Prior to operation of this air compressor,
ensure that all operators read and
understand this INSTRUCTION
MANUAL completely, thereby operating
it safely and properly.
Place the INSTRUCTION MANUAL
near the air compressor to make it
available at any time, and refer to it as
the need arises.
● This INSTRUCTION MANUAL explains in detail
the important items that require attention;
observed as the following:
Always observe Instructions of WARNING,
●
CAUTION
considerable risks to safety.
WARNING
CAUTION
Air-Cooled
Water-Cooled
IMPORTANT
and IMPORTANT, as they indicate
GRAPHIC DESCRIPTIONS:
:Indicates warnings. If handled
improperly, death or severe injury
could result.
:Indicates cautions. If handled
improperly, injury and/or physical
damage could result.
:Indicates air-cooled type.
:Indicates water-cooled type.
:Indicates variable speed type.
:Indicates information that needs
attention, other than WARNING and
CAUTION.
:Indicates a reference page.
How to Use This Instruction Manual
● This Instruction Manual covers the standard models of the Hitachi DSP air compressor.
● This Instruction Manual intended to assist daily operators and maintenance personnel
in the installation, operation, control and service of the air compressor.
● Prior to operation of this air compressor, ensure that all operators read and understand
this INSTRUCTION MANUAL completely, thereby operating it safely and properly.
Place the INSTRUTION MANUAL near the air compressor to make it available at any
time, and refer to it as the need arises.
● If there are any questions or comments, please contact the local Hitachi distributor/
master dealer or representative office.
● Fill your compressor’s model name, Serial Number, etc. in Section 13 of this
Instruction Manual. Such information may be helpful when ordering parts, periodic
maintenance, and overhaul.
■ Model Code
Dry or Oil-Free Rotary
Screw Air Compressor
WARNING
Never remove a protective device from the air compressor or
modify the air compressor.
It is imperative to install an earth leakage (ground) circuit breaker
on the power cable. This prevents a ground fault accident.
DSP air compressors are not designed, intended or approved for
breathing air applications. Hitachi does not approve specialized
equipment for breathing air applications and assumes no responsibility or liability for compressors used for breathing air services.
DSP-90VA6N
NEXTseries
Frequency (5: 50 Hz, 6: 60 Hz)
Packaged
Cooling Method (A: air-cooled ,
W: water-cooled)
V: V type
without V: fixed-speed type
Nominal Output (kW)
● For improvement of the product, contents in this manual are subject to change without notice. Please be forewarned.
14. OPERATION RECORD LOGBOOK…………………………………………………………………………… 121
15. STANDARD SPECIFICATIONS………………………………………………………………………………… 122
1
1. SAFETY PRECAUTIONS
013B0816
012B1240012B1240
To ensure safe and proper operation of the air compressor, it is indispensable to carefully
read and understand the following warnings and instructions detailed below. These
warnings and instructions are attached to the air compressor as shown in the figure
below.
Air-Cooled
DSP- 90/110A6N
90/110VA6N
WARNING
Hot Surface!
●Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
●Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
Heated!!
WARNING
Rotating Parts!
●Keep hands and rods, etc. away from
the rotating parts (Cooling fans, etc.)
●Use caution at all times, when air com-
pressor is powered. The air compressor may be capable of restarting without hitting the START button.
●When the air compressor is operating,
do not remove or open the enclosure
panels and doors.
●
Before servicing the air compressor,
stop it, disconnect the power, especially when accessing any rotating parts.
Discharge Air pipe
Air End
WARNING
Hot Surface!
●Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
●Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
WARNING
Hot Surface!
●Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
●Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
Air End
Discharge Air Pipe
Heated!!
2
Aftercooler
Heated!!
Intercooler
1. SAFETY PRECAUTIONS
WARNING
Electric Shock Hazard!
●Before servicing or wiring the
air compressor, disconnect
the power. This will prevent
anyone from turning on the
power and causing an electric shock that could lead to
severe injury or death.
●Do not allow any unlicensed
person to wire the air compressor. Always use a licensed
electrician.
●Ground the air compressor.
WARNINGWARNING
Do Not Breathe Air!
Discharge air can contain Carbon Monoxide and
other contaminants. Breathing the air can cause
severe injury or death.
WARNING
Electric Shock Hazard!
●
Before servicing or wiring the air compressor,
disconnect the power. This will prevent anyone
from turning on the power and causing an electric
shock that could lead to severe injury or death.
●
Do not allow any unlicensed person to wire the air
compressor. Always use a licensed electrician.
●Ground the air compressor.
●
High pressure air can cause severe injury or death.
Be careful when air compressor is operating.
Pressurized air can blow out of air relief valves and
etc. at incredibly high velocities.
●When using compressed air to clean equipment,
use extreme caution and/or wear eye protection.
●Before servicing the air compressor, stop it,
disconnect the power, and relieve pressure before
removing filter, plug, fitting or cover.
WARNING
High Pressure Air!
Hot Surface!
●Do not directly touch the air end, discharge air
pipe,and coolers when the air compressor is
operating and immediately after it has stopped,
because these parts are heated then.
Before servicing the air compressor (especially
●
when accessing to the heated parts), stop it, disconnect the power, and wait until it is cooled down.
WARNING
●Keep hands and rods, etc. away from the rotating
Rotating Parts!
parts (Cooling fans, etc.)
●Use caution at all times, when air compressor is
powered. The air compressor may be capable of
restarting without hitting the START button.
●When the air compressor is operating, do not
remove or open the enclosure panels and doors.
●Before servicing the air compressor, stop it, dis-
connect the power, especially when accessing
any rotating parts.
3
1. SAFETY PRECAUTIONS
013B0816
012B1240012B1240
Water-Cooled
DSP- 90/110W6N
90/110VW6N
WARNING
Hot Surface!
●Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
●Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
Heated!!
Discharge Air pipe
Air End
WARNING
Rotating Parts!
●Keep hands and rods, etc. away from
the rotating parts (Cooling fans, etc.)
●Use caution at all times, when air com-
pressor is powered. The air compressor may be capable of restarting without hitting the START button.
●When the air compressor is operating,
do not remove or open the enclosure
panels and doors.
●
Before servicing the air compressor,
stop it, disconnect the power, especially when accessing any rotating parts.
Air End
Discharge Air Pipe
Heated!!
4
WARNING
Hot Surface!
●Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
●Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
Heated!!
Intercooler
WARNING
Hot Surface!
●Do not directly touch any component
inside the air compressor enclosure
when the air compressor is operating
or immediately after it has stopped,
as the components are extremely hot
and can cause severe injury.
●Before servicing the air compressor,
stop it, disconnect the power, then
wait for the air compressor to cool
down.
Aftercooler
1. SAFETY PRECAUTIONS
WARNING
Electric Shock Hazard!
●Before servicing or wiring the
air compressor, disconnect
the power. This will prevent
anyone from turning on the
power and causing an electric shock that could lead to
severe injury or death.
●Do not allow any unlicensed
person to wire the air compressor. Always use a licensed
electrician.
●Ground the air compressor.
WARNINGWARNING
Do Not Breathe Air!
Discharge air can contain Carbon Monoxide and
other contaminants. Breathing the air can cause
severe injury or death.
WARNING
Electric Shock Hazard!
●
Before servicing or wiring the air compressor,
disconnect the power. This will prevent anyone
from turning on the power and causing an electric
shock that could lead to severe injury or death.
●
Do not allow any unlicensed person to wire the air
compressor. Always use a licensed electrician.
●Ground the air compressor.
●
High pressure air can cause severe injury or death.
Be careful when air compressor is operating.
Pressurized air can blow out of air relief valves and
etc. at incredibly high velocities.
●When using compressed air to clean equipment,
use extreme caution and/or wear eye protection.
●Before servicing the air compressor, stop it,
disconnect the power, and relieve pressure before
removing filter, plug, fitting or cover.
WARNING
High Pressure Air!
Hot Surface!
●Do not directly touch the air end, discharge air
pipe,and coolers when the air compressor is
operating and immediately after it has stopped,
because these parts are heated then.
Before servicing the air compressor (especially
●
when accessing to the heated parts), stop it, disconnect the power, and wait until it is cooled down.
WARNING
●Keep hands and rods, etc. away from the rotating
Rotating Parts!
parts (Cooling fans, etc.)
●Use caution at all times, when air compressor is
powered. The air compressor may be capable of
restarting without hitting the START button.
●When the air compressor is operating, do not
remove or open the enclosure panels and doors.
●Before servicing the air compressor, stop it, dis-
connect the power, especially when accessing
any rotating parts.
5
2. GENERAL DESCRIPTION
2.1 Appearance
This section illustrates and describes the major components of the DSP air compressor. Be familiar
with the name, location and function of each component before using the DSP air compressor.
Air-Cooled
DSP- 90/110A6N
90/110VA6N
[Front View]
Air Exhaust
(Air Compressor Package)
This panel discharges
the hot air generated
in the air compressor.
Left Door
Open the left door only
when servicing the
DSP air compressor.
Keep it closed when
operating the DSP air
compressor.
OMR
8.5 for the details
Oil Filling Port
Use the port to fill the
gear case with oil.
Air Exhaust
Air Intake
Air Intake
Enclosure
Enclosure panels
lower the sound level
of the air compressor
package.
Instrument Panel
3.1
Plate of Operating /
Servicing Instructions
Read carefully the
plate before operating
and servicing the DSP.
Oil Level Gauge
This indicates the
quantity of the oil in
the gear case. Check
the oil level before
starting the DSP and
when operating it.
[Rear View]
Compressor Name plate
Model designation,
manufacturing number
and specification are
printed.
Air Intake
(Air for inverter)
Air Intake
Power Supply Port
Check the specifications, power supply
and voltage before
connecting the power
supply.
Air Intake
(Inlet to the Air End)
Air Exhaust
Compressed Air Discharge
Sling Fitting
Use the sling fitting
when moving and
installing the DSP air
compressor.
Air Intake
(Air for coolers)
6
Air Intake
Air Intake
Air Intake
(Air Compressor Package)
2. GENERAL DESCRIPTION [Appearance]
Water-Cooled
DSP- 90/110W6N
90/110VW6N
[Front View]
Air Exhaust
(Air Compressor Package)
This panel discharges
the hot air generated
in the air compressor.
Left Door
Open the left door
only when servicing
the DSP air compressor. Keep it closed
when operating the
DSP air compressor.
OMR
8.5 for the details
Oil Filling Port
Use the port to fill the
gear case with oil.
Air Exhaust
Air Intake
Air Intake
Enclosure
Enclosure panels
lower the sound level
of the air compressor
package.
Instrument Panel
3.1
Plate of Operating /
Servicing Instructions
Read carefully the
plate before operating
and servicing the DSP.
Oil Level Gauge
This indicates the
quantity of the oil in
the gear case. Check
the oil level before
starting the DSP and
when operating it.
[Rear View]
Air Intake
(Air for inverter)
Air Intake
Power Supply Port
Check the specifications, power supply
and voltage before
connecting the power
supply.
Air Intake
(Inlet to the Air End)
Air Exhaust
Compressed Air Discharge
Sling Fitting
Use the sling fitting
when moving and
installing the DSP air
compressor.
Air Intake
(Air for Package)
Air Intake
Air Intake
Air Intake
(Air Compressor Package)
7
2. GENERAL DESCRIPTION [Components]
2.2 Components
Air-Cooled
Hi-precooler
DSP- 90/110A6N
90/110VA6N
Discharge pipe (Compressed
Air Discharge)
Air relief valve
Cooling fan
Oil cooler
Check valve
Aftercooler
Intercooler
Enclosure
Instrument panel
Control panel
Oil mist remover
2nd-stage air end
1st-stage air end
Common base
Main motor
Air intake filter
Oil filter
Oil level gauge
8
2. GENERAL DESCRIPTION [Components]
Water-Cooled
Oil mist remover
DSP- 90/110W6N
90/110VW6N
Discharge pipe
(Compressed air discharge)
Intercooler
Aftercooler
Air relief valve
Cooling fan
Enclosure
Instrument panel
Control panel
2nd-stage air end
Oil cooler
1st-stage air end
Oil filter
Common base
Check valve
Main motor
Air intake filter
Oil level gauge
9
2. GENERAL DESCRIPTION [Daily Operating Components]
2.3 Daily Operating Components
Controls on the Instrument Panel
12
● Indicates the operation control section.
(
3.1)
● Power ON → The Power light ON.
● Start: Press the START button. → Start light ON.
● Stop: Press the UNLOAD STOP button. →
The compressor unloads for 5 minutes and then
stops. → Start light OFF.
● Power OFF: → Power light OFF.
MONITOR
AUTO
MONITOR
MENU
+/−
UP/
DOWN
SET
RUNNINGCONTROL
ALARM
FUNC
RESET
REMOTE
STR
[×10h]
SELECT/WIDE
1
RUNNINGMODE
REMOTE
LOAD
SHUTDOWN
2
START
POWER
AUTOSTART
STOP
UNLOAD STOP
Oil Level Gauge
● Verify that the oil stays between the upper and
lower red lines of the oil level gauge during the
operation.
Oil level might be higher than upper line during air
compressor
and pipings.
stopping due to oil returning from the cooler
Oil Filling Port
Lubricating Oil
34
Oil: Use genuine Hitachi GL-68 DSP Compressor Oil.
Replace the oil every 8,000h operating hour or every
2-year, whichever comes earlier.
Oil Level Gauge
Aftercooler and Intercooler - Condensate Drain Valve
● Verify that air containing condensate is discharged
intermittently from the intercooler and aftercooler
drain ports.
The higher temperature and humidity, the more condensate
is produced. Condensate may not be produced on the
intercooler side during winter.
[Fixed speed type]
Control pipe filter
drain port
Intercooler
drain port
Aftercooler
drain port
10
Intercooler
drain port
Aftercooler
drain port
Water-Cooled
2. GENERAL DESCRIPTION [Daily Operating Components]
Cooling Water
5
① Stop the cooling water flow when the DSP has
stopped running.
② Open the water drain peacock and the water drain
valve at the water drain port to remove the cooling
water from the system.
③Take care to completely drain the cooling water
during the winter season to prevent freezing in the
cooling water pipes (
Water drain peacock
8.3)
Control Line Filter
6
[Fixed speed type]
● Check the sight glass on the control line filter to
make sure that the condensate discharged
properly.
Control line filter
Sight Glass
Water drain port
Stopping operation
7
● Normally use the UNLOAD STOP button to stop
the air compressor. The air compressor then
unloads for 5 minutes and stops running.
(In the case of an emergency, press the
EMERGENCYSTOP button to stop operation.)
RUNNINGCONTROL
ALARM
FUNC
RESET
REMOTE
STR
MONITOR
AUTO
MONITOR
MENU
+/−
UP/
DOWN
SET
IMPORTANT
Keeping the second-stage air end as dry as possible
is essential for preventing it from rusting due to a long
term operation suspension. When stopping the DSP,
therefore, execute an unloading operation and thereby
remove the moisture from the second-stage air end.
[×10h]
SELECT/WIDE
1
RUNNINGMODE
REMOTE
LOAD
SHUTDOWN
2
START
POWER
AUTOSTART
STOP
UNLOAD STOP
11
3. OPERATING PROCEDURE
3.1 Instrument Panel
LCD monitor
Displays the operation data,
various settings, shutdown/
alarm information, etc.
( 3.3)
MONITOR ButtonRESET Button
Switches the monitor display.
( 3.3.1)
AUTO light (yellow)
ON (glowing) when an
automatic operation (an
AUTO operation, a scheduling operation, or lead/lag
operation) is activated.
ON (blinking) when external
calendar or scheduling
operation is abnormal.
( 3.3.3, 3.3.5)
Resets SHUTDOWN
and ALARM screens.
( 3.3.3)
AUTO
MONITOR
MENU Button
Displays the menu screen.
Also used to move the
cursor. ( 3.3.4)
+/- UP DOWN Button
Moves the cursor.
( 3.3.4)
MONITOR
Saves any adjusted set
points.
SET Button
MENU
+/−
UP/
DOWN
SET
Contrast adjustment
SET + [ ] buttons:
Increases brightness.
SET + [] buttons:
Decreases brightness.
( 3.3.6)
12
Digital Monitor
Used for basic settings as well
as other various settings in
combination with the LCD monitor.
( 3.3.6)
● ALARM light (green): Blinks if
an alarm failure occurs.
3. OPERATING PROCEDURE [Instrument Panel]
EMERGENCY STOP button
Stops for emergency.
( 3.2.3)
G
E
R
N
E
M
E
S
C
P
T
O
RUNNING MODE Light
● POWER light (yellow): Lights up when the main power
is turned on.
● REMOTE light (green):
ON (glowing) when the REMOTE button is pressed in
order to activate a remote operation.
ON (blinking) when an external remote-operation-
activation switch has been turned on in order to
activate a remote operation. ( 3.4.6)
● LOAD light (yellow): ON (glowing) when the air
compressor is loading.
● AUTO START light (green):
ON (glowing) while the air compressor is in a stop due
Y
to an AUTO operation,lead/lag operation, or
scheduling operation.
ON (blinking) while the air compressor is in a stop due
to a restartable instantaneous power interruption.
( 3.3.3)
● SHUTDOWN light (red): Blinks if a shutdown failure
occurs. ( 3.3.3)
RUNNINGCONTROL
REMOTE
ALARM
[×10h]
FUNC
Press this button to stop the air compressor.
The air compressor will stop after removing the
condensate from the air end.
※This stop button is effective while a stand alone operation.
RESET
REMOTE
STR
SELECT/WIDE
1
LOAD
SHUTDOWN
2
RUNNINGMODE
POWER
AUTOSTART
START
UNLOAD STOP
STOP Button
Stops the compressor
immediately without unloading.
( 3.2.2)
STOP
UNLOAD STOP Button
Stops the compressor in normal
state.
The compressor stops running
after removing the condensate
from the air end. ( 3.2.2)
REMOTE Button
Activates or deactivates a
remote start/stop operation
locally or on the instrument
panel. ( 3.4.6).
SELECT/WIDE Button/Light (Yellow)
Press to confirm the measurement
values, shutdown history, and
setting status. ( 3.4.1, 3.4.2)
To set the ECOMODE [Energy
saving mode] (Fixed speed type
only), hold down the
SELECT/WIDE
button for at least 7 seconds. The
light blinks and ECOMODE is set.
START Button
Starts the air compressor.
The START light turns ON while
air compressor is running.
13
3. OPERATING PROCEDURE [Start/Stop Operation]
3.2 Start/Stop Operation
3.2.1 Connecting the Power
When the power is connected, the POWER light turns
ON and the following Hitachi logo display appears on
the LCD. After 5 seconds, monitoring display appears;
it shows operation type, discharge air pressure, total
operating hours, etc.
When the START button is pressed, the START light
turns on and the compressor star ts operating.
When the compressor starts running, the asterisk on
the right side of running hours blinks and running time
starts to be counted.
To stop the operation, press the UNLOAD STOP
button. Operation stops after 5-minute drying of air end
and air piping.
To stop the compressor immediately without
unloading, press the STOP button.
Note) If the STOP button is pressed during unloading,
the compressor stops immediately.
IMPORTANT
(1) The air compressor does not start for 10 second after
power on to secure the safety.
For
15 seconds after power-on, the AUTO START light will
blink up to 10 seconds for operation preparation and
then the compressor starts running.
(2) Make sure that the door is closed before starting the
air compressor.
(3) Buttons, such as START/STOP/RESET function shall
be pressed for more than 0.3 seconds.
, if the START button is pressed within 10 to
3.2.3 Emergency Stop
※ The asterisk blinks when the clock and total
running hours are active.
If phase is reversed, “Connection Error: Reverse
Phase” will be displayed on the LCD monitor as a
setting/connection check message. In this case,
exchange 2 out of the 3 main power cables. If the air
compressor has control transformer in the control
panel, Open Phase is indicated as Reverse Phase. So
check the power cable connection of T Phase.
In case of open phase, “Connection Error: Open Phase” will be displayed on the LCD monitor. In this
case, check the power cables.
Pressing EMERGENCY STOP button, the DSP
compressor immediately stops.
This switch should only be pressed in emergency.
The compressor can not be restarted until the switch is
manually reset.
Turn the switch knob clockwise and press the RESET
button to reset.
14
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
3.3 How to Use the Liquid Crystal Display (LCD)
3.3.1 How to Move between the Various Displays
■Monitoring Displays
There are three monitoring displays as shown
below. This monitoring display is the top screen.
The monitoring display switches every time the
MONITOR button is pressed.
About the LCD Backlight
(1) In the event that no button has been used for 10
minutes, the LCD backlight automatically turns OFF for
protection to the display panel. It comes ON again if
any button is pressed, other than the START and STOP
buttons.
(2) If an event happens while the LCD backlight is off, the
backlight automatically turns ON and stays ON as long
as the event exists. Remote and instant stop mode
can't be set by the LCD monitor. Set after referring to
“3.4 How to Use the Digital Monitor.”
■ Message Display
Automatic restart/stop messages after shutdown or
warning occurrence and inspection/maintenance
messages is preferentially displayed in the Monitor
Display 3.
By pressing the MONITOR button here, the display
can be switched but is back to the Monitor Display 3
after approximately 10 seconds.
15
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
Displayed when stop is limited for AUTO
operation (Standard: no symbol)
fixed speed type.
3.4.8)
(
INTE : Indicates fixed speed type used the standard, 2-step
䠆
control system.
AUTO : Indicates fixed speed type used the automatic motor
stop/restart capacity control system.
(10)
VSDB : Indicates Vtype without the AUTO capacity control.
VSDA : Indicates Vtype with the AUTO capacity control
(standard setting for Vtype).
EXIT : Indicated the external capacity control is used.
(11)
MR : Indicates multi unit control system through the
communication is used
IMPORTANT
“CURRENT” reading is an approximate S-phase Amp
reading.
“OUTPUT” reading is an approximate calculated power
reading.
(1) Indicates current time. An asterisk blinks.
(2) Indicates the control state.
(3) Indicates a discharge pressure (DIS.PRESS)
(4) Indicates total running hours (RUN HOUR), total
loaded hours (LOAD HOUR), and total number of
loads (LOAD TIMES).
Blinking asterisk means counting the running
hours.
(5) Indicates a percentage of load to unload of the DSP
air compressor (LOAD RATE).
For Vtype, the rate is calculated based on only
frequency. Indicates “***”, if PQ wide mode is
selected.
(6) Indicates the amperage current of the package
input (CURRENT).
(7) Indicates the operating frequency of the main motor
(FREQUENCY).
(8) Indicates “***” for this air compressor.
(9) Indicates (MASTER), when the air compressor is
master in lead-lag operation.
(10) Indicates each pressure and temperature. “***”
indicates not in use.
(11) Indicates the number of hours until the next
maintenance service (HR. TO MAINT), and the
next maintenance type (NEXT MAINT).
16
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
3.3.3 Message Displays
■ Shutdown Messages
① When the shutdown occurs for the compressor, the SHUTDOWN light and shutdown contents on the LCD
monitor (contents are displays on the left side and details are displayed on the right side) blink and the
compressor stops running. There are 2 types of screens for shutdown: SHUTDOWN and FAILURE.
(Example)
When the PROBLEM and BATTERY OUT blink, it indicates
the battery replacement period.
②Take the proper corrective action, and press the RESET button.
For further information,
Section 4.
NOTE) Malfunction detection of water failure (LOW W) is available for only water cooled single stage compressor.
Malfunction detection of dryer (DRYER) is available for only built-in dr yer models. Malfunction detection of
oil water separator (W/O SEP) is not available.
17
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
■ Messages of Automatic Stop Display
When the air compressor stops automatically, the AUTO START light glows or blinks and RESTART display
appears. After the air compressor restarts, monitoring display appears again.
● SCHEDULED STOP: Schedule operation setting
<AUTO light glows>
This indicates that the air compressor has been
㻞㻜㻝㻞䠋㻜㻥䠋㻜㻝㻝㻥䠖㻜㻞㻖
㼀㼅㻼㻱䠖 㼂㻿㻰㻭㻌
㻰㻵㻿䠊㻼㻾㻱㻿㻿䠖 䚷䚷㻢㻣㼜㼟㼕
䠘㻾 㻱 㻿 㼀 㻭 㻾 㼀䠚
㻌㻌 㻌㻌㻌
automatically stopped by a pre-set time.
The air compressor starts automatically when the
pre-set restart time comes.
<AUTO light glows>
This indicates that the air compressor is waiting for
starting as a slave unit in a two-unit-alternate
operation or a backup operation.
● DRYER PRESTARTED (Built-in dryer model)
<AUTO light blinks>
This indicates that the dryer has started and air
compressor is waiting for the start. The RESTART
WAIT field shows an expected waiting period until
the air compressor can start in seconds.
● AUTO OPERATION
<AUTO light glows>
This indicates that the air compressor in AUTO
operation has stopped due to the low air demand and
is waiting for restarting when demand is needed.
The RESTART WAIT field shows an expected
waiting period until the air compressor can restart in
seconds.
18
● INSTANT STOP / RETRY (Retry is for only Vtype)
<AUTO light blinks>
For both fixed speed and Vtype, this indicates that
the air compressor has stopped due to an
instantaneous power interruption (IPI). The
RESTART WAIT field shows an expected waiting
period until the air compressor can restart in
seconds.
For Vtype, this indicates that the air compressor has
stopped due to the variable speed drive failure and is
waiting for restart as well. The RESTART WAIT
field shows an expected waiting period until the air
compressor can restart in second.
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
■ Maintenance Notice Messages
① Periodical maintenance
A maintenance date is determined by the amount of total operating hours or an elapsed calendar period, whichever
comes first. When the maintenance date or time arrives, the maintenance notice message appears on the display
under the heading of MESSAGE.
This function is only for the notice and is not output externally.
The consumable parts for the suction throttle valve shall be replaced this maintenance notice or L COUNT OVER
appears, whichever comes first.
Standard Maintenance Schedule (A) (for yearly 8,000-or-less operating hours)
B
Standard Maintenance Schedule (B) (for yearly 4,000-or-less operating hours)
Half-yearly
CAUTION
If a message of maintenance notice is displayed, carefully read it and service the air compressor as
instructed by this manual. After servicing the air compressor, press the SET button and hold it down for
more than seven (7) seconds; the MAINT. COMPLETED message appears. After one (1) minute, the
monitor display appears.
Note:
1. MAINTenance can be reset, if the servicing is done earlier than expected and if the remaining operating time to next maintenance is
less than 2,000h in the case of A, 1,000h in the case of B.
2. On the contrary, if the servicing is done after the maintenance notice has appeared, the remaining operating hours to the next
maintenance has been zero until the maintenance is done. After maintenance and resetting the counter, new counting time starts
just after the maintenance notice message has appeared on the display.
② Other Message Displays
(1) SWITCH TO LOCAL
If set to local by remote operation following
shutdown restoration, the air compressor will
automatically return to local operation in case of
a shutdown, and the message will be displayed
for 1 minute. (
3.4)
(2) IN OVERRIDE MODE.
Indicates that the compressor is in override
mode.
(3) IN UNLOAD STOP
Blinks when the UNLOAD STOP button is used.
The air compressor unloads for 5 minutes and
then stop.
19
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
3.3.4 How to Move within a Menu Display and to Change a Setting
The method and procedure for altering settings is displayed using the following as an example.
How to MOVE within a [FUNCTION MENU] Display
1
[FUNCTION MENU]
1 䠊 BAS I C SE T UP
2 䠊 MUL T I - UN I T
3 䠊 CAPAC I T YCONTROL
4 䠊 SCHEDULE
5 䠊 OPE RA T I ONDAT A
6 䠊 LOAD DATA
7 䠊 ALARM HI STORY
8 䠊 SHUTDOWNHI STORY
or 2 is appeared
② Press the
desired item number.
③ Press the SET button to open the related setting
display.
The following explanation uses [MULTI-U SETTING display] as an example.
① Press the MENU button when the monitor display 1
SET䠖 OPE N MON䠖 BACK
How to Select or Change a Setting within a Setting Display
Item number with a dash “-“ cannot be selected on LCD
monitor. It can be selected from digital monitor. (
How to Use the Digital Monitor for the detail.)
When contacting the local Hitachi distributor, inform
this information as a based setting status.
㻡䠊㻜
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
This display contains software version (VER.), air
compressor series (SERIES NAME), cooling method
(COOLING METHOD), number of air compression
stages (NO. OF STAGE), action against instantaneous
power interruption (IPI) and etc. “** ” means the
setting that is not required.
① Indicates board software version.
② Indicates compressor type.
③ Displays cooling type.
④ Displays the number of compressor stages.
⑤ Displays pressure specification.
⑥ Displays interstage pressure.
⑦ Indicates CT setting value.
⑧ Displays water failure detection conditions for water
cooled compressor.
⑨ Displays status of instantaneous power interr uption
(IPI) restart setting.
⑩
Displays compressor number. (Must be distinguished
by number is using communication function.)
Operation Mode Setting
2
Confirm the settings by lead/lag and multi unit
control (option). These options need wiring
modification. Item number with a dash “-“ cannot be
selected on LCD monitor.
If using the backup function, switch to the digital
monitor for setting.
Operation mode set on the digital monitor.
IMPORTANT
㻌㻿㻺
㻜㼔
㻻㼂㻾 㻾㻸
㼟㼕
2. DUAL TIME: Alternate operation hours of lead/
lag operation.(Setting range : 0.1 to 99.9 hours;
initial value: 8.0)
3. METHOD: Switching method (overlap or interval)
of lead/lag operation.
4. SWITCHOVER: Switching-over or overlapping
period of lead/lag operation. (Setting range : 5 to
300 seconds; initial value: 15)
SNGLOperates an air compressor independently
Operates by multi roller EX of exclusive use for NEXT
series using communication function.
STPR
By this setting RS485 communication port is effective.
The setting of air compressor number is required.
DUAL
BKUP
OVERLAP
INTERVAL
Operates two air compressors alternately according to
a time schedule. The AUTO light comes ON (glowing).
Operates two air compressors according to a preset
back up pressure. Starts the back up slave unit when
the pressure has dropped to the desired preset back up
pressure. The AUTO light comes ON (glowing)
Slave unit starts, master/slave units overlap in operation
for a preset period, and then master unit stops.
Master unit stops, a non-operating interval passes, and
then slave unit starts.
5. BACKUP: Pressure to start a backup unit in a
backup operation (cut-in (load) pressure – α)
6. UNLOAD: Pressure to unload both the units in a
backup operation (cut-out (unload) pressure – α)
7- ALT. TIME: Displays time remaining until switch for
dual / backup operation. Time is not counted down
when operating 2 units for backup operation. When
operation is stopped, remaining time is maintained.
8- CONTROL MODE: Control mode A or B for Vtype
(
3.3.2). “**” is indicated in fixed speed type.
IMPORTANT
The settings can be memorized while the air compressor
is stopped.
21
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
Capacity control
3
This function sets the pressures and times for capacity
control. Two dif ferent combinations (P1 and P2) of
pressures can be used. Item number with dot “ . ” can
be select from LCD monitor. Item number with a dash “
and target pressure setting 1 and 2 can be confirmed.
Target means target pressure for ECOMODE
7. TIME LIMIT (Fixed speed type only)
⑤ Indicates the time limit of load/unload one-cycle
time for ECOMODE. Load/unload one-cycle time
must be 30 seconds or more. (
3.4.8)
8. TIME:⑥ Can set the time to use pressure setting 2.
When set the value properly, ② is indicated in “ S-A”. If
the start and stop time is set at same value, pressure
setting 2 is not in use and ② is indicated in S-1. And
pressure setting 1 and 2 can be changed by external
switch. Set the F018 on digital monitor “2”. (
3.4.2
and 3.4.7)
IMPORTANT
The settings can be memorized while the air compressor
is stopped.
This illustration indicates a scheduling operation from 7:00 to
20:00. TIME field indicates a current time of 19:07.
㻝㻥䠖㻜㻣
1. MODE:
OFFOperates without a schedule.
Schedule Operates according to a daily 24- hour calendar.
(1) to (5) : Five Start/Stop Time Patterns
・ START : Star ting Time
・ STOP : Stopping Time
・ Y or N : Starts or Stops as scheduled
IMPORTANT
When the schedule is selected, the AUTO light comes ON
(glowing) if the time setting is valid and ON (blinking) if the
time setting is invalid. The settings can be memorized
while the air compressor is stopped.
2.-3. RECORD1, 2 : This function allows for the
capability to record data over a desired time in a day.
To view the recorded data, refer to “5. Operation data
display” on the next page.
22
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
Operation Data Display
5
㼇㻻㻼㻱㻾㻭㼀 㻵㻻㻺 㻰㻭㼀㻭㼉
㻝䠊㻜㻤䠋㻜㻝㻝 㻜 䠖 㻜 㻜
㻼䠖㻜㻠㻢䚸㻜㻝㻥䚸㻜㻝㻢䚸㻖㻖㻖
㻯䠖㻜
㼀䠖 㻞㻡䚸 㻟㻟䚸㻖㻖䚸㻖㻖䚸㻖㻖
㻸䠖㻡㻥䚸㻝㻤䠊㻤
㻞䠊㼍 㼍䠋㼎 㼎㼏 㼏 䠖㼐㼐
㻼䠖㻖㻖㻖䚸㻖㻖㻖䚸㻖㻖㻖䚸㻖㻖㻖
㻯䠖㻖㻖㻖
㼀䠖㻖㻖㻖䚸㻖㻖㻖䚸㻖㻖䚸㻖㻖䚸㻖㻖
㻸䠖㻖㻖㻖䚸㻖㻖㻖㻖㻖
㻹㻻㻺 䠖 㻮 㻭㻯㻷
Data can be recorded for a maximum of twelve (12)
times. The 13th recorded data is automatically deleted
and the 1st recorded data is added. The most recent
data is arranged at the top of the display. If a change to
these settings is desired, the sampled data before the
settings change will be left as is and the new recorded
data will be applied after the change.
Press the
△
or
▽
button to move within the display.
1. and 2. : Indicates the MONTH / DAY HOUR: MINUTE.
P - Represents a pressure (psi) and indicates from left
to right: Discharge air pressure, Interstage
pressure, Oil pressure, ***
C - Represents an amperage current (A)
T - Represents a temperature (°F) and indicates from
left to right: 1st stage discharge air temperature,
2nd stage discharge air temperature, oil
temperature, ***, 2nd stage suction temperature.
L -Represents a load ratio percentage (%)
Unavailable fields are filled with asterisks.
This display shows the averaged load data per day. Data
can be recorded for a maximum of 6 days; the 7th day
of averaged load data is automatically deleted and the
1st or most recent averaged data is added. The most
recent data is arranged at the top of the display. Press
the
△
or
▽
button to move within the display.
Data is averaged from start to stop every day. If 24h
operation is done, data is averaged at AM 0:00.
Alarm History
7
㼇㻭㻸㻭㻾㻹 㻴 㻵㻿㼀㻻㻾㼅 㼉
㻝䠊㼍㼍㼍㼍㼍㼍㼍㼍㼍㼍㼍㼍㼍
㻯㻻㻰㻱䠖㻞㻝㻸 㻺㻻㻿䠊䠖㻌 㻝
㻜㻣䠋㻜㻤䠋㻜㻝 㻝㻥䠖 㻞㻢
㻞䠊㻖㻖㻖㻖㻖㻖㻖㻖㻖㻖㻖㻖㻖
㻯㻻㻰㻱䠖㻖㻖㻖 㻺㻻㻿䠊䠖㻖㻖
㻖㻖䠋㻖㻖䠋㻖㻖 㻖㻖䠖 㻖㻖
㻟䠊㻖㻖㻖㻖㻖㻖㻖㻖㻖㻖㻖㻖㻖
㻯㻻㻰㻱䠖㻖㻖㻖 㻺㻻㻿䠊䠖㻖㻖
㻖㻖䠋㻖㻖䠋㻖㻖 㻖㻖䠖 㻖㻖
㻹㻻㻺 䠖 㻮 㻭㻯 㻷
①
This display shows a maximum of 6 alarms and
displays the following information as such: type of
alarm, the number of times, and the date and time. If
the same alarm occurs in a short period of time, the
older data is deleted and the more recent data is stored,
and alarm NOS. is updated. The most recent data is
arranged at the top of the display. Press the
▽
button to move within the display.
△
or
① Indicates operating condition.
L: When loading, U: When unloading,
S: When Stopped
This display shows a maximum of 6 shutdowns and
displays the following information as such: type of
shutdown, the number of times the air compressor has
shutdown, and the date and time of the shutdown. The
shutdown history display also shows the operation data
(pressure, temperature, current) sampled at the time of
shutdown.
To view the operation data sampled when the shutdown
occurred; in the shutdown histor y display, move to the
item number of the targeted shutdown to view. Press
the SET button to open the [DETAILS] display.
● How to clear the all alarm and shutdown histories.
Set the F041 on digital monitor “1”. (
3.4.2).
23
3. OPERATING PROCEDURE [How to Use the Liquid Crystal Display (LCD)]
3.3.6. Other Settings
Initial Setting
The calendar and clock are set by Hitachi prior to
delivery. To reset the calendar and clock, contact
the local Hitachi distributor.
Brightness Adjusting
Adjust the LCD brightness as follows:
To brighten:
Hold down the SET button and press the
MONITOR button.
To darken:
Hold down the SET button and press the
FUNCTION button.
Digital Monitor Operation Classification
The following is a table of contents that can be set by
the LCD monitor and digital monitor (next section).
FunctionItem
MULTI-U SETTING
display
CONTROL SETTING
display
SCHEDULE SETTING
display
Other settings
Reset
MODE-
DUAL TIME
METHOD
SWITCHOVER
BACKUP
UNLOAD
ALT.TIME
CONTROL MODE
TYPE (left)
TYPE (center)
TYPE (right)
P-LOSS
PI-CA
P1
P2
TARGET- Prohibited to change
TIME LIMIT
TIME
MODE
START/STOP
RECORD 1, 2
Air compressor No.
IPI
Remote operation
Dryer operation
AUTO operation
ECOMODE
Shutdown/Alarm
Load count
Maintenance
Shutdwon/Alarm history
△
3-Language Display Switch
The language of the display can be switched to
Japanese, English or Chinese by the dip switch on
the back of the LCD monitor board. If the language
needs to be changed, consult with the local Hitachi
distributor.
Japanese OFFOFFOFF
EnglishONOFFOFF
ChineseOFFONOFF
Setting for United
States
Test modeONONOFF
Power must be turned off before setting.
LCD monitor
operation
○
○
○
○
○
(automatic change)
-
○
○
○
-
○
○
○
○
-
○
-
Bit1234 - 8
ONOFFON
Digital monitor
(F mode)
○ F000
-
○ (Factory set)
○ F019
○ F018
-
○ F022 -
○ F022 -
○ (Factory set)
-
○ F001
○ F002 -
○ F005 -
○ F008 -
○ F011 -
○
○
○
-Set button 7 sec. ON
○ F041
Dual, backup, etc
Differential pressure
Differential pressure
V type only
Example: I type (load/unload type)
Example: Setting 1
Option (not supported)
Option (not supported)
Option (not supported)
Setting 1, Setting 2
Setting 1, Setting 2
Energy saving mode decision time
Function switching
Operation data measurement
Display switch button operation
Reset button operation
Remote + display switch button
Remarks
Not
used
24
3. OPERATING PROCEDURE [How to Use the Digital Monitor]
3.4 How to Use the Digital Monitor
3.4.1 How to Display Operation Status, Shutdown History, and Status of Various Settings
All display contents of the digital monitor are linked with the LCD monitor. All of the following display contents can
be confirmed by the LCD monitor.
Use the following operations to display the contents of other operation/setting status on the LCD monitor and
readily confirm operation status and setting status by the digital monitor.
(1) How to Display the Operation Status
P: Discharge pressure (psi)
SELECT/WIDE
Blinks when operation time is added.
Total running hour (×10)
SEL ECT /WID E
Pres s once to go to
the next item.
Press once to go to
the previous item.
Return to discharge
pressure display
2
RESET
1
To shutdown history display
b: Interstage pressure (psi)
C: 1st-stage air end outlet temp (゜F) (320゜F)
L: Vtype: Not in use
Fixed speed type: Load ratio (%)
U: Load count (×10,000 times)
H:
Vtype: Main motor operating frequency (Hz)
Fixed speed type: Not in use (display only)
d: Fan motor operating frequency (Hz)
Water-cooled type: Not in use (display only)
IMPORTANT
1. When other than P (Discharge pressure is
displayed), it automatically returns to P in 3 minutes.
2. Load ratio is a reference-calculated value.
1
Press
When the power is turned on, discharge pressure is displayed
on the screen of the digital monitor. Use the following
procedure to switch the digital monitor to other display.
① Press the SELECT/WIDE button. Operation time is
displayed on the screen.
② Press the SELECT/WIDE button. Interstage pressure is
displayed on the screen with “b.”
③ Press the SELECT/WIDE button. 1st-stage air end outlet
temperature is displayed on the screen with “C.”
④
Press the SELECT/WIDE button. Load rate is displayed
on
the screen with “L.”
⑤ Press the SELECT/WIDE button. Load count is displayed
on the screen in units of 10,000 times with “U.”
Air-Cooled
⑥ Press the SELECT/WIDE button. Operation frequency of
the fan motor is displayed on the screen with “d.”
To return to one item at a time, press the
2
button. To
return to discharge pressure, press the RESET button.
● If the alarm or shutdown light is blinking, the shutdown
code is displayed with “E0” (
page 36, 37).
“E0” indicates the contents of the latest shutdown.
● If the alarm or shutdown light is blinking, it indicates that
the alarm or shutdown has not been reset. Check E0.XX
and reset.
25
3. OPERATING PROCEDURE [How to Use the Digital Monitor]
(2) How to Display Shutdown History
Discharge pressure display
SELECT/WIDE
Press once to go to
the next item.
Press once to go to
the previous item.
Return to discharge
pressure display.
1
2
RESET
SELECT/WIDE
1
Press 8 times.
[Latest shutdown]
[Previous shutdown]
XX : Shutdown code
[Oldest shutdown]
History consists of 6 date items.
Not used (display only)
Not used (display only)
To display of various settings
Use the following procedure to display shutdown history.
① Press the SELECT/WIDE button 8 times. “E0.” is the
displayed with the shutdown code (
Section 4). “0”
indicates the most recent shutdown. (The display
automatically changed to “E.0” when shutdown or alarm
occurs.)
② Press the SELECT/WIDE button. “E1.” is displayed along
with the shutdown code. “1” indicates shutdown that
occurred previously. Six items of data (0 to 5) are
recorded. “E5” indicates the oldest shutdown.
③ Press the RESET Button. The screen is returns to the
operation status.
IMPORTANT
If the shutdown code “XX ”is “”, it Indicates that
there is no shutdown history. Also, when anything
other than shutdown history is displayed without
shutdown resetting, the display is return to the latest
shutdown history in 3 minutes.
(3) How to Display Various Settings (Perform operation only when confirmation is
necessary.)
Dischargepressuredisplay
1
Proceeds by 1
each time pressed.
2
Returns by 1 each
time pressed.
RESET
Returns to
discharge pressure.
SWITCHDISPLAY
1
Press16times.
No.0 : Control status
A : Capacity control type
No.1 : Start pressure 1
100 : 100psi
No.2 : Recover pressure 1
087 : 87psi
No.3 : Pressure differential 1
007 : 7psi
No.4 : ECOMODE
Cycle time
30 second
No.5 : Start pressure 2
100 : 100psi
No.6 : Recover pressure 2
087 : 87psi
No.7 : Pressure differential 2
007 : 7psi
No.8 : Instantaneous power
interruption (IPI) setting
Invalid
:
000
No.9 : Compressor address
001 : No.1
Use the following procedure to display capacity control type
and pressure setting values for confirmation.
① Press the SELECT/WIDE button 16 times. “0.A**” is
then displayed on the screen. The content of “**” varies
depending on specifications. “A” may be “L” or “U”
depending on capacity control specifications.
② Consists of items 0 - 9. Pressure setting status and
optional pressure setting 2 can be confirmed each time
the SELECT/WIDE button is pressed.
③ Press the RESET Button. The screen is returns to the
usual discharge pressure display.
IMPORTANT
Symbol displayed at No. 0 and corresponding capacity
control type
A: AUTO function setting
L: Fixed speed type setting
(INTE …Load/unload operation)
U: Vtype setting (AUTO function canceled)
(
3.3.5 and 8.4)
26
3. OPERATING PROCEDURE [How to Use the Digital Monitor]
3.4.2 How to Set Control Functions
■ Various settings (instantaneous power interruption (IPI), remote operation, capacity control
setting, pressure setting, etc.)
Switches the display from monitor mode to setting mode (F mode).
Setting can be changed and memorized from the digital monitor without opening the control panel.
■ F Mode table
Function
Multiple unit control
setting
Instantaneous power
interruption (IPI)
restart setting
Remote operation
setting
7 segment
display
ItemRange
F000Control setting0 - 110
F002
Instantaneous power
interruption (IPI) setting
0 - 1100: Valid, 1: Invalid
Instantaneous power
F003
interruption (IPI)
1 - 51 sec1
detection period setting
F005
F006
F007
Remote control switch
method
Remote operation
method
Remote shutdown
recovery
0 - 310
0 - 1100: Pulse input, 1: Level input
0 - 1100: Invalid, 1: Valid
Precision/
unit
DefaultRemarks
0: Stand alone operation,
1: Multiple unit control
(communication supported)
When the IPI function is available,
instantaneous power interruption is
detected between 20 ms and the
setting detection period set here, and
air compressor restarts. (
3. OPERATING PROCEDURE [How to Use the Digital Monitor]
Function
Pressure
setting 1
※2
V type
Pressure
setting 2
※2
Pressure
setting 1
※2
100 / 125 psi (0.69 / 0.86 MPa) specifications
Fixed
speed
type
Pressure
setting 2
※2
7 segment
display
F022
F023
F024
F025
F031
F032
F033
F034
F023
F024
F025
F032
F033
F034
ItemRange
Control pressure
setting 1 psi (MPa)
Cut-out pressure 1
psi (MPa)
Cut-in pressure 1
psi (MPa)
Restart pressure 1
psi (MPa)
Control pressure2
psi (MPa)
Cut-out pressure 2
psi (MPa)
Cut-in pressure 2
psi (MPa)
Restart
pressure 2
psi (MPa)
Cut-out pressure 1
psi (MPa)
Cut-in pressure 1
psi (MPa)
Restart pressure 1
psi (MPa)
Cut-out pressure 2
psi (MPa)
Cut-in pressure 2
psi (MPa)
Restart
pressure 2
psi (MPa)
71 〜 125
(0.5 〜 0.86)
71 〜 128
(0.5 〜 0.88)
71 〜 122
(0.5 〜 0.84)
71 〜 122
(0.5 〜 0.84)
71 〜 125
(0.5 〜 0.86)
71 〜 128
(0.5 〜 0.88)
71 〜 122
(0.5 〜 0.84)
71 〜 122
(0.5 〜 0.84)
71 〜 100 [125]
(0.5 〜 0.69 [0.86])
73 〜 86 [110]
(0.5 〜 0.59 [0.76])
73 〜 86 [110]
(0.5 〜 0.59 [0.76])
73 〜 100 [125]
(0.5 〜 0.69 [0.86])
73 〜 86 [110]
(0.5 〜 0.59 [0.76])
73 〜 86 [110]
(0.5 〜 0.59 [0.76])
Precision/
unit
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
1psi
(0.01MPa)
DefaultRemarks
125
(0.86)
128
(0.88)
120
(0.83)
120
(0.83)
125
(0.86)
128
(0.88)
120
(0.83)
120
(0.83)
100 [125]
(0.69 [0.86])
85 [110]
(0.59 [0.76])
85 [110]
(0.59 [0.76])
100 [125]
(0.69 [0.86])
85 [110]
(0.59 [0.76])
85 [110]
(0.59 [0.76])
※Setting can be altered at
any time.
※Setting can be altered at
any time.
Shutdown history clear
F041 (*1)
History clear
0 〜 1
10
0:Enter, 1:History clear
Note:
※ Setting of the items without ※ in remarks can be memorized while the air compressor is stopped.
*1: When set to “1”, history is cleared. After clearing, the value is automatically reset to “0”.
*2: Refer to the below table about the Capacity control pressure setting conditions.
Do not change the setting of F items that are not specified in the table above.
● Capacity control pressure setting conditions
TypeSetting conditions (Example of Pressure setting 1)
Fixed-speed
Variable-speed
Note 1: The same setting condition is applied for Pressure Setting 2 (F031 to F034).
IMPORTANT
1. Pressure setting when minimum air receiver tank is installed (5.4.4)
Vtype : Pressure differential between cut-out and cut-in shall be 7 psi (0.05 MPa) or more, and pressure differential between
cut-out and target shall be 3 psi (0.02 MPa) or more.
Fixed speed type : Pressure differential between cut-out and cut-in shall be 15 psi (0.1 MPa) or more.
2. External selection of Cut-in/Cut-out pressure combination 1 or 2 is an option. (F018-2)
① F023 shall be set F024 +3 psi (0.02 MPa) or higher, and F025+3 psi (0.02 MPa) or higher.
① F023 shall be set F022+3 psi (0.02 MPa) or higher.
② F024 and F025 shall be set F022 or lower.
28
3. OPERATING PROCEDURE [How to Use the Digital Monitor]
3.4.3 Change of Pressure Setting
Pres.
setting1
FUNC
1
2
Pressthebutton.
Change
values.
Pressthebutton.
STR
3.4.4 Change of Capacity Control Type
AUTOsetting
FUNC
(Initialvalue:0)
1
2
Pressthebutton.
Change
values.
STR
Pressthebutton.
SetAUTOOFF.
Use the following procedure to change the pressure
setting of the capacity control system.
① Switch the display from monitor mode to setting
mode (F mode).
② Set Pressure Setting 1 in F mode.
(
3.4.2)
IMPORTANT
For operation procedure, refer to the various settings.
After entering setting values, be sure to press the
STORE button and return to the monitor mode.
Make sure to press the STORE button to memorize
the setting value.
AUTO (automatic motor stop/restart function) can be
selected properly.
① Switch the display from monitor mode to setting
mode (F mode).
② Set 0 (valid) or 1(invalid) while the air compressor is
stopped.
Capacity control typeAUTO ONAUTO OFF
F0110: Valid1: Invalid
Digital monitor display0. AXX0. UXX
After setting change, confirm the capacity control type
by checking the settings on the digital monitor
3.4.1.
(
(
3.4.7, 3.4.8 and 8.4)
3.4.5 Restart for Instantaneous Power
Interruption
RUNNINGMODE
REMOTE
LOAD
SHUTDOWN
2
IPI is standard function. IPI can be canceled by F002.
refer to the page 27.
START
②③
POWER
AUTOSTART
STOP
UNLOAD STOP
③
In item F018, pressure setting 1 and 2 can be switched.
① This function is available for IPI between 20 ms and
the set value (F003: 1 to 5 sec).
② When IPI occurs , the air compressor stops and the
START light turns of f.
③ After power recovers within F003 set condition, the
AUTO light blinks and the START light turns ON
(glowing) to inform that the air compressor is
waiting for restarting from IPI.
④ The air compressor restarts 15 seconds after power
recovers.
IMPORTANT
(1) IPI means that the power voltage drops to zero (0)
instantaneously.
(2) For the IPI time of less than 20 ms, the air compressor
continues to run.
(3) For the IPI time of more than the setting, the air
compressor judges it as a power failure; the air
compressor stops but does not restart automatically.
Press the START button to restart the air compressor.
29
3. OPERATING PROCEDURE [How to Use the Digital Monitor]
3.4.6 Remote Operation Setting
The REMOTE button on the instrument panel sets
(1) Remote setting by instrument panel
On
(2) Remote setting fixed
REMOTE
IMPORTANT
● When F001 is set to “1:Multi unit control”, remote
operation is selected automatically and the REMOTE
light turns ON (blinking).
●Remote/ local setting change from the setting mode (F
mode) can be memorized while the air compressor is
stopped.
● When the remote operation is active, the air
compressor still can be stopped locally by pressing the
STOP button on the instrument panel.
On
(3) Remote setting by external operation button
Blinking
Local setting
Off
remote operation as (1). In addition, remote operation
can be set by (2) and (3).
(1) To change the Local or remote operation by
REMOTE button on the instrument panel
① Press the REMOTE button.
② REMOTE light turns ON (glowing) to indicate the
remote operation is effective.
③ To return to local operation mode, press the
REMOTE button again.REMOTE light turns OFF
to indicate the remote operation is ineffective.
(2) To fix the remote operation
① Switch the display from monitor mode to setting
mode (F mode).
Remote
control
switching
FUNC
(Initialvalue:1)
1
Alter
values.
2
Pressthebutton.
STR
Pressthebutton.
Setto"Remote
settingfixed."
② Change the value of F005 to “2: Remote”.
(
3.4.2)
③ REMOTE light turns ON (glowing) to indicate the
remote operation is effective.
(3) To change the Local or remote operation by
external contact.
( Contact the local HITACHI distributor/master
dealer or representative office.)
① Connect the external contact wiring. (
8.2)
② Switch the display from monitor mode to setting
mode (F mode).
③ Change the value of F005 to “3: Selectable by
external contact”. (
3.4.2)
④ Short the external contact to set the remote
operation.
⑤ REMOTE light turns ON (glowing) to indicate the
remote operation is effective.
30
3. OPERATING PROCEDURE [How to Use the Digital Monitor]
3.4.7 Pressure Setting Switching Function
Two different combinations of cut-out pressure and cutin pressures can be used: Pressure combination 1 and
2. The Combination 1 is used as the standard daily
settings. The Combination 2 is used for a limited time
period where different settings may be required, and
can be set for a certain time
3.3.5 and 3.4.2)
(
Load light turns on (glowing) during load and turns off
during unload when pressure combination 1 is
selected. Load light turns on (blinking) during load and
turns off during unload when pressure combination 2 is
selected. ECOMODE and PQ wide mode is invalid
during pressure combination 2 is activated.
External selection of Cut-in/Cut-out pressure
combination
local HITACHI distributor/master dealer or
representative office.
1 or 2 is an option. (F018-2). Contact the
Cut-out
press.1
Cut-out
press.2
Cut-in
press.1
Cut-in
press. 2
Line pressure
Load light
External contact (option)
Load Unload
GlowOFF Glow
Energy Saving Effect
Glow
Blink
Time
BlinkOFFOFFOFF
ONOFF
Blink
3.4.8 ECOMODE Function (only for Fixed speed type)
(1) Setting of ECOMODE (Energy Saving Mode)
ECOMODE is set OFF on factory setting. See
SELECT/WIDE button in page 13 to be activated.
This function enables a power saving operation by
reducing the cut-out pressure to a preset target
value, based on if the load/unload cycling interval is
longer than the set interval. If the cycling interval
time is longer than set interval, the system reduces
the cut-out pressure to a target so as to make the
cycling interval closer to the set value. Minimum
cut-out pressure is cut-in pressure + 7 psi (0.05
MPa). Minimum cycle time is 30 seconds.
If the cycle time is 30 seconds or more, SELECT/
WIDE light turns on (blinking) to indicate
ECOMODE is effective. By setting the ECOMODE
to ON, the display’s TYPE field shows SAVE for a
power saving operation. (
3.3.2)
(2) Caution for using ECOMODE
Larger than standard air receiver tank is required to
keep the ECOMODE effective. (
5.4.4).
Factorysetting
Pressure differential between cut-in and cut-out pressure: 15 psi (0.1MPa)
Allowable pressure differential for ECOMODE: 7 psi (0.05MPa) (unable to change)
Minimum cycle time: 30 seconds
RUNNING CONTROL
ALAR M
FUNC
Cut-out
pressure
Cut-in
pressure
Line pressure
RESET
ON : The light blinks.
OFF : The light turns off.
SELECT/WIDE
REMOTE
STR
1
SELECT/WIDE
Press the button for 7 seconds or more to set.
Energy Saving Effect
Load Unload
Time
SELECT/WIDE
1
Cut-out is
automatically
reduced.
31
3. OPERATING PROCEDURE [Daily Operation of Air Compressor]
3.5 Daily Operation of Air Compressor
CAUTION
● When using the air compressor, do not raise the discharge pressure excessively. Operating the air
compressor over the rated pressure can result in main motor overload, shutdown of the airend and/or
damage of parts.
● If the air relief valve has blown or a protective device has shutdown the air compressor, investigate
the cause of and take corrective action. If there are any questions or comments in taking these
actions, contact the local HITACHI distributor/master dealer or representative office.
3.5.1 Preparing the air compressor
RUNNING CONTROLRUNNING MODE
SELECT/WIDE
1
REMOTE
LOAD
SHUTDOWN
2
ALARM
RESET
FUNC
REMOTE
STR
③
3.5.2 Starting the air compressor
②
POWER
AUTO START
STOPSTART
UNLOAD STOP
① Connect the power.
② Check the POWER light and LCD, and verify that:
the POWER light is ON, and the monitor display has
-
appeared.
③ Check the oil level gauge, and verify that:
-
the oil stays around the upper or lower red lines of the oil
level gauge.
④ Close the petcock and water relief valve.
Water-Cooled
⑤ Open the cooling water valve.
IMPORTANT
Verify that the oil stays between the upper and lower red
lines of the oil level gauge while air compressor is running.
Since the oil comes back to the oil case after the air
compressor stops, the oil level during air compressor
running is lower than during air compressor stopping.
② Verify that the intercooler/aftercooler condensate
drain is discharged intermittently when the air
compressor is loading.
③ When the air compressor is unloading, condensate
drain is discharged one (1) second a five (5)
minutes.
① Press the UNLOAD STOP button to stop the air
compressor.
The air compressor unloads for 5 minutes and stops.
(In the case of an emergency, press the
EMERGENCYSTOP button.)
② Check the pressure after the air compressor stops
running.
-
Both oil pressure and interstage pressure shall be 0 psi
( The pressures may be 1 psi depending on operation
conditions.)
③
④
[Rear View]
③ Check the sight glass on the control line filter to
confirm that drain is properly discharged. (Fixedspeed type)
④ Close the valve on the discharge side.
Water-Cooled
⑤ Close the cooling water stop valve. Open the
petcock and cooling water drain valve to drain the
cooling water from the air compressor. Be careful
not to damage the parts, such as coolers and casing,
by cooling water freezing.
33
3. OPERATING PROCEDURE [
Daily Operation of Oil Mist Remover
]
3.6 Daily Operation of Oil Mist Remover
3.6.1 When Setting3.6.2 When Stopped
Make sure that the vacuum indicator shows a red mark.
8
φ
Make sure that the
vacuum indicator does not
show a red mark.
Make sure that the pressure
gauge reads as follows:
Pressure Gauge
51 to 58 psi
Make sure that the
condensate is not
collected in the
filter bowl.
If the condensate is
collected, push up
the cock to drain
the condensate.
Condensate Drain Cock
(see the left drawing)
34
3.7 Adjusting Procedure
3. OPERATING PROCEDURE [Adjusting Procedure]
3.7.1 Adjusting the Suction Bypass
Valve (For Fixed-Speed type)
①④
Suction
throttle
valve
②④
Air intake filter
③
Adjusting Bolt
(Suction Bypass Valve)
Usually keep the bolt
Locknut
Seal washer
tightened, but not
excessively.
① When dust particles accumulate on the valve plate of
the suction throttle valve, the suction vacuum
pressure may drop and eventually causing the
discharge air temperature to rise.
② The first steps to resolve the lower suction vacuum
pressure are as following. If the unloaded interstage
pressure drops as low as -12 psi (-0.08 MPa) or
discharge air temperature is gradually increased.
A) Clean or replace the air intake filter.
B) Clean the suction throttle valve’s valve plate.
③ If the air compressor cannot be shutdown to clean
these parts, turn the adjusting bolt (the suction
bypass valve) counterclockwise to open. This will
allow the air intake and increase the discharge air
pressure to be greater than -12 psi (-0.08 MPa) when
running unloaded.
④ Replace the consumable parts in the air intake filter
and suction throttle valve with new consumable
parts in accordance with the appropriate
maintenance schedule. (
Section 9)
3.7.2 Regulating the Oil Pressure
Oil Relief Valve
IMPORTANT
The interstage pressure of as low as
unloading period may increase the discharge air
during
temperature.
-12 psi (-0.08 MPa)
① Use the oil relief valve to regulate the oil pressure.
To regulate the oil pressure, open the oil relief valve
cap, loosen the lock nut, and turn the regulating bolt
to keep the oil pressure at the specified 18 psi to 23
psi (0.12 to 0.16 MPa).
18 psi to 23 psi (0.12 to 0.16 MPa) when the ambient
・
temperature is 68 degree F (20 degree C) or higher.
・ 20 psi to 26 psi (0.14 to 0.18 MPa) when the
ambient temperature is 68 degree F (20 degree C)
or lower.(for V type, adjust at the maximum
operating frequency.)
② Turn the regulating bolt clockwise to increase the
oil pressure and vice versa.
③ Tighten the locknut and replace the cap.
IMPORTANT
If the oil pressure is reduced to the specified or lower, the
oil pressure sensor detects it and shutdown the air
compressor.
specified value for each type of air compressor
4. TROUBLESHOOTING to the
35
4. TROUBLESHOOTING
CAUTION
If a shutdown, alarm, problem or failure occurs, investigate the cause and take proper corrective action
before restarting. If there is any questions or comments, contact the local HITACHI distributor/master
dealer or representative office.
4.1 Protective Device
The air compressor is provided with the protective devices listed below. If shutdowns are detected by these protective
devices, remove the cause with referring to the LCD monitor indication and this manual, and then press the RESET
button to clear the shutdown indication. Depending on the type of shutdown, contact the local HITACHI distributor/
master dealer or representative office.
■ When connecting the power
HeadingTrouble Description
POWER
LCD Indication
Reversal phase connection
(Note 2)
Phase-lacking connection
Instantaneous power interruption
Brief instantaneous power
interruption
What and How to Detect
Detected for 3
seconds after
connecting the power
Power interruption for 1 to 5 sec.
Power interruption for
1 sec or less.
Failure
Light
SHUTDOWN
Blinks
-
Detector
CPU
(Note 1)
CPU
(Note 1)
CPU
CPU
Shutdown
Ye s
Ye s
Restart
Restart
What Actions to Take
Reconnect the power cable tightly, check the
power supply and incoming power for loose
connections and change the connection
location of 2 of the 3 phases, be sure to follow
all electrical safety procedures.
Reconnect the power cord tightly, check the
power supply, and take a corrective remedy.
3.4.5
3.4.504E0.04
4.2.
How to
Reset
Press RESET
button.
-
History
code
01E0.01
02E0.02
03E0.03
Error
code
■ During Operation
LCD Indication
HeadingTrouble Description
1st stage discharge air temperature
(HIGH DIS. TEMP. 1)
1st stage discharge air temperature
2nd stage discharge air
temperature
(HIGH DIS. TEMP. 2)
Interstage pressure
[Fixed speed type]
Interstage pressure44psi 0.30MPa or higher
2nd stage suction air temperature
(2ND SUCT. TEMP)
SHUTDOWN
FAILURE
INV STOP
Oil temperature
(OIL HIGH TEMP)
Oil pressure
[Fixed speed type]
Oil pressure
(OIL-LOW PRESS)
Answer error of 52
Overloading(main motor)
[Fixed speed type]
Overloading (main motor)Detected during operation
Overloading (auxiliary motor)
Answer error of 52
Answer error of 42
[Fixed speed type]
Inverter tripping or main
motor overloading with
automatic retrials.
What and How to Detect
About 437 [419]℉
225 [215]℃ or higher
The discharge temperature at 1st
stage rises above the below settings.
100 psi model
0.69 MPa model
125 psi model
0.86 MPa model
● For working pressure of 100psi 0.69 MPa : About 446[428]℉
(1) Depends on the specification, reverse phase relay is used.
(2) The air compressor using reverse phase relay, such as for 460 V/60 Hz, indicates a phase-lacking connection as reversal phase.
(3) Communication error details:
Port 1(65) =Main circuit communication (Vtype), Port 2 (66)=Fan inverter communication (Air-cooled model)
Port 3 (67)= LCD communication, Port 4 (68)= Multiple unit control communication, Port 5 (63)= External communication
Failure
Detector
Light
ALARM
CPUNo
Blinks
ALARM
CPUNo See 3.3.5 (4)
Blinks
ALARM
CPUNo
Blinks
SHUTDOWN
Thermistor
Blinks
ALARM
Pressure
Blinks
sensor
SHUTDOWN
CPUYes
Blinks
SHUTDOWN
CPUYes
Blinks
SHUTDOWN
CPUYes
Blinks
SHUTDOWN
CPUYes
Blinks
SHUTDOWN
CPUYes
Blinks
SHUTDOWN
CPUYes
Blinks
SHUTDOWN
CPUYes
Blinks
SHUTDOWN
CPUYes
Blinks
SHUTDOWN
CPUYes
Blinks
Shutdown
What Actions to Take
Disconnect the power and replace the
battery with a new one.
Check the wire and the operation setting
on the instrument panel.
Ye s
Check the wire and the operation setting.
Check the wire and the operation
Ye s
setting.
Disconnect the power and then reconnect the
power. If problem is persists, change the PCB.
Disconnect the power and then reconnect the
power. If problem is persists, change the PCB.
Disconnect the power and check the
pressure sensor wire for tightness.
Disconnect the power and check the
thermistor sensor wire for tightness.
9.4 (12).
How to
Reset
Press RESET
button.
Press RESET
button.
Press RESET
button.
Press RESET
button.
Press RESET
button.
Press RESET
button.4347, 48
Press RESET
button.
Press RESET
button.
Press RESET
button.
Press RESET
button.
Press RESET
button.
Press RESET
button.
Press RESET
button.
Press RESET
button.
History
Error
code
code
64E0.64
62E0.62
5BE0.5B
63 65
E0.63 65
〜 68
〜 68
63 65
E0.63 65
〜 68
〜 68
E0.43
47, 48
41, 42 46E0.41,
42 46
33E0.33
34E0.34
39E0.39
32E0.32
35E0.35
36E0.36
37E0.37
37
4. TROUBLESHOOTING [Troubleshooting of Air Compressor]
4.2
4.2 Troubleshooting of Air Compressor
■ Most common problems, causes and corrective actions are described below.
1. Cooling water pump – failed, or
cooling water temp. – Fluctuating
(Water-cooled model)
2. Intercooler – Dirty
1. Oil cooler – Dirty
2. Room temperature – High
3. Oil temperature control valve –
Failed
1. Oil strainer and/or oil fi lter – Dirty
2. Oil level – Low
1. Clean or change the air intake fi lter
2. Lower the suction air temperature
1. Replace the check valve.
2. Clean the Suction throttle valve.
[Fixed speed type]
Note: For information about the Suction
bypass valve,
3.7)
1. Check the cooling water system
(Water-cooled model).
2. Clean the intercooler
1. Check the oil cooler.
2. Lower the room temperature.
3. Check the oil temperature control
valve.
1. Clean the oil strainer
2. Replace the oil fi lter.
3. Add the oil.
Shutdown –
Motors overload
Shutdown –
Inverter
38
<S H U T D O W N>
OVERLOAD : MAIN
Press
<S H U T D O W N>
OVERLOAD : SUB
Press
RES
after CHK.
RES
after CHK.
[Water-cooled type] [Vtype]
<S H U T D O W N>
CONTACTOR ERR : 52
Press
<F A I L U R E>
SYSTEM RETRY :
RES
after CHK.
1. Power supply voltage – Low
2. Discharge air pressure – Too high
3. Power supply - Imbalance
4. Motor Insulation - Failure
1. Power supply voltage – Low
2. Cooling fan motor – Failed
3. Power supply - Imbalance
4. Motor Insulation - Failure
1. Power supply voltage – Low or in
unbalance
2. Discharge air pressure – Too high
3. Main motor – Overloading
NOTE: 4th retry action in ten minutes
becomes shutdown failure.
1. Rectify the power supply voltage.
2. Check the suction throttle valve
[Fixed speed type]
3. Check the capacity control system.
4. Check the insulation resistance.
1. Rectify the power supply voltage.
2. Check the cooling fan motor.
(Measure insulation resistance etc.)
1. Rectify the power supply voltage.
2. Check the capacity control system.
3. Measure insulation resistance etc. or
check the main motor.
4. TROUBLESHOOTING [Troubleshooting of Oil Mist Remover]
4.3 Troubleshooting of Oil Mist Remover
Problems and actions to be taken are as follows.
① The vacuum indicator shows a red mark
The pressure gauges reads zero (0) MPa.The control air is not supplied.
NO
Pressure setting of the regulator is lower ?
NO
Pressure of a control air is lower than the regulator
setting value ?
NO
The gear case or gear case vent pipe has a leak
(for example, the oil filling port plug on the gear case is not tight).
NO
The solenoid valve may have problem or the remover
element may be dirty.
If the solenoid valve has no problem replace the element.
YES
YES
YES
YES
Reset the regulator to a proper pressure.
Clean the filter.
Maintain the pressure of a control air at the regulator
setting value.
- Tighten every screw and plug to remove all leaks.
- Make sure that the OMR relief valve is closed.
② The OMR relief valve opens immediately when starting the air compressor (the control air pressure is still
low) or when the DSP has stopped. This is a normal occurrence.
The OMR relief valve is dirty or stuck open by a foreign
object.
NO
Go to the procedure ①. The vacuum indicator shows a
red mark. (Gear case has a positive internal pressure.)
NOTE:
The OMR relief valve opens immediately when starting the DSP (the control air pressure is still low) or when the DSP has
stopped. This is a normal occurrence.
YES
Disassemble and clean the OMR relief valve.
Replace if necessary.
③ Oil is vented through the ejector’s compressed air outlet (the separated oil is not being recovered).
Accumulated oil is visible in the tube between the
element housing and the fl oat trap.
No
Upper or lower packing is not seated properly on the
element ?
No
Control air contains oil ?Check the control air for oil contents.
No
Element may be dirty.
Inspect the element and replace if necessary.
YES
YES
YES
Clean the nozzle of the fl oat trap.
Reinstall the element, seating the packing properly for a
maximum sealing performance.
④ Oil pressure is low (oil pump may be inhaling air).
Problem of compressor (dirty oil filter, low oil pressure due
to oil leakage, failure of oil pump or OMR relief valve, etc.)
NO
Foreign matter in float trap nozzle (Check for a large
amount of air sucked from the oil collecting pipe to oil
pump suction side.)
NOTE:
The oil mist remover makes the gear case internal pressure negative during operation, reducing the pressure by 0.7 to 1.5 psi
(0.005 to 0.01 MPa). This is not unusual; reset the oil pressure on the air OMR relief valve.
YES
YES
Perform necessary adjustment or replacement.
Disassemble and clean the float trap nozzle and the
float trap.
39
5. INSTALLING AND PIPING THE DSP
5.1 Unpacking the Air Compressor
■ After unpacking the crate, verify that the air compressor is what you have ordered, by referring to Section 15.
“STANDARD SPECIFICATIONS and also by checking the model nameplate.
■ Verify that product is not damaged or deformed during transpor tation.
Model Nameplate
Output (kW)
Model
Frequency (Hz)
Main Standard Accessories
Foundation bracket, Foundation bolt/nut (M20) 4 pieces
Use the strong wires.
Adjust the wire length to
keep the balance when
hoisting it.
Use the attached
tie frame.
ModelTotal Mass
DSP-90A6N
DSP-110A6N
DSP-90W6N
DSP-110W6N
ModelTotal Mass
DSP-90VA6N
DSP-110VA6N
DSP-90VW6N
DSP-110VW6N
5,250 lbs
(2,380kg)
5,600 lbs
(2,540kg)
5,030 lbs
(2,280kg)
5,380 lbs
(2,440kg)
5,470 lbs
(2,480kg)
5,580 lbs
(2,530kg)
5,250 lbs
(2,380kg)
5,360 lbs
(2,430kg)
Use the adhesive tapes
to prevent the front door
from detached during
conveyance.
Lift the unit balanced.
Use the adhesive tapes
to prevent the front door
from detached during
conveyance.
■ After installing the air compressor, plug the fork slots
with the fork slot covers.
Common Base
Fork Slot Cover
Bolt (M6×15)
40
5. INSTALLING AND PIPING [Installing the Air Compressor]
V
5.3 Installing the Air Compressor
(Selection of a proper installation location is essential to a long service life for the Air Compressor.)
WARNING
1. Keep flammable solvents or any other hazardous chemicals away from the air compressor. Such
chemicals may be ingested into the air compressor and could cause an explosion during the
compression process.
2. Do not use fire near the air compressor; otherwise the sparks may enter the airend and burn it internally.
■ Install the air compressor in a bright, wide, and airy room as follows:
entilating fan
If you install the air
compressor in a small room,
provide a ventilating fan to
keep the room temperature
at 104℉ (45℃) or lower.
Maintenance Space
Plug the fork slots with
the fork slot covers
(standard accessory)
Maintenance Space C
Foundation
Provide a vibration-absorbing
mat if the foundation is
vibrative. If it is too vibrative,
look for another dequate
Maintenance Space B
Maintenance Space A
※ Keep spaces of indicated in the
Maintenance Space inches (mm)
■Install the air compressor in a dry and dust-free room, and avoid the following.
Raindrops, Basements, Steam
Metals, Sand, Other Hard Materials
()
table below, or more for daily
operation and periodical
maintenance and for keeping the
enough cooling air for coolers.
Item
A
Front
B
Right
CRear
DLeft
Air-cooled model
39 (1000)47 (1200)
47 (1200)31 (800)
39 (1000)39 (1000))
39 (1000)39 (1000)
Water-cooled model
Harmful Gases
Toxic gases such as chlorine gas, hydrogen
sulfide gas, sulfurous acid gas, high consistency
ozone, ammonia gas
Causes electric leak, generation of
drain/rust, microcomputer malfunction.
■ Install the air compressor on a level floor.
To ensure an appropriate amount of oil
To prevent noise and vibration
Causes motor insulation failure, bearing
damage, microcomputer malfunction.
Prohibited
Do not set the air
compressor on blocks.
CAUTION
Causes deterioration of oil, wear of cooler,
detachment of coating from rotor surface.
Do not install the air compressor near a wall.
■
Doing this may cause the operating noise
to resonate and increase the noise levels.
● Install the air compressor indoors. Installing it outdoors may lead to damage of the airend due to
water vapor, dust, etc.
● The air compressor installation room should have an air intake opening, an air exhaust opening and
have good ventilation. If the room is poorly ventilated, hot air exhausted by the air compressor may
cause the room temperature to rise excessively and lead to damage of the air compressor.
41
5. INSTALLING AND PIPING [Piping the Air Compressor]
5.4 Piping the Air Compressor
5.4.1 General Instructions
① Use the degreased pipe as a plant airline pipe.
② Install an isolation stop valve on the compressed air
outlet pipe (see figure below). Close the isolation
stop valve when stopping the air compressor.
Stop Valve
Discharge Air
③
Using flange joint to connect the air compressor to an
existing compressed air piping installation allows for
minimal disassembly of the enclosure panels (see
figure above).
⑦ If the air compressors discharge pipe is connected to
the main compressed air piping, run the discharge
up above the main compressed air piping and then
down into the top of the main compressed air piping
(see figure below). This prevents the backflow of
condensate.
5.4.2 Parallel piping
Stop Valve
Main compressed air pipe
From air compressor
Motorized isolation valve
Opened
④ If the plant compressed air piping installation is
extensive in length, using a larger diameter pipe
assists in lowering pressure drop throughout the
piping system.
⑤ If there is an area in the compressed air piping that
is concaved or vertical (see figure below), provide a
condensate drain valve at its bottom as a drip leg.
Stop Valve
Condensate Drain Valve
IMPORTANT
Prevent the backflow of condensate from the plant
compressed air system back to the air compressor.
If the compressed air piping near the air compressor is
⑥
to be elevated, keep a space of 20inches (500mm)
between the elevated piping and the enclosure for ease
of maintenance (see figure below)
20inches or more
(500mm)
Discharge
Air
Operating DSP
Air Receiver Tank
Stop Valve
Motorized isolation valve
Closed
Non-Operating DSP
If one air compressor is operated, close the stop valve
of the stopped air compressor. For automatic operation,
such as lead/lag and multi unit controlled, replace the
stop valve to an optional motorized isolation valve.
Ensure that the motorized isolation valve is closed
while the compressor is not running. If you use a
solenoid valve as the automatic stop valve, consult your
Hitachi distributor or local Service Station given on the
rear cover.
Contact the local HITACHI distributor/master dealer
or representative office for more detail.
IMPORTANT
42
As shown in the figure above, when one compressor is
operating and the other is stopped with opening the stop
valve, back pressure is applied to the aftercooler and
check valve of the stopped air compressor. This may
cause more condensate going into the air compressor
and more rusting of aftercooler and check valve.
5. INSTALLING AND PIPING [Piping the Air Compressor]
5.4.3 How to Install Automatic
Discharge Valve
Discharge
Air
Air Receiver Tank
Stop Valve
Pressure
detecting
piping
The air compressor is equipped with AUTO restart/
stop function as a standard function. The pressure for
capacity control is detected at the secondary side of the
motorized isolation valve. Install the motorized
isolation valve and pressure detecting piping (standard
accessory). Connect the pressure detecting piping
from upper side of main piping to pressure detecting
port of the air compressor as above.
Install the pressure detecting piping as close as
motorized isolation valve. The operation with NOT
installed pressure detecting piping results in the air
relief valve action.
IMPORTANT
The motorized isolation valve is closed when the air
compressor is stop. The operation WITHOUT the
motorized isolation valve results in the backflow of
condensate from the plant compressed air system. Then
it results in the early damage of check valve, aftercooler
and etc by rusting
Motorized isolation
Flange
5.4.5 Reciprocating Compressor and
5.4.4 Air Receiver Tank
Pressure detecting piping
Discharge
Air
Air Receiver Tank
Failure to install an adequately sized air
receiver tank may cause the air compressor to
frequently load/unload. This may shorten the
mechanical life of the air compressor.
Install the air receiver tank because this air
①
compressor is equipped with 2-step capacity control
system. To prevent the pressure fluctuation and to
maximize the energy saving feature, the minimum size
of the air receiver tank is indicated in the table blow.
Install the air receiver tank of 620 USgal (2.26m3) of more
for the AUTO operation, multi-unit control or lead/lag
operation in order to achieve the better energy saving effect.
③ Install the air receiver tank of 620 USgal (2.26m3) of
more for using ECOMODE in order to achieve the
better energy saving effect on all load ratio.
Stop Valve
Motorized
isolation valve
CAUTION
Dis.Pressure
psi [MPa]
100/125
[0.69/0.86]
Flange
Minimum Capacity of
Air Receiver Tank US gallon [m3]
620
[2.26]
Parallel Piping
Discharge Air
Stop Valve
Piping to air receiver
tank outlet
IMPORTANT
Check ValveStop Valve
・ This is to prevent the reciprocating compressor's air
pulsation from affecting this air compressor.
・ Typical operation is to run this air compressor as long
as possible as the primary and start, and stop the
reciprocating air compressor in parallel as a floating
trim air compressor, as required by the compressed air
demand.
CAUTION
Do not install a check valve between this air
compressor and the air receiver tank. This
could result in short cycling (frequent loading
and unloading) and operating problems to the
capacity control system.
43
5. INSTALLING AND PIPING [Piping the Air Compressor]
A
5.4.6 Drain Pipe
To drain
pit
Drain Pipe
① Leave the end of any condensate drain line open.
② Do not merge the air compressor’s condensate drain
lines (for the aftercooler, intercooler, control line
filter) into one common piping. Do not merge any
condensate drain line into an external condensate
drain line (for example, do not merge an air
compressor condensate drain line with a condensate
drain line on an air receiver tank). This could
generate a pressure differential, which could result
in no draining or inconsistent draining out of the air
compressor. Capability to observe the draining of
the air compressor is also impaired.
5.4.8 OMR Control Air Piping
Pressure gauge
Filter regulator
The Oil Mist Remover needs the pressure of a control
air at the regulator setting value or more. To properly
install the control air line, connect the control air pipe
to the connection marked “A” on the filter/regulator of
the Oil Mist Remover. This piping and compressed air
shall be supplied by customer.
IMPORTANT
The control air must be as dry as possible. Run the
control air pipe from the downstream side of the air dryer.
If an air dryer is not used, run the control air pipe from the
upper section of an air receiver. Installing downstream of
the air dryer or air receiver allows for less moisture
accumulation in the filter bowl of the oil mist remover.
CAUTION
Un-drained condensate can backflow to the
air compressor and cause a failure.
5.4.7 Cooling water piping
Water-Cooled
Cooling drain discharge valve
Water
outlet
Water
Inlet
① The pipings for water inlet and outlet for coolers are
required.
② Mount the water drain valves of the cooling water
outlet and inlet downward facing downward as
shown in the figure. The water drain valves may
also be mounted facing sideways.
③ Using flange joint to connect the air compressor to
the water pipings, allows for minimal disassembly of
the enclosure panels.
44
5. INSTALLING AND PIPING [Ventilation of Air Compressor Room]
A
5.5 Ventilation of Air Compressor Room
5.5.1 Air-Cooled model
CAUTION
Air-Cooled
Provide a ventilating system to the air
compressor room in the event that the room
temperature exceeds the allowable ambient
operating temperature of 104°F (40°C).
Operating the air compressor at an ambient
operating temperature above 104°F (40°C) may
cause a serious problem.
IMPORTANT
● Stop the ventilating fan when the air compressor has
stopped.
● The ventilating fan should be running while the air
compressor is operating. If the ventilating fan is not
running, the loss of air flow may reduce the performance
of the cooler.
The duct should be detachable for ease of maintenance
Provide the air compressor room with an enough air
intake opening that:
- is positioned as low as possible on the wall.
- is located in an environment free of external dust
and harmful material.
② Ventilation without Duct (Fig. A)
For ventilation without an exhaust duct, install a
ventilating fan with the specified capacity shown in
the Recommended Ventilation Fan① or more
row in the lefttable. The specified capacity is based
on the allowable room temperature rise of 9°F (5℃).
Position of the ventilating fan is as high as possible
on the wall.
③ Ventilation with Duct and without Ventilating
Fan (Fig. B)
● For ventilation with an exhaust duct, calculate the
duct’s pressure loss based on information shown in
the Air Exhaust (Air Compressor) row in the table.
If the calculated pressure loss is less than 0.08
inchAq (20 Pa), a ventilating fan is not required on
the duct. Install the duct with its detachable end
directly in contact with the grilled air exhaust on top
of the air compressor.
● If the calculated duct’s pressure loss is 0.08 inchAq
(20 Pa) or larger, a ventilating fan is required on the
duct. Install the duct, keeping a gap “h” of 8 to 12
inches (200 to 300 mm) between the duct and the
grilled air exhaust on top of the air compressor. On
the other end of the duct, install a ventilating fan with
the specified capacity shown in the Recommended
Ventilation Fan ② or more in the lefttable. (Fig. C)
● Pay attention to the duct opening location. Noise
may be transmitted to outside through the duct.
Provide the noise absorbing material inside the duct
if required.
Exhaust air
air exhaust
(air compressor)
Ventilating fan
See “Recommended
ir intake
opening
Fig. AFig. BFig. C
fan capacity ①” in
the table.
Exhaust
Duct
Air intake
opening
Exhaust air
Ventilating fan
See “Recommended
fan capacity ③” in the
table.
Shall be
removable.
Exhaust
Duct
Air intake
opening
Exhaust air
h
Ventilating fan
See “Recommended
fan capacity ②” in
the table.
45
5. INSTALLING AND PIPING [Ventilation of Air Compressor Room]
CAUTION
When installing exhaust ducts, install a single
duct for each compressor. Alternatively, when
installing a collecting duct for multiple
compressors, install it as shown in Fig. C.
Also, be sure to install a ventilating fan with a
capacity of the value of "exhaust air from the
compressor x quantity" or more on the other
end of the duct.
Air inlet
Ventilating
fan
See “Recommended
fan capacity” in the
table.
Fresh
air
Exhaust air
Exhaust air
5.5.2 Water-Cooled Type
Water-Cooled
① For the small air compressor room installation,
install a ventilating fan and an air intake opening.
The position of the ventilating fan is as high as
possible and the position of the air intake opening is
as low as possible on the wall.
Select a ventilating fan with required capacity
specified in the table or higher (Fig. A). Also ensure
that the flow rate at the air intake opening is 2 m/s
or lower.
Technical Data for Room Ventilation
Item/Unit
Heat
Generation
Recommended
fan capacity ①
The specified capacity is based on the allowable room
temperature rise of 9°F (5℃) and static pressure is zero0 psi
(0 MPa).
Model
KBTU4653
(MJ/h)(49)(56)
cfm4,5905,300
3
/min)(130)(150)
(m
DSP-90W6N
DSP-90VW6N
DSP-110W6N
DSP-110VW6N
Air inlet
Fig. A
Exhaust air
Exhaust air
Fresh
air
Fig. B
② For the factory installation with enough ventilation
capacity, select a well ventilated area (Fig. B).
46
6. STARTUP OPERATION
The instructions in this chapter should be followed when starting up the air compressor for the first time or after a
long term suspension.
6.1 Startup Operation of the Air Compressor
CAUTION
● Before connecting the power, verify that the air compressor is correctly installed, piped and wired.
● Check the power supply; verify that it is firmly grounded and that the voltage is within an allowable
range (-5% to +10%).
● Remove transport fixtures (3 locations in yellow). If you run the air compressor leaving the transport
fixtures attached, it may break the pipes due to excessive vibration.
● When transporting the unit, tighten All 4 transport fixture
●
Ensure that the main motor is properly greased during the start up commissioning. If the air
compressor has not been operated for (3) months, grease before restarting. (
9.4 14)
6.1.1 Before Operation
④
RUNNING CONTROLRUNNING MODE
SELECT/WIDE
REMOTE
LOAD
AUTO START
SHUTDOWN
2
1
UNLOAD STOP
ALARM
RESET
FUNC
REMOTE
STR
①
IMPORTANT
If the compressor (Air-cooled model) restart just after
stopped, the air compressor shutdowns by fan motor overload with indication of OVERLOAD SUB in LCD monitor
and E0.53 in digital monitor. Reset and restart the air compressor after 30 seconds or more.
① Fill the oil in the oil filling port until the oil reaches
the upper red line on the oil level gauge.
Use the recommended oil indicated in 2.3.
Water-Cooled
② Close the petcock and cooling water drain valve and
open the manual stop valve for cooling water.
POWER
③ Verify that the pressure and flow rate of the cooling
STOPSTART
water.
④ Connect the power, and verify that the POWER light
is ON. (
3.2)
⑤ In case of Reverse phase indication on LCD monitor,
refer to
4.2 and take proper action.
WARNING
Hitachi does NOT fill the air compressor with oil.
Before startup operation, fill the air compressor
with the oil. If oil is not added and the air
compressor is operated, it may burn or fail.
Water-Cooled
[Front view][Rear view]
Transport fixturesTransport fixtures
47
6. STARTUP OPERATION [Startup Operation of the Air Compressor]
6.1.2 Starting
② Verify that the air compressor has proper rotation.
① Fully open the discharge stop valve, and press the
START button.
If rotation is not correct (phase reversal), change 2 of
the 3 wires of the power cable.
③ Verify that the oil pressure rises 18psi (0.12 MPa) or
greater within ten (10) seconds after starting the air
compressor. If pressure has failed to rise, press the
STOP button and clean the oil strainer. And/or
regulate the oil pressure by oil relief valve. (
④ In the case of the fixed speed type, switch to full load
operation within 20 seconds, and for the V type,
switch in approx. 10 seconds.
⑤ Raise the pressure step by step as illustrated below.
100
Pressure Raising Pattern
for the rated
90
discharge pressure
100 psi (0.69 MPa)
75
60
45
30
15
Discharge pressure (psi)
0
0.5hr 1hr 1.5hrs 2hrs
3.7)
Method of Raising Pattern:
During startup operation, raise the discharge pressure by
following these steps. 1.) After starting the air compressor,
operate at 29psi (0.20MPa) for 30 minutes with the discharge
stop valve completely open. 2.) Raise the pressure 14 psi
(0.1MPa) (close the discharge stop valve) every 15 minutes
until the pressure reaches the rated pressure. During the
startup operation, perform this method without any failures.
(DIS. PRESS), interstage air pressure (INTSTG. P),
oil pressure (OIL PRES), 1st stage discharge air
temperature (DIS. TEMP 1), 2nd stage discharge air
temperature (DIS. TEMP 2), 2nd stage suction
temperature (2ND SUC. T.) and oil temperature (OIL
TEMP) are within the normal range, as shown in the
UNLOAD STOP
Proper Pressure/ Temperature Indications on LCD
table below.
③
Verify that the condensate is discharged
intermediately
from the intercooler/aftercooler drain port.
CAUTION
Ensure that the main motor is properly greased
during the start up commissioning. If the air
compressor has not been operated for (3)
months, grease before restarting. (
9.4 14)
① Grease the main motor bearing at once. Refer to the
9 Maintenance 13 for the detail.
48
WARNING
During inspection of the operation of the air
relief valve, use the appropriate facial protection. High pressure air containing dust particles
can cause severe injury.
6. STARTUP OPERATION [Startup Operation of the Air Compressor]
Proper Pressure/Temperature Indications on LCD
LCD IndicationUnit
Operating State
Discharge Air Pressure
Interstage Air Pressure
Working Pressure
100psi (0.69MPa)
125psi (0.86MPa)
DSP-90A6N, DSP-90W6N
DSP-110A6N, DSP-110W6N
−LoadingUnloadingLoadingPurging
psi
(MPa)
psi
(MPa)
100 (0.69) or less
125 (0.86) or less
25 to 38
(0.17 to 0.26)
85 (0.59) to 100 (0.69)
110 (0.76) to 125 (0.86)
-11 to 0
(-0.08 to 0)
DSP-90VA6N, DSP-90VW6N
DSP-110VA6N, DSP-110VW6N
103 (0.71) or less
128 (0.88) or less
25 to 42
(0.17 to 0.29)
3 to 15
(0.02 to 0.10)
* 13 to 26 (0.09 to 0.18)
Oil Pressure
psi
(MPa)
* 16to26
(0.11 to 0.18)
(Freq. 45Hz or higher)
7 to 23 (0.05 to 0.16)
(Freq. less than 45Hz)
1st-Stage Discharge Air Temperature
2nd-Stage Discharge Air Temperature
Oil Temperature
2nd-Stage Suction Air Temperature
100psi (0.69MPa)
125psi (0.86MPa)
100psi (0.69MPa)
125psi (0.86MPa)
℉(℃)
℉(℃)
℉ (℃)
℉ (℃)
Note) * The oil pressure may exceed 26 psi (0.18 MPa) temporarily when starting. The oil pressure may exceed 26 psi (0.18 MPa) temporarily
when PQ wide mode ON for Vtype. These are normal.
426/408 (219/209) or Less435/408 (224/209) or Less
426/408 (219/209) or Less 435/408 (224/209) or Less
435/417 (224/214) or Less 435/417 (224/214) or Less
489/471 (254/244) or Less489/471 (254/244) or Less
compressor. Operation stops when the air end and
the air piping have dried for 5 minutes. To stop the
compressor immediately without unloading, press
the STOP button.
② Check the LCD for pressures, and verify that:
Oil pressure, interstage air pressure, 0 psi (0 MPa)
or 1 psi (0.01 MPa) depending on your operating
conditions).
③ Check the condensate drain discharge from the
control line filter by checking the sight glass on the
control line filter. (Fixed speed type)
④ Close the stop valve.
Water-Cooled
⑤ Open the water drain valve. Do not fail to drain the
cooling water specifically winter season because the
remaining water may be frozen inside and as a result
the casing and/or coolers may be burst.
49
6. STARTUP OPERATION [Initial Setting of OMR Regulator]
6.2 Initial Setting of OMR Regulator
① Set a control air pressure to a maximum level.
Example: If a control air pressure varies between
80 psi (0.55 MPa) and 95 psi (0.65 MPa),
maintain it at its maximum 95 psi
(0.65 MPa).
② Pull up the regulator knob, and then the regulator is
unlocked or settable.
Turn the regulator knob so that the pressure gauge
reads as follows:
③ The pressure gauge readings may increase/
decrease by 4 psi (0.03 MPa) as the control air
pressure decreases/increases by 15 psi (0.10 MPa),
respectively. Due to the regulator’s characteristics,
the pressure gauge reading rises as the control air
pressure drops.
Standard Setting of Regulator
psi (MPa)
51 - 55
(0.35 - 0.38)
Air Flow Rate
cfm (liter/min)
about 2.1 (60)
④ Make sure that the vacuum indicator does not show
a red mark.
⑤ Make sure that there is no leak of the control air
pipe joints.
⑥ Press down the regulator knob to lock.
⑦ The oil mist remover makes the gear case internal
pressure negative during operation reducing the oil
pressure by 0.7 to 1.5 psi (0.005 to 0.01 MPa). This
is not abnormal.
Reset the oil pressure on the OMR relief valve.
⑧ Stop the air compressor. Make sure that the
solenoid valve is de-energized to the closed position
and the vacuum indicator shows a red mark.
CAUTION
1. Maintain the pressure of a control air at the regulator setting value or more. If a control air pressure
of this level cannot be obtained, the ejector cannot operate and as a result, the gear case internal
pressure rises.
When the gear case internal pressure reaches approximately 196 Pa (20 mmH
valve opens to atmosphere to prevent excessive rise. This results in the venting of oil fume to
atmosphere.
Therefore, if a control pressure cannot be maintained at the regulator setting, value, take
precautions to keep the air compressor from inhaling the oil fume back into the air intake.
2. If two or more air compressors are in parallel, the system may force a specific unit to unload for a
long period of time. The unloaded air compressors oil mist remover ejector may seldom operate,
thus opening its OMR relief valve frequently and venting oil mists to atmosphere. To solve this
problem, connect the unloaded air compressors control air pipe to an area in the plant air piping
system where pressure is consistently available, minimizing the amount of time the OMR relief valve
opens.
3. The OMR relief valve shortly opens when the air compressor starts and stops, even when control air
pressure is high. After repeated starts and stops, the OMR relief valve may ooze a slight amount of
oil. This is not unusual.
4. The oil mist remover consumes compressed air of approximately the value indicated above table.
The exact air consumption depends on the setting of the regulator.
O), the OMR relief
2
5. Take precautions if the air compressor is used in AUTO operation mode, as the air compressor may
not stop automatically, due to the uninterrupted consumption of the compressed air by the oil mist
remover.
50
7. WIRING
WARNING
1. Always use a licensed electrician. Do not allow an unlicensed person to wire the air compressor. An
unlicensed person may wire the air compressor wrongly, and a wrong wiring may cause an electric shock.
2. Do not remove any protective relays on the air compressor. Also, do not make a modification of the
control circuit that may result in impairing the protective relay's function. Remember that the loss of the
protective relay's function may cause serious damage to the air compressor such as a burning of the air
end. In the event that you need to modify the control circuit, consult your distributor.
3. Before opening the control panel to service or wire the air compressor, disconnect the power; otherwise
you may receive an electric shock. In addition, attach a notice on the power supply stating “Under the
maintenance work. Keep the switch off.” to prevent someone from carelessly turning the switch on.
7.1 Power Supply Equipment
Use a power supply transformer with adequate kVA
capacity and a power cable with adequate thickness and
length. If properly sized transformers and cables are not
used, excessive voltage drop could occur when the
START button is pressed, resulting in 1.) Motors failing
to fully accelerate and/or, 2.) An inefficiently energized
control circuit; thus shutting down the air compressor.
To keep a starting voltage drop within an allowable range
transformer and power cable shown below table. Lower
thickness values are based on the power cable length of
less than
393 inches (10 m)
cable is longer than
power cable. Provide intermediate terminals to keep the
power cable thickness lower than the maximum values at
the air compressor terminal block. The maximum
voltage imbalance between the phases shall be within 1%.
(5% of the rated voltage), use the power supply
Model
Power Supply Voltage460V
Power Transformer Capacity
Power Cable Thickness AWG (mm2)
Capacity values are reference data; some power supplies may require a larger-capacity transformer.
(1)
(KVA)200 or more250 or more200 or more250 or more
DSP-90A6N
DSP-90W6N
4/0 to 300
(125 to 150)
DSP-110A6N
DSP-110W6N
250 to 300
(125 to 150)
7.2 MIV and WIVM wiring
WIRING FOR MIV
1
2
3
4
5
WIRING No. 'DA'
WIRING No. '44'
WIRING No. '43'
CABLE FROM TB3 IN THE CONTROL PANEL
TERMINAL BOX OF MIV
① Electrical wiring of Motorized Isolation Valve (MIV),
and Motarized Water Isolation Valve (WIVM) shall
be install on side. Refer to the drawing.
(WIVM is only for water-cooled.)
. In the event that the power
393 inches (10 m)
DSP-90VA6N
DSP-90VW6N
4/0 to 300
(125 (2) to 150)
, employ a thicker
DSP-110VA6N
DSP-110VW6N
250 to 300
(125 to 150)
BLACK
WHITE
RED
GREEN
YELLOW
WIRING FOR WIVM
WIRING No. 'DA'
WIRING No. '46'
WIRING No. '45'
CABLE FROM TB3 IN THE CONTROL PANEL
TERMINAL BOX OF WIVM
51
7. WIRING [Connecting the Power Cable]
7.3 Connecting the Power Cable
① Wiring inside the air compressor is completed prior
to shipment by Hitachi.
Refer to “Wiring Diagram” on
② Ground resistance requirements are required when
connected the power cable and grounding cable.
The ground resistance requirements are shown in
the table below:
Power Supply Voltage
460VType C10 Ωor less
③ For service accessibility to the air compressor,
install the power cable away from the enclosure.
④ Both main disconnect means and branch circuit
protection shall be provided. In addition, main
disconnect means shall be provided on the line side
of the branch circuit protection.
The type(Fuse disconnect, Circuit breaker, or Earth
leakage (ground) circuit breaker) and its sizing
must be selected in accordance with national or local
electric code requirements. (Recommendation type:
(
“Wiring Diagram”)
Ground Resistance Type
7. 4 .
Ground Resistance Value
Do not use simple disconnect such as knife switch in
wiring.
The type and sizing not supplied by Hitachi is the
responsiblitiy of the customer.
NOTE: Use the earth leakage circuit breaker that is
sensitivity-current-switchable (selectable,either
100 mA or 200 mA) and set its earth leakage
sensitivity current to 200 mA
⑤ Disconnect the power and verify that it is safe before
1.) Overhauling the DSP, 2.) Adding oil to the DSP
and/or 3.) Servicing the starter/control box.
⑥ Field wiring connections must be made by UL and
CSA certificated ring lug terminal connectors sized
for the wire gauge being used. The connector must
be fixed using the crimping tool specified by the
connector manufacturer.
Remove the control panel cover and connect the power
cables as illustrated below.
CAUTION
Protect the power cables with using attached
rubber bush, conduits and/or protective tubes.
An unprotected power cable can come into
direct contact with the steel plates on the
power cable holes with a slight amount of
vibration. This could damage the cover over
time and result in a short circuit accident.
CAUTION
● Install an earth leakage circuit breaker at the right primary side of the air compressor.
Do not install a disconnect switch such as a knife switch in the wiring, as it is not protect the air
compressor and may result in the burning of motors if a ground fault occurs.
● Ground the air compressor to prevent electric shock or an air compressor failure. Ground
independently and directly to the earth (Do not use the steel skeleton of the building as a ground, as it
could cause an operational failure).
52
7. WIRING [Connecting the Power Cable]
■ Other Operating Precautions
(1) A thermal relay is not provided on the main circuit
of the inverter-controlled DSP. Instead, the
electronics-type thermal relay is built into the
inverter for protecting the main circuit.
(2) Phase failure is only enabled immediately after
connecting the power. If a phase failure occurs
during operation, it is not detected and eventually
causes the inverter to overheat. Tightly fasten,
therefore, the cables/wires.
(3) Do not install a power-factor enhancing capacitor
on the motor side. Failure to observe this may
cause the inverter’s capacitors to receive the
larger charging current, resulting in a failure of
the inverter.
(4) In the cases that a phase advance capacitor
installed between power and the air compressor
opens and closes, a surge voltage may be
generated in the controller input side, which may
cause a controller failure. In such cases, install an
AC reactor shown in the right table between power
and the air compressor.
(5) If radios, TV sets, or any other electronics devices
are located around the air compressor, install the
HITACHI noise filters as specified in the right
table on the primary side of the air compressor.
(5) The inverter in the starter is attached with a digital
operator for setting and operating the inverter.
Hitachi has finished adjusting the digital operator to
the appropriate settings, before shipping the DSP
from the factory. Do not operate the attached digital operator; otherwise the inverter may
malfunction and cause a problem.
Recommended AC reactor
ModelAC reactor
90VA6N, 90VW6N
110VA6N, 110VW6N
CAUTION
ALI-180H2
Immediately after disconnecting the power,
the inverter is still live. Before servicing the
starter/control box, therefore, make sure that
the inverter’s charge indicator is off or wait for
10 minutes after disconnecting the power.
Description
Zero phase
reactor
Radio noise
filter for input
Noise filter
for inverter
90VA6N,90VW6N
110 VA 6N,110 VW 6 N
460VZCL-A
460VCFI-H
460V
NF-H250
Functions
Reduces the radio frequency
interference, etc.
Reduces the conductive
noise in the power cable
wiring by the inverter.
Reduces radiated noise
from the power cable.
53
7. WIRING [Wiring Diagram, Control panel/LCD Monitor Specifications]
Dry contacts (1) Operation signal output : a contact × 1
Instantaneous Power Interruption
and Restarting
Note) Setting(1): Time selected on the instrument panel (from 1 to 5 seconds)
Setting (2): 15 to 60 seconds
Unload Stop: Operated by the Unload Stop button located lower on the operating monitor.
"This wiring diagram is for reference. Refer to the wiring diagram drawing in the control panel for the detail."
5. Wiring Diagram 2 (DSP-90/110N)
59
8. STANDARD COMPONENTS AND SUBSYSTEMS
8.1 Standard Components
⑴ Airend
A rotor assembly rotates while the timing gear keeps
a precise clearance between the male and female
rotors. This non-contacting, high speed rotation of
the rotor assemblies compresses the intake air.
There is no oil injected into the rotor assemblies
during the compression process, allowing the air
compressor to discharge oil free compressed air.
⑴Roto rs: The surfaces of the rotors are finished
with a special heat-resistant PTFE-free
coating designed to precisely limit the
clearances between the male and female
rotors and prevent rust.
⑵Beari ng: The heavier male rotors are supported
by bearings that are larger in diameter,
thus increasing service life.
⑶Case: The jackets for oil (air-cooled model) or
for cooling water (water-cooled model) are
provided on the case to absorb the heat of
compression.
⑷Timin g gears:
gears is mounted on the ends of the rotor
shafts to keep a precise clearance between the
rotors and prevent contact during rotation.
⑸Shaft seal: The sealing mechanism consists of
both 1.) Air seals and 2.) Visco-type seals.
Air seals prevent the compressed air from
leaking out of the compression chamber.
Visco-type seals prevent the oil in the gear
case from entering the compression chamber.
A pair of precision finished timing
⑵ Compressor Drive Train
The air compressor employs a high efficient, 2-pole
for fixed speed type or 6-pole for Vtype, totally
enclosed, fan cooled (TEFC) motor. The rotation
speed of both the 1st and 2nd stage airends are
increased to a properly rated level by a set of step-up
gears in the gear case.
⑶ Capacity Control System
[Fixed-speed type]
When the demand of compressed air decreases, the
system closes the suction throttle valve and
exhausts the internal compressed air to atmosphere
at the same time, thus unloading the air compressor.
When demand of the compressed air decreases, the
system reduces the motor speed. And When
demand of the compressed air decreases more,
purges the compressed air to atmosphere.
⑷ Intercooler
Air-Cooled
The air-cooled intercooler is made of aluminum. The
intake air is compressed up to 29 psi (0.20 MPa) (and
consequently heated) by the 1st stage airend. The
intercooler cools the heated air to an atmospheric
temperature + approx. 27°F (15℃) and separates the
water vapor from the discharge air before the air
enters the 2nd stage airend in the process.
Water-Cooled
The water-cooled intercooler is shell and tube type.
The intake air is compressed up to 29 psi (0.20
MPa) (and consequently heated) by the 1st stage
airend. The intercooler cools the heated air to
cooling water temperature + approx. 27〜36°F (15
〜20℃) and separates the water vapor from the
discharge air before the air enters the 2nd stage
airend in the process.
⑸ Hi-Precooler
The air-cooled Hi-precooler is located between the
2nd stage airend and the intercooler, and has the
following functions:
-Primarily cool the hot compressed air discharged
by the airend.
Air-Cooled
⑹ Aftercooler
Air-Cooled
The air-cooled aftercooler is made of aluminum. It is
located downstream of the check valve and reduces
the discharge air temperature down to an atmospheric
temperature +27°F (15℃) or lower and separates the
water vapor from the discharge air in the process.
Water-Cooled
The water-cooled intercooler is shell and tube type. It
is located downstream of the check valve and reduces
the discharge air temperature down to cooling water
temperature + 23°F (13℃) and separates the water
vapor from the discharge air in the process.
⑹Check valve
The check valve is located downstream of the 2nd stage
airend and prevents backflow of the discharge air.
⑺Lubricating system
The lubricating subsystem consists of the oil pump,
oil strainer, oil filter, oil cooler and oil relief valve.
The oil pump circulates the oil in the gear case oil
sump through the lubrication subsystem, keeping
the bearings, gears, etc. lubricated.
60
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil/Water Flow]
8.2 Air/Oil/ Water Flow
⑻ Air intake filter
The air intake filter is a dry type for easy cleaning or
replacement.
⑼ Fan
Air-Cooled
The low noise cooling fan cools the cooler, exhausts
the hot air within the enclosure, and exhausts the
internal compressed air that is released to
atmosphere during the unloading (purging) process.
Water-Cooled
The small cooling fan cools the inside of the
package, and exhausts the internal compressed air
that is released to atmosphere during the
unloading (purging) process.
※ The indication in the ( ) is for Vtype.
⑽ Control panel
The control panel employs a printed circuit board
on which a microprocessor is mounted to achieve
easy operation. The air compressor can be operated
remotely.
⑾ Enclosure
The enclosures are attached with the sound
absorbing materials. The front and left enclosure
panel includes a door that enables easy maintenance.
Compressed Air Flow
Intake air is compressed and heated by the 1st stage
airend and pressure builds up to approximately 29 psi
(0.20MPa) The heated air is cooled down by the
intercooler and then further compressed and heated by
the 2nd stage airend as pressure builds up to the rated
pressure level of the air compressor. The reheated air
flows through the check valve to the aftercooler, where
the compressed air is cooled down and then discharged
to the plant compressed air piping.
Oil Flow
The oil sump is located in the bottom of the gear case.
Oil is sucked through an oil strainer (oil strainer has a
100-mesh filter screen) by the oil pump and is
hydraulically fed to the oil cooler where it is cooled.
During the cooling process, oil flows through the highprecision oil filter and is then injected onto the bearings
of the 1st and 2nd stage airends as well as the stepup
gears. Oil returns to the oil sump, where it continues
to circulate through the system.
Air-Cooled
Cooling Air Flow
The cooling fan removes the heat from the air-cooled,
cooler, intercooler, aftercooler and Hi-precooler, and
oil
this heat exchanged air is
exhaust grill on the top of the enclosure.
Water-Cooled
Cooling Water Flow
Incoming water cools the intercooler, the water jackets
of the airends, the aftercooler and the oil cooler. Refer
to “Cooling Water Flow Diagram” for the detail of
cooling water flow (
page).
exhausted through the air
see the flow diagram from next
61
8. STANDARD COMPONENTS AND SUBSYSTEMS [Air/Oil/Water Flow]
Flow Diagram (Fixed speed type)
53
Suction
39
PS4
TH4
TH3
38
54
22
63SV
1
2
31
Air-Cooled
ExhaustExhaust
5251
21
4
32
3
23
24
MOHR
33
TH5
41
37
Control air
Air Intake
for Motor
5
34
36
35
Air Intake
for coolers
40
8
14
13 16
Legend of the Diagram
Compressor Air Flow
11st-Stage Air-End
22nd-Stage Air-end
3Gear Case
4Stepup Gear
5Main Motor
6Intercooler
7Check Valve
8Hi-Precooler
Thermostat (for main motor bearing)
Pressure Differential Sensor
63SV
(For suction Filter clogging detection)
Description
65
8. STANDARD COMPONENTS AND SUBSYSTEMS [Cooling Water]
8.3 Cooling Water
Water-Cooled
1. Cooling Water Quality
If a cooling tower (open-type circulatory cooling water
system) supplies the cooling water to the Air
compressor, problems such as corrosion, scale, and
slime may be caused by:
(1) higher mineral content due to concentration,
(2) contamination by foreign matter like insects, and/or
(3) production of algae or bacterium. Using the best
quality cooling water is highly recommended.
(4) Refer to the table “Cooling Water Quality” below for
the open type circulatory system.
① Stop the cooling water flow, when the air compressor
has stopped. Open the petcock and the water drain
valve to drain the cooling water (see Figure 1 below).
Failure to perform step 1, can lead to the following:
Water Relief Pet Cock
a) The cooling water pipe could freeze and burst in
cold temperatures.
b) The airend case can be overcooled and develop
moisture internally; thus leading to scaling in the
cooling water jackets.
② Clean the cooling water subsystem (cooling water
jackets of the first- and second-stage airends,
intercooler, aftercooler, and oil cooler) periodically.
2. Control of Cooling Water
The service life of the cooling water system depends on
water quality. If the cooling water quality is not within
specification, the cooler pipes can corrode or scaling can
occur. To avoid the problem, periodically sample the
cooling water used and subject it to a quality inspection.
3. Quantity and Pressure of Cooling Water
Refer to the table “Quantity and Pressure of Cooling
Water” below.
CAUTION
Performance of the coolers varies depending
on the extent of throttling the stop valves at
the cooling water inlet and outlet.
To control the cooling water flow rate, throttle
Water Drain Valve
the stop valve at the outlet and leave the stop
valve at the inlet opened completely.
■ Cooling Water Quality
No
pH [at 77
1
2
Electrical Conductance [at 77
3
Chloride Ion Cl
4
Sulfuric Acid Ion SO
5
Acid Consumption [at pH 4.8] (mgCaCO
6
Total Hardness (mgCaCO
7
Calcium Hardness (mgCaCO
8
Ferrous Substance (mgFe/ℓ)
9
Sulphur Ion S
10
Ammonium Ion NH
11
Ionizing Silica SiO
12
Isolated Carbonic Acid CO
13
Nitric Acid Ion NO
14
Organic Substance (KMnO4 Consumption) (mg/ℓ)
15
Turbidity (mg/ℓ)
Notes: 1. System Water is the one that passes through a heat exchanger of circulatory or qnon-circulatory system.
2. Above No. 1, 2, 4, 5, 7〜12 are based on the standard: JRA-GL-02-1994.JRA: (Japan Refrigeration and Air Conditioning Industry Association)
3. The above criteria does NOT give any assurance of trouble-free or problem-free conditions due to other and time-depending factors but the minimum
°F(25℃)]
ー
(mgClー/ liter)
2ー
(mgS2ー /ℓ)
Make-up Water is the one that is supplied to a cooling tower.
requirement.
ItemMake-up Water
°F(25℃)] (ms/m)
2ー
4
(mgNH
4
(mgSiO2 / liter)
2
ー
(mgNO3 ー /ℓ)
3
(mgSO
/ℓ)
3
+
/ℓ)
4
(mgCO2 /ℓ)
2
2ー
4
/ℓ)
3
/ℓ)
/ℓ)
3
6.0 to 8.0
less than 30
less than 50
less than 50
less than 50
less than 70
less than 50
less than 0.3
Not detected
less than 0.1
less than 30
less than 4
less than 0.5
less than 10
less than 10
System Water Used
6.5 to 8.0
less than 80
less than 200
less than 200
less than 100
less than 200
less than 150
less than 1.0
Not detected
less than 1.0
less than 50
less than 4
less than 0.5
less than 10
less than 10
Problem
CorrosionScale
○
○
○
○
−
−
−
○
○
○
−
○
○
○
○
○
○
−
−
○
○
○
○
−
−
○
−
−
○
○
■ Quantity and Pressure of Cooling Water
Model
Item
Max. inlet temp.
Total flow rategpm (liter/min)42 (160)48 (180)
Min. pressure differential (between inlet and outlet)psi (MPa)22 (0.15)
Temp. differential (between inlet and outlet)
Required water pressure psi (MPa)22 - 71 (0.15 - 0.49)
°F
°F
(℃)
(℃)
DSP-90W6N
DSP-90VW6N
DSP-110W6N
DSP-110VW6N
95 (35)
16 (9)
66
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
8.4 Capacity Control System
8.4.1 Load-Unload Operation (Only for Fixed Speed Type)
The unloading process occurs when the compressed air
demand decreases and the discharge pressure rises as
high as cut-out pressure. The pressure sensor (PS)
detects the high pressure and energizes the 3-way solenoid
valve (20Ux), changing its port to port connection. The
control air is now flowing to and pressurizing chamber
(A) of the suction throttle valve (STV), consequently
closing the suction throttle valve (STV) and unloading the
airend while the blowoff valve opens and exhausts the
internal compressed air to atmosphere.
The loading process occurs when the compressed air
demand increases and the discharge pressure dropped as
low as cut-in pressure. The pressure sensor (PS) detects
the low pressure and 3-way solenoid valve (20Ux), suction
throttle valve (STV), and blowoff valve work in reverse
action and the airend reloads.
STARTING
Suction throttle valve (STV) closed
START button ON
Airend starts rotation to
compress minor amounts of air
Starts in no load
Changes to full voltage delta connection
3-way solenoid valve (20Ux)
switched over to connect
Chamber (A) & Chamber (C)
Suction throttle valve (STV) opens
Loading
Vacuum Valve
Pressure sensor (PS) operates
Internal air in discharge pipe is
UNLOADINGRELOADINGSTOPPING
Air demand decreases
Discharge pipe pressure rises
3-way solenoid valve (20Ux)
switched over to pressurize
Chamber (A)
Suction throttle valve
(STV) closes
Blowoff valve opens
exhausted to atmosphere
To Chamber (B)
To Chamber (A)
Blowoff
Valve
Air demand increases
Discharge pipe pressure drops
Pressure sensor (PS) operates
3-way solenoid valve (20Ux)
switched over to pressurize
Chamber (B)
Suction throttle valve
(STV) opens
Blowoff valve closes
Loading
3-Way Solenoid
Valve (4)
3-Way Solenoid
Valve (20US)
20US
NO
20U4
COM
NC
COM
NC
STOP button ON
3-way solenoid valve (20Ux)
switched over to pressurize
Chamber (A)
Suction throttle valve
(STV) closes
Blowoff valve opens
Internal air in discharge pipe
is exhausted to atmosphere
Compressor stops
3-Way Solenoid
Valve (1)
NO
COM
20U1
Control Air Flow
Starting/Stopping
Loading
Unloading
Suction Throttle Valve
1st-Stage
Air End
Intercooler
Check Valve
2nd-Stage
Air End
Chamber
(C)
Chamber (B)
NC-COM connected for
5 seconds after reactor
is changed over to a
fullvoltage connection.
Chamber (A)
20U3
3-Way Solenoid
Valve (3)
Check ValveAftercooler
NC
NO
COM
To the
Atmosphere
NC
20U2
3-Way Solenoid
Valve (2)
COM
NO
PS
NC
NO
Control Line Filter
Pressure Sensor
Compressed Air Discharge
For 20 seconds
after starting with a
star-delta starter.
67
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
8.4.2 AUTO Operation (Only for Fixed Speed Type)
AUTO operation is Auto start - stop function in addition
to a standard on-off line, 0% or 100% capacity 2-step
control. The CPU on the PC board is continually
calculating a load ratio.
STARTINGUNLOADINGRELOADINGSTOPPING
Suction throttle valve (STV) closed
START button ON
Airend starts rotation to
compress minor amounts of air
Starts in no load
Changes to full voltage
delta connection
3-way solenoid valve (20Ux)
switched over to connect
Chamber (A) & Chamber (C)
Suction throttle valve (STV) opens
Loading
Air demand decreases
Discharge pipe pressure rises
Pressure sensor (PS) operates
3-way solenoid valve (20Ux)
switched over to pressurize
Chamber (A)
Suction throttle valve
(STV) closes
Blowoffvalve opens
Internal air in discharge
pipe is exhausted to
atmosphere
Air demand increases
Discharge pipe pressure drops
Pressure sensor (PS) operates
3-way solenoid valve (20Ux)
switched over to pressurize
Suction throttle valve
(STV) opens
Blowoff valve closes
When the load ratio is less than 30%. CPU stop the main
motor. And automatically restart when the line
pressure is dropped to cut-in pressure.
Chamber (B)
Loading
STOP button ON
3-way solenoid valve (20Ux)
switched over to pressurize
Chamber (A)
Suction throttle valve
(STV) closes
Blowoff valve opens
Internal air in discharge
pipe is exhausted to
atmosphere
Compressor stops
Load-Unload Operation
Less
than
specified
What is the plant
compressed air piping
pressure ?
10 seconds
or more
More than specified
How long has
motor been
running ?
15 minutes or more
Load ratio ?
Less than 30%
Has motor stopped and
restarted 3 times or more for
150 minutes ?
NO
Motor stops automatically
How long has
motor been
stopped ?
Less than
10 seconds
Less than 15 minutes
30% or more
YES
If 120 minutes or more has
passed after the third stop, the
motor will continue to operate
for a minimum of 30 minutes
after restart of the air compressor, and then return to the initial
150 minute cycle.
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
8.4.3 Typical Change of Pressure
⑴Offline-or-Online, 0%-or-100%-Capacity, 2-Step Control (Only for Fixed Speed Type)
Starting and
100
85
Pressure
Raising
LoadingUnloadingLoading
Pressure
psi
15
Air Receiver Pressure
⑵ AUTO Operation
(1) Stop Delay
(10 minutes)
Starting
and
Pressure
Raising
100
85
Pressure
psi
15
(2) Stop Delay
Loading
⑶ ECOMODE Operation
Starting
and
Loading
Pressure
Raising
(30% load)
Repeated
Loading/Unloading
Air Receiver Pressure
Time
Unloading
Loading
Time
(3) Start Delay
(15 seconds)
Automatic
Motor Stop
Indications on LCD
Unloading
Air End Outlet Pressure
Automatic
Motor Restart
Air discharge pressure
after aftercooler
Power Save Operation
load/unload cycling interval
(standard 30 seconds)
Loading
Unloading
Loading
Unloading
⑴
Stop Delay Time-Requires 15 seconds
of motor operation to sufficiently cool
down the motor.
If the third stop is done after 70
minutes or more has passed after
the first stop, the motor continues
to operate for 20 minutes after
restart of the air compressor, and
then return to the initial cycle.
Stop Delay Time – The air compressor
⑵
is continually calculating a load ratio.
If the load ratio is 30% and the motor
has stopped/restarted maximum 3
times for the past 90 minutes, then
the motor stops.
Stop Delay Time – Requires 10 seconds
⑶
to completely exhaust internal
compressed air and prepare to restart.
The pressure with asterisk may vary
depending on the air receiver’s capacity
15
Time
and the amount of air consumption.
69
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
8.4.4 Capacity Control System V-type
1st-stage
airend
Intercooler
2nd-stage
airend
Air
intake
Air intake filter
1st-stage
Blowoff solenoid valve (2)
1st-stage
Blowoff solenoid valve (1)
2nd-stage
Blowoff solenoid valve (1)
2nd-stage
Blowoff solenoid valve (2)
Check valve
Aftercooler
Blowoff
silencer
Pressure
sensor
PS2
Purging Air Flow and Action of Blowoff Solenoid Valve
Operation phase
StartingFully openedFully closed
LoadingFully closedFully closed
PurgingFully openedFully closed
StopFully openedFully opened
Power Interruption
Blowoff solenoid
valve (1)
Fully closedFully opened
Blowoff solenoid
valve (2)
Air
discharge
8.4.5 Relationship between Air Consumption Rate and Capacity Control System
Figure in[ ]are for 125 psi(0.86 MPa) models.
※
Air
consumption
(%)
100 to 45
45 to 525
5to0
The air compressor supports the three (3) capacity control systems as shown above.
Depending on the varying air consumption, an appropriate system is automatically selected. For more information, see
the following page. Operation frequency is shown by Digital monitor. LCD monitor displays up to first figure after
decimal place.
Operating frequency (Hz)
90kW110kWSetting itemsFactory
60 to 35
〔52 to 35〕
60 to 37
〔51 to 37〕
Capacity control system
①
CPCS Motor speed control
Pressure settings psi [MPa]
Control
pressure
Cut-out
②
Two-step purge control
pressure
Cut-in
pressure
Motor stopped
③
Motor stop/restart control
Cut-in
pressure
Lower
example
125 [0.86]100 [0.69]
128 [0.88]104 [0.72]
123 [0.85]85 [0.59]
123 [0.85]85 [0.59]
SW3
settings
AUTO ON
(VSDA)
or
AUTO OFF
(VSDB)
AUTO ON
(VSDA)
or
AUTO OFF
(VSDB)
AUTO ON
(VSDA)
IMPORTANT
To change the pressure setting and the capacity control
type,
2.4.2 and 3.4.3.
70
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
① CPCS Motor Speed Control
Based on the pressure signals detected by the pressure
sensor, the built in circuit board’s CPU performs PID
operations or calculates the motor speed that meets the
compressed air consumption rate, and then inputs the
calculated results to the inverter. The inverter outputs
the instructions of the corresponding frequency to the
motor. The discharge pressure is controlled within a
targeted range due to the increasing and decreasing
speeds of the motor.
CPCS Motor Speed Control by Inverter and CPU
IMPORTANT
PID stands for Proportional, Integral, and Differential.
CPCS stands for Constant Pressure Control System.
Pressure
P: proportional
I: integral
D: differential
Inverter
② Two-Step Purge Control
Two-Step Purge Control is activated if the following
conditions occur at the same time:
・The operating frequency drops to 35 Hz (equivalent
to 45% of the air consumption).
・The pressure detected by the pressure sensor rises
to an upper (purge-start) pressure point.
The blowoff solenoid valve (1) operates to start purging
the compressed air (contained between the airend and
the check valve) to atmosphere. The system decreases
the operating frequency to its lowest operating
frequency, 27 Hz, thus saving power. When the
pressure detected by the pressure sensor drops to a
cut-in (purge-stop) pressure, the system increases the
frequency to 35 Hz and the blowoff solenoid valve (1)
operates to stop the purging, returning the system
control back to CPCS Motor Speed Control.
③ Motor Stop/Restart Control
Motor Stop/Restart Control is activated under one of the
following conditions:
・Air consumption decreases to 4 %
・Purge operating continues for 3 minutes.
The system then automatically stops the motor. For
protection, the motor can only be stopped once every 10
operating minutes. When the pressure detected by the
pressure sensor drops to a cut-out (purge-stop) pressure,
the system automatically restarts the motor, returning
the system control to CPCS Motor Speed Control.
Motor
DSP
Compressed
Air
Pressure Sensor
Constant Pressure
of the Discharge Air
IMPORTANT
The differential range between the upper pressure point
and the lower pressure point must be 7 psi (0.05 MPa) or
more.
Pressure
Upper Pressure
Standard Pressure
Lower Pressure
Q>45%
or
Hz>35
Operation Frequency Hz
①②
CPCS Motor
Speed Control
①
(Q≦45%)
Q>5%
or
T<3 minutes
Two-Step Purge
Start/Stop Control
②
Q≦45%
Hz≦35
Air Consumption Q
Purging Time T
①
Time
or
or
N>1
③
Motor Stop/Restart
Minimum
7psi
Minimum
1psi
Q≦5%
or
T≧3 minutes
Number of
Motor Stopping N
(for 10 minutes
)
N≦1
Control
IMPORTANT
(1) Once the motor has stopped, it cannot restart for 15
seconds.
(2) The plant’s system pressure may drop drastically before the
motor will restart, 15 seconds later. To avoid such problems,
install an air receiver tank of 620 USgal (2.26 m
3
) or larger.
100
Q (%)
Air Consumption
0
①
②②
③ ③
②
Time
71
8. STANDARD COMPONENTS AND SUBSYSTEMS [Capacity Control System]
8.4.6 PQ Wide Mode – Capacity Control Flow Settings
NOTE: PQ Wide Mode is set to OFF at the time of shipment from the factory. If PQ Wide Mode is required, it
needs to be set to ON on the instrument panel.
(1) PQ Wide Mode
Power Savings are Desired
Reliable energy savings are achieved
by lowering operating pressure.
100
90
Power consumption (%)
80
125psi(0.86MPa)
106psi(0.73 MPa)
87psi(0.60 MPa)
90100110
Air consumption (%)
This figure is intended for 125psi(0.86 MPa) model.
PQ Wide Mode:
OFF
①
②
① By reducing the operating pressure from 125 psi
(0.86 MPa) to 106 psi (0.73 MPa), the maximum
consumption power is automatically limited to
approximately 92% of the consumption power at 125
psi (0.86 MPa).
Higher Capacity is Desired
Increasing the capacity of the air compressor is
achieved by utilizing the maximum power of
the air compressor at lower operating pressure.
100
90
125psi(0.86 MPa)
Power consumption (%)
80
100psi(0.69 MPa)
8090100 117
Air consumption (%)
PQ Wide Mode:
ON
②
①
① By reducing the operating pressure from 125 psi
(0.86 MPa) to 100 psi (0.69 MPa), PQ-Wide Mode
utilizes the surplus power from the reduction in
pressure to increase the capacity up to
approximately 117% of the rated capacity.
② By reducing the operating pressure further down to
87 psi(0.60 MPa), the consumption power is reduced
to approximately 86%. The lowest set pressure is
71 psi (0.49 MPa).
If reducing the power is desired; the “PQ Wide Mode:
OFF” is recommended.
(2) PQ wide mode settings
The settings for PQ Wide Mode are to be changed
while the air compressor is stopped. Press the
SELECT/WIDE button o the instrument panel.
3.4.2 and 3.4.3 for the control pressure setting.
②The lowest set pressure is 100 psi (0.69 MPa). The
power consumption at 100 psi (0.69 MPa) is 100%.
The consumption power is 100%, utilizing the maximum
rated power of the air compressor at a lower operating
pressure for maximum capacity. If maximum capacity
is desired; the “PQ Wide Mode: ON” is recommended.
RUNNINGCONTROL
ALARM
RESET
FUNC
SELECT/WIDE
REMOTE
STR
1
SELECT/WIDE
1
ON: The Light blinks.
OFF: The Light is off.
SELECT/WIDE
Set by button
72
8. STANDARD COMPONENTS AND SUBSYSTEMS [Oil Mist Remover System]
8.5 Oil Mist Remover System
OMR Relief Valve
Opens when pressure in
the gear case excessively rises to prevent internal pressure increase.
Vacuum Indicator
Indicates that the ejector is operating properly
and that the gear case
internal pressure is
negative.
Air Source
Filter
Removes dust particles
and condensate from
the air source.
Remover Element
A high-performance
element to separate
fine oil mists.
Regulator
Maintains supply
pressure to the
ejector constant.
Pressure Gauge
Indicates supply pressure to the ejector.
Uses compressed air
to generate a vacuum
pressure, which maintains a negative pressure in the housing.
Float Trap
Automatically collects oil
to the suction side of oil
pump when oil is accumulated in the housing.
Ejector
Air End
Oil Pump
Gear Case
Solenoid Valve
Closes when the
compressor stops
running, stopping the
consumption of air.
When the compressor starts running,
oil mist is vented from the vent pipe.
When the line pressure rises,
the ejector actuates.
Negative pressure is maintained in
the oil mist remover.
Without increase of gear case internal pressure,
the high-performance remover element removes
oil mist.
Separated oil is
recovered in the gear case and reused.
CAUTION
The incorporated ejector uses the compressed air to
generate a vacuum pressure, which maintains a
negative pressure on the oil mist remover subsystem.
This prevents the gear case internal pressure from
rising due to a resistance of the element.
By installing the oil mist remover:
There is no need to extend a gear case vent pipe
outdoors, avoiding any type of trouble that may be caused
①
by incorrect installation of the gear case vent pipe.
Oil mists are prevented from venting from the gear
case to atmosphere, keeping the compressor room/
②
area clean.
Oil expenses and labor costs to add extra oil are
lowered because the oil is automatically recovered in
③
the gear case.
The oil mist remover reduces oil consumption to almost zero. However, the oil should still be replaced.
(
Section 9)
73
9. MAINTENANCE
CAUTION
● Before servicing the compressor, carefully read “1. SAFETY PRECAUTIONS” again.
● Before servicing, be sure to disconnect the power of the compressor. Failing to do so may cause
electric shock or other accident.
● Before removing or disassembling a part or component of the compressor, make sure that the
internal pressure has dropped to an atmospheric pressure. Otherwise, compressed air may gush out
of the compressor when a bolt, pipe, or any other part is removed, leading to an accident.
9.1 Periodical maintenance of Air compressor
Daily Operation Control
1
On a daily basis, fill out the OPERATION RECORD
LOGBOOK (
and conditions of the air compressor. If the data
deviates from the benchmark in the logbook, service
the air compressor or call the local HITACHI
distributor/master dealer or representative office for
service.
observe other daily operating instructions (
75 and 78).
Drain the condensate on a daily basis and
Section 14) with the operating data
page
Maintenance at Periodic Intervals
2
①
The standards indicate normal maintenance schedule.
If your compressor is in sever environmental or
operating conditions, service it at more frequent
intervals.
The maintenance schedule differs between 4,000 or
less operating hours per year and 8,000 hours. If your
compressor is in severe (high-humid, dusty, etc.)
conditions, however, always follow the maintenance
schedule for 8,000 operating hours per year.
② Any of the maintenance intervals is not a warranty
period.
Overhauling
3
Overhauling consists of changing the existing
airend with a new replacement airend.
Overhaul the air compressor at 6 years.
③ If any abnormality is detected during inspection,
replace the part.
④ Do not neglect a yearly maintenance schedule as it
is most important from a preventive maintenance
standpoint.
⑤ Use HITACHI genuine parts for replacement.
74
9. MAINTENANCE [Standard Maintenance Schedule]
9.2 Standard Maintenance Schedule
Maintenance Schedule A (For 8,000 hours or less operating hours per year)
Follow this schedule (A) if the MAINT.SCHEDULE : A appears on the LCD monitor.
※ A in Type category stands for Air-cooled type ○●… Replace △○… Complete service in house
※ W in Type category stands for Water-cooled type △▲… Clean or check ▲●…
Daily and 3-month Schedule (for 8,000 hours/year or less operation)
1
Ask your distributor to service
Part or ItemAction
LCD indicationsCheck
Oil levelCheck
Aftercooler/Intercooler - CondensateDrain
Control line filter - CondensateCheck
Main motor greasing-
Discharge pipe (Compressed
Air Discharge)
Air relief valve
Cooling fan
Oil cooler
Hi-precooler
CategoryType
Every
Daily
3-month
△
△
△
△
△
Aftercooler
Fixed/V A/W
Fixed/V A/W
Record data in the OPERATION RECORD LOGBOOK.
Fixed/V A/W Add as required.
Fixed/V A/W
FixedA/W
Fixed/V A/W
Check valve
Intercooler
Remarks
Enclosure
Instrument panel
Control panel
Oil mist remover
2nd-stage air end
1st-stage air end
Oil filter
Bi-Annual Schedule (for 8,000 hours/year or less operation)
Annual and 3-year Schedule (for 8,000 hours/year or less operation)
3
Part or ItemAction
Lubricating oilReplace
Joints, Bolts, Nuts
Gasket - Inter/Aftercooler condensate strainer
O-ring - Inter/Aftercooler condensate strainerReplace
Oil filter (secondary)Replace
Consumable parts - Suction throttle valveReplace
Seal washer - Suction throttle valveReplace
Seal gasket - Suction throttle valve Replace
Thermistor, Pressure sensor, PCB other Electric parts
Cooling fan
Orifice - Aftercooler condensateCheck/Clean
Orifice and Check valve - Intercooler condensate
Aftercooler/Intercooler/Oil coolerCheck/Clean
Hi-PrecoolerCheck/Clean
Demister - Drain separatorCheck/Clean
3-Way solenoid valve & Capacity control system
Blowoff solenoid valveCheck
Air relief valve
Protection, Safety deviceCheck
Motors
Relay (Drain solenoid valve)Replace
2-year and 4-year Schedule (for 8,000 hours/year or less operation)
4
Part or ItemAction
Control line filter elementReplace
Blowoff solenoid valve (1) (2)Replace
Consumable parts - Oil pumpReplace
Check valveReplace
Solenoid valve - Intercooler/Aftercooler condensate
Check valve and Strainer - Intercooler condensate
Check valve - Control lineReplace
VFD (Variable Frequency Drive)Check
Cooling capacity for VFDReplace
Cooling fan for control panelReplace
FixedA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/WClean as required.
Fixed/VA/WClean as required.
Fixed/VA/W
Fixed/V
Fixed/VA/W
FixedA/W Replace as required.
Fixed/VA/W
Fixed/VA/W
Fixed/VA/WMeasure insulation resistance and clean.
Fixed/VA/W
●
Fixed/VA/W
FixedA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/WReplace the strainer together.
Fixed/VA/W
FixedA/W
Fixed/VA/W
●
A only
VA/W
VA/W
VA/WClean the heat sink fin
VA/W
VA/W
Remarks
Change any operating parts in need of replacement.
Change any operating parts in need of replacement.
Check for contamination and discoloration. Replace if
faulty. May be used further if appropriate. (Except FFC)
6-year (Overhaul) (for 8,000 hours/year or less operation)
5
Part or ItemActionCategory
Airend (1st-stage, 2nd-stage)Replace
Main motor bearingReplace
Fan motor bearingReplace
Demister - Drain separatorReplace
3-Way solenoid valveReplace
Oil strainer (primary)Replace
Control line filter - CondensateReplace
Oil level gaugeReplace
Shaft seal - Main motorCheck/Clean
Temperature control valveReplace
Smoothing condenser - Controller Replace
※ For the 3rd overhaul, the air ends shall be replaced with new ones.
Check/Clean/
Replace
Check/Clean/
Replace
●
●
●
●
●
●
●
●
▲
●
●
●
●
▲
●
76
Type
Fixed/VA/W
Fixed/VA/WA whole airend is replaced with a new
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W
FixedA/W
Fixed/VA/W
FixedA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W
VA/W
Fixed/VA/W
VA/W
Fixed/VA/WReplace as required.
Fixed/VA/W
Check for contamination and discoloration.
Replace if faulty.
Check for contamination and discoloration.
Replace if faulty.
Remarks
May be used further if appropriate.
May be used further if appropriate.
9. MAINTENANCE [Standard Maintenance Schedule]
Maintenance Schedule B (For 4,000 hours or less operating hours per year)
Follow this schedule (B) if the MAINT.SCHEDULE : B appears on the LCD monitor.
※ A in Type category stands for Air-cooled type ○●… Replace △○… Complete service in house
※ W in Type category stands for Water-cooled type △▲… Clean or check ▲●…
Daily Schedule (for 4,000 hours /year or less operation)
1
Part or ItemAction
LCD indicationsCheck
Oil levelCheck
Aftercooler/Intercooler - CondensateDrain
Control line filter - CondensateCheck
Discharge pipe (Compressed
Air Discharge)
Air relief valve
Cooling fan
Oil cooler
Hi-precooler
CategoryType
DailyFixed/V A/W
△
△
△
△
Aftercooler
Fixed/V A/W
Fixed/V A/W Add as required.
Fixed/V A/W
FixedA/W
Check valve
Record data in the OPERATION RECORD LOGBOOK.
Intercooler
Ask your distributor to service
Remarks
Enclosure
Instrument panel
Control panel
Oil mist remover
2nd-stage air end
1st-stage air end
Oil filter
Bi-Annual Schedule (for 4,000 hours /year or less operation)
Annual Schedule (for 4,000 hours /year or less operation)
3
Part or ItemActionCategory
Lubricating oilReplace
Joints, Bolts, Nuts
Gasket - Inter/Aftercooler condensate strainer
O-ring - Inter/Aftercooler condensate strainerReplace
Oil strainer (primary)Clean
Thermistor, Pressure sensor, PCB other Electric parts.
Cooling fan
Orifice - Aftercooler condensateCheck/Clean
Orifice and Check valve - Intercooler condensate
Aftercooler/Intercooler/Oil cooler (air side)Check/Clean
Hi-PrecoolerCheck/Clean
Demister - Drain separatorCheck/Clean
3-Way solenoid valve & Capacity control system
Blowoff solenoid valveCheck
Air relief valveCheck/Clean
Protection, Safety deviceCheck
MotorsCheck/Clean
3-year and 4-year Schedule (for 4,000 hours /year or less operation)
4
Part or ItemAction
Control line filter elementReplace
Oil filter (secondary)Replace
Consumable parts - Suction throttle valveReplace
Seal washer - Suction throttle valveReplace
Seal gasket - Suction throttle Valve Replace
Blowoff solenoid valve (1) (2)Replace
Consumable parts - Oil pumpReplace
Check valveReplace
Solenoid valve - Intercooler/Aftercooler condensate
Check valve and Strainer -Intercooler condensate
Check valve - Control lineReplace
VFD (Variable Frequency Drive)Check
Cooling capacity for VFD.Replace
Cooling fan for Control panelReplace
Relay (Drain solenoid valve)Replace
PC Board - Inverter, Module, FFC (Flat cable)
※ When the power-saving operation is used, the parts need to be replaced every 2 years.
Tighten/Check
Replace
Check
Check for crack/Clean
Check/Clean
Check
Replace
Replace
Check/Clean/
Replace
○
△
○
○
▲
▲
▲
▲
▲
▲
▲
▲
▲
▲
▲
▲
▲
CategoryType
3-year 4-year
○
●
●
●
●
●
●
●
●
●
●
▲
●
●
●
●
Type
Fixed/V A/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W
Fixed/V
Fixed/VA/W Clean as required.
Fixed/VA/W Clean as required.
Fixed/VA/W Clean as required.
Fixed/V A only
Fixed/VA/W
FixedA/W Replace as required.
VA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W Measure insulation resistance and clean.
Fixed/V A/W
FixedA/W
Fixed/VA/W
FixedA/W
FixedA/W
FixedA/W
VA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W Replace the strainer together.
Fixed/VA/W
FixedA/W
VA/W Clean the heat sink fin.
VA/W
Fixed/VA/W
Fixed/VA/W
VA/W
Remarks
Replace every 8,000h operating hour or 2 year, whichever comes earlier)
Change any operating parts in need of replacement.
Change any operating parts in need of replacement.
Remarks
※
※
※
Check for contamination and discoloration. Replace if
faulty.
May be used further if appropriate. (Except FFC)
6-year (Overhaul) (for 4,000 hours /year or less operation)
5
Part or ItemActionCategory
Airend (1st-stage, 2nd-stage)Replace
Main motor bearingReplace
Fan motor bearingReplace
Demister - Drain separatorReplace
3-Way solenoid valveReplace
Oil strainer (primary)Replace
Control line filter - CondensateReplace
Oil level gaugeReplace
Shaft seal - Main motorCheck/Clean
Temperature control valveReplace
Smoothing condenser - ControllerReplace
Fixed/VA/W A whole airend is replaced with a new.
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W
FixedA/W
Fixed/VA/W
FixedA/W
Fixed/VA/W
Fixed/VA/W
Fixed/VA/W
VA/W
Fixed/VA/W
VA/W
Fixed/VA/W Replace as required.
Fixed/VA/W
Check for contamination and discoloration.
Replace if faulty. May be used further if appropriate.
Check for contamination and discoloration.
Replace if faulty. May be used further if appropriate.
Remarks
9. MAINTENANCE [Standard Maintenance Schedule]
9.3 Maintenance Schedule for Oil Mist Remover
① To ensure long and successful operation of the Oil
Mist Remover, follow the standard maintenance
schedule attached below.
The standard maintenance schedule service intervals
②
stated below are based on normal environmental and
operating conditions. If the Oil Mist Remover is in
severe environmental and operating conditions, use
more frequent service inter vals.
ItemDaily
Regulator settings
Vacuum indicator
OMR relief valve
Regulator performance
Float trap nozzle
Vacuum indicator
Filter element
Remover element
Filter element
OMR relief valve sheet/spring
Vacuum indicator
Filter regulator
Ejector
Solenoid valve
Solenoid valve coil assembly
Bi-annually
△
△
△
△
△
△
△
③ These maintenance inter vals are not considered
warranty.
④ If an inspected part is worn, faulty or damaged,
replace it as soon as possible.
⑤○●: Replace △▲: Clean or check
○△: Complete service in house
●▲: Ask your distributor to service
Annually
●
●
●
●
●
▲
▲
6-yearly
●
Remarks
Disassemble and clean.
Disassemble and clean.
Disassemble and clean.
Disassemble and clean.
Replace diaphragm and valve stem.
Disassemble and clean.
Replace if it is too dirty.
Disassemble and clean. Replace as
required.
CAUTION
The oil mist remover reduces oil consumption to almost zero. However, the oil should still be replaced
biannually.
79
9. MAINTENANCE [How to Service the Air Compressor]
9.4 How to Service the Air Compressor
Before servicing the air compressor, stop it, disconnect the power (turn off the earth leakage (ground) circuit
breaker) and verify that the compressor’s internal pressure has dropped to atmospheric pressure.
The maintenance intervals shown refer to the standard Maintenance Schedule (A).
Cleaning of Air Intake Filter (Bi-Annually)
1
A pressure sensor is provided on the suction throttle
Differential Pressure Sensor
Air Intake Filter
Wing Nut
valve to detect the pressure differential across the air
intake filter. When the sensor detects a pressure
differential as large as 0.72 psi (4.98 kPa) during
operation, AIR FILTER appears on the LCD display
with E0.21 on digital monitor. If this occurs, clean or
replace the air intake filter in accordance with
Maintenance Schedule (A) or (B). The procedure for
cleaning the air intake filter is as follows.
① Stop the air compressor, disconnect the power and
verify no internal pressure.
Cover
② Remove the front cover (left side).
③ Remove the filter cover and wipe dirt off the inner
surface of filter duct.
④ Loosen the wing nut and remove the air intake filter.
Make sure the contamination and/or dust doesn’t
enter the airend side.
⑤ Tap the air intake filter to remove large particles.
Then blow air to clean the surface of filter.
⑥ In the case of oily or carbon dust, dip the element
into neutral detergent and water solution for about
30 minutes. Rinse the element several times with
clean water (water pressure is less than 39 psi
(0.27MPa)) and air-dry it. Confirm the element is
dried completely.
⑦ Reinstall and tighten the wing nut.
CAUTION
If the air intake filter is clogged with dust/dirt particles; Differential pressure (resistance of flow) across
the air intake filter increases, which results in decreased air intake to the airend and a rise in discharge
air temperature. To avoid a problem, service the air intake filter regularly. If the compressor room
environment is dusty or dirty, service the air intake filter more frequently than instructed on the
Maintenance Schedule.
80
Depressurizing the System
2
9. MAINTENANCE [How to Service the Air Compressor]
Air-Cooled
After cooler side
Ⓔ
Ⓕ
Two-way Valve (2)
Water-Cooled
Two-way Valve (1)
Ⓑ
Ⓐ
Three-way change valve
Ⓓ
Ⓒ
Intercooler side
Before cleaning the drain pipe, intercooler, aftercooler,
control line filter, or replacing the check valve, reduce
the internal pressure to 0 (zero) by opening the
condensate drain. Stop the air compressor and
disconnect the main power. Close the stop valve of the
compressed air discharge. Remove rear panel (1) [Ref
No. 967] .
(1) Intercooler side
Turn the three-way change valve from Ⓐ to Ⓑ.
(2) Aftercooler side
Turn the Two-way Valve (1) from Ⓒ to Ⓓ. And
Turn the Two-way Valve (2) from Ⓔ to Ⓕ.
Verify that the interstage pressure (INTSTG.P) and
discharge pressure (DIS PRESS) is 0 (zero) on the
LCD monitor. In addition, remove the parts slowly
because the pressure is still remained in air pipings due
to the wrong operation or piping works.
After cooler side
Ⓔ
Ⓕ
Two-way Valve (2)
Two-way Valve (1)
Ⓒ
Ⓓ
Ⓑ
Ⓐ
Intercooler side
Three-way change valve
81
9. MAINTENANCE [How to Service the Air Compressor]
Condensate drain port (Intercooler/Aftercooler) (Daily check)
3
Clean the strainer elements (Bi-Annually) & Orifices (Annually)
■ Check the condensate drain
Moisture in the intake air, especially in hot and humid environments, is condensed inside the air compressor during
compression. Daily inspect intercooler/aftercooler condensate drain to verify that there is a discharge of
compressed air (with condensate) when the air compressor is loaded. Bi-annually, clean the strainer element and
annually clean the orifice for both intercooler/aftercooler.
◆ Cleaning of strainer
[Aftercooler side]
[Intercooler side]
Strainer
◆ Cleaning of orifice
Loosen
Element
Gasket
Cover
Tighten
■ Cleaning of strainer element
The strainers for both the intercooler and
aftercooler shall be cleaned.
①Discharge the compressed air in the procedure
2
in 9.4
② Remove the cover of the strainer.
③ Remove the element, wash with water and blow
air.
④Remove the element from inside the strainer and
wash with water.
⑤ Replace the cleaned element in its original
position and set the gasket, and plug properly.
.
■ Cleaning of orifice
Inspect and clean the orifices annually. Be sure to
stop the air compressor before inspecting and/or
cleaning the orifices.
Orifices
■Replacement of the strainer and solenoid
valve
Replace the solenoid valve and the strainer ever y 2
years (if operating 8000 hours/year) or 3 years (if
operating 4000 hours/ year) to new whole
assembled parts.
CAUTION
● Verify that discharged air with condensate
is discharged through the drain ports of
intercooler and aftercooler every 20
seconds during loading.
● If compressed air is not discharged, clean
and unclog the drain port (filter & orifice).
● Operating the air compressor without
draining the condensate from the
intercooler/afterooler, may rust the airend
internally and cause a major failure.
82
◆
Disassembly of strainer element during operation
Air-Cooled
Two-way valve
Water-Cooled
Two-way valve B
After cooler side
Ⓔ
Ⓕ
Ⓐ
After cooler side
Ⓔ
Ⓕ
Ⓐ
Two-way valve A
Ⓒ
Ⓓ
Ⓑ
Intercooler side
Three-way change valve Ⅰ
Two-way valve A
Ⓒ
Ⓓ
Ⓑ
9. MAINTENANCE [How to Service the Air Compressor]
■ Cleaning the strainer element during
operation
If the strainer needs to be cleaned while the air
compressor is running, contact the local HITACHI
distributor/master dealer or representative office.
While the air compressor is running, strainer is
always pressurized. Be careful extremely to the
high pressure when the strainer is removed.
(1) Intercooler side
① Turn three-way change valve on the intercooler
side from Ⓐ to Ⓑ.
② Element is still pressurized depending on the
solenoid valve action, so be careful extremely
when opening the strainer plug. Remove the
strainer element.
③ Wash the element with water and blow air, and
reassemble it.
④ Turn three-way change valve from Ⓑ to Ⓐ.
(2) Aftercooler side
Intercooler side
Three-way change valve Ⅰ
◆ Valve condition during normal operation
Air-Cooled
ater-Cooled
After cooler side
Two-way valve B
Ⓔ
Three-way change valve
After cooler side
Two-way valve B
Ⓔ
Two-way valve A
Ⓒ
Intercooler side
Two-way valve A
Ⓒ
① Turn two-way valve A on the aftercooler side
from Ⓒ to Ⓓ.
② Check that two-way valve B is completely closed
(Ⓔ side). In this state, strainer pressure in the
solenoid valve is released by solenoid valve
action.
③ After verifying the compressed air is discharged,
remove the strainer element. If two-way valve A
or B is opened even slightly, strainer is still
pressurized.
④ If two-way valve B is opened to the Ⓕ side in this
state, condensate can be drained while cleaning
the strainer element.
⑤ Wash the element with water and blow air, and
reassemble it.
⑥ Turn two-way valve A on the aftercooler side
from Ⓓ to Ⓒ. Also check that two-way valve B is
completely closed (Ⓔ side).
Three-way change valve
Strainer
Intercooler side
83
9. MAINTENANCE [How to Service the Air Compressor]
Lubricating oil Replacement (Annually)
4
■ Oil drain
① Stop the air compressor and disconnect the power.
Remove the front door [Ref. No. 904], left door [Ref.
Air-Cooled
Plug ⑤
(Oil air vent)
No. 912] and rear panel (1) [Ref. No. 967]
② Remove the plug ⑤ for oil air vent.
③
Remove the plugs of oil drain ports ①②③. Place oil
pans under the oil drain ports ①②③. Open the
Front door
drain valve ①②③. The dimension of oil pan is
approximately 3 × 10 × 14 inches (75 × 250 × 350 mm).
④ Place the oil pan under the oil drain port ④.
Remove the plug ④ to drain the oil.
⑤ Replace all lubricating oil annually. Also once a year,
Left door
Hole for waste oil hose
(Oil drain hose is not supplied
with the compressor.)
Air-cooled type
Air-Cooled
Oil drain valve ③
(For draining oil cooler)
Oil pan
remove the oil port cover and wipe the sludge off of
the bottom of the gear case with a sponge and clean.
⑥ Close oil drain valves ①②③. Tighten removed
plugs with seal tape to oil drain ports ①②③④⑤
and oil air vent.
■ Oil filling
⑦ Fill the oil case with oil. Open the oil plug of the oil
case and pour new oil until the oil level reaches the
Rear panel (1)
upper red line of the gauge. (Do not exceed the
yellow line when the oil is initially charged.)
Oil filter
Oil casing
Oil pan
Air-Cooled
Oil port
Plug ④
Air-cooled type
Plug ③
Oil port cover
Open
Close
Yellow
line
Oil filter
drain port
Oil drain valve ②
(For draining oil casing)
Oil level gauge
Inspection
Open
Oil drain valve ①
(For draining oil casing)
port cover
Close
Plug ②
Plug ①
■ Check/refilling
⑧ Turn on the power, press the START button and
turn the compressor of f 5 – 6 seconds later.
⑨ Check the oil level on the oil level gauge. The oil
level drops when lubricating oil flows to the piping,
oil cooler and case jacket (air-cooled type only).
Turn off the power and add oil from the oil supply port.
⑩
⑪ After refilling is complete, close the oil plug tightly.
⑫ Turn the power back on, press the START button
and make sure the oil level is between the upper and
lower red lines of the oil level gauge.
⑬ Make sure no oil leaks from the oil drain valve and
plugs.
WARNING
● Change the oil regularly, as instructed in the
standard maintenance schedule ( page
75 to 78). Neglecting to change the oil
causes oil deterioration that could result in
clogging of the oil strainer and a fire.
● Be sure to use the recommended lubricating
oil on page 10. Absolutely DO NOT mix
different types of lubricating oil.
Overfilling with lubricating oil may increase
●
shaft power and result in rise in oil temperature.
84
9. MAINTENANCE [How to Service the Air Compressor]
Cleaning of Oil Strainer (Primary) – (Bi-Annually)
5
①Stop the air compressor and disconnect the power.
② Open oil drain valve ① (see previous page) and
drain the lubricating oil from the oil casing.
③ Remove the strainer cover, remove the oil strainer
and clean it.
④ For overhauling, replace the oil strainer.
IMPORTANT
Oil Strainer
Strainer cover
Replacement of Oil Filter (Secondary) (Annually)
6
Clogging of the oil strainer drops the oil pressure of the air
compressor.
●Vtype
If the oil pressure sensor detects an oil pressure as low
as 12 psi (0.08 MPa) or lower for operation frequency
45 Hz or higher, or 6 psi (0.04 MPa) for operation
frequency less than 45Hz, the air compressor
automatically shutdowns.
●Fixed-speed type
If oil pressure sensor detects an oil pressure as low as
12 psi (0.08 MPa) or lower.
①Stop the air compressor and disconnect the power.
② Drain the lubricating oil from inside the compressor
in accordance with previous page.
③ Place a pan under the oil filter.
④ Remove the element using a filter wrench.
⑤ Apply clean oil onto the filter O-ring. Tighten the oil
filter until the O-ring surface comes in contact with
the oil filter seating surface.
⑥ Seat the oil filter O-ring by tightening the filter with
both hands. Immediately after the air compressor
restart verify that there is no leaks on the oil filter.
IMPORTANT
Clogging of the oil filter drops the oil pressure of the air
compressor.
● Vtype
If oil pressure sensor detects an oil pressure as low as
Oil FilterOil Pan
12 psi (0.08 MPa) or lower for operation frequency 45 Hz
or higher, or 6 psi (0.04 MPa) for operation frequency
less than 45Hz, the air compressor automatically
shutdowns.
● Fixed-speed type
If oil pressure sensor detects oil pressure as low as 12
psi (0.08 MPa) or lower, the air compressor
shutdowns.
automatically
85
9. MAINTENANCE [How to Service the Air Compressor]
Operation Check of Air Relief Valve (Bi-Annually)
7
① Maintain the rated maximum discharge pressure
[Rear view]
Air relief valve
(insaide the cover)
(ex. 100 psi (0.69 MPa).
② Pull the ring connected to air relief valve.
③ Verify that the air relief valve operates properly and
get a hand off of the ring.
During inspection of the operation of the air
relief valve, use the appropriate facial
protection. High pressure air containing dust
particles can cause severe injury.
WARNING
Cleaning of Control Line Filter (Bi-Annually) [Fixed-Speed type]
8
① Depressurize the system described in 9.4 2.
② Remove the left enclosure panel.
③ Remove the control line filter element, and then use
an air nozzle to blow out the inside surface (reverse
flow action) of the control line filter element in order
to remove any dust particles.
④ Replace the element annually..
86
Air-Cooled
Cleaning of Cooler (Annually)
9
9. MAINTENANCE [How to Service the Air Compressor]
For light and non-greasy dust particle
1
① Remove the right side cover, the front cover and the
rear cover.
② Remove the right and left intake duct.
③ Remove the maintenance cover.
④ Use an air nozzle to blow the cooler surfaces.
For heavy and greasy dust particles
2
(detaching the cooler)
① Remove the enclosure panels.
② Drain the oil from the system.
Cooler duct plate (4)
Left intake
duct
Right intake
duct
Maintenance cover
Maintenance cover
Cooler duct
plate (5)
③ Disconnect all the sensor wires from the cooler.
④ Disconnect all air / oil pipes at the joints.
⑤ Disconnect the discharge pipe.
⑥ Loosen and remove the cooler bolts.
For heavy and greasy dust particles
3
(cleaning the detached cooler):
① Use an air nozzle to blow the cooler surfaces.
② Soak the cooler in a detergent bath or spray
detergent onto the cooler. Use an air nozzle to blow
the cooler surfaces.
Generally, there are 3 kinds of dust and dir t par ticles.
③
・ Light dust par ticles
・ Heavy dust par ticles
・ Greasy dust par ticles
Contact the local HITACHI distributor/master
dealer or representative office for the detail.
87
9. MAINTENANCE [How to Service the Air Compressor]
Water-Cooled
Cleaning of Cooler (Annually)
10
● Oil Cooler
Scale Removal
Remove the oil cooler water chamber cover. Flush
with scale remover and use a brass wire brush to
remove the scale from the inner surfaces of the oil
cooler tube nest.
Wire-Brush
● Aftercooler/Intercooler
If scale build up occurs often, contact the local
HITACHI distributor/master dealer or representative
office for scale removal.
Oil Cooler
88
9. MAINTENANCE [How to Service the Air Compressor]
Replacement of Check Valve (2-Yearly)
11
Air-Cooled
Air-Cooled
Duct plate (1)
Duct plate (4)
2 stage
packing (1)
Check valve assembly
Partition plate (B)
Upper check valve cover
Partition
plate (A)
Flow
direction
(direction
of arrow)
Depressurizing the System
1
Depressurize the compressed air in the air compressor
2
as described in 9.4
Removing the Enclosure Panels
2
.
① Remove the front door and enclosure panels.
Air-Cooled
② Remove cooler ducts such as duct plate (1) and duct
plate (4).
Disassembly
3
① Remove the fastening bolts of the check valve cover.
② Remove the upper check valve cover for Air-Cooled
(check valve cover for Water-Cooled), gasket, check
valve, and gasket in this order.
Lower check
valve cover
Water-Cooled
Gasket
Check
valve
Gasket
Flow direction
(direction of arrow)
Check valve
cover
Gasket
Check valve
Gasket
③ Be careful of the mounting direction of the check
valve.
Cleaning and Inspection
4
Air-Cooled
① Clean the check valve mounting surfaces on the
upper and lower check valve covers so that the
surfaces are free from rust and fragmented gasket.
Water-Cooled
② Clean the check valve mounting surfaces on the
check valve cover and cooler header so that the
surfaces are free from rust and fragmented gasket.
Cooler header
89
9. MAINTENANCE [How to Service the Air Compressor]
Battery Replacement (6-Yearly)
12
(2) Battery replacement method
When “BATTERY OUT” is displayed for “PROBLEM”
on the LCD monitor, replace the battery. When
replacing, disconnect the power and complete the
replacement work within 15 minutes.
③
Tab
③
① Remove the screw on the right of the LCD display.
② Insert the special tool attached with the batter y to
the slots shown as figure provided and lift up the
LCD unit from the instrument panel.
④
Mounting screws
②
⑤
CN11 BT
Special tool openings
Battery
LCD unit board
(1) Battery life and specifications
ItemSpecs
BatteryCoin type manganese dioxide lithium battery
Voltage3V
Capacity
Battery model
Special specs
Replacement
criteria
Life
Lead wire connector connection
Battery replacement display on LCD monitor
Approx. 1 year with power off
Approx. 6 years under ordinary service conditions
220mAh
CR2032
③ To remove the LCD unit, pull it to right side so
that the tabs are not damaged.
④ The battery is mounted on the back of the LCD
unit. Unplug the battery connector. The battery
is held by double-sided adhesive tape.
⑤ Replace with new battery.
(3) Cautions for disposal of old batteries
The used battery shall be returned to your
distributor or disposed of properly in accordance
with your local government disposal regulations.
Used battery is furthermore shorted if the positive
and negative terminals come in contact with each
other or come in contact other metal objects, and
could cause the battery to produce heart, rupture or
catch fire. Do not expose the battery to fire. Used
batteries cannot be recharged.
The batteries is an exclusive part. Contact the local
●
HITACHI distributor/master dealer or representative
office.
90
Maintenance of Main Motor
13
9. MAINTENANCE [How to Service the Air Compressor]
① Temperature increase
The motor coil has a specified maximum allowable
temperature rise of 180℉ (100℃), based on an
ambient temperature of 104℉ (40℃). If the motor is
unusually hot during normal operation, regardless of
the specified temperature rise, investigate the cause
of the excessive heat utilizing the Motor Diagnostics
and troubleshooting chart below
② Cleaning
Clean the main motor periodically to prevent dust
particles from accumulating inside and outside of
the motor.
When servicing the air compressor, measure
the insulation resistance of the motor coil with
a 500V megohmmeter and verify that the
insulation resistance is 1MΩ or more.
Motor Diagnostics and Troubleshooting
Phenomenon
③ Disassembling
In a severe environment (dirty, corrosive, high dust or
high powder), disassemble and service the motor
every two years. In a normal environment, disassemble
and service the motor every six years. For the most
common motor problems, see the Motor Diagnostic and Troubleshooting chart below. If the problem
cannot be solved with the chart, contact the local
HITACHI distributor/master dealer or representative
office.
Overheat
Cause
Loose bolts
Installation
Poor gounding
Inadequate breaker capacity
Broken wires
Wiring
Failed breaker, controller or contactor
Reduced cooling performance due
to dust accumulation
Excessive ambient operating
temperature
High humidity
Environment
Large external vibration/shock
Single-phase operationv
Widely dropped voltage
Power
Fluctuating voltage
Overload
Thrust force by the machine
Load
Excessive bearing noise NOTE 2
Burnt motor coil NOTE 2
NOTES)
1. ◎ : Close relationship between the cause and type of problem. 〇 : Relationship between the cause and type of problem.
2. Detect the fundamental cause of the problem and take corrective action.
3. Breaker, controller or contactors are hot.
Abnormal noise
Abnormal rotation
Vibration
○◎○
Note 3
○
○
Note 3
○
○
○
◎○◎
◎
◎◎○◎ ◎○
○○ ◎ ◎
○○○○
○◎◎○
○○◎
◎◎◎○
○○ ○ ◎◎◎○
Frame
Bearing
Thermal relay operation
Circuit breaker operation
Electric Leak
◎
◎
◎
Low Insulation Resistance
Retighten the bolts.
Ground properly.
Replace with properly specified capacity breaker.
Install new wires.
Check the contacts and replace if necessary.
Properly clean motor.
Improve the room ventilation or contact the local
Hitachi distributor.
Contact the local Hitachi distributor
Take countermeasures against vibration and shock.
Check the connections of circuit breaker, switch
andvlead wire.
Check the wire thickness and length and contact the
local power utilities company.
Contact the local power utilities company.
Check the capacity controller of compressor.
Center the shaft.
Contact the local Hitachi distributor.
Contact the local Hitachi distributor.
Corrective Action
91
9. MAINTENANCE [How to Service the Air Compressor]
Main Motor Greasing
14
Feed the main motor with grease in accordance with the
Grease Filling Amount table. Grease to be used is Raremax
Super by Kyodo Yushi (Hitachi part name: RMS grease)
(P/N 455).
① Open the front door. Grease the specified amount
through the grease port using a grease gun.
Check the grease pan, and clean the pan as necessary.
②
③ Close the front door.
Grease filling amount
ModelLoad-Side bearing
DSP-90A6N
DSP-90W6N
DSP-90VA6N
DSP-90VW6N
DSP-110A6N
DSP-110W6N
DSP-110VA6N
DSP-110VW6N
1.2oz
(30g)
Anti-Load Side
bearing
2.5oz
(70g)
● Example of grease gun
Lever-type grease gun CH-400 Micro-Hose (pin type
SPK-1C) by Yamada Corporation.
IMPORTANT
● Contact the local HITACHI distributor/master dealer or
representative office for the grease detail.
● Greasing must be done while the main motor
operating.
● Cleaning of grease pan must be done while the air
compressor stops.
Load-side bearing
Grease port
Anti-Load-Side bearing
Grease port
CAUTION
Grease panBolt with knob
Be cautious of replenishing grease more than the spcified amont. It may cause leaking of grease and/or
malfunction of the protective device due to overheat of the bearing. Grease at once during start-up
commissioning.
Periodically replace the main motor bearing in accordance with
Compressor” in page 74 and
Maintenance Schedule B
in pages 75 to 78.
“9.2 Standard Maintenance Schedule”
“9.1 Periodical Maintenance of
Maintenance Schedule A
92
Oil Mist Remover
15
9. MAINTENANCE [How to Service the Air Compressor]
1. Replacement of remover element
① Remove the pipe provided at the top of the remover
if required. Then remove 4 set screws (A) from the
oil mist remover housing.
Pull up the upper part of the housing.
②Loosen nut (B) and remove the cover. Now you can
remove the remover element.
③Install a new element. Carefully seat the upper and
lower rubber gaskets on the element without
allowing any gaps.
After replacement
④
of element, grease
the O-ring, replace
the housing, and
tighten 4 set screws
(A) diagonally and
evenly.
(B)
Cover
Rubber packing
Remover
element
O-ring
Rubber packing
3. Maintenance of OMR Relief Valve (See Fig. A.)
①Turn the nut at the top of the OMR relief valve and
remove the plate. Replace the sheet and the spring
with new components.
②Ensure that the spring is positioned at the center
before assembly.
4. Maintenance of Vacuum Indicator (See Fig. B.)
①Contamination of the vacuum indicator may cause
malfunction of indicator.
emove and clean the indicator at least every six
R
months. In addition, replace the indicator once a year.
② Pull down the indicator while pushing up the locked
pipe joint at the top.
Plate
Nut
Spring
Valve seat
3/8
(A)
φ12
2. Maintenance of Filter Regulator
①Turn the cover to remove. Remove the baffle and
replace the filter element with a new one.
Remove the upper 4 set screws and remove the
②
upper part of the regulator. Replace the diaphragm
and the valve stem with new components. Be careful
not to install the new diaphragm upside down.
Diaphragm
OUT
Valve
Screw (4 pcs)
Stem
IN
Regulator
O-ring
Locked joint
Pull
Fig. A
Fig. B
5. Maintenance of Ejector
① If the ejector is dirty, performance may decrease.
Disassemble and clean at least once a year.
② The maintenance procedure is as follows:
(1) Disconnect the control air tube at its detachable
connection.
Loosen nut A (the nut can be turned independently
(2)
from the ejector body) and disconnect the ejector
from the manifold.
(3) Remove the plastic case.
(4) Clean the ejector body with a neutral detergent
and dry it with an air nozzle. Assemble all of the
parts.
Cover
Filter element
Baffle
Nut A
93
10. CAUTIONS FOR A LONG TERM OPERATION SUSPENSION
① If the compressor is not to be used for a week or
more, be sure to press the UNLOAD STOP button
on the instrument panel.
The compressor then unloads for 5 minutes and
automatically stops when the airend and the piping
are dry.
IMPORTANT
If unloading is executed before the compressor is stopped,
moisture will be removed from the second-stage air end.
To prevent the second-stage air end from rusting during a
long-time suspension, it is effective to dry the inside of
the air end before stopping the compressor..
② To prevent the inside of airend from rusting, press
the UNLOAD STOP button and dry the compressor
for 5 - 10 minutes a week.
MONITOR
AUTO
MONITOR
MENU
+/−
UP/
DOWN
SET
RUNNINGCONTROL
[×10h]
SELECT/WIDE
1
REMOTE
SHUTDOWN
2
ALARM
RESET
FUNC
REMOTE
STR
UNLOAD STOP button
RUNNINGMODE
LOAD
START
POWER
AUTOSTART
STOP
UNLOAD STOP
③ Be sure to turn of f the power if the compressor is
not to be used for an extended period of time.
CAUTION
● If the air compressor is stops for a week or more without taking action described in this page, serious
damage for the airend may occur due to the lack of lubrication or airend internal rusting.
● Use unload stop button not only for long operation suspension but also for daily operation to prevent
the airend from the rusting.
● If the air compressor can’t be operated weekly, rust prevented action and periodical inspection is
required. Contact the local HITACHI distributor/master dealer or representative office for the detail.
■ How to perform the unload stop action with
lead-lag or multi unit control operation (option)
Unload stop button is ineffective when the operation
mode setting is NOT “Single”. Refer to the page 21
for the detail. Deactivate the lead-lag or multi unit
control at once and perform unload stop. When the
air compressor is restarted, set the operation setting
to required mode.
94
11. PARTS LIST
Air End Assembly
1
277
278
277
235
234
233
278
232
235
278
299
Gear Case Assembly
2
233
277
375
375
383
369
396
364
※177 (Air Cooled)※177
243
178
200
135
134
133
132
371
322
338
336
135
326
398
370
334
307
338
339
339
※183
(Air Cooled)
317
883
884
399
B32
398
389
316
133
370
G64
G65
(Water Cooled)
143
178
184
334
388
318
319
H78
887
100
※183
(Water Cooled)
321
333
E83
F39
323
Ref.
No.
100 1st-Stage Air End (new)
132
133
134
135
143
320
301
324
Description
1st-Stage Air End Discharge Cover
1st-Stage Air End Jacket Cover
Gasket, 1st-stage air end discharge cover
Gasket, 1st-stage air end jacket cover
Pinion Gear, 1st-stage air end
332
Ref.
No.
177
178
183
184
200 2nd-stage Air End (new)
232
233
234
235
243
277
278
299
Jacket Upper Cover, 1st-stage air end
Gasket, 1st-stage air end jacket upper cover
Jacket Lower Cover, 1st-stage air end
Gasket, 1st-stage air end jacket lower cover
2nd-Stage Air End Discharge Cover
2nd-Stage Air End Jacket cover
Gasket, 2nd-stage air end jacket cover
Gasket, 2nd-stage air end jacket cover
Pinion Gear, 2nd-stage air end
Seat, 2nd-stage air end jacket
Seat Gasket, 2nd-stage air end jacket
1st stage or 2nd stage Air End Assembly (new)
Description
O-Ring, 1st-stage air end
O-Ring, 2nd-stage air end
Oil Temperature Control Valve
95
11. PARTS LIST
Motor Assembly
3
415
460
306
461
302
426
391
462
F73
393
419
394
H56
340
F72
427
428
425
401
453
454
455
J26
H55
Ref.
No.
302 Pull Gear
306 Pinion Gear, oil pump
340 Key
391 Shaft Seal
393 Gasket, shaft seal
401 Motor
415 O-Ring (motor flange)
419 Cover, shaft seal
425
426 Support Bolt, gear case
427 Stad Bolt, motor support
428 Spacer
453 Bearing (Load-side)
454 Bearing (Anti-Load-side)
455 Grease
461 Gear Shaft, oil pump
462 M8 Flat Head Bolt
F72 Grease Pan (1)
F73 Grease Pan (2)
H55 Bolt with assistant
H56 Spacer, base
J26 Thermostat
Valve Sheet, blowoff valve piston
508 Plate
509 Spindle, air cylinder
510 Rod Metal
511 Gasket, air cylinder
512
Gasket (1), air end air intake
513 Gasket, STV cover
514 Valve Plate, STV
515 Seal Gasket (1)
516 Seal Gasket (2)
517 Piston, air cylinder
518 Seal Gasket (3)
519 Seal Gasket (4)
520 O-Ring, air cylinder
521 Seal Gasket (5)
522 Bush, air cylinder
515
504
F28
Description
516
11. PARTS LIST
509
522
Ref.
No.
525 Tying Rod, air cylinder
526 Cover, air cylinder
529 Spring Washer (SUS)
530 Rod Nut
532 Body, blowoff valve
534 Seal Washer, air cylinder
535 Nut
536 Wave Spring
537 O-Ring (piston)
538 O-Ring (spacer)
539 O-Ring (needle)
540 O-Ring (2), air cylinder
541 Holder, piston
542 Spacer
550 O-Ring (1), air cylinder
551
Set of Air Cylinder Consumable Parts
554 Unloader Cover (1)
555 O-Ring, unloader 1
558
Adjusting Bolt, suction bypass valve
559
Seal Washer, suction bypass valve
569 Grease, air cylinder
574 Valve Plate, STV
F27 C-type Snap Ring
F28 Backup Ring
F42 Support Plate, unloader
F44 Air Intake Duct
F46 O-Ring
Description
F42
F46
513
554
502
559
511
555
F44
512
Ref.
No.
500
502 Body, STV
511 Gasket, air cylinder
512 Gasket, air end air intake
513 Gasket, STV cover
554 Unloader Cover (1)
555 O-Ring
559 Seal Washer
F42 Support Plate, unloader
F44 Air Intake Duct
F46 O-Ring