Thank you for choosing the Hioki CM4141-50 AC Clamp Meter. To ensure your ability to get the
most out of this instrument over the long term, please read this manual carefully and keep it
available for future reference.
Read the separate document “Operating Precautions” carefully before using the instrument.
Latest edition of instruction manual
The contents of this manual are subject to change, for example as a result of product
improvements or changes to specications.
The latest edition can be downloaded from Hioki’s website.
https://www.hioki.com/global/support/download
Target audience
This manual has been written for use by individuals who use the product in question or who
teach others to do so. It is assumed that the reader possesses basic electrical knowledge
(equivalent to that of someone who graduated from the electrical program at a technical high
school).
Introduction
1
Notations
HIOKI CM4141C961-00
Trademarks
• Microsoft Excel is a registered trademark or a trademark of Microsoft Corporation in the United States and
other countries.
• The Bluetooth
of such marks by Hioki E.E. Corporation is under license. Other trademarks and trade names are those of
their respective owners.
Notations
Safety notations
In this document, the severity levels of risk and hazard are classied as follows.
DANGER
WARNING
2
®
word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use
Indicates an imminently
hazardous situation that,
if not avoided, will result in
death or serious injury.
Indicates a potentially
hazardous situation that, if
not avoided, could result in
death or serious injury.
IMPORTANT
Indicates information or
content that is particularly
important from the stand
point of operating or
maintaining the instrument.
Indicates a high-voltage
hazard. Failure to verify
safety or improper handling
of the instrument could lead
to electric shock, burn injury,
or death.
CAUTION
HIOKI CM4141C961-00
NOTICE
Indicates a potentially
hazardous situation that, if
not avoided, could result in
minor or moderate injury.
Indicates potential risks of
damage to the supported
product (or to other
property).
Notations
Indicates the presence of a
hazard caused by a strong
magnet. The product could
interfere with the proper
operation of electronic
medical devices such as
pacemakers.
Indicates an action that
must not be performed.
Indicates an action that
must be performed.
3
Notations
HIOKI CM4141C961-00
Symbols shown on the instrument
Indicates the presence of a potential hazard. For more information about locations where
this symbol appears on instrument components, see the “Operating Precautions” (p. 12),
warning messages listed at the beginning of operating instructions, and the accompanying
document entitled “Operating Precautions.”
Indicates that a dangerous voltage is generated from this terminal.
Indicates that the product can be attached or detached while the circuit is live.
Indicates alternating current (AC).
Indicates direct current (DC).
Indicates the grounding terminal.
Indicates the instrument is protected throughout by double insulation or reinforced insulation.
4
Symbols for various standards
HIOKI CM4141C961-00
Indicates that the product is subject to the Waste Electrical and Electronic Equipment (WEEE)
Directive in EU member nations. Dispose of the product in accordance with local regulations.
Indicates that the product complies with standards imposed by EU directives.
Screen display
The instrument screen displays the alphanumeric characters as follows.
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
1 2 3 4 5 6 7 8 9 0
Notations
Some displays may be different from
those indicated on the left.
: Wire break detected
5
Notations
HIOKI CM4141C961-00
Accuracy labeling
Instrument accuracy is expressed by dening a percentage of the reading, a percentage of full scale, a
percentage of the setting, or a limit value for errors in terms of digits.
Reading
(display value)
Full scale
(maximum
display value)
Other notations
Indicates a buzzer sound (either intermittent or continuous).
(p. )Indicates the page number to reference.
*Indicates additional information is described below.
6
Indicates the value displayed by the instrument.
Limit values for reading errors are expressed as a percentage of the reading (“% rdg”).
Indicates the maximum display value for each measurement range. Measurement range
values for the instrument indicates that maximum display value. Limit values for full-scale
errors are expressed as a percentage of full scale (“% f.s.”).
Checking Package Contents
HIOKI CM4141C961-00
When you receive the instrument, inspect it to ensure that no damage occurred during shipment. Pay
particular attention to included accessories, panel keys, and terminals. If you nd any damage or discover
that the instrument does not perform as indicated in its specications, please contact your authorized Hioki
distributor or reseller.
CM4141-50
AC Clamp Meter
L9300 Test Lead (p. 30)
C0203 Carrying Case
LR03 Alkaline batteries ×2
Instruction Manual (this manual)
Operating Precautions (0990A907)
Checking Package Contents
7
Options
HIOKI CM4141C961-00
Options
The options listed below are available for the instrument. To order an option, please contact your
authorized Hioki distributor or reseller.
Options are subject to change. Check Hioki’s website for the latest information.
Connection cables
When attaching the L4933 or L4934 to test leads, set the test
leads to the measurement category II conguration (for the
L9207-10, remove the sleeves).
L9207-10 Test Lead*
L9300 Test Lead*
8
1
1
L4933 Contact Pin Set*
L4934 Small Alligator Clip Set*
6
5
Options
HIOKI CM4141C961-00
L4930 Connection Cable Set*
(length: 1.2 m)
L4931 Extension Cable Set*
(length: 1.5 m, with the coupling
connector)
DT4910 Thermocouples (K)
P2000 DC High Voltage Probe*
*1: CAT IV 600 V/CAT III 1000 V/CAT II 1000 V, 10 A*6: 30 V AC/60 V DC, 3 A
*2: CAT IV 600 V/CAT III 1000 V, 10 A*7: CAT III 600 V/CAT II 600 V, 10 A
*3: CAT III 1000 V, 2 A*8: CAT IV 1000 V, 2 A
*4: CAT III 600 V, 5 A*9: CAT II 1000 V, 1 A
*5: CAT III 300 V/CAT II 600 V, 3 A*10: CAT III 600 V, 10 A
L4935 Alligator Clip Set*
2
L9243 Grabber Clip*
L4936 Bus Bar Clip Set*
2
L4937 Magnetic Adapter Set*
9804 Magnetic Adapter*
L4932 Test Pin Set*
L4938 Test Pin Set*
L4939 Breaker Pin Set*
11
*11: CAT IV 1000 V/CAT III 2000 V
2
9
4
3
8
1
7
10
9
Options
HIOKI CM4141C961-00
Carrying cases
The instrument, test leads, and the instruction manuals can be accommodated.
C0203 Carrying Case
Z3210 Wireless Adapter
10
C0207 Carrying Case (bag type)
Connecting the Z3210 to the instrument enables the wireless
communication function.
See “2.8 Wireless Communications Function (Z3210 required)” (p. 49).
Safety Information
HIOKI CM4141C961-00
Safety Information
Measurement categories
The instrument conforms to the safety requirements for CAT III 1000 V and CAT IV 600 V
measuring instruments.
Distribution panel
Service entrance
Service drop
CAT IV
(≤600 V)
Power meter
Internal wiring
CAT III
(≤1000 V)
Fixed installation
CAT II
(≤1000 V)
T
Outlet
11
Operating Precautions
HIOKI CM4141C961-00
Operating Precautions
Observe the following precautionary information to ensure that the instrument can be used
safely and in a manner that allows it to perform as described in its specications. Carefully
read the separate document entitled “Operating Precautions” before use. Use of the instrument
should conform not only to its specications, but also to the specications of all accessories,
options, and other equipment in use.
Do not touch the section beyond the barrier during operation.
Do not measure any current in excess of the derating.
12
DANGER
Failure to do so could cause the operator to experience an electric shock.
See “1.2 Part Names” (p. 20).
Doing so can cause overheating of the sensor, resulting in bodily injury, re, or
damage to the instrument.
See “Frequency derating” (p. 65).
The maximum measurement current varies with the frequency, and the current
that can be measured continuously is limited. Operating the instrument at less
than this limitation is referred to as derating.
Do not apply a voltage across the measurement terminals
HIOKI CM4141C961-00
when the resistance measurement, continuity check,
diode check, capacitance measurement, or temperature
measurement function is selected
Conrm that the white portion (insulation layer) inside the
cable is not exposed.
Operating Precautions
DANGER
Doing so could cause an electric shock or damage the instrument. To avoid
electrical accidents, turn off the circuit before measuring it.
Using the instrument with a color inside its cable exposed could cause the
operator to experience an electric shock.
13
Operating Precautions
HIOKI CM4141C961-00
Do not allow the instrument to get wet.
Do not take measurements with wet hands.
When using the instrument while connected to test leads,
do not make measurements that exceed either of the ratings
indicated on the instrument or on the test leads, whichever is
lower.
14
WARNING
Failure to do so could cause the operator to experience an electric shock.
Using the instrument to make measurements that exceed either rating could
cause the operator to experience an electric shock.
IMPORTANT
HIOKI CM4141C961-00
Operating Precautions
Do not allow any foreign object to be caught between
the facing core surfaces of the jaws.
Do not scratch the facing core surfaces of the jaws.
Do not touch the facing core surfaces of the jaws
with your ngers.
Do not insert any foreign object into the gap of the
jaws.
Do not drop the instrument.
Do not subject the instrument to any shock.
Doing so may adversely affect the measurement accuracy
and open/close operation.
Clamp the instrument around only one conductor. Clamping the
instrument around two or more of conductors in a bundle prevents
the instrument from measuring any current regardless of whether
the measurement target is a single-phase or three-phase circuit.
15
Operating Precautions
HIOKI CM4141C961-00
L4937 Magnetic Adapter Set / 9804 Magnetic Adapter
People with electronic medical devices such as pacemakers
should not use the magnetic adapter.
Keep the magnetic adapter away from the body.
16
DANGER
Failure to do so may affect proper operation of the electric medical devices,
presenting a hazard to human life.
Do not drop the magnetic adapter.
HIOKI CM4141C961-00
Do not subject the magnetic adapter to mechanical shock.
Do not use the magnetic adapter in locations where it may be
exposed to rainwater, dust, or condensation.
Do not bring the magnetic adapter near magnetic storage devices,
such as oppy disks, magnetic cards, prepaid cards, or magnetized
tickets.
Do not bring the magnetic adapter near precision electronic
equipment, such as computers, TV screens, or electronic wrist
watches.
Operating Precautions
NOTICE
Doing so could damage the magnetic adapter.
Doing so could decompose or deteriorate the magnetic adapter. In addition,
diminished magnetic adhesion cause the instrument to drop, resulting in
damage to the instrument.
Doing so could damage such devices or data stored in them.
17
Operating Precautions
HIOKI CM4141C961-00
18
1
HIOKI CM4141C961-00
Overview
1.1 Product Overview and Features
This instrument is a clamp meter that can
perform true RMS measurement of current
simply by clamping it around a circuit. In
addition to current, it can measure voltage,
frequency, rush current, resistance, diode,
capacitance, and temperature.
Installing the Z3210 Wireless Adapter
(optional) to the instrument allows your mobile
device to display waveforms and measure
harmonics.
Measurement function list
Temperature
Capacitance, diode
Continuity check, resistance
AUTO V, AC voltage, DC voltage,
AC+DC voltage
AC current
19
Part Names
HIOKI CM4141C961-00
1.2 Part Names
FrontRear
1
2
20
1Operation grip
2Fn key (Selects function indicated in blue
lettering)
3
4
5
6
7
8
9
10
11
12
3Jaws (p. 32)
4Barrier
5 Serial number (The serial number
consists of 9 digits. The rst two (from
the left) indicate the year of manufacture,
and the next two indicate the month of
manufacture.)
6Rotary switch
7HOLD key
8LCD
9Battery cover
10 Operation keys
11 Measurement terminals
12 Strap hole
2
NO
NONO
HIOKI CM4141C961-00
Making Measurements
2.1 Inspection Before Measurement
Check if there is any damage to the instrument occurred during storage or shipping and
verify that instrument operates normally before using it. If you nd any damage, contact your
authorized Hioki distributor or reseller.
CheckInspection detailsCheckInspection details
The battery cover is closed and its screw
has been securely tightened.
There is no foreign matter on the
measurement terminals (p. 20).
The test leads are not broken. (p. 41)
There is no damage to the test lead
insulation, and neither the white sheathing
nor metal conductor inside the wire are
exposed.
The instrument is neither damaged nor
cracked.
No segments are missing.
OK
1 Ω or less
(All segments appear)
21
Installing Batteries and the Z3210 Wireless Adapter
HIOKI CM4141C961-00
2.2 Installing Batteries and the Z3210 Wireless Adapter
Installing the Z3210 to the instrument enables the wireless communications function. (p. 49)
Before removing the battery cover, remove the instrument
from an object under measurement and set the rotary switch
to the OFF position.
22
WARNING
Failure to do so could cause the operator to experience an electric shock. When
the instrument is clamped around the object under measurement, the battery
contact terminals are regarded as high-voltage parts.
After replacing the batteries or installing/removing the Z3210
HIOKI CM4141C961-00
Wireless Adapter, install the battery cover and tighten the
screw, then use the instrument.
Secure the battery cover with the screw attached to the
instrument at the time of shipment.
Do not mix batteries of different ages or types.
Do not use a battery whose recommended service life has expired.
Do not reverse the battery polarity.
Do not leave the exhausted batteries in the instrument.
Installing Batteries and the Z3210 Wireless Adapter
WARNING
Use of the instrument with the battery cover removed could result in bodily
injury.
Securing the battery cover with another screw could damage the instrument,
resulting in bodily injury. If you have lost the screw or nd that the screw is
damaged, please contact your authorized Hioki distributor or reseller.
NOTICE
Doing so may cause the batteries to leak, damaging the instrument.
23
Installing Batteries and the Z3210 Wireless Adapter
HIOKI CM4141C961-00
NOTICE
Use the specied type of batteries only (LR03 Alkaline batteries).
Remove the batteries when the instrument is not in use for an
extended period of time.
Doing so may cause the batteries to leak, damaging the instrument.
Before handling the Z3210, eliminate static electricity on your body
by touching any metallic part, such as a doorknob.
Failure to do so may cause static electricity to damage the Z3210.
• When the
with new ones in good time. The instrument may be turned off when the display is
backlighted or the buzzer sounds. After use, be sure to turn off the instrument.
• Dispose of the batteries in accordance with local regulations.
24
mark blinks, the batteries will be exhausted. Replace the batteries
Loading...
+ 78 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.