EH-TP500 Series
Operating Instructions
VER 1.00
4
Introduction
Introduction
The operational guidelines described below are information which relates to the device, installation,
transportation, storage, assembly, use and maintenance.
This Operating Instruction describes the main features of EH-TP500 Series operator panels. The
Manual refers to the following models:
EH-TP504
EH-TP507
EH-TP510
EH-TP513
EH-TP515
Operator interface with TFT color 4.3” display touchscreen
Operator interface with TFT color 7” widescreen display touchscreen
Operator interface with TFT color 10.4” display touchscreen
Operator interface with TFT color 13.3” widescreen display touchscreen
Operator interface with TFT color 15” display touchscreen
EH-TP500 Series
Operating Instructions
VER 1.00
5
Safety Guide
CAUTION
!
ATTENTION
!
DANGER
Safety Guide
The manual contains safety standards that must be respected for the personal safety and to avoid damage.
Indications of attention are divided into three levels of severity:
DANGER: indicates a failure to observe safety rules and such failure may cause death or serious injuries.
ATTENTION: indicates a failure to observe safety rules and that deficiency may cause damage.
CAUTION: indicates a failure to observe safety rules and that deficiency may cause defects to the
equipment or inconsistencies.
EH-TP500 Series
Operating Instructions
VER 1.00
6
Product Overview
1.
Product Overview
The Hitachi EH-TP500 Series HMI products combine state-of-the-art features and top performance
with an outstanding design. They are the ideal choice for all demanding HMI applications including
factory and building automation.
The EH-TP500 Series HMI panels have been designed to run the HiMobile software.
Designed for use with HiMobile HMI software.
Full vector graphic support. Native support of SVG graphic objects. Transparency and
alpha blending.
Full object dynamics: control visibility and transparency, move, resize, and rotate any object on
screen. Change properties of basic and complex objects.
TrueType fonts.
Multilanguage applications. Easily create and manage your applications in multiple languages to
meet global requirements. Far East languages are supported. Tools available in HiMobile Studio
support easy third-party translations and help reducing development and maintenance costs of the
application.
Data display in numerical, text, bar-graph, analog gauges and graphic image formats.
Rich set of state-of-the-art HMI features: data acquisition, alarm handling, scheduler and timed
actions (daily and weekly schedulers, exception dates), recipes, users and passwords, RSS feeds,
rotating menus.
Includes support for a wide range of communication drivers for Factory systems.
Multiple drivers’ communication capability.
Remote monitoring and control. Client-Server functionality.
On-line and Off-line simulation with HiMobile Studio.
Powerful scripting language for automating HMI applications. Script debugging improves efficiency
in application development.
Rich gallery of vector symbols and objects.
Optional plug-in modules for fieldbus systems, I/O and controllers.
EH-TP500 Series
Operating Instructions
VER 1.00
7
Standards and Approvals
2.
Standards and Approvals
The products have been designed for use in an industrial environment in compliance with the 2014/30/
EU EMC Directive.
The products have been designed in compliance with:
EN 61000-6-4 EN 55011 Class A
EN 61000-6-2 EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
The installation of these devices into the residential, commercial and light-industrial environments is
allowed only in the case that special in measures are taken in order to ensure conformity to EN 61000-6-
3.
The products are in compliance with the Restrictions on Certain Hazardous Substances (RoHS) Directive
2002/95/EC
In compliance with the above regulations the products are CE marked.
Product Identification
The product may be identified through a plate attached to the rear cover. You will have to know the type
of unit you are using for correct usage of the information contained in the guide.
An example of this plate is shown in the figure below:
EH-TP504
ETOP504H4P1
04/15
S.N. 00000000000
XXXXXXXXXXXXXXX version id of the product
product model name
product part number
month/year of production
serial number
EH-TP500 Series
Operating Instructions
VER 1.00
8
Technical Specifications
Environmental conditions
Operating temperature (surrounding
0 ÷ +50°C
EN60068-2-14
air temperature)
Storage temperature
-20 ÷ +70°C
EN60068-2-14
Operating and storage humidity
5 ÷ 85 % RH not-condensing
EN60068-2-30
Vibrations
Shock
Protection class
5 ÷ 9 Hz, 7 mm
p-p
9 ÷ 150 Hz, 1 g
± 50 g, 11 ms, 3 pulses per axis
IP66 front panel *
* The front face of the unit, installed in a solid panel, has been tested using conditions equivalent to
the standards shown in the “Environmentalconditions”. Even though the level of resistance unit is
equivalent to these standards, oils that should have no effect on the panel can possibly harm the
unit. This can occur in areas where either vaporized oils are present, or where low viscosity cutting
oil are allowed to adhere to the unit for long periods of time. If the front face protection sheet on the
panel becomes peeled off, these conditions can lead to the ingress of oil into the unit and separate
protection measures are suggested.
If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from
the panel, the original level of the protection cannot be guaranteed.
EH-TP500 Series
Operating Instructions
VER 1.00
9
Technical Specifications
Electromagnetic Compatibility (EMC)
Radiated disturbance test Class A EN 55011
Electrostatic discharge immunity test 8 kV (air electrostatic discharge) EN 61000-4-2
4 kV (contact electrostatic discharge)
Radiated, radio-frequency, 80 MHz ÷ 1 GHz, 10V/m EN 61000-4-3
electromagnetic field immunity test 1,4 GHz ÷ 2 GHz, 3 V/m
2 GHz ÷ 2.7 GHz, 1 V/m
Burst immunity test± 2 KV dc power port EN 61000-4-4
± 1 KV signal line
Surge immunity test± 0,5 KV dc power port (line to earth) EN 61000-4-5
± 0,5 KV dc power port (line to line)
± 1 KV signal line (line to earth)
Immunity to conducted disturbances 0.15 ÷ 80 MHz, 10V EN 61000-4-6
inducted by radiofrequency field
Voltage dips, short interruptions and Port: AC mains; Level:
voltage variations immunity test 100% duration: 1 cycle and 250 cycles (50Hz);
40% duration: 10 cycles (50Hz);
70%
duration: 25 cycles (50Hz);
Phase: 0°-180°
Test executed on the 230Vac side of the Exor International S.p.A. Power Supply EN 61000-4-11
Durability information
Backlight service life 40000 Hrs. or more
(LED type) (Time of continuous operation until the brightness of
the backlight reaches 50% of the rated value when the
surrounding air temperature is 25°C) - see Note 1
Front foil 10 years if the surrounding air temperature is 25°C
(without directly exposure to
sunlight or UV ray)
UV Resistance Indoor applications: After 300 hours cycled humidity
Touch screen reliability > 1 million operations
in QUV accelerated weathering, some yellowing and
brittleness may be present. - see Note 2.
Note 1: Extended use in environments where the surrounding air temperature is 40°C or higher may
degrade backlight quality/reliability/durability.
Note 2: Solvent resistance:
Contact for 1/2 hour at 21°C, No visible effect: Acetone, Butyl Cellosolve, Cyclohexanone, Ethyl Acetate,
Hexane, Isopropyl Alcohol, MEK, Methylene Chloride, Toluene, Xylene
Contact for 24 hours at 49°C, No visible effect: Coffee, Ketchup, Lemon Juice, Mustard (slight yellow
stain), Tea, Tomato juice.
EH-TP500 Series
Operating Instructions
VER 1.00
10
Technical Data
Model
EH-TP504
EH-TP507
Display / Backlight
TFT Color / LED
TFT Color / LED
Colors
64K 64K
Resolution
480X272
800X480
Diagonal (inches)
4.3”
7” widescreen
Dimming
yes yes
User memory flash
128MB
128MB
SD card slot
yes yes
Recipe memory
Yes. Flash memory storage
limited only by available memory
Yes. Flash memory storage
limited only by available memory
Serial Port
RS-232,RS-485, RS-422 DB9
female software configurable
RS-232,RS-485, RS-422 DB9
female software configurable
Ethernet port
2 10/100 Mbit with integrated
switch
2 10/100 Mbit with integrated
switch
USB port
1 Host interface version 2.0 and
1.1
2 Host interface, 1 version 2.0, 1
version 2.0 and 1.1
Expansion slot
1 Optional Plugin
2 Optional Plugin
Battery
rechargeable
rechargeable
Real Time Clock
yes yes
Voltage
10-32Vdc (*)
10-32Vdc (*)
Current rating (at 24VDC)
0.4A
0.65A
Weight
1 Kg
1 Kg
4.
Technical Data
(*) For applications requiring compliance with EN 61131-2 and specifically in reference to 10 ms voltage dips, the
minimum power supply voltage is 18Vdc,
EH-TP500 Series
Operating Instructions
VER 1.00
11
Technical Data
Model
EH-TP510
EH-TP513
Display / Backlight
TFT Color / LED
TFT Color / LED
Colors
64K 64K
Resolution
800X600
1280X800
Diagonal (inches)
10.4”
13.3” widescreen
Dimming
yes yes
User memory lash
256MB
256MB
SD card slot
yes yes
Recipe memory
Yes. Flash memory storage
limited only by available memory
Yes. Flash memory storage
limited only by available memory
Serial Port
RS-232,RS-485, RS-422 DB9
female software configurable
RS-232,RS-485, RS-422 DB9
female software configurable
Ethernet port
2 10/100 Mbit with integrated
switch
2 10/100 Mbit with integrated
switch
USB port
2 Host interface, 1 version 2.0, 1
version 2.0 and 1.1
2 Host interface, 1 version 2.0, 1
version 2.0 and 1.1
Expansion slot
2 Optional Plugin
2 Optional Plugin
Battery
rechargeable
rechargeable
Real Time Clock
yes yes
Voltage
10-32Vdc (*)
10-32Vdc (*)
Current rating (at 24VDC)
1A 1.2A
Weight
2.1 Kg
2.8 Kg
(*) For applications requiring compliance with EN 61131-2 and specifically in reference to 10 ms voltage dips, the
minimum power supply voltage is 18Vdc.
EH-TP500 Series
Operating Instructions
VER 1.00
12
Technical Data
Model
EH-TP515
Display / Backlight
TFT Color / LED
Colors
64K
Resolution
1024X768
Diagonal (inches)
15”
Dimming
yes
User memory lash
256MB
SD card slot
yes
Recipe memory
Yes. Flash memory storage
limited only by available memory
Serial Port
RS-232,RS-485, RS-422 DB9
female software configurable
Ethernet port
2 10/100 Mbit with integrated
switch
USB port
2 Host interface, 1 version 2.0, 1
version 2.0 and 1.1
Expansion slot
2 Optional Plugin
Battery
rechargeable
Real Time Clock
yes
Voltage
10-32Vdc (*)
Current rating (at 24VDC)
1.4A
Weight
3.5 Kg
(*) For applications requiring compliance with EN 61131-2 and specifically in reference to 10 ms voltage dips, the
minimum power supply voltage is 18Vdc,
EH-TP500 Series
Operating Instructions
VER 1.00
13
Technical Data
MODELABCDEF
EH-TP504
149mm/5.86”
109mm/4.29”
136mm/5.35”
96mm/3.78”
56mm/2.40”
4mm/0.16”
Cut out
4.1.
Dimensions
EH-TP500 Series
Operating Instructions
VER 1.00
14
Technical Data
MODELABCDEF
EH-TP507
187mm/7.36”
147mm/5.79”
176mm/6.90”
136mm/5.35”
47mm/1.85”
4mm/0.16”
EH-TP510
287mm/11.3”
232mm/9.13”
276mm/10.86”
221mm/8.70”
56mm/2.20”
4mm/0.16”
EH-TP513
336mm/13.22”
267mm/10.51”
326mm/12.83”
256mm/10.07”
56mm/2.20”
4mm/0.16”
EH-TP515
392mm/15.43”
307mm/12.08”
381mm/15”
296mm/11.65”
60mm/2.36”
4mm/0.16”
Cut out
EH-TP500 Series
Operating Instructions
VER 1.00
15
Technical Data
4.2.
Installation Environment
The equipment is not intended for continuous exposure to direct sunlight.
This might accelerate the aging process of the front panel film.
The equipment is not intended for installation in contact with corrosive chemical compounds. Check the
resistance of the front panel film to a specific compound before installation.
Do not use tools of any kind (screwdrivers, etc.) to operate the touch screen of the panel.
In order to meet the front panel protection classifications, proper installation procedure must be followed:
the borders of the cutout must be flat
screw up each fixing screw until the bezel corner get in contact with the panel.
the cutout for the panel must be of the dimensions indicated in this manual.
The IP66 is guaranteed only if:
max deviation from the plane surface to the cut-out: O0.5mm
thickness of the case where is mounted the equipment: from 1,5mm to 6mm
max surface roughness where the gasket is applied: O120 um
Applying the gasket
The gasket should be applied on the rear of the frame.
A. Gasket
B. Installation cut-out
Fig. 4.1: EH-TP504, EH-TP507
Fig. 4.2: EH-TP510, EH-TP513, EH-TP515
EH-TP500 Series
Operating Instructions
VER 1.00
16
Technical Data
CAUTION
Screw each fixing screw until the bezel corner gets in contact with the panel.
4.3.
Installation Procedure
Place the fixing brackets as shown in figure (Fig. 4.3).
Fig. 4.3
EH-TP500 Series
Operating Instructions
VER 1.00
17
Connections
EH-TP504
5.
Connections
1.
Serial Port
2.
2x Ethernet Port
3.
USB Port
4.
Power Supply
5.
Expansion slot for Plugin module
6.
SD Card Slot
Fig. 5.1
EH-TP500 Series
Operating Instructions
VER 1.00
18
Connections
EH-TP5xx
1.
Serial Port
2.
2x Ethernet Port
3.
USB Port (version 2.0 - 1.1)
4.
USB Port (version 2.0 High speed only)
5.
Power Supply
6.
2x Expansion slot for Plugin module
7.
SD Card Slot
Fig. 5.2
EH-TP500 Series
Operating Instructions
VER 1.00
19
Connections
Pin
Description
1
GND
2
3
TX
4
RX
5
6
+5V output
7
CTS
8
RTS
9
Pin
Description
1
GND
2
3
CHA-
4
CHB-
5
6
+5V output
7
CHB+
8
CHA+
9
5.1.
Serial Port
The serial port is used to communicate with the PLC or with another type of controller.
Different electrical standards are available for the signals in the PLC port connector: RS-232, RS-422
and RS-485.
The serial port is software programmable. Make sure you select the appropriate
interface in the programming software.
RS-422, RS-485
RS-232
SERIAL PORT
To operate in RS485 pins 4-3 and
8-7 must be connected externally.
The communication cable must be chosen for the type of device being connected.
EH-TP500 Series
Operating Instructions
VER 1.00
20
Connections
5.2.
Ethernet Port
The Ethernet port has two status indicators. Please see description in figure.
1
8
OFF: Valid link has NOT been detected
ON: Valid link has been detected
ON: No activity BLINKING: Activity
EH-TP500 Series
Operating Instructions
VER 1.00
21
Connections
5.3.
Optional plugin module
EH-TP500 Series panels have several optional plugin module, multiple modules configurations are
possible.
Slot#2 and Slot#4 are available only if plugin module has the “bus extension connector”.
Each slot carries three communication channels:
• 1 serial interface
• 1 CAN interface
• 1 SPI interface
Note: It is not possible to stack two modules that are using the same type of interface.
EH-TP500 Series
Operating Instructions
VER 1.00
22
Connections
Module
Application
Max Modules
Interface Type
Bus Extension
connector
EH-TPICNE
CAN
1 for EH-TP50x
2 for EH-TP51x
CAN
Y
EH-TPICN
CAN
1 for EH-TP50x
2 for EH-TP51x
CAN
N
EH-TPI232
Serial RS232
2
Serial
Y
EH-TPI485
Serial RS485
2
Serial
Y
EH-TPIPB
Profibus DP
1
SPI
N
Below you can find relation between modules and max number of modules that can be used into EH-TP500
Series panels, based on their Interface Type:
Max modules refers to max number of modules can be plugged into the HMI (all slots),
If you are planning to use EH-TPI232 and EH-TPI485 (additional serial ports) you will obtain following
“COM
- Slot#” association:
• a module plugged in Slot#1 or into Slot#2 will be COM2,
• a module plugged in Slot#3 or into Slot#4 will be COM3.
If you are planning to use two EH-TPICNE (CAN interface) you will obtain following Slot# association:
• a module plugged in Slot#1 or into Slot#2 will be the CanPort 0,
• a module plugged in Slot#3 or into Slot#4 will be the CanPort 1.
EH-TP500 Series
Operating Instructions
VER 1.00
23
Power Supply, Grounding and Shielding
Note: Ensure that the power supply has enough power capacity for the operation of the equipment.
6.
Power Supply, Grounding and Shielding
The power supply terminal block is shown in the figure below.
Fig. 6.1
The unit must always be grounded to earth. Grounding helps limit the effects of noise due to electromagnetic interference on the control system.
Earth connection will have to be done using either the screw or the fasten terminal located near the power
supply terminal block. A label helps identify the ground connection. Also connect to ground the terminal
3 on the power supply terminal block.
The power supply circuit may be floating or grounded. In the latter case, connect to ground the power
source common as shown in figure (see below) with a dashed line.
When using the floating power scheme, note that the panes internally connects the power common to
ground with a 1Mresistor in parallel with a 4,7nF capacitor. The power supply must have double or
reinforced insulation. The suggested wiring for the power supply is shown below.
Fig. 6.2
All the electronic devices in the control system must be properly grounded. Grounding must be performed
according to applicable regulations.
EH-TP500 Series
Operating Instructions
VER 1.00
24
Battery
ATTENTION
!
Dispose of batteries according to local regulations.
Battery
Battery
7.
Battery
These devices are equipped with rechargeable Lithium battery, not user-replaceable.
The following information is maintained by the battery:
hardware real-time clock (date and time)
Charge:
At first installation must be charged for 48 hours.
When the battery is fully charged, it ensures a period of 3 months of data back-up at 25°C.
Fig. 7.1: EH-TP504
Fig. 7.2: EH-TP507, EH-TP510,
EH-TP513, EH-TP515
EH-TP500 Series
Operating Instructions
VER 1.00
25
Cleaning Faceplates / Getting Started
8.
Cleaning Faceplates
The equipment must be cleaned only with a soft cloth and neutral soap product. Do not use solvents.
9.
Getting Started
EH-TP500 Series HMI products must be programmed with the software HiMobile Studio. HiMobile
Studio is a software tool that must be properly installed on a computer running Microsoft Windows.
There are two options to transfer a HiMobile application project to a HMI device:
Ethernet Connect the HMI device to the computer with an Ethernet network connection. From
HiMobile Studio choose the command Run/Download to target. You may have to
ensure that the proper firewall policy has been configured in the computer to allow
HiMobile Studio to access the network.
USB or SD Create an Update Package using HiMobile Studio and copy it to a USB Flash drive
or to an SD memory card.
EH-TP500 Series
Operating Instructions
VER 1.00
26
System Settings
10.
EH-TP500 Series HMI products have a system settings tool to allow configuration of system options.
The user interface of System Settings tool is based on a rotating menu. Use navigation buttons Next/
Back to scroll through the available options.
System Settings
The active item is highlighted on the left side. The info pane on the right side shows relevant
information, when applicable. Touch the active item to start the associated function.
System Settings has two modes of operation:
User Mode HiMobile runtime is running or the HMI device is in “factorydefault” status.
System Mode HiMobile runtime is not running or the HMI device has a software failure.
System Mode includes all options available in User Mode and offers in additions
commands dedicated to system upgrade and recovery.
Activation of System Settings in User Mode:
Factory default status Press “SystemSetting” button on the HMI screen
HiMobile runtime running Recall context menu and select “SystemSettings”. To recall the
context menu click and hold any unused area of the touchscreen for a
few seconds. Default hold time is 2 seconds.
EH-TP500 Series
Operating Instructions
VER 1.00
27
System Settings
Activation of Systems Settings System Mode:
Normal operation If HiMobile runtime is not running: Press “SystemSettings” button
on the HMI screen.
If HiMobile runtime is running: recall context menu, select “SystemSettings”
Select the Restart option then choose the “Configuration OS” option.
Note: To recall the context menu click and hold any unused area of
the touchscreen for a few seconds. Default hold time is 2 seconds.
Recovery operation If panel is not responsive, use the so-called “tap-tap” procedure. This
procedure consists in tapping the surface of the touchscreen during the
device power-up phase. Tapping frequency must be high. You have to start
tapping the touchscreen as soon as power has been applied to the device.
When the sequence has been recognized, the system shows the message:
“Tap Tap detected, Going to Config Mode” on the screen.
User Mode includes options for basic settings of the device.
Calibrate Touch calibrate the touchscreen interface
Plugin list show if optional plug-in modules are installed
Network
configure IP Address of Ethernet interface
BSP settingsshow the BSP (Board Support Package) version, check the operating hours
for the device and for the display backlight, manage the buzzer
Time
change the device date and time, including time zone, Daylight Saving Time
and NTP Server
Regional Settings customize Windows Regional Settings, such as date format
Display settings configure automatic backlight turnoff and adjust brightness
Close close System Settings
Restart
restart the device. “Main OS” option restarts as per default, “Configuration
OS” option restart panel directly into System Settings in System Mode
System Mode is the complete interface of the System Settings tool where all functions are available,
in addition to the options available in “UserMode”.
Format Flashallows to format internal device Flash disk. All projects, the Runtime
and System settings will be deleted, returning the device to factory
condition.
Restore Factory Settingsrestore factory settings with choice of what to delete. Can be used as
alternative to Format Flash. Options available are:
Uninstall HMI removes the Runtime and all projects.
Clear system settings reset the system parameters like IP Address,
date/time, etc
Clear Controller Application remove CODESYS application
.
EH-TP500 Series
Operating Instructions
VER 1.00
28
System Settings
Resize Image Area reserved to authorized technical personnel
Download Configuration OS update the Configuration OS module of BSP Download Main OS update the Main OS module of BSP
Download Splash Image replace the splash screen image displayed by the device at power-
up; the image must be supplied in the appropriate binary format. We
recommend changing the splash screen image with the use
of HiMobile Studio
Download OS Partition reserved to authorized technical personnel
Download Data Partition reserved to authorized technical personnel
Download Disk Image reserved to authorized technical personnel
Download Bootloader update the Bootloader module of BSP
Upload Bootloader reserved to authorized technical personnel
Upload Configuration OS reserved to authorized technical personnel
Upload Main OS reserved to authorized technical personnel
Upload Splash Image copy to an USB Memory or SD Card the current splash screen image
in binary format
Upload OS Partition reserved to authorized technical personnel
Upload Data Partition reserved to authorized technical personnel
Upload Disk-Image copy to an USB Memory or SD Card the content of whole Flash disk
in binary format
Only for EH-TP510, EH-TP513 and EH-TP515 System Mode includes also:
Download Main FPGA update the Main FPGA module of BSP
Download Safe FPGA update the Safe FPGA module of BSP
Download System Supervisor update the System Supervisor module of BSP
Upload Main FPGA reserved to authorized technical personnel
Upload Safe FPGA reserved to authorized technical personnel
Upload System Supervisor reserved to authorized technical personnel
EH-TP500 Series
Operating Instructions
VER 1.00
29
LED Indicator on Front Panel / Unpacking and Packing Instructions
LED Indicator
Status
Meaning
Symbol
Color
Red
ON
Hardware fault / Battery low
Green
ON
Normal operation
BLINK
Communication error
1
2
3
11.
LED Indicator on Front Panel
The table below shows the symbol of the LED indicator dedicated to special functions.
12.
Unpacking and Packing Instructions
To repack the unit, please follow the instructions backwards.