY DURING REPAIR WORK
1. In order to disassemble and repair the unit in question, be sure to disconnect the power cord plug from the power outlet before starting the work.
2. If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit, and the replacement must be effected in correct manner according to the instructions in the Service Manual of the unit.
If the contacts of electrical parts are defective, replace the electrical parts without trying to repair them.
3. After completion of repairs, the initial state should be restored.
4. Lead wires should be connected and laid as in the initial state.
5. Modification of the unit by user himself should absolutely be prohibited.
6. Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
7. In installing the unit having been repaired, be careful to prevent the occurence of any accident such as electrical shock, leak of current, or bodily injury due to the drop of any part.
8. To check the insulation of the unit, measure the insulation resistance between the power cord plug and grounding terminal of the unit. The insulation resistance should be 1M or more as measured by a 500V DC megger.
9. The initial location of installation such as window, floor or the other should be checked for being and safe enough to support the repaired unit again. If it is found not so strong and safe, the unit should be installed at the initial location reinforced or at a new location.
10. Any inflammable thing should never be placed about the location of installation.
11. Check the grounding to see whether it is proper or not, and if it is found improper, connect the grounding terminal to the earth.
DANGER
First, I must disconnect the power cord plug
from the power outlet.
– i –
Page 3
WORKING STANDARDS FOR PREVENTING BREAKAGE OF SEMICONDUCTORS
1. Scope The standards provide for items to be generally observed in carrying and handling semiconductors in relative manufacturers during maintenance and handling thereof. (They apply the same to handling of abnormal goods such as rejected goods being returned).
2. Object parts
(1) Micro computer (2) Integrated circuits (IC) (3) Field-effect transistors (FET) (4) P.C. boards or the like on which the parts mentioned in (1) and (2) of this paragraph are equipped.
3. Items to be observed in handling
(1) Use a conductive container for carrying and storing of parts. (Even rejected goods should be handled in
the same way).
Fig. 1. Conductive Container
(2) When any part is handled uncovered (in counting, packing and the like), the handling person must always
use himself as a body earth. (Make yourself a body earth by passing one M ohm earth resistance through a ring or bracelet).
(3) Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being
taken.
(4) Be sure to place a part on a metal plate with grounding.
(5) Be careful not to fail to turn off power when you repair the printed circuit board. At the same time, try
to repair the printed circuit board on a grounded metal plate.
1M
Fig. 2. Body Earth
Body earth (Elimik conductive band)
Clip for connection with a grounding wire
IC
A conductive polyvinyl bag
IC
Conductive sponge
– 1 –
Page 4
(6) Use a three wire type soldering iron including a grounding wire.
Bare copper wire (for body earth)
Working table
Resistor of 1 M (1/2W)
Earth wire
Fig. 3. Grounding of the working table
2
Screw stop at the screwed part using a rag plate
Soldering iron
Grounding wire
Fig. 4. Grounding a soldering iron
Use a high insulation mode (100V, 10M or higher) when ordinary iron is to be used.
(7) In checking circuits for maintenance, inspection or some others, be careful not to have the test probes of the
measuring instrument shortcircuit a load circuit or the like.
Metal plate (of aluminium, stainless steel, etc.)
Staple
– 2 –
Page 5
1. In quiet operation or stopping the running, slight flowing noise of refrigerant in the refrigerating cycle is
heard occasionally, but this noise is not abnormal for the operation.
2. When it thunders near by, it is recommend to stop the operation and to disconnect the power cord plug
from the power outlet for safety.
3. The room air conditioner does not start automatically after recovery of the electric power failure for
preventing fuse blowing. Re-press START/STOP button after 3 minutes from when unit stopped.
4. If the room air conditioner is stopped by adjusting thermostat, or missoperation, and re-start in a moment,
there is occasion that the cooling and heating operation does not start for 3 minutes, it is not abnormal and this is the result of the operation of IC delay circuit. This IC delay circuit ensures that there is no danger of blowing fuse or damaging parts even if operation is restarted accidentally.
5. This room air conditioner should not be used at the cooling operation when the outside temperature is
below 10°C (50°F).
6. This room air conditioner (the reverse cycle) should not be used when the outside temperature is below
–15°C (5°F). If the reverse cycle is used under this condition, the outside heat exchanger is frosted and efficiency falls.
7. When the outside heat exchanger is frosted, the frost is melted by operating the hot gas system, it is not
trouble that at this time fan stops and the vapour may rise from the outside heat exchanger.
!
CAUTION
– 3 –
Page 6
SPECIFICATIONS
MODEL
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
TEMPORARY SWITCH
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH (LIQUID CRYSTAL)
RAD-25NH4 RAD-40NH4
20W
NO
NO
NO
NO
NO
NO
NO
NO
YES
NO
NO
NO
NO
YES(IC)
YES
----------
40 W
NO
NO
NO
YES
YES
3.0A
G4A
NO
NO
YES
NO
450NR
YES
YES(IC)
NO
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
UNIT
PIPES (MAX. 20m)
REFRIGERANT CHARGING VOLUME (Refrigerant 410A)
RAC-25NH4 RAC-50NH4
JU1012D JU1013D
1400g1150g
– 4 –
Page 7
– 5 –
CAUTION
Always install the indoor unit level. Units not installed level may leak.
9
7
6
5
PLUG
Be sure to com­pletely seal any gap with putty.
The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commercial products.)
Drain pipe Must be installed separately. Insulate indoor part of pipe to prevent condensation.
Adiabated pipes must always be used for both large and small diameter. Wrap pipes with tape. An adiabator will weather excessively if not tape-wrapped.
Maximum pipe length 20m
Minimum pipe length 5m
above 200mm
above 700mm
above 200mm
above 50mm when installed on the ceiling of balcony
(
)
above 100mm
above 100mm give clearance as
wide as possible
Use the holder when the pipe is drawn from the left.
If connect indoor unit RAD-40NH4 with outdoor unit RAC-50NH4, opitional flare adaptor for piping is
necessary. Flare adaptor for piping: ø9.52 (3/8”) ø12.7 (1/2”)
{Parts number TA261D-4 001}
[Indoor unit installation]
Page 8
– 6 –
Page 9
– 7 –
Page 10
– 8 –
FULL DUCT
SEMI DUCT
NON DUCT
Page 11
9
Page 12
– 10 –
an speed f
Page 13
11
Page 14
– 12 –
displa
Page 15
13
Page 16
14
Page 17
15
Page 18
– 16 –
(ON) mark b
(ON) mar
Page 19
– 17 –
(ON) mar (RESER
A beep occurs and the (TIMER) lamp lights on the indoor unit.
The setting of the current time
The time indication star
lighting instead of flashing.
(OFF) mar
sign lights A beep occurs and the (TIMER) lamp lights on the indoor unit.
Page 20
18
Page 21
– 19 –
Page 22
20
Page 23
21
Page 24
22
Page 25
23
Page 26
24
Page 27
– 25 –
CONSTRUCTION AND DIMENSIONAL DIAGRAM
MODEL RAD-25NH4, RAD-40NH4
Cautions:
1. Use insulated pipes for both large and small diameters.
2. An connection cable.
15
148
235
216
Wide pipe
(
)
Narrow pipe
(
)
24
11
62177
750
20
790
35
70
319
75
40
5
400
Hanger
(
Use for hanging unit
)
28 347
Drain hose
53
Electric box
(
Possible to move,Right side
)
29
73
53
143
Indication panel
56
147
18
Wireless remote controller
Unit: mm
Page 28
26
CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR
MODEL RAC-25NH4
MODEL RAC-50NH4
16556
28 750
852
76
570
95
166
559
2616 280
195
340
280
Handle
Air suction
grille
10464
26 850
955
79
650
96
169.5
638
1010
10
320
340
Air outlet
340
2022 298
201
Handle
Holes for anchor bolt
(2-ø12)
Fixing hole
507 198
57
12 37
Notch for anchor bolt
(2-ø12 Notchs)
More than
More than
More than
100
More than
700
100
100
Service space
Page 29
27
MAIN PARTS COMPONENT
THERMOSTAT
Thermostat Specifications
FAN MOTOR
Fan Motor Specifications
CONNECTION
TEMPERATURE °C (°F)
INDICATION
16
INDICATION
24
INDICATION
32
MODEL RAD-25NH4/RAD-40NH4
THERMOSTAT MODEL IC
OPERATION MODE COOL HEAT
ON 14.9 (59.3) 20.4 (68.8)
OFF 14.3 (58.3) 21.0 (69.1)
ON 22.9 (73.7) 28.4 (83.1)
OFF 22.3 (72.7) 29.0 (84.1)
ON 30.9 (88.1) 36.4 (97.7)
OFF
30.3 (87.1) 37.0 (98.8)
M
RED
YEL
BLU
5V
0~35V
MODEL
RAD-25NH4 RAD-40NH4
POWER SOURCE DC: 0 ~ 35V
DC360V
OUTPUT 20W
40W
BLU : BLUE YEL : YELLOW BRN : BROWN WHT : WHITE
GRY : GRAY ORN : ORANGE GRN : GREEN RED : RED
BLK : BLACK PNK : PINK VIO : VIOLET
RED
360V
BLK
0V
WHT
15V
M
YEL
0~6V
BLU
0~15V
RAC-25NH4 RAC-50NH4
Page 30
– 28 –
WHITE
RED
YELLOW
MODEL
COMPRESSOR MODEL
PHASE SINGLE
RATED VOLTAGE AC 220 ~ 240 V
RATED FREQUENCY 50 Hz
POLE NUMBER 4
COMPRESSOR MOTOR
Compressor Motor Specifications
CONNECTION
20°C
(68°F)
75°C
(167°F)
( )
RESISTANCE VALUE
!
CAUTION
When the refrigerating cycle has been operated for a long time with the capillary tubes clogged or crushed or with too little refrigerant, check the color of the refrigerating machine oil inside the compressor. If the color has been changed conspicuously, replace the compressor.
2M = 1.05
2M = 1.28
(U)
(V)
(W)
M
M
M
WHITE
YELLOW
RED
RAC-25NH4 RAC-40NH4
JU1012D JU1013D
Page 31
MODEL RAD-25NH4 / RAC-25NH4
RAD-40NH4 / RAC-40NH4
WIRING DIAGRAM
– 29 –
SYSTEM POWER
MODULE 2
RED
BLK
WHT YEL BLU
GRN
BLK BLK
REVERSING VALVE
FAN MOTOR
M
BLU : BLUE YEL : YELLOW BRN : BROWN WHT : WHITE GRY : GRAY ORN : ORANGE GRN : GREEN RED : RED BLK : BLACK PNK : PINK VIO : VIOLET
INDOOR UNIT
C
RED
BRN
(
BRN
)
(
RED
)
TERMINAL
BOARD
D
BLU
YEL
BLU
YEL
CN16
RED
MAIN P. W . B .
BLK
WHT
WHT
REMOTE CONTROL
WIRELESS
LIGHT RECEIVING UNIT
BLK
BLK
RED
RED
GRY
GRY
CN12
CN8
CN10
EXCHANGER THERMISTOR
HEAT
THERMISTOR
ROOM TEMP.
BLK
BLK
BLK
M
RED
INDOOR FAN MOTOR
AUTO SWEEP
(STEPPING MOTOR)
MOTOR(RAD-BD
)
FLOAT SW
M
M
6
WHT
WHT
WHT
WHT
DRAIN PUMP M OTOR
CN11A
CN3
CN1
1
HA
CN9
C1 C2 M1 M2
1234
TEST
2
CN5
3 45678
OUTDOOR UNIT
COMPRESSOR
WHT
L2
L1
YEL
RED
WHT
UVW
YEL
YEL
YEL
YEL
R008
C006
C003
L001
CT1
DIODE STACK
VARISTOR3
MAIN P.W.B.
VARISTOR
C001
C002
R001
R007
COIL
NF COIL 1
25A FUSE
SURGE ABSORBER
BRN
C
D
L
RED
BLK
WHT
GRN
N
AC 220-240V
50Hz
CONNECTING
CORD
GREEN & YELLOW
GREEN & YELLOW
GREEN & YELLOW
POWER RELAY
3A FUSE
ICP
RELAY
REACTOR
RED
C501 C502 C503
CN14 CN14
10
5
5
CN11 CN11
CN12
CN12
2A FUSE
BLU
RED
GRY
DIODE STACK
CN13 CN13
C011
C010
R002
C007 C012 C014
C008
VARISTOR2
L002
CN6 WHT
C013 C015
R011
CN2 RED
POWER CIRCUIT
R010
GRY
OUTDOOR TEMPERATURE THERMISTOR
DEFROST THERMISTOR
OH THERMISTOR
ELECTRIC EXPANSION VAVLE
CN10
RED
CN9 BLU
CN8 WHT
CN15
WHT
GRY
GRY
GRY
RED
RED
Page 32
Remote Control
CIRCUIT DIAGRAM
– 31 –
1 2 3 4 5 6 7 8
10 11
13 14 15 16 17
19 20
9
12
18
SEG19 SEG18 SEG17 SEG16 SEG21 SEG24 SEG25 SEG26 SEG27 SEG28
NC NC NC NC NC NC NC NC NC
SEG20
SEG5 SEG0
SEG1
SEG2 SEG3 SEG4 SEG5 SEG6
SEG7 COM3 COM2 COM1 COM0
SEG14
SEG13
SEG12
SEG11
SEG13
SEG9
SEG8
40 39 38 37 36 35 34 33
31 30
28 27 26 25 24
22 21
32
29
23
40 39 38 37 36 35 34 33
31 30
28 27 26 25
32
29
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
48 47
46
45
44
43
41
42
65 66 67 68 69 70 71 72
74 75
77 78 79 80
73
76
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17 18
19
20
21
22
24
23
SEG20 SEG21 SEG22 SEG23 SEG24 SEG25 SEG26 SEG27 SEG28 SEG29 SEG30 SEG31 SEG32
SEG33 SEG34
SEG35
SEG19
SEG18
SEG17
SEG16
SEG15
SEG14
SEG13
SEG12
SEG11
SEG10
SEG9
SEG8
SEG7
SEG6
SEG5
SEG4
SEG3
SEG2
SEG1
SEG0
SEG43
SEG42
SEG41
SEG40
P40
P41
P42
P43
P00
P01
P02
P03
P10
P11
P12
P13
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
BEEP
P20
P30 P31
NCVL C1
VL C2 VL C3
XC IN
XC OUT
VDD
X OUT
X IN
RESET
CARR
P23 P22
P21
VSS
IC 1 M3455OM6A-504FP
LCD 1
C8
50v/1u
K 1 D3 RB425D(1/2)
K2K3
K4
K5
P10
P11
P12
K6
K7 K8
K9 K10
K11K12
K18
K17
K15 K16
K13 K14
D0
D1
D2
D3
R1
100k
SW1
R2
P
100k
R3
100k
R4
100k
R5
Q1 2SC3443 or 2SC2982
R6
R7
R9
D2D1
D1 D2
EL-1L7
D3
(1/2)
RB425D
R10 12M
K19
X1
C9
R11
R15
R16
R13
R14
910kHz
105
104
104
150k
X2
kHz
C4
C5
C6
C7
18p
22p
R12 220k
220K
220k
100k
100k
32.768
C1
C2
C3
220p
220p
334
R6 R9
24(1/8W)
R8
330
SW-187-2P
Key matrix table
Input
D3D2D1
D0
Output
Door open Automatic swingFan speed selectionOperation selectionStart/Stop
Door shut Automatic swingStart/Stop
Door open Day
present timeHour downHour upOn timer
Door shut Fan speedRoom temperature downRoom temperature up
Door open CancelReservationOff timer
Door shut Sleep
P10
P11
P12
Page 33
CIRCUIT DIAGRAM
MODEL RAD-25NH4
RAD-40NH4
– 33 –
Page 34
CIRCUIT DIAGRAM
MODEL RAC-25NH4
RAC-50NH4
– 35 –
Page 35
– 37 –
PRINTED WIRING BOARD LOCATION DIAGRAM
MODEL RAD-25NH4, RAD-40NH4
MAIN P.W.B.
Marking on P.W.B.
COMPONENT SIDE
SOLDERING SIDE
Page 36
– 38 –
MODEL RAC-25NH4, RAC-50NH4
MAIN P.W.B. Marking on P.W.B
COMPONENT SIDE
Page 37
– 39 –
Wireless receive circuit
Operation. Timer.
Auto sweep motor for Air deflector
Drain Pump Motor
LCD wireless
Heat exchanger thermistor
Room temperature thermistor
Reset circuit
Initial setting circuit
Temporary switch
Electric Expansion valve drive circuit
Electric
Expansion
valve
Outdoor microcomputer / HIC (AX-8N00)
Trip signal synthesis circuit
L
N
RAD-25NH4 / RAC-25NH4 RAD-40NH4 / RAC-50NH4
SPM2
Outdoor unit Terminal board
Indoor microcomputer (AX-7R11)
Page 38
– 41 –
47.
RAD-25NH4, RAD-40NH4
27 16
25
25
25
16
27
Page 39
– 43 –
Table 1 Mode data file
RAD-25NH4 RAD-40NH4
LABEL NAME VALUE
WMAX 4400 min
–1
5400 min
–1
WMAX2 4500 min
–1
5400 min
–1
WSTD 3500 min
–1
4700 min
–1
WBEMAX 2800 min
–1
3500 min
–1
CMAX 2700 min
–1
4700 min
–1
CMAX2 2800 min
–1
4700 min
–1
CSTD 2450 min
–1
4300 min
–1
CKYMAX 2200 min
–1
3500 min
–1
CJKMAX 1800 min
–1
2700 min
–1
CBEMAX 1600 min
–1
2000 min
–1
WMIN 1500 min
–1
1800 min
–1
CMIN 1500 min
–1
1800 min
–1
STARTMC 60 Seconds 60 Seconds
DWNRATEW 80% 80%
DWNRATEC 80% 80%
SHIFTW 5.00°C 5.00°C
SHIFTC 1.66°C 1.66°C
CLMXTP 30.00°C 30.00°C
YNEOF 20.00°C 20.00°C
TEION 2.00°C 2.00°C
TEIOF 9.00°C 9.00°C
SFTDSW 2.00°C 2.00°C
DFTIM1 50 Minutes 55 Minutes
DFTIM2 60 Minutes 60 Minutes
DFTIM3 90 Minutes 90 Minutes
Page 40
– 45 –
Reversing valve (heating on mode)
NOTE (9)
Notes: (1) Condition for entering into Cool Dashed mode. When fan set to “Hi” or Auto mode and temperature difference between indoor temperature and set temperature has a
corresponding compressor rpm (calculated value in Table 7) larger than WMAX.
(2) Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3°C (thermo off) and iii) when room temperature
has achieved setting temperature –1°C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change operation
mode. (3) During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3°C. After thermo off, operation continue in Fuzzy control mode. (4) Compressor minimum “ON” time and “OFF” time is 3 minutes. (5) During normal cooling mode, compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP. No time constrain if indoor temperature
is higher than CLMXTP. (6) When fan is set to “Hi”, compressor rpm will be limited to CKYMAX. (7) When fan is set to “Med”, compressor rpm will be limited to CJKMAX. (8) When fan is set to “Lo”, compressor rpm will be limited to CBEMAX. (9) During Cool Dashed, when room temperature reaches set temperature –1°C compressor rpm is actual rpm x DWNRATEC.
Temperature Calculated
difference compressor rpm
1.66 2265 min
–1
2 2435 min
–1
2.33 2600 min
–1
2.66 2765 min
–1
3 2935 min
–1
3.33 3100 min
–1
3.66 3265 min
–1
4 3435 min
–1
4.33 3600 min
–1
4.66 3765 min
–1
5 3935 min
–1
5.33 4100 min
–1
5.66 4265 min
–1
6 4435 min
–1
6.33 4600 min
–1
6.66 4765 min
–1
7 4935 min
–1
7.33 5100 min
–1
7.66 5265 min
–1
8 5435 min
–1
8.33 5600 min
–1
8.66 5765 min
–1
9 5935 min
–1
9.33 6100 min
–1
9.66 6265 min
–1
10 6435 min
–1
10.33 6600 min
–1
10.66 6765 min
–1
11 6935 min
–1
Table 2 ∆TCMAX
Note:
1. See the data in Table 1 on page 43 for each constant in capital letters in the diagrams.
Page 41
– 47 –
Notes:
(1) The sleep operation starts when the sleep key is pressed. (2) When the sleep key is set, the maximum compressor speed is limited, and the indoor fan is set to “sleep Lo”. (3) 30 minutes after the sleep key is set, the sleep shift of temperature starts, and upper shift is made at least 6 times. If 25˚C
is not reached after 6 shifts, shifts repeat unit 25˚C is reached. (4) The sleep shift upper value of set temperature is 28˚C. (5) After 6 hours, a shift down to the initial set temperature is made at a rate of 0.33˚C/5 min. (6) If the operation mode is changed during sleep operation, the set temperature is cleared, and shift starts from the point when
switching is made. (7) The indoor fan speed does not change even when the fan speed mode is changed. (8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue to be
counted. (9) If the set lime is changed during sleep operation, all data including set temperature, time, etc. is cleared and restarted. (10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Cooling Sleep Operation
Compressor speed
Horizontal air deflector
Shut
Horizontal
Facing down
Maximum speed
Indoor fan
Outdoor fan
Timer lamp
Operation lamp
Sleep key
(Cooling/dehumidifying set temperature = Remote control set temperature (+) SHIFTC)
Final set temperature (Cooling/dehumidifying set temperature (+) sleep shift)
Set to 7 hours
0.5hr
1.5hr
3hr
P1
2.5hr 3.5hr 6hr 7hr
Hi
See basic operation
Med
Lo (sleep)
Lo
Page 42
+
+
Delay
–1.33˚C
–0.66˚C
49
Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33°C) or less after 30 seconds from starting the operation, the operation is done assuming
as the preset temperature = (room temperature at the time) - (2°C). (2) The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute. (3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation. (4) The compressor is operated forcedly for 3 minutes after operation is started. (5) The minimum ON time and OFF time of the compressor are 3 minutes.
Page 43
– 51 –
1.33˚C.
SFTDSW
0.66˚C.
Fan speed set to "auto"
1 min.
Hi
Lo Hi Hi Hi
ultra Hi
Basic Heating Operation
Start
Stop Star t Start StopStop
Thermo
OFF
Thermo
OFF
Heating set temperature
(remote control set temperature
(+))
Start/stop switch
Thermo judgment
Indoor fan
Ultra-Hi
Hi
Med
Lo
Ultra-Lo
Operation lamp
Max.
Rating
3000
0
Compressor speed
Outdoor fan
Reversing valve (heating "on" model)
Thermo OFF
Dash period
TWMAX
Wtd
Defrost signal
Preheating judgment
30sec. 30sec.
10sec.
15sec. 15sec.
15sec. 15sec. 15sec.
10sec.
15sec.
15sec.
150sec. Delay
150sec. Delay150sec. Delay
3min.
Max. 3 min.
Preheating released
Control by heat exchanger temperature
Control by heat exchanger temperature
15sec.
Control by heat exchanger temperature
Control by heat exchanger temperature
Control by heat exchanger temperature
18˚C
10sec.
30sec. 30sec.
10sec.
30sec. 30sec.30sec. 30sec. 30sec. 30sec.
10sec.
Preheat released
WMIN
(WSTD)
(WMAX)
NOTE (11)
WMAX2
Notes: (1) Condition for entering into Hot Dashed mode. When fan set to “Hi” or Auto mode and i) Indoor temperature is lower than 18°C, and ii) outdoor temperature is lower than 10°C,
and iii) Temperature difference between indoor temperature and set temperature has a corresponding compressor rpm (calculated value in Table 3) larger than WMAX. (2) Hot Dashed will release when i) Room temperature has achieved the set temperature + SFTDSW. ii) Thermo off. (3) During Hot Dashed operation, thermo off temperature is set temperature (with shift value) +3°C. After thermo off, operation continue in Fuzzy control mode. (4) Compressor minimum “ON” time and “OFF” time is 3 minutes. (5) During normal heating mode, compressor maximum rpm WMAX will maintain for 120 minutes if indoor temperature is higher than 18°C. No time limit constrain if indoor temperature
is lower than 18°C and outdoor temperature is lower than 2°C. (6) During Hotkeep or Defrost mode, indoor operation lamp will blink at interval of 3 seconds “ON” and 0.5 second “OFF”. (7) When heating mode starts, it will enter into Hotkeep mode if indoor heat exchanger temperature is lower than YNEOF + 0.33°C. (8) When fan is set to “Med” or “Lo”, compressor rpm will be limited to WBEMAX. (9) In “Ultra-Lo” fan mode, if indoor temperature is lower than 18°C, indoor fan will stop. If indoor temperature is higher than 18°C + 0.33°C, fan will continue in “Ultra-Lo” mode.
During Hotkeep or Defrost mode, fan will continue in “Ultra-Lo” mode. (10) During Hot Dashed or outdoor temperature is lower than –5°C, compressor rpm is WMAX2. (11) During Hot Dashed, when room temperature reaches set temperature + SFTDSW compressor rpm is actual rpm x DWNRATEW.
Temperature Calculated
difference compressor rpm
1.66 1965 min
–1
2 2135 min
–1
2.33 2300 min
–1
2.66 2465 min
–1
3 2635 min
–1
3.33 2800 min
–1
3.66 2965 min
–1
4 3135 min
–1
4.33 3300 min
–1
4.66 3465 min
–1
5 3635 min
–1
5.33 3800 min
–1
5.66 3965 min
–1
6 4135 min
–1
6.33 4300 min
–1
6.66 4465 min
–1
7 4635 min
–1
7.33 4800 min
–1
7.66 4965 min
–1
8 5135 min
–1
8.33 5300 min
–1
8.66 5465 min
–1
9 5635 min
–1
9.33 5800 min
–1
9.66 5965 min
–1
10 6135 min
–1
10.33 6300 min
–1
10.66 6465 min
–1
11 6635 min
–1
Table 3 ∆TWMAX
Notes:
1. See the data in Table 1 on page 43 for each constant in capital letters in the diagrams.
Page 44
– 53 –
1 min
WMIN
TDF TDF TDF
TDF
TDF
TDF
Notes: (1) The sleep operation starts when the sleep key is pressed. (2) When the sleep key is set, the maximum compressor speed is limited to WSTD+2000/2, and the indoor fan is set
to sleep Lo. (3) 30 minutes after the sleep key is set, the sleep shift of set temperature starts. (4) The maximum sleep shift of set temperature is 5°C, and the minimum is 12°C. (5) If the operation mode is changed during sleep operation, the changed operation mode is set and sleep control
starts. (6) The indoor fan speed does not change even when the fan speed mode is changed. (Lo) (7) When defrosting is to be set during sleep operation, defrosting is engaged and sleep operation is restored after
defrosting. (8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue
to be counted. (9) If the set time is changed during sleep operation, all data including set temperature, time, etc. is cleared and
restarted. (10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Setting Defrosting Inhibit Period
D F T I M 3
D F T I M 2
Time
Outdoor temperature
– 1 0 – 5˚C0˚C
D F T I M 1
Notes: (1) The first inhibit time after operation start is set to DFTIM1. (2) From the second time onwards, the inhibit time is set according to the time required for
defrosting. Reverse cycle operation time [DEFCOL] : DFTIM1 is set. Reverse cycle operation time < [DEFCOL] : The time corresponding to outdoor tempera­ture is set.
Page 45
– 55 –
REFRIGERATING CYCLE DIAGRAM
MODEL RAD-25NH4
RAC-25NH4
COOLING, DEHUMIDIFYING, DEFROSTING
OUTDOOR UNIT
REVERSING VALV E
SUCTION TAN K
SERVICE VALVE
(3/8)
INDOOR UNIT
SINGLE-ENDED UNION (3/8)
COMPRESSOR
SINGLE-ENDED UNION (1/4)
SERVICE VALVE
(1/4)
ELECTRIC EXPANSION VALVE
STRAINER
STRAINER
CHARGING PIPE
HEATING
OUTDOOR UNIT
REVERSING VALV E
SUCTION TAN K
SERVICE VALVE
(3/8)
INDOOR UNIT
SINGLE-ENDED UNION (3/8)
COMPRESSOR
SINGLE-ENDED UNION (1/4)
SERVICE VALVE
(1/4)
ELECTRIC EXPANSION VALVE
STRAINER
STRAINER
CHARGING PIPE
Page 46
56
REFRIGERATING CYCLE DIAGRAM
MODEL RAD-40NH4
RAC-50NH4
COOLING, DEHUMIDIFYING, DEFROSTING
OUTDOOR UNIT
REVERSING VALV E
SUCTION TANK
SERVICE VALVE
(1/2)
INDOOR UNIT
SINGLE-ENDED UNION (3/8)
COMPRESSOR
SINGLE-ENDED UNION (1/4)
SERVICE VALVE
(1/4)
ELECTRIC EXPANSION VALVE
STRAINER
STRAINER
HEATING
OUTDOOR UNIT
REVERSING VALV E
SUCTION TANK
SERVICE VALVE
(1/2)
INDOOR UNIT
SINGLE-ENDED UNION (3/8)
COMPRESSOR
SINGLE-ENDED UNION (1/4)
SERVICE VALVE
(1/4)
ELECTRIC EXPANSION VALVE
STRAINER
STRAINER
ADAPTOR
ADAPTOR
12.7
Page 47
– 57 –
OPERATING SPECIFICATION
REFERENCE
OPERATION OPERATION MODE AIR DEFLECTOR
PRESENT CONDITION
KEY INPUT
THERMO. ON
(INTERNAL FAN
ON)
THERMO. ON
(INTERNAL FAN
OFF)
MAIN SWITCH
ON
MAIN SWITCH
OFF
CHANGE OF
OPERATION
STOP
DURING
OPERATION
DURING
OPERATION
STOP
DURING
OPERATION
DURING
OPERATION
EACH MODE
AUTO COOL
COOL
FAN
AUTO DRY
DRY
AUTO HEAT
HEAT
CIRCULATOR
AUTO DRY
DRY
AUTO HAET
HEAT
CIRCULATOR
COOL
FAN
DRY
HEAT
CIRCULATOR
EACH MODE
EACH MODE
STOP SWINGING AND MODE BECOMES INITIALIZING
CONDITION.
INITIALIZING CONDITION OF EACH MODE.
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
2 UPWARD
INITIALIZE
1 DOWNWARD
INITIALIZE
1 DOWNWARD
2 UPWARD
STOP AT THE MOMENT.
START SWINGING
1 DOWNWARD
2 UPWARD
3 DOWNWARD
STOP AT THE MOMENT.
START SWINGING
1 DOWNWARD
2 UPWARD
3 DOWNWARD
STOP AT THE MOMENT.
ONE SWING (CLOSING AIR DEFLECTOR)
1 DOWNWARD
2 UPWARD
INITIALIZE AT NEXT
OPERATION.
INITIALIZE AT NEXT
OPERATION.
STOP
DURING ONE SWING
STOP
DURING SWINGING
STOP
DURING SWINGING
TEMPORARY STOP
DURING SWINGING
STOP
DURING ONE SWING
STOP
DURING ONE SWING
STOP
DURING SWINGING
DURING
INITIALIZING
STOP
DURING SWINGING
AUTO SWING FUNCTION
MODEL: RAD-25NH4, RAD-40NH4
STOP SWINGING TEMPORARILY.
(SWING MODE IS CLEARED IF SWING COMMAND IS
TRANSMITTED DURING TEMPORARY STOP.)
START SWING AGAIN.
INPUT SIGNAL
Page 48
58
The reset circuit initializes the microcomputer program when power is ON or OFF.
Low voltage at pin 7 resets the microcomputer and Hi activates the microcomputer.
When power ON 5V voltage rises and reaches 4.4V, pin 1 of IC521 is set to Hi. At this time the
microcomputer starts operation.
When power “OFF voltage drops and reaches 4.2V, pin 1 of IC521 is set to “Low. This will RESET the
microcomputer.
DESCRIPTION OF MAIN CIRCUIT OPERATION
MODEL RAD-25NH4, RAD-40NH4
1. Reset Circuit
Fig. 1-1
Fig. 1-2
2
1
5
3
7
NORMAL : HI RESET : LO
RES
Microcomputer
C524
R521
C522
C521
R522
5V
0V
IC521
Voltage
5.0V
Reset enter at 4.2V
Reset release at 4.4V
voltage
5.0V
Voltage at pin
7
of microcomputer
Voltage supply to pin
2
of IC521
Page 49
59
2. Receiver Circuit
The light receiver unit receives the infrared signal from the wireless remote control. The receiver amplifies
and shapes the signal and outputs it.
3. Buzzer Circuit
Fig. 3-1 Buzzer Circuit
Sound wave
Metal diaphragm
V
Pizoelectric element
V
Fig. 3-2 Buzzer Operation
Microcomputer
Buzzer output
BZ
12V
0V
R722
Q722
30
BZ
When the buzzer sounds, an approx.
3.9kHz square signal is output from buzzer output pin of the microcomputer. After the amplitude of this signal has been set to 12Vp-p by a transistor, it is applied to the buzzer. The piezoelectric element in the buzzer oscillates to generate the buzzers sound.
Fig. 2-1
30
0V
0V
13
RECEIVER I/P
Microcomputer
R419 R611
C405
IRR
GND
V
out
V
DD
5V
C611
Page 50
60
4. Auto Sweep Motor Circuit
Fig. 4-1 shows the Auto sweep motor drive circuit; the signals shown in Fig.4-2 are output from pins
15 – 18 of microcomputer.
As the microcomputers outputs change as shown in Fig.4-2, the core of the auto sweep motor is excited
to turn the rotor. Table 4-1 shows the rotation angle of horizontal air deflectors.
Table 4-1 Auto sweep Motor Rotation
Rotation angle per step (˚ ) Time per step (ms.)
0.0882 10Horizontal air deflectors
Microcomputer pins Step width
Horizontal air
deflectors: 10ms.
Horizontal air deflectors
15
16
17
18
1234 5678
Fig.4-2 Microcomputer Output Signals
Fig.4-1
Microcomputer
18
17
16
15
IC711
C711
9
7
10
11
12
13
15
16
P.W.B. MAIN
14
6
5
4
3
2
1
8
0V
CN8
M
12V
1
2
3
4
5
6
7
8
9
10
AUTO SWEEP MOTOR FOR HORIZONTAL AIR DEFLECTOR
The air deflectors are driven by the stepping motors, which are instructed by the microcomputer.
The air deflectors on the left and right are each driven by two stepping motors.
The stepping motors and main unit are connected via relay connectors. The air deflectors will not operate
unless the relay connectors are connected: Securely connect the relay connectors identified by colors when attaching the panel.
Before removing the panel for servicing, be sure to disconnect the relay connector to protect the lead
wires.
Page 51
61
5. Room Temperature Thermistor Circuit
Fig. 5-1 shows the room temperature
thermistor circuit.
5
4
3
2
1
0
010
Room temperature (˚C)
Fig. 5-2
20 30 40
0V
Room temperature thermistor
0V
5V
Fig. 5-1
62
A
R305
C302
Microcomputer
Room temp. input
Voltage at
(V)
R301
0V
Heat exchanger temperature thermistor
0V
5V
Fig. 6-1
61
A
R306
C303
Microcomputer
Heat exchanger temperature input
R302
A
5
4
3
2
1
0
010
-10
Heat exchanger temperature (˚C)
Fig. 6-2
20 30 40
Voltage at
(V)A
6. Heat exchanger temperature thermistor circuit
The voltage at depends on the room
temperature as shown in Fig. 5-2.
The circuit detects the indoor heat
exchanger temperature and controls the following.
(1) Preheating.
(2) Low-temperature defrosting during cooling and dehumidifying operation.
(3) Detection of the reversing valve non-operation or heat exchanger temperature thermistor open.
The voltage at depends on the heat exchanger temperature as shown in Fig. 6-2.
A
A
Page 52
62
7. Initial Setting Circuit (IC401)
When power is supplied, the microcomputer reads the data in IC401 (E
2
PROM) and sets the preheating
activation value and the rating and maximum speed of the compressor, etc. to their initial values.
Data of self-diagnosis mode is stored in IC401; data will not be erased even when power is turned off.
Fig. 7-1
Microcomputer
External ROM
SCL SDA
0V
0V
0V
5V
5V 5V
C401
IC401 (E
2
PROM)
R404
R403
27 26
1
2
3
4
8
7
6
5
}
Page 53
63
Model RAC-25NH4, RAC-50NH4
1. Power Circuit
This circuit full-wave rectifies 220-240V AC applied between terminals L and N, and boosts it to a required
voltage with the active module, to create a DC voltage.
The voltage becomes 260-360V when the compressor is operated
(1) Active module
The active filter, consisting of a reactor and switching element, eliminates higher harmonic components contained in the current generated when the compressor is operated, and improves the power-factor.
(2) Diode stacks
These rectify the 220-240V AC from terminals L and N to a DC power supply.
< Reference >
In case of malfunction or defective connection:
Immediately after the compressor starts, it may stop due to abnormally low speed active error, etc.
The compressor may continue to operate normally, but the power-factor will decrease, the operation current will increase, and the overcurrent breaker of the household power board will probably activate.
In case of active module faulty or defective
connection:
Although the compressor continues to operate normally, the power-factor will decrease, the operation current will increase, and the overcurrent breaker of the household power board will probably activate.
< Reference >
If diode stack 1 is faulty, the compressor may stop
due to lp, anbormally low speed, etc. immediately after it starts, or it may not operate at all because no DC voltage is generated between the positive e and negative d terminals.
If diode stack 1 is faulty, be aware that the 25A fuse might also have blown.
If diode stack 2 is faulty, DC voltage may not be
generated and the compressor may not operate at all. Also, be aware that the 3A fuse might have blown.
L
25A FUSE
SURGE­ABSORBER
VARISTOR1
VARISTOR3
CT1
C009
L001
C001
C004C005
C006
R007
L002
JW6
R008
ICP RELAY
TB2
TB8
TB7 TB6
TB10 TB11 TB12
U V W
N1
L1 L2
3A FUSE
R002
C008
C007
C012
C013
C014
C015
DIODE
STACK 2 (RC2)
DIODE
STACK 1
(D25VB60)
VARISTOR2
C011
POWER CIRCUIT
R010R011
C002
C003
R001
0V
0V
NF COIL1
COIL
POWER RELAY
TERMINAL
BOARD
N
REACTOR
C010
SPM2
P1
Vdba
Fig. 1-1
Page 54
– 64 –
(3) Smoothing capacitor (C501, C502, C503)
This smoothes (averages) the voltage rectified by the diode stacks.
<Notes> Smoothing capacitor C501 is not available for model RAC-25NH4 and RAC-35NH4.
(4) Smoothing capacitor (C010, C011)
This smoothes (averages) the voltage rectified by the diode stack2. A DC voltage is generated in the same way as in Fig. 1-3. Voltage between + side of C010 and – side of C011 is about 330V.
(5) C001 to C003, C012 to C015, C007, C008, NF COIL1, COIL,
absorb electrical noise generated during operation of compressor, and also absorb external noise entering from power line to protect electronic parts.
(6) Surge absorber, Varistor 1, 2, 3,
absorbs external power surge.
(7) Inrush protective resistor (R007, R008)
This works to protect from overcurrent when power is turned on.
< Reference >
When inrush protective resistor is
defective, diode stack may malfunction. As a result, DC voltage is not generated and no operation can be done.
Be careful to avoid an electric shock as a
high voltage is generated. Also take care
not to cause a short-circuit through incorrect
connection of test equipment terminals. The
circuit board could be damaged.
Fig. 1-3
Fig. 1-2
a
b
OV
OV
OV
Vd
DC voltage (approx. 260-360V during operation)
Smoothing Capacitors
SPM2
Page 55
65
2. Indoor/Outdoor Interface Circuit
The interface circuit superimposes an interface signal on the DC 35V line supplied from the outdoor unit
to perform communications between indoor and outdoor units. This circuit consists of a transmiting circuit which superimposes an interface signal transmit from the microcomputer on the DC 35V line and a transmiting circuit which detects the interface signal on the DC 35V line and outputs it to the microcomputer.
Communications are performed by mutually transmiting and receiving the 4-frame outdoor request signal
one frame of which consists of a leader of approx. 100 ms., start bit, 8-bit data and stop bit and the command signal with the same format transmit from the indoor unit.
Communication signal from outdoor microcomputer to indoor microcomputer. At first outdoor microcomputer
will send a request signal (SDO) to indoor microcomputer. A high-frequency IF signal approx. 38 KHz is generated and modulated by the request signal (SDO) inside the outdoor microcomputer then output to pin 11 of microcomputer. This modulated IF signal is output to pin 30 of HIC and amplified by amp. This signal is superimposed to DC 35V line via C801 and L801. To prevent erroneous reception, the outdoor microcomputer is designed so that it cannot receive a signal while it is outputting a request signal. The receiving circuit in the indoor unit consists of a comparator and transistor. The interface signal from the outdoor unit on the DC 35V line is supplied to C821, where DC components are eliminated, and is then shaped by the comparator. The shaped signal is detected by diode, amplified by amp, and output to pin 49 of the indoor microcomputer. Fig. 2-2 shows the voltages at each component when data is transferred from the outdoor microcomputer to the indoor microcomputer.
Communication signal from indoor microcomputer to outdoor microcomputer. The request signal (SDO)
generates by indoor microcomputer is output to pin 50 , and amplifies by C801. IF signal approx. 38 kHz is generated by comparator, then modulate by the request signal from pin 50 of indoor microprocessor. This modulated IF signal is then amplified and superimposed to DC 35V line via L801 and C802 of indoor interface circuit. Fig. 2-3 shows the voltages at each component when data is transferred from outdoor microcomputer to indoor microcomputer. The circuit operation of the outdoor receiving circuit is same as indoor receiving circuit.
Page 56
66
Fig. 2-1 shows the interface circuit used for the indoor and outdoor microcomputers to communicate with
each other.
Indoor P.W.B.
Outdoor P.W.B.
Terminal board
Terminal board
CD
CD
D101
I/F 0V
C821 R821
C822
0V
0V 0V0V
5V 5V 5V
0V
0V
0V
5V
0V
C801
R829
R830
Q821
C824
0V
IC801
C823
R828
R823
R825
D821
R827
R826
0V
0V
0V
I/F 0V
0V
IF transmit output (SDO)
IF receive input (SDI)
MICROCOMPUTER
5V
0V
5V
5V
12V
5V 5V
5V
5V5V
5V
C802
R813
L801
R812
Q803
C803
C804
R811
Q802
Q801
R824
3 2
1
R822
R806
R807
R805
R803
R804
5
7
6
IC801
R810
50
49
IF transmit output (SDO)
HIC
IF receive input (SDI)
MICROCOMPUTER
11
30
68
29
0V
L801
L802
C801
C809
R802 Q801
5V
0V
R801
R803
0V
0V
0V
0V
0V
0V
0V0V
C808
NF COIL2
C810
C802
C806
C807
C812
C811
Interface relay
35V
(Communications from outdoor microcomputer to indoor microcomputer)
(Communications from indoor microcomputer to outdoor microcomputer)
Fig. 2-1 Indoor/outdoor interface Circuit
Page 57
– 67 –
Outdoor HIC
29
Pin
30
Pin
Indoor microcomputer
DC 35V line
49
Pin
50
Pin
100ms. Leader
33ms. 1 frame
0.7V
0V
5V
0V
5V
0V
5V
0V
35V
Indoor microcomputer
4.95ms. Transmit / receive switching time
33ms.
1 frame
Outdoor HIC
30
Pin
0V
29
Pin
5V
0V
50
Pin
5V
0V
49
Pin
5V
0V
DC 35V line
35V
Fig. 2-2 Voltages Waveforms of indoor / Outdoor Microcomputers (Outdoor to Indoor Communications)
Fig. 2-3 Voltages Waveforms of indoor / Outdoor Microcomputers (Indoor to Outdoor Communications)
Page 58
– 68 –
[Serial Communications Format during Normal Communications]
(1) Outdoor microcomputer (HIC) to indoor microcomputer
(2) Indoor microcomputer to outdoor microcomputer (HIC)
(3) Communications waveforms
1 frame = 100ms. + 33.3ms. x 8 + 4.95ms. = 371.35ms.
Outdoor message
Indoor message
[Example] When the outdoor message is all 0s
and indoor message is all 1s:
36 (V)
35 (V)
34 (V)
When reset
(approx. 10ms.)
Transmit/
receive
switching time
(4.95ms.)
Character No.
0
(33.3ms.)
1
(33.3ms.)
2
(33.3ms.)
3
(33.3ms.)
Character No.
0
(33.3ms.)
1
(33.3ms.)
2
(33.3ms.)
3
(33.3ms.)
Bit No = 0
Bit No = 0
07
0707077
07077
Leader
(100ms.)
When reset
(approx. 10ms.)
Leader
(100ms.)
Fig. 2-4
Page 59
– 69 –
[ Serial Communications Data ]
7
1/0
6
1/0
5
1/0
4
1/0
3
1/0
2
1/0
1
1/0
0
1/0
7
1/0
6
1/0
5
1/0
4
1/0
3
2
1
0
7
6
5
4
3
2
1
0
7
6
5
4
0
3
1/0
2
1/0
1
1/0
0
1/0
Character No.
Bit No.
Data
0 0 0 1/0 1/0 1/0 0 1/0 0 0 1/0 1/0 1/0 1/0 1/0
OVL up
Compressor command speed (0 LSB)
Compressor ON
Reversing valve
2-way valve
Fan (2 MSB)
Fan (1
Fan (0 LSB)
Capacity code (3 MSB)
Capacity code (2)
Capacity code (1)
Capacity code (0 LSB)
Indoor in-operation bit
Operation mode (2 MSB)
Operation mode (0 LSB)
Contents
0
1
2
3
(2) Indoor message
Operation mode (1)
Compressor command speed (1)
Compressor command speed (2)
Compressor command speed (3)
Compressor command speed (4)
Compressor command speed (5)
Compressor command speed (6)
Compressor command speed (7 MSB)
15/20(A)
Compressor minimum rotation speed (4 MSB)
Compressor minimum rotation speed (3)
Compressor minimum rotation speed (2)
Compressor minimum rotation speed (1)
Compressor minimum rotation speed (0 LSB)
7
0
6
0
5
0
4
0
3
0
2
0
1
1
0
0
7
1/0
6
1/0
5
1/0
4
1/0
3
2
1
0
7
6
5
4
3
2
1
0
7
6
5
4
1/0
3
1/0
2
1/0
1
0
0
1/0
Character No.
Bit No.
Data
1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0
Fan-7-step request
Actual compressor rotation speed (5 MSB)
Actual compressor rotation speed (4)
Actual compressor rotation speed (3)
Actual compressor rotation speed (2)
Actual compressor rotation speed (1)
Actual compressor rotation speed (0 LSB)
Compressor during operation
Compressor during operation
Outside temperature (7 MSB)
Outside temperature (6)
Outside temperature (5)
Outside temperature (4)
Outside temperature (3)
Outside temperature (2)
Outside temperature (1
Outside temperature (0 LSB)
Self-diagnosis (3 MSB)
Self-diagnosis (2)
Self-diagnosis (1)
Self-diagnosis (0 LSB)
Defrost request signal
During forced operation
Multi-bit
Contents
0
1
2
3
(1) Outdoor message
Page 60
70
3. Power Module Circuit
Fig. 3-1 shows the system power module and its peripheral circuit.
The three transistors on the positive e side are called the upper arm, and the three transistors on the negative d side, the lower arm.
+
W
U
V
W
W
+
V
V
+
U
U
A
+
DC
Compressor
motor
U coil
V coil
W coil
System Power module 2
+
C501
+
C502
+
C503
R24
0.35
m
H
Power relay
Coil
R007
R008
Inrush current
protection
relay
C006
R001
Noise filter
coil
L
N
Terminal
board
FUSE (25A)
Fig. 3-1 Power module circuit (U
+
is ON, V
is ON)
Page 61
71
DC 260-360V is input to system power module and system power module switches power supply current
according to rotation position of magnet rotor. The switching order is as shown in Fig. 3-2.
E
F
UVVW
Upper arm transistor
Lower arm transistor
Time
++T+
+
T
U
V
W
U transistor chopped
U transistor ON
ON
Voltage at
Upper arm transistor
Current at
Chopping period
260V-360V
A
+
-
B
At point E: U+ is ON, V– is ON (circuit in Fig. 3-1) At point F: U+ is chopped (OFF), V– is ON (circuit in Fig. 3-4)
[]
Upper arm transistor is controlled to ON/OFF by 3.3kHz chopper signal. Rotation speed of the compress
is proportional to duty ratio (ON time/ ON time + OFF time) of this chopper signal.
Time T in Fig. 3-2 shows the switching period, and relation with rotation speed (N) of the compressor is
shown by formula below;
Fig. 3-2 Switching order of power module
N = 60/2 X 1/T
Fig. 3-3 shows voltage waveform at each point shown in Figs. 3-1 and 3-4. First half of upper arm is
chopper, second half is ON, and first half of lower arm is chopper, second half is ON.
Fig. 3-3 Voltage waveform at each point
When power is supplied U
+
[ U–, because of that U+ is chopped, current flows as shown below;
(1) When U+ transistor is ON: U+ transistor [ U coil [ V coil [ V– transistor [ DC current detection
resistor [ Point (Fig. 3-1)
(2) When U+ transistor is OFF: (by inductance of motor coil) U coil [ V coil [ V– transistor [ Return
diode [ Point (Fig. 3-4)
A
B
B
Page 62
– 72 –
+
U
U
V
W
U
+
V
V
+
W
W
_
+
System Power Module 2
260V-360V
R24
DC current (Id) detection resistor
A
U coil
DC compressor motor
V coil
W coil
B
Fig. 3-5
Since current flows at point only when U+ transistor is ON, the current waveform at point becomes
intermittent waveform as shown in Fig. 3-3. Since current at point is approximately proportional to the input current of the air conditioner, input current is controlled by using DC current (Id) detection resistor.
<Reference>
If power module is detective, self diagnosis lamps on the control P.W.B. may indicate as shown below:
Simplified check of power module (Lighting mode when operated with compressor leads disconnected)
(1) Disconnect connector of 3-pole (WHT, YEL, RED) lead wire connecting to compressor located at the
lower part of electric parts box.
(2) Set to compressor operation state (other than FAN mode) and press Start/stop switch of remote
control.
(3) If normal operation continues for more than 1 minute (LD303 lights), power module is considered
normal.
Refer to other item (troubleshooting on page 94) for independent checking of power module.
Fig. 3-4 Power module circuit (U+ is ON, V– is ON)
Self-diagnosis
Self-diagnosis lamp and mode
lp (peak current cut)
LD301
Abnormal low speed
rotation
LD301
Switching incomplete
LD301
Blinks 2 times
Blinks 3 times
Blinks 4 times
Table 3-1
B B
B
Self diagnosis lamps (LD303, 302, 301)
P.W.B (Main)
Page 63
73
4. Power Circuit for P.W.B.
Fig. 4-1 shows the power circuit for P.W.B. and waveform at each point.
22
18
19
+
D908
R917
R915
D909
R918
L903
REG1
C911
20
21
+
D907
C910
R914
C912
16
17
+
C903
C907
+
+
C914
14
13
R916
L902
35V
17V
5V
FM–15V
I/F0V
0V
0V
0V
FM–0V
C913
D910
REG2
Q706
C924
R920
R921
R922
PQ2
1
1
2
4
3
4
3
1
2
2
3
PQ1
VR1
R923
C906
C918
R911
D906
C908
PQ1
12
C
11
D904
R908
R909
D903
D905
D911
R910
R901
C901
R902
R903
R002
Diode stack 2
(RC2)
R904
2 5
3 4
1
+
+
IC901
C011
C010
R011
R010
C905
D902
R906
L901
R907
Switching transformer (T1)
Fig. 4-1 Power circuit for P.W.B.
1
9
+
C919
+
C921
C920
12V
D912
R919
R925
R924 ZD904
C909
15
1 2
JW8
JW8
4 3
In the power circuit for P.W.B., power supply for microcomputer, peripheral circuits, and system power
module driver circuit and, as well as DC 35V, are produced by switching power circuit.
Switching power circuit performs voltage conversion effectively by switching transistor IC901 to convert
DC 330V voltage to high frequency of about 20kHz to 200kHz.
Transistor IC901 operates as follows:
(1) Shifting from OFF to ON
DC about 330V is applied from smoothing capacitors C010 Œ and C011 œ in the control power circuit.
With this power, current flows to pin of IC901 via R903 and R904 and IC901 starts to tum ON. Since voltage in the direction of arrow generates at point at the same time, current passing through R910 and D903 is positive-fed back to IC901.
4
C
Page 64
– 74 –
(2) During ON
The drain current at IC901 increases linearly. During this period, the gate voltage and current become
constant because of the saturation characteristics of the transformer.
(3) Shifting from ON to OFF
This circuit applies a negative feedback signal from the 12V output. When the voltage across C919
reaches the specified value, REG2 turns on and current flows to PQ2 1-2. This turns the secondary circuits on, sets IC901 pin 1 to “Hi”, and turns IC901 off.
(4) During OFF
While IC901 is on, the following energy charges the primary windings of the transformer:
Energy=LI2/2. Here, L : Primary inductance
I : Current when IC1 is off
This energy discharges to the secondary windings during power off. That is, C910, C911, C912, C914 is charged according to the turn ratio of each winding.
At the start, an overcurrent flows to IC901 because of the charged current at C910, C911, C912, C914.
The drain current at IC901 generates a voltage across R906. If it exceeds the IC901 base voltage, it sets
the IC901 gate voltage to “HI”.
R906 limits the gate voltage to prevent excessive collector current from flowing to IC901.
<Reference>
If the power circuit for P.W.B. seems to be faulty:
(1) Make sure that 5V and 12V on the control P.W.B., upper arm U, V and W, and the lower arm power
voltage are the specified values.
(2) When only the 5V output is low:
REG 1 (regulator) faulty, 5V-0V shorted, output is too high, or REG 1 is abnormal.
(3) When 12V and 5V are abnormal:
The following defects can be considered:
1 Fan, operation, power, rush prevention relay (shorting in relay, etc.) 2 Microcomputer is abnormal. 3 REG 1 (regulator is abnormal), etc.
Shorting on primary circuits. When shorting occurs in the secondary circuits, there is no abnormality in the primary circuits because of overcurrent protection. The voltage rises when an opening occurs in the primary circuits, or the feedback system is abnormal.
(4) When 15V and 17V are abnormal:
D908, D909 or drive circuit is abnormal.
(5) When all voltage are abnormal:
IC901, R906, etc. are possibly abnormal.
* If IC901 is abnormal, be aware that other components, such as the power module, REG (regulator), etc.
are possibly defective.
[When the switching power supply seems to be abnormal, the voltage between IC901 pin 4 (to be measured at the leads of R904 and R903) and IC901 pin 5 (to be measured at R906 lead) may be between 11 and 16V. This is because the protection circuit of IC901 is operating.]
Page 65
75
5. Reversing valve control circuit
Reversing valve control circuit can switch reversing valve ON/OFF according to instruction from indoor
microcomputer depending on the operation condition shows in Table 5-1.
Voltage at each point in each operation condition is approximately as shown below when measured by tester. (When collector voltage of Q701 is measured)
3
1
16
24
I/F 0V
0V
Fig. 5 – 1
D702
CN2
Q701
DC voltmeter or tester
Reversing valve
R701
R703
R219
Q705
FUSE RESISTOR
MICROCOMPUTER
PQ701
1
23
4
5V
HIC
I/F 35V
R702
V
Operation condition Collector voltage of Q701
Cooling
Heating
Dehumidifying
General operation of Cooling
In normal heating operation
MAX. rotation speed instructed by indoor microcomputer after defrost is completed
Defrosting
Sensor dry
About 35V
About 0.8V
About 0.8V
About 35V
About 35V
Table 5-1
Page 66
76
6. Rotor magnetic pole position detection circuit
A
B
C
D
E
18
19
20
Outdoor microcomputer
C605
+5V
0V
HIC
0V
+12V
WV U
C608
System power module
DC brushless motor for compressor
R604
R605
R606
R607
R601
R602
R603
R604
R603
R602
R608
C503
C502
C501
R611
R610
R609
0V
C606
0V
C607
0V
36
33
34
35
47
Fig. 6-1 Rotor magnetic pole position detection circuit and voltage waveform at each point
E
D
C
A
No power supplied
Upper armONNo power
supplied
No power supplied
Lower arm
ON
60 120 60 120
Induced voltage
Comparing process
60
Vd 150 ~330
Spike voltage
U phase terminal voltage
Drive signal
Pole position detection signal
(B) reference voltage (1/2Vd)
Detection point
W
+
W
+
U
+
U
+
U
V
V
W
V
+
To detect U phase, voltage at point C is produced by driving motor induced voltage signal (voltage at point A ) and
1/2 voltage of Vd (voltage at point B ), and comparing with comparator.
For V phase and W phase, voltage at point
D
and voltage at point E are produced in the same way as above. Voltage at point C is taken into indoor unit microcomputer, switching timing to U+ transistor from W+ transistor is produced by delaying 30° from rise waveform, ignoring spike voltage. In addition, switching timing to U-transistor from W-transistor is produced by delaying 30° from fall waveform.
For V phase and W phase, in the same way as above, drive signals are produced from voltages at point
D
and point
E
. Phases are shifted by 120° and 240°, respectively, comparing with U phase.
Page 67
77
7. Drive Circuit
Fig. 7-1 shows the drive circuit. The circuits for U phase, V phase and W phase have the same Configuration.
In low speed rotation mode (PWM range), as shown in Fig. 7-2, 0-5V chopper signal is ouput from microcomputer for each phase. S
ignal
output from microcomputer is ouput to IC1 and is inverted by active Lo to become 0-15V chopper signal; it is then drive the tra
nsistor
of each phase.
In high speed rotation mode (PWM range), as shown in Fig. 7-3, 0-5V drive signal is ouput from microcomputer for each phase (wi
th
no chopper because of full duty). Signal output from microcomputer is input to IC1 and is inverted by active Lo to become 0-15V
drive
signal; it is then drive the transistor of each phase.
Fig.. 7-1
6
5
4
3
2
1
MICROCOMPUTER
A
R512
R521
R511
R510
R509
R508
R507
10
9
4
3
2
1
8
7
6
5
1
13
14
15
16
17
18
1
23
11
8
7
5
4
10
6
3
9
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
19
20
21
2
3
4
5
6
7
8
9
10
12
22
B
B
B
45
44
43
42
41
38
39
40
46
IP CUTTER Id CONTROL CIRCUIT
0V
17V
R501
C404
CN14
17V
0V
PWB (MAIN)
SPM2
0V
17V
U
+
V
+
W
+
U
V
W
IP
Id
IC1
VCC
VCU
PGU
U
VCV
PGV
V
VCW
PGW
W
NGU
NGV
NGW
SVT
SWT
SUB
SVB
SWB
F
OC
CB
A
0
A
GL1
GL2
SUT
R502
R503
R504
R505
R506
Q506
R536
R535
R525
Q504
R534
Q503
R524
R533
Q502
Q501
R522
R532
R531
R526
Q505
R523
HIC
P2
N1
HIC
+
GRY
R24
U
COMPRESSOR MOTOR
V
W
Page 68
– 78 –
U
+
V
+
5V 0V
W
+
V
-
W
-
U
-
U
+
V
+
15V
0V
W
+
V
-
W
-
U
-
Drive signal at point B Drive signal at point A
V
+
U
+
W
+
V
+
U
+
V
-
W
-
U
-
V
-
W
-
[Low speed rotation mode]
[High speed rotation mode]
V
+
U
+
W
+
V
+
U
+
U
+
V
+
5V 0V
W
+
V
-
V
-
W
-
U
-
U
+
V
+
15V
0V
W
+
V
-
W
-
U
-
W
-
U
-
V
-
W
-
Drive signal at point
B
Drive signal at point
A
Fig. 7-2
Fig. 7-3
Page 69
79
8. HIC and Peripheral Circuits
Fig. 8-1 shows the micro computer and its peripheral circuits, Table 8-1, the basic operations of each
circuit block, and Fig. 8-2, the system configuration.
Table 8-1
Circuit block
Basic operation
Peak current cutoff circuit
Set value circuit
Voltage amplifier circuit
Reset circuit
Trip signal synthesis circuit
Detects DC current flowing power module and during overcurrent (instantaneous value) flows, stops upper/lower arm drive circuits and also produces lp signal by which drive signal output is stopped.
Compares voltage detected, amplified and input to HIC with set voltage value in microcomputer, and controls overload when set value exceeds input voltage.
Voltage-amplifies DC current level detected by the detection resistor and inputs this to microcomputer. Internal or external overload is judged in microcomputer.
Produces reset voltage.
Modulates chopper signal to drive signal and stops according to presence/ab­sence of lp signal or reset signal.
59
17
61
48
58
62
+
+
60
Is
D104
L
CT1
N
R005
0V0V
0V
0V
R221
C218
12V
R292
R247
C107
0V
0V
R006
C105
+
+
C217
C009
JW10
R252
R222
R248
IC4
C205
R288
IC5
+
2
3
1
+
6
5
7
Fig. 8-1 Microcomputer and Peripheral Circuits
RESET
Is
Id
Ip
Vd
CN13CN14
R41
R24
N1
IC1
SPM2 – HIC
DC260-380V
P2
SPM2
MAIN P.W.B
Direct Current
DC Current
Detection Resistor
OC
F
0V0V
HIC
IC1
C2260VR285
R286
D205
D204
R249
R284
0V
C225
C224
0V
0V
C222
0V
0V
C204
0V
C215
R289
0V
0V
5V
5V
R253
R500
R42
R43
C34
37
521
19
20
8
99
10
3938
MICROCOMPUTER
0V
R245
Page 70
– 80 –
Drive
signal
Chopper
signal
Chopper
signal
DC Current level
DC current
Detection
resistor
5V
DC 260V
-360V
Reset circuit
Over-load external
setting circuit
Current amplified
circuit
Drive
Circuit
IP signal
Reset Voltage
Peak current cut off circuit
Outdoor microcomputer
Trip signal
synthesis circuit
Compressor
motor
Powe r module
Fig. 8-2
The following describes the operations of each circuit in detail.
(1) Peak current cut off circuit Fig.8-3 Peak Current Cut off Circuit and Waveforms at Each Section.
DC current Id
Voltage at point
1.05V (1.35V for RAC-50NH4)
21A (27A, for RAC-50NH4)
Voltage at point
A
B
A
Fig.8-3
Detection
resistor
Negative Terminal
DC current
0V
0V
R43
0V
R41
QC
R42
SPM2
SPM2 – HIC
Main P.W.B
HIC
IC1
CN14
IP Outdoor microcomputer
F
R43
9 9
8
20 9 2 39 17
B
The Ip cut off circuit detects an instantaneous excessive current and stops inverter to protect parts such
as SPM2, etc.
As shown in diagram, if current exceeding 21A (27A for RAC-50NH4) flows, voltage at point recognized
by detecting resistor is input to pin of SPM2 – HIC, and voltage divided by R41 and R43 is input to pin
of IC1. Since threshold of IC1 is exceeded in this case, Lo signal is input from pin (Voltage at point . When Lo signal is input to pin of microcomputer, microcomputer stops drive output.
When drive output from microcomputer is stopped, all drive output goes Hi, and microcomputer is initialized
to enter drive signal standby mode. 3 minutes later, microcomputer outputs drive signal again, to start operation.
10
8
9
B
A
17
Page 71
– 81 –
(2) Overload control circuit (OVL control circuit)
Overload control is to decrease the speed of the compressor and reduce the load when the load on the
air conditioner increases to an overload state, in order to protect the compressor, electronic components and power breaker.
Overloads are judged by comparing the DC current level and set value.
Fig. 8-4 shows the overload control system configuration and Fig. 8-5 is a characteristic diagram of
overload judgement values. There are two judgement methods-external judgement which compares the externally set value with the DC current value regardless of the rotation speed and internal judgement which compares the set value that varies according to the rotation speed programmed in the microcomputer software with the DC current value.
To power module negative terminal
(R24)
DC current
Voltage amp
circuit
(Internal judgement)
DC voltage
Judgement value according to the rotation speed
(internal judgement value)
OVL judgement with respect to externally set value
A/D
converter
A/D
converter
Judgement OVL according to the rotation speed
Selects data according to the rotation speed and DC voltage
OVL start current data
Rotation speed data
Motor control process
Microcomputer
Detection
resistor
Fig. 8-4 Overload Control System Configuration
Fig. 8-5
DC current
Rotation speed
1. Overload external judgement circuit
Fig. 8-1. The filter consisting of R245 and C217 removes high harmonic components from the voltage
generated by the current flowing to Detection resistor; R245 and C217 average the voltage. This voltage is then input to IC4 pin is then amplified and supplied to microcomputer pin . The microcomputer compares this input with the internally set value, and if the input exceeds the set value, it enters overload control status.
Fig. 8-7 shows the rotation speed control. When the voltage at pin of the microcomputer exceeds the
set value, the microcomputer decreases the rotation speed of the compressor and reduces the load regardless of the rotation speed commanded by the indoor microcomputer.
5
60
60
Page 72
– 82 –
60
Fig. 8-6
Fig. 8-7
Voltage at microcomputer pin
Rotation speed of compressor
Deceleration DecelerationAcceleration Acceleration
Commanded rotation speed
Actual rotation speed
59
61
58
+
60
Is
D104
L
CT1
N
R005
0V0V
0V
0V
0V0V
R247
R006
C105
+
C217
C009
R222
C218
R221
R248IC4
+
6
5
7
Is
Id
Vd
CN13
CN14
R24
N1
DC 260-380V
SPM2
MAIN P.W.B.
P2
Direct Current
DC Current
Detection Resistor
HIC
IC1
Microcomputer
D205
D204
C224
0V
C222
0V0V
5V
5V
R253
R249
R500
+
C205
0V
5
1
373938
R245
10
1
2. Voltage amp. circuit
The voltage amp. circuit amplifies the DC current level detected by the detection resistor after being
converted to a voltage and supplies it to the microcomputer. Receiving this, the microcomputer converts it to a digital signal and compares it with the internal data to judge whether or not overload control is required.
< During overload control >
The filter consisting of R245 and C217 removes high harmonic components from the voltage generated
from the DC current flowing to the detection resistor, and supplies it to IC4 pin 5 IC4 forms a non-inverting voltage amp. circuit together with the peripheral elements.
The microcomputer stores the set values which vary according to the rotation speed. When the DC current
level exceeds the set value, the microcomputer enters the overload control state.
The set Value is determined by the amplification of the voltage amp. circuit.
Amplification : high [ DC current : low
Amplification : low [ DC current: high
{
Page 73
83
R500, R253, detect the DC voltage at the power circuit. The microcomputer receives a DC voltage (260-
380V) via HIC U and applies correction to the overload set value so the DC current is low (high) when the DC voltage is high (low).
(Since the load level is indicated by the DC voltage multiplied by DC current, R247, R248, R249 are provided to perform the same overload judgement even when the voltage varies.)
< During start current control >
It is required to maintain the start current (DC current) constant to smooth the start of the DC motor for
the compressor.
RAC-25NH4, RAC-35NH4, RAC-50NH4 uses software to control the start current.
The start current varies when the supply voltage varies. This control method copes with variations in the
voltages as follows.
(1) Turns on the power module's U+ and V– transistors so the current flows to the motor windings as shown in Fig8-9.
(2) Varies the turn-ON time of the W+ transistor according to the DC voltage level and the start is controlled so the start current is approx. 10A as shown in Fig. 8-10.
Fig. 8-8
DC current
G
0
0
Rotation speed
Amplification : low DC voltage : low DC current : high
Amplification : high DC voltage : high DC current : low
Amplification : 8.5 times DC voltage : 260V
U
+
U
V
+
V
W
+
W
U V
W
Compressor motor
DC current
Power module
DC 260-360V
Detection
resistor
Fig. 8-9
Fig. 8-10
20
15
10
5
0
DC current (A)
W transistor
ON-time
Start
DC voltage (start current)
Set value
Time
Chopper duty: high
DC voltage: low DC voltage: 280V DC voltage: high
Page 74
84
9. Temperature Detection Circuit
The Over heat thermistor circuit detects the temperature at the surface of the compressor head, the
Defrost. thermistor circuit detects the defrosting operation temperature.
A thermistor is a negative resistor element which has the characteristics that the higher (lower) the
temperature, the lower (higher) the resistance.
When the compressor is heated, the resistance of the Over heat thermistor becomes low and voltage at
pin 62 of microcomputer is increased.
Microcomputer compares the voltage present at pin
62
with the internal set value, if it is exceeded the
set value microcomputer judges that the compressor is overheated and stops operation.
When frost forms on the outdoor heat exchanger, the temperature at the exchanger drops abruptly.
Therefore the resistance of the Defrost. thermistor becomes high and the voltage at pin
63
of microcomputer drops. If this voltage becomes lower than the set value stored inside, the microcomputer starts defrosting control.
During defrosting operation the microcomputer transfers the defrosting condition command to the indoor
microcomputer via the circuit interface.
The microcomputer always reads the outdoor temperature via a thermistor (microcomputer pin
64
), and transfers it to the indoor unit, thus controlling the compressor rotation speed according to the value set at the EEPROM in the indoor unit, and switching the operation status (outdoor fan on/off, etc.) in the dry mode.
The following shows the typical values of outdoor temperature in relation to the voltage:
<Reference>
When the thermistor is open, in open status, or is disconnected, microcomputer pins 62 – 64 are approx. 0V; when the thermistor is shorted, they are approx. 5 V, and LD301 blinks seven times.
However, an error is detected only when the OH thermistor is shorted; in such a case, the blinking mode is entered 12 minutes after the compressor starts operation.
Table 9-1
Outdoor temperature (°C)
Microcomputer pin 5 voltage (V)
-10
1.1901.69102.23
20
3.22403.62
627
0V
+5V
O.H. thermistor
O.H.
Normal 2.7V or less Over heat 2.7V or more Reset 2.3V or less
CN8
636
0V
+5V
DEF. thermistor
DEF.
Normal 2.4V or more Over heat 2.4V or less Reset 2.9V or more
CN9
645
0V
+5V
Outdoor temperature thermistor
Outdoor temperature
Refer to the table 10-1
CN10
Microcomputer
HIC
Fig. 9-1
2.75
30
Page 75
85
10. Reset Circuit
The reset circuit initializes the microcomputer program when Power is ON or OFF”.
Low voltage at pin
48
resets the microcomputer, and HI activates the microcomputer.
Fig. 10-1 shows the reset circuit and Fig. 10-2 shows waveform at each point when power is turned on
and off.
When power is turned on, 12V line and 5V line voltages rise and 12V line voltage reaches 10.9V and
reset voltage input to pin 48 of microcomputer is set to Hi.
Reset voltage will be hold “Hi until the 12V line voltage drops to 9.90V even though the power shuts down.
Microcomputer
R252
R289
0V0V
R288
0V
5V
12V
HIC
R284
JW10
IC5 (1/2)
C204
48
RESET
Main
P. W . B
Fig. 10-1
C215
R286
C225
C107
C226
R285
0V
1
3
2
62
8
+
+
0V
0V
R292
12V line
12V line
5V line
5V line
Fig. 10-2
Reset voltage
Reset voltage
12
6
0
Power is ON
Voltage (V)
12
6
0
Power is OFF
Voltage (V)
Time
Time
Page 76
– 86 –
R297
R298
C208
R108
R107
C101
VSD
RC Filter
Motor coil
System power module
Power supply for DC fan motor from smoothing capacitor in system power module
Smoothing Capacitor
U
V
W
BOARD
DC Fan motor with control board
ONE CHIP DRIVER IC
R242
HIC
0V
0V
0V
0V
R283
R246
Q201
5V
PQ102
5V
5V
t
33.3KHz
Ap 7V
T/2
14
23
T
0V
0V
Vcc
PWM control voltage
FG Pulse
CN6
FM-0V
FM-15V
D101
Q101
R101
R102
Main P.W.B
CN12
FM-15V
FM-0V
12V
0V
0V
IC4
R244
Microcomputer
R243
D105
R104
R105
R103
R106
C104
C219
R114
C209
FM–60˚ el FG Pulse input
Fig. 11-1
1
3
60
61
59
2
8
15
75
65
+
+
C106
C103
ZD101
+
R115
7
6
5
4
3
2
1
321
123 4 5321
+++
2A-FUSE
11. Outdoor DC Fan Motor control circuit.
This model uses DC Fan Motor which has a controller circuit in the Motor.
This DC Fan Motor will rotate by control voltage apply to Vsp input. (Voltage range: 1.7 to 7V DC)
Vsp high : Faster ; Vsp low : slower ; Vsp lower than 1.7V : stop
Motor will output FG pulse by following this motor revolution.
Outdoor Microprocessor will output PWM control signal from FMCHOP terminal by following the instruction
from indoor Microprocessor.
This PWM control signal will convert to Vsp voltage by smoothing circuit (Q101 & RC filter)
Fan motor will start to rotate when Vsp was proceeding over than 1.7V, and generate FG pulse by rotation
speed.
FG pulse will feed back to Outdoor Microprocessor through PQ102.
PQ102 is the isolator between Microprocessor circuit and DC Fan Motor circuit, which has to match the Fan
Motor revolution with instructed revolution. Such as...
FG feedback: Faster – Instruction: Slower ... Decrease pulse width FG feedback: Slower – Instruction: Faster ... Increase pulse width
FG pulse is also used for Fan Motor failure detection
Microprocessor will monitor FG pulse 30 seconds after start the fan motor. If there is no signal detected, it
will consider that the Fan Motor was malfunction and stop the operation. In this case, LD302 on control PWB will blink 12 times. (Fan Motor lock detected)
R107 and IC4 are used for Fan Motor over current
Page 77
– 87 –
< Reference >
When operation stop with LD301 blinks 12 times, it may be caused by faulty DC fan motor.
In this case, please check CN6 and CN12 connection first. It makes Fan Motor Lock also if those
connectors are in misconnection.
DC Fan Motor has broken when 2A Fuse was burned. Please replace both DC Fan Motor and 2A Fuse
together.
It will makes Fan Lock Stopwhen something has disturb the Fan rotation by inserting materials into
propeller fan or ice has growing inside of outdoor unit by snowing.
It may make Fan Lock Stop by strong wind (ex. 17m/sec or above) against the Fan rotation. In this case,
unit will be restart again after a while.
In case of Fan Lock Stop even though the DC Fan Motor is rotating correctly, the possible casue is
Fan Motor problem or PQ102 on board or control board problem. Stop after the Fan motor runs 2 minutes, Fan Motor may be broken.
< Caution >
Please take care for the electrical shock by high voltage of DC Fan Motor power source which is common
with compressor when you are servicing this unit.
You can not confirm the coil and wiring of Motor due to the built in control circuit in Fan Motor.
Page 78
– 88 –
Power factor is controlled to almost 100%. (Effective use of power)
With IC in ACT module, control is performed so that input current waveform will be similar to waveform of input voltage
12. Power Factor Control Circuit
* Assuming the same current capacity (20A), power can be used about 10% effective, comparing with curent use (power factor of 90%), and maximum capacity is thereby improved.
I (input current)
V (input voltage)
Invalid power area
(Even if voltage is applied. current does not flow)
Effective
voltage
area
input voltage
input current
Effective
voltage area
Page 79
– 89 –
SERVICE CALL Q & A
Model RAD-25NH4
RAD-40NH4
COOLING MODE
The compressor has stopped suddenly during cooling operation.
Sound of running water is heard from indoor unit during dehumidifying.
Compressor occasionally does not operate during dehumidifying.
The circulation stops occasionally during Heating mode.
When the fan speed is set at HIGH or MED, the flow is actually Weak.
Heating operation stops while the temperature is preset at "30".
Check if the indoor heat exchanger is frosted. Wait for 3-4 minutes until it is defrosted.
If the air conditioner operates in cooling mode when it is cold, the evaporator may get frosted.
Normal sound when refrigerant flows in pipe.
Compressor may not operate when room temperature is 10°C or less. It also stops when the humidity is preset humidity or less.
It occurs during defrost­ing. Wait for 5-10 minutes until the condenser is defrosted.
At the beginning of heating, the fan speed remains LOW for 30 seconds. If HIGH is selected, it switches to LOW and again to MED after additional 30 seconds.
If temperature is high in the outdoor, heating operation may stop to protect internal devices.
DEHUMIDIFYING MODE
HEATING MODE
Q1
A1
Q2
A2
Q3
A3
Q4
A4
Q5
A5
Q6
A6
Page 80
– 90 –
AUTO FRESH DEFROSTING
AUTO OPERATION
NICE TEMPERATURE RESERVATION
INFRARED REMOTE CONTROL
After the ON/OFF button is pressed to stop heating, the outdoor unit is still working with the OPERATION lamp lighting.
Fan speed does not change when fan speed selector is changed during auto operation.
When on-timer has been programmed, operation starts before the preset time has been reached.
Does “Nice temperature reservation” function operate during dehumidifying?
Even if the same time is preset, the operation start time varies.
Timer cannot be set.
The current time display disappears soon.
The timer has been programmed, but the preset time disappears.
Auto Fresh Defrosting is carried out : the system checks the outdoor heat exchanger and defrosts it as necessary before stopping operation.
At this point fan speed is automatic.
This is because “Nice temperature reservation” function is operating. This function starts operation earlier so the preset temperature is reached at the preset time. Operation may start maximum 60 minutes before the preset time.
It does not work. It works only during cooling and heating.
This is because “Nice temperature reservation” function is operating. The start time varies according to the load of room. Since load varies greatly during heating, the operation start time is corrected, so it will vary each day.
Has the clock been set? Timer cannot be set unless the clock has been set.
The current time disappears in approx. 10 seconds. The time set display has priority.
Is the current time past the preset time? When the preset time reaches the current time, it disappears.
When the current time is set the display flashes for approx 3 minutes.
Q7
A7
Q8
A8
Q9
A9
Q10
A10
A11
Q12
A12
Q13
A13
Q14
A14
Q11
Page 81
– 91 –
OTHERS
Q15
A15
Q16
A16
Q17
A17
Q18
A18
Q19
A19
The indoor fan varies among high air flow, low air flow and breeze in the auto fan speed mode. (Heating operation)
This is because the cool wind prevention function is operating, and does not indicate a fault.
The heat exchanger temperature is sensed in the auto speed mode. When the temperature is low, the fan speed varies among high air flow, low air flow and breeze.
Loud noise from the outdoor unit is heard when operation is started.
When operation is started, the compressor rotation speed goes to maximum to increase the heating or cooling capability, so noise becomes slightly louder. This does not indicate a fault.
Noise from the outdoor unit occasionally changes.
The compressor rotation speed changes according to the difference between the thermostat set temperature and room temperature. This does not indicate a fault.
There is a difference between the set temperature and room temperature.
There may be a difference between the set temperature and room temperature because of construction of room, air current, etc. Set the temperature at a comfortable for the space.
Air does not flow immediately after operation is started.
Preliminary operation is performed for one minute when the power switch on and heating or dehumidifying is set. The operation lamp blinks during this time for heating. This does not indicate a fault.
Page 82
– 92 –
TROUBLE SHOOTING
Model RAC-25NH4
RAC-50NH4
PRECAUTIONS FOR CHECKING
Power source
+
~
+
~
ACT Module
+–+
N
C
D
L
Compressor motor
System power module 2
Indoor unit electric parts
Control P. W . B .
DC35V
0V
(0V)
MAIN P.W.B.
Power module
a
b
M
1. Remember that the 0V line is biased to 155-170V in reference to the ground level.
2. Also note that it takes about 10 minutes until the voltage fall after the power switch is turned off.
DANGER
Across a – b (0V line)....................
Across a – ground..........................
Across b (0V line)– ground............
approx 260-360V
approx 155-170V
approx 155-170V
When using an oscilloscope, never ground it. Don't forget that high voltages as noted above may apply to the oscilloscope.
DANGER
Always keep your hands and metallic things away from the enclosure of the oscilloscope.
DANGER!
Dont install
the ground
line.
Oscilloscope
Outdoor unit P.W.B.
Page 83
– 93 –
1. Turn OFF the Power supply to the outdoor unit.
2. After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover and apply soldering iron of 30 to 75W for 15 seconds or more to P2 and N1 terminals on system power module, in order to discharge voltage in smoothing capacitor.
3. Remove receptable of red/gray lead wire connected to system power module from diode stack before performing operation chech of each circuit.
Caution
Voltage of about 300-330V is charged between both ends of smoothing capacitors
During continuity check for each part of circuit in indoor unit electrical parts, disconnect red/gray lead wire connected from diode stack to system power module (SPM2) to prevent secondary trouble. (Be sure to discharge smoothing capacitor)
Do not use a soldering iron with transformer: If one is used, thermal fuse inside transformer will be blown
DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
WARNING
As shown above, apply soldering iron to metal parts (receptable) inside the sleeve corresponding to P1 and N1 terminals of system power module: Do this with smoothing capacitors kept connected. By removing red/ gray lead wire from diode stack, power supply can be shut off. (corresponding to + and – terminals of system power module)
N1
P1
Soldering iron
System power module
SPM2
Smoothing capacitors
SPM2
Smoothing capacitors
RAC-25NH4
RAC-50NH4
Page 84
94
CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING CYCLE
Model RAC-25NH4
RAC-50NH4
Does the timer lamp on the indoor unit blink?
Is the compressor in the outdoor unit operating?
Does the operation lamp on the indoor unit start to light or blink?
Remove the outdoor unit cover and electrical parts cover, and check self-diagnosis lamp LD301
Does LD301 blink one time ? * Repeats 0.25-second on and 2-second off.
Blinking other than one time
One-time blinking
Yes
Yes
Yes
Yes No
No
No
Normal
No
No
Timer lamp
Press the service switch for 1 sec. Does the compressor operate? (After checking, be sure to press the service switch to stop the operation).
Check the refrigerating cycle.
Check the outdoor electrical parts.
Check the indoor electrical parts.
Check to see whether the F­cable is connected incorrectly or disconnected
See Out door unit self-diagnosis lamp lighting mode .
See Troubleshooting when the timer lamp blinks .
Is approx. DC 33 to 37V being generated? Is the polarity correct?
Remove the terminal cover and check the voltage between terminal (C) and terminal (D)
Service switch
P. W. B Self diagnosis lamps (LD303, 302, 301)
CN17
IC3
022527
Page 85
– 95 –
TROUBLESHOOTING WHEN TIMER LAMP BLINKS. Model RAD-25NH4, RAD-40NH4 Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301 blink.
SELF-DIAGNOSIS LIGHTING MODE Model: RAD-25NH4, RAD-40NH4
No. Timer indicator flashing mode Reason for display Section of estimated fault
Four-way valve faulty
The room heat exchange temperature is low during heating, or it is high during cooling.
Outdoor unit forced operation
The outdoor unit is in forced operation or undergoing balancing after forced operation.
Indoor/outdoor interface faulty
The interface signal from the outdoor unit has been interrupted.
Outdoor electrical assembly defective.
Abnormal water level detection
All stop when the float switch has been activated.
Drain pump forced operation.
When the knob of drain pump test switch at Indoor P.W.B main slide to test position.
Room thermistor or heat exchanger thermistor is faulty
When room thermistor or heat exchanger thermistor is opened circuit or short circuit.
DC fan motor overcurrent detection
Overcurrent in indoor DC fan motor has been detected.
IC401 data reading fault
There was error in the data read from IC401
(1) Four-way valve faulty. (2) Disconnection in heat exchange
thermistor (only during heating)
Service SW in outdoor electrical parts turned ON.
(1) Indoor interface circuit (2) Outdoor interface circuit
Please check at the outdoor electrical led lamp blinking (LD301) and refer to self diagnosis lighting mode for outdoor unit.
(1) Drain stopped up (2) Drain pump (3) Float switch
(1) Indoor P.W.B. Main.
(1) Room thermistor (2) Heat exchanger thermistor
(1) Indoor fan locked (2) Indoor fan motor (3) Indoor P.W.B. Main
IC401 faulty
<Cautions>
(1) If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed.
(2) If the indoor unit does not operate at all, check to see if the F-cable is connected or disconnected.
(3) To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark 1).
1
2
3
4
5
6
7
8
9
( –– Lights for 0.35 sec. at interval of 0.35 sec..)
5
–– 7 times
– ––––– 3 times
– ––––––– Once
– –––––– Twice
–– 9 times
5 sec.
5 sec.
5 sec.
5 sec.
5 sec.
1
–– 6 times
5 sec.
–– 4 times
5 sec.
–– 10 times
5 sec.
–– 13 times
5 sec.
Page 86
– 96 –
SELF-DIAGNOSIS LIGHTING MODE
MODEL: RAC-25NH4, RAC-50NH4
Page 87
– 97 –
1. Power does not come on (no operation)
Is AC 220-240V AC being generated between terminals L and N on the outdoor unit terminal board?
Is DC 35V being generated between terminals C and D on the outdoor unit terminal board?
Check the indoor/outdoor unit connection cable, and correct any defective section (wrong connection, incomplete insertion reversed).
Check AC outlet and breaker, and repair any defective part.
Check the outdoor unit power circuit, and repair the defective section.
Is DC 35V being generated between terminals C and D on the terminal board?
Are control voltages (12V, 5V) being generated normally?
Check according to the proper method for checking the power circuit.
No No
No
No
Yes
Yes
Do the air deflectors perform initial operation when the power supply is turned on and off?
Check the indication P.W.B. connection cord and light receiving unit.
No
No
Is the microcomputer reset input (pin 7 ) Hi ?
Replace the P.W.B Main
Perform final operation check.
Check the reset circuit, and repair any defective section.
Yes
No
Is the microcomputer clock signal 10MHz at pin
10 11
being
generated normally?
Replace the microcomputer and oscillator.
Yes
Yes
Yes
CHECKING INDOOR UNIT ELECTRICAL PARTS
Page 88
98
2. Outdoor unit does not operate (but receives remote infrared signal)
Page 89
99
3. Only indoor fan does not operate (other is normal)
Is approx 20 V DC generated between pins 2 (blue) and 4 (red) of CN 10 when operated at high fan speed during cooling?
Are pulses of approx. 33 Vp-p generated at the collectors of Q901 in the fan operation mode? Are collectors of Q903 approx. O V?
Are microcomputer fan PWM outputs (micro computer pins r)Hi or are pulses output in the fan operation mode?
Has the fan been stopped by remote control?
Are microcomputer fan PWM outputs micro computer pins F Hi?
Is 5 V DC generated between pins
2
(blue) and 1 (yellow) of CN10?
Is there 1 or less between L901 and L902?
Replace indoor fan motor.
Check disconnection, etc of lead wires.
Replace Q901.
Replace L901.
Replace Q903.
Replace micro computer.
Perform final operation check.
Replace micro computer.
Replace Q903.
Replace Q901.
Replace micro computer.
Replace micro computer.
Replace the air deflector motor.Replace IC111.
Perform final operation check.
Perform final operation check.
Is there a voltage higher than 15V across C114 (12 V line)?
Is pulse signal output to micro computer pins %~* with air deflector set to auto during cooling?
No
Yes
No
No
Are the collectors of Q903 approx OV?
No
No
Yes
No
Yes
No
No
Yes Yes
No
Yes
Yes
Yes
4. Indoor fan speed does not change (other is normal)
5. Air deflector does not move (other is normal)
No
Yes
Yes
Page 90
100
6. All systems stop from several seconds to several minutes after operation is started (all indicators are also off)
Set to the "Hi" fan mode.
The operation lamp lights once and goes out in 5-10 seconds.
Disconnect, CN10 and set to the fan mode again.
The operation lamp lights once and goes out in 5-10 seconds.
Check to see if shorting, etc. has occurred in the P.W.B. pattern.
Can the indoor fan be lightly turned by hand? (Set the power switch to "off" to check.)
Replace the indoor fan motor.
Yes
Yes
Check to see if the indoor fan is touching the chassis, etc. If it does, repair.
No
Yes
No
Page 91
101
CHECKING THE REMOTE CONTROLLER
Page 92
– 102 –
MODEL RAC-25NH4, RAC-50NH4
[No operation or abnormal operation]
Is AC220-240V being
supplied to terminal L and N?
Is the 25A fuse normal?
If the 25A fuse has blown, be aware
that other parts may also be
defective (mainly, varistor 2, diode
stack, smoothing capacitors, system
power module, etc.).
No
Ye s
CHECKING THE OUTDOOR UNIT ELECTRICAL PARTS
Replace any defective parts.
Is the power circuit normal?
See the description on
power circuit for details.
Is 5V being generated
between Pin 4 (0V) and pin
3 (5V) at CN 18 (test pin)?
Operate the outdoor unit
according to the instruction
How to operate the outdoor
unit independently
.
How did the self-diagnosis
lamp (LD301) light?
Is the switching power circuit OK?
Has the 3A fuse blown?
See the self-diagnosis lamp
lighting mode.
Check to see whether the
connected C and D cable
correctly? If reversed, correct the
cable connection.
Replace any defective parts.
If the 3A fuse has blown, the
switching transformer (T1),
R906, etc. may also be
defective.
()
No
Ye s
Ye s
No
Ye s
Page 93
– 103 –
LD301 blinks 9 time.
Communication error.
Is DC 35V being output at
terminals C and D? (Normally,
DC 33-38.5V is output.)
Ye s
Interface relay
Coil terminal
Contact terminal
Is DC 35V being output across R914?
Is DC 12V being supplied across
the control side (coil terminal) of
interface relay?
Is a voltage (at least 10V) being
generated between the contact
terminals of interface relay?
Check the interface curcuit.
Ye s
Ye s
No
No
Ye s
D907 and C910 may be defective.
There is a defective section between the
12V output of switching power supply on
the main P.W.B. and interface relay (also,
check for contact with solder, etc.).
Repalce the interface relay.
No
Page 94
– 104 –
Ye s N o
No
Ye s
Ye s
Ye s
No
No
No
LD301 blinks 8 time.
Acceleration defect.
LD301 blinks 7 time.
Thermistor abnormal.
Is the power module normal?
Is the drive circuit normal?
Is the thermistor connector
disconnected?
The problem may be
forgetting
to connect after servicing
.
Is the continuity of thermistor normal?
Is the thermistor circuit normal?
Replace the power module.
Replace any defective parts.
Connect the thermistor.
Replace the thermistor.
Replace parts in the
thermistor circuit.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Page 95
– 105 –
LD301 blinks 6 time.
The temperature at the
OH thermistor rises.
LD301 blinks 5 time.
Overload lower limit cut.
LD301 blinks 4 time.
Failure of switching.
LD301 blinks 3 time.
Abnormal low speed.
Replace parts in the
thermistor circuit.
No
No
No
Check continuity of new parts.
Check continuity of pattern and
lead wires according to the
P.W.B. and schematic diagrams.
Ye s
Ye s
Replace system power
module or defective parts.
Replace the system power
module.
Replace any defective
parts.
Is the thermistor circuit normal?
Are R503, R541, R542, R549
and peripheral circuits of
system power module normal?
Replace the main P.W.B.
Is the system power module
normal?
Is the drive circuit normal?
Page 96
106
Page 97
107
POWER CIRCUIT
Phenomenon 1 <Rotation speed does not increase>
Is the DC voltage at least 350V?
Is the OVL lamp lit? If the lamp is lit, it does not indicate fault, but the unit is overload status.
Recheck cord, etc. of the system power module. If they are disconnected, connect them securely.
If abnormality continues, replace the system power module.
Overvoltage defect: system power module faulty (15-times blinking)
Ye s
No
Page 98
– 108 –
CHECKING THE REFRIGERATING CYCLE
1. Troubleshooting procedure (No operation, No heating, No cooling)
Connect U,V,W phase leads to the power module again and operate the air conditioner.
Gas leaks. Repair and seal refrigerant.
Is the self-diagnosis lamp mode as shown on the right?
YES
Gas leaking (less than 4kg/cm
2
G)
(less than 0.39 MPaG)
Normal (0.39-0.98 MPaG) (4-10 kg/cm
2
G)
Perform a final check of operation.
When the self-diagnosis lamp lights in the same condition as above.
The compressor is defective. Replace it and seal refrigerant.
If the compressor checker for an inverter type air conditioner is available, re-check using it.
( )
(JUDGING BETWEEN GAS LEAKAGE AND COMPRESSOR DEFECTIVE)
Blinking off
Time until the
lamp lights
Approx. 10 seconds
Approx. 10 seconds
Approx. 10 seconds
Within Approx. 30 seconds
Compressor
Compressor
Gas leakage
Possible
malfunctioning
part
LD301
Self­diagnosis lamp
Lighting mode
Blinks
2 times
Blinks
3 times
Blinks
4 times
Blinks
5 times
Blinks
6 times
Blinks
8times
Stop to operate and check the gas pressure in balancing mode.
Checking the system power module
Page 99
109
HOW TO CHECK SYSTEM POWER MODULE
+
+
+
– +
+
P1 P2 U
WV
N1
L2 L1
+
+
+
P1 P2 U
WV
N1
L2 L1
Checking system power module using tester
Set tester to resistance range (X 100) If indicator does not swing in the following conductivity check, the system power module is normal. (In case of digital tester, since built-in battery is set in reverse direction, + and – terminals are reversed.)
CAUTION
If inner circuit of system power module is disconnected (open), the indicator of tester will not swing and this may assumed as normal. In this case, if indicator swings when + and – terminals are connected in reverse of diagram below, it is normal. Furthermore, compare how indicator swings at U, V and W phases. If indicator swings the same way at each point, it is normal.
Page 100
110
HOW TO OPERATE USING THE SERVICE SWITCH THE OUTDOOR UNIT
MODEL RAC-25NH4, RAC-50NH4
1. Turn off the power supply to outdoor unit and then turn on again.
2. Remove the electrical box cover.
LD303 (red) will light and the unit will operate in the forced cooling mode at this time.
Never operate the unit for more than 5 minutes.
(Cautions) (1) If interface signal (DC 35V) terminals C and D are not connected when the outdoor unit is in forced cool mode, the outdoor
unit defect indicator (LD301) will blink 9 times during operation to indicate communication error.
(2) If checking is done with the compressor connector disconnected, the unit will continue normal operation when the
electrical parts are normal, or it will repeat operating for approx. one minute and stop due to overload power limit cut, or it will operate in the overload status.
Be sure to push the service switch again to stop the forced cool operation.
HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
The operation method is the same as How to operate using the connector to servicing the outdoor unit”.
1 The charging amount of 300g is equivalent to the load in normal operation.
Charge refrigerant of 300g after vacuuming (
1 )
Do not operate for more than 5 minutes
Parts to be prepared
(1) Reducing union
2/8 (6.35mm)
1/2 (12.7mm) (2) Copper pipe (2/8” and 1/2”) (3) Shorting leads
2 leads approx. 10 cm long
with alligator clip or IC clip
1. Connect the large dia. pipe side and small dia. pipe side service valves using a pipe.
Large dia. service valve
Reducing union (2/8” and 3/8”)
Copper pipe (2/8”)
Small diameter service valve
Reversing valve
Compressor
Outdoor unit
Connect the small diameter service value and the large diameter service valve using the reducing union and copper pipe as shown on the right.
Electrical Box Cover
Electrical Box Cover
RAC-25NH4
RAC-50NH4
Self diagnosis lamps (LD303, 302, 301)
Service switch
(forced-cooling mode is set by pressing for 1 second or more, and stopped by pressing again.)
Loading...