Henny Penny CEC-103, CEC-104, CEC-106, CEC-108 Installation Manual

Model CEC-103, 104, 106, 108
SECTION 2. INSTALLATION
2-1. INTRODUCTION This section provides the installation and unpacking instructions for
Henny Penny cold express case.
Installation of this unit should be performed only by a qualified service technician.
Do not puncture the unit with any objects such as drills or screws, or component damage or electrical shock could result.
and expertly packed to insure arrival at its destination in the best possible condition. The grids are packed separately inside the unit. The cabinet rests on a wooden skid and is then packed inside a heavy cardboard carton with sufficient padding to withstand normal shipping treatment.
To avoid damage to the components, do not lay the unit on its side. If the unit has been on its side, the unit must be in an upright position for at least 4 hours before power is applied to the unit.
Check all components, for signs of being loose or dam­aged, and make sure the system has refrigerant.
When moving the cold express case be careful not to damage the refrigerent circuit.
Any shipping damage should be noted in the presence of the delivery agent and signed prior to his or her departure.
To remove the Henny Penny cold case from the carton:
1. Carefully cut banding straps.
2. Lift the carton off the unit.
3. Lift the unit off the skid.
303 2-1
Model CEC-103, 104, 106, 108
2-2. UNPACKING (Continued)
Take care when moving the unit to prevent personal injury or damage to the refrigeration system. The units weigh between 550 lbs. (250 kg) and 1200 lbs. (544 kg).
4. Peel off any protective covering from exterior of the cabinet.
5. Install the shelves into unit.
6. Your cold express case is now ready for operation.
2-3. ELECTRICAL The cold express case is available as a 120 VAC, or 240VAC,
60 Hz., single phase unit, both for domestic and international use. (See table below) The data plate, located on the left side of the unit, specifies the correct electrical supply. The cold express cases are shipped with cord and plug, and requires a grounded receptacle with a separate electrical line protected by a fuse or circuit breaker of the proper rating.
This unit must be adequately and safely grounded. Refer to local electrical codes for correct grounding procedures. If unit is not adequately grounded, electri­cal shock could result.
To avoid electrical shock, this appliance must be equipped with an external circuit breaker which will disconnect all ungrounded (unearthed) conductors.
Refer to the table below for electrical ratings:
Model No. Volts Amps Phase Max. Fuse Size
CEC-103 120 18.3 1 20 CEC-104 240 12.6 1 20 CEC-106 240 10.9 1 30 CEC-108 240 16.1 1 30
2-2 503
Loading...
+ 2 hidden pages