Henny Penny HHC-990 User Manual

Page 1
SECTION 5. TROUBLESHOOTING
5-1. TROUBLESHOOTING GUIDE
PROBLEM CAUSE CORRECTION
Product not • Doors left open • Keep doors closed except holding temperature to load and serve product
• Product held too long • Hold product only for recom­mended times
• Door gasket torn or worn • Replace bad door gaskets
Model HHC-990
Cabinet steaming • Humidity setpoint too high • Decrease humidity setpoint product soggy (SP-4) in Special Program Mode
Product dry • Humidity setpoint too low • Increase humidity setpoint
(SP-4) in Special Program Mode
• No water in pan • Pour water in water pan
Unit not heating • Blown fuse • Change15 amp fuse
Unit not reaching set • Doors left open • Keep doors closed except temperature to load and serve product
• Door gasket torn or worn • Replace bad door gaskets
More detailed troubleshooting information is available in the T echnical Manual, available at www .hennypenny .com,
or 1-800-417-8405 or 1-937-456-8405.
5-1 703
Page 2
Model HHC-990
5-2. ERROR CODES AND The display shows the following error codes and warnings when a WARNINGS fault is detected, along with an alarm sound. Both the heat and
humidity systems shut down, except when specified otherwise.
Display Cause Panel Board Correction
“E-4 CPU TOO HOT” • Control board too hot;
unit overheating or louvers clogged
“E-5 AIR TEMP TOO HOT” • Faulty relay, PC board,
or air probe
“E-54A CPU TEMP SENSOR • Faulty PC board
OPEN”
• Turn switch to OFF position, then back to ON; if display still shows “E-4”, the PC board is getting too hot; clean louvers and check cooling fan; if cooling fan is not working, have it replaced; once panel cools down, the controls should return to normal; if “E-4” persists, have the PC board replaced
• Turn switch to OFF position, then back to ON; if display shows “E-5”, the heating circuits and temperature probe should be checked; once the unit cools down, the controls should return to normal; if “E-5” persists, have the PC board replaced
• Turn switch to OFF position, then back to ON; if display shows “E-54A”, the control should be re-initialized (see Pro­gramming Section); if the error code persists, have PC board replaced
“E-54B CPU TEMP SENSOR • Faulty PC board
SHOR TED”
• Turn switch to OFF position, then back to ON; if display shows “E-54B”, the control should be re-initialized (see Pro­gramming Section); if the error code persists, have PC board replaced
“E-6A AIR TEMP SENSOR • Faulty air probe
F AILED OPEN”
• Turn switch to OFF position, then back to ON; if the display shows “E-6”, the temperature probe should be checked; once the temperature probe is repaired, or replaced, the controls should return to normal; if “E-6” persists, have the PC board replaced
303 4-7
Page 3
5-2. ERROR CODES AND
WARNINGS (Continued)
Display Cause Panel Board Correction
E-6B AIR TEMP SENSOR • Faulty air temperature
FAILED SHORTED” probe
Model HHC-990
• Turn switch to OFF position, then back to ON; if the display shows “E-6”, the temperature probe should be checked; once the temperature probe is repaired, or replaced, the controls should return to normal; if “E-6”persists, have PC board replaced
“E-12A WA TER HEATER • Faulty water
SENSOR FAILED heater probe OPEN”
“E-12B WATER HEATER • Faulty water
SENSOR FAILED heater probe CLOSED”
“E-17 HUMIDITY SENSOR • Faulty humidity sensor
FAILED”
• Turn switch to OFF position, then back to ON; if the display shows “E-12A”, the water heater should be checked and repaired or replaced (the water heater probe is built into the water heater); the controls should return to normal; if “E-12A” persists, have PC board replaced
• Turn switch to OFF position, then back to ON; if the display shows “E-12B”, the water heater should be checked and repaired or replaced (the water heater probe is built into the water heater); the controls should return to normal; if “E-12B” persists, have PC board replaced
• Turn switch to OFF position, then back to ON; if the display shows “E-17”, the humidity sensor should be checked; once the humidity sensor is repaired, or replaced, the controls should return to normal; if “E-17” persists, have PC board
replaced
“E-18 NO WATER, FLOAT • Float switch stuck or
SWITCH F AILED” faulty; faulty relay
(stuck on);water pan needs cleaned; loose or faulty water heater sensor; acorn nuts on water heater cover loose, or water heater insulation missing or damaged
A humidity error only shuts down the humidity system. If a humidity error occurs, and you want to use the cabinet without humidity , turn the humidity off by following the directions for SP-4, Humidity Setpoint, in Special Programming Section of this manual. Once the setpoint is off, the alarm stops, but the error code shows in display . (Includes “E-12A”, “E-12B”, “E-17” and “E-18”).
4-8 107
• Turn switch to OFF position, then back to ON; if the display shows “E-18”, check and clean float switch; clean water pan; have relay and water heater sensor checked and replace if necessary; tighten acorn nuts on water heater cover; make sure insulation is under the water heater cover; if “E-18” persists, have PC board replaced
Page 4
5-2. ERROR CODES AND WARNINGS (Continued)
Display Cause Panel Board Correction
Model HHC-990
“E-41 SYSTEM DA T A LOST” • Memory scrambled
“E-46 DA T A SA VE F AILED” • Memory scrambled
“E-80 VENT STUCK OR V ent on rear of module BAD SWITCH” stuck or faulty vent
activation switch
“PLEASE DE-LIME • W ater pan needs W ATER P AN” cleaned
• Turn switch to OFF position, then back to ON; if the display shows “E-41”, the control should be re-initialized (see Pro­gramming Section); if “E-41”persists, have PC board replaced
• Turn switch to OFF position, then back to ON; if the display shows “E-46”, the control should be re-initialized (see Pro­gramming Section); if “E-46”persists, have PC board replaced
• Check vent on rear of module for obstruc­tions, or have vent activation switch replaced
• Follow the weekly cleaning procedures; this warning will not shut down the heat or humidity; if “PLEASE DE-LIME W ATER P AN” persists, have PC board replaced
“W ATER LEVEL LOW, PLEASE” W ater pan low on water
or empty
• Fill water pan, in bottom of unit, to the maximum water fill mark; this warning won’t shut down the heat or humidity
303 4-8
Loading...