Hekatron LRS 01, LRS 02, Smoke Switch ORS 210 Installation Instructions Manual

Ventilation-Duct Smoke Switch System
LRS 01 Basic
Installation Instructions
Installation Instructions LRS 01
2
HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg 7002428 100206.VDA Ausgabe 10.02.2006
Installation Instructions LRS 01
3
Installation Instructions LRS 01
3
Table of contents
Introduction ....................................................................4
1. Project planning ........................................................5
2 Technical data............................................................6
3 General information .................................................7
3.1 Operation of the LRS 01 ......................................... 7
3.2 Transport, storage and unpacking ......................... 7
3.3 Scope of supply ...................................................... 7
4 Rules and regulations................................................8
5 Installation instructions.............................................9
5.1 Mounting the LKS 02 .............................................. 9
5.2 Electrical connection of the ORS 210 ................... 12
6 Commissioning ........................................................14
6.1 Functional testing ................................................ 14
6.2 Display of operating status of the ORS 210 ........ 14
7 Maintenance instructions........................................15
8 Ordering data..........................................................16
Installation Instructions LRS 01
4
HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg 7002428 100206.VDA Ausgabe 10.02.2006
Installation Instructions LRS 01
5

Introduction

Figure 01
The LRS 01 consists of a ventilation duct socket LKS 02 and an ORS 210 optical Smoke Switch with alarm latching. It is used for monitoring smoke in ventilation ducts.
The LKS 02 provides a mounting for Smoke Switch ORS 210 and is fitted on the outside of a ventilation duct. The LRS 01 is intended for use inside buildings.
Installation Instructions LRS 01
5

1. Project planning

The socket LKS 02 is designed for use on rectangular ventilation ducts with dimension “a” from 0.15 m to 1.0 m. It can also be used on circular ducts from
0.2 m to 1.0 m in diameter. The lateral reach of the inlet tube into a duct is ca. 500 mm. The ventilation duct socket must be placed so that reliable smoke detec­tion can be assumed. Disruptive factors, which could affect reliable operation of the LRS 01 must be eliminated.
A2
A2
B
B
A1
A1
min. 3 x a
A1: Ideale Betriebsumgebung
A2: Erhöhte Staubbelastung
B: Bereich für Rauchfrüherkennung ungeeignet.
a: Kanalmaß
a
a
Luftstromrichtung
Figure 02
Figure 02 provides recommendations for project planning.
To ensure reliable smoke detection, in large ducts several LRS 01 Smoke Switches should be instal­led. The airflow parameters must be taken into account when determining their positions.
Zentrum
Figure 03
Direction of Airflow
A1: ideal operating environment
A2: higher dust loadings
B: zone unsuitable for early detection of smoke
a: duct dimension
Centre
Installation Instructions LRS 01
6
HEKATRON Vertriebs GmbH · Brühlmatten 9 · D-79295 Sulzburg 7002428 100206.VDA Ausgabe 10.02.2006
Installation Instructions LRS 01
7

2 Technical data

Housing LKS 02
Field of application ventilation ducts Min. air speed 1 m/s Max. air speed 20 m/s Temperature range see Smoke Switch ORS 210 Degree of protection IP 54 (on duct surface) Colour blue / transparent Material PC / aluminium tube Installation Openings
on a ventilation duct
2 x Ø 28-30 mm at 150 mm pitch centres
for mounting in housing
2 x max. 6 dia. at 206 mm pitch centres Cable entries 4 x Ø6-10 mm Dimensions without tube L 25 cm x B 13.5 cm x H 10 cm Weight without tube ca. 350 g
The temperature range of the socket LKS 02 and Smoke Switch ORS 210 combi­nation is determined by the technical data of the Smoke Switch. Temperature range: - 20 °C to + 75 °C Permissible rel. humidity: up to 95 % RH (dewing and steam condensation can cause false alarms)
Smoke Switch ORS 210
Operating principle light-scattering
Reaction thresholds to construction and testing rules for
smoke-triggered installations (12/76)
Operating voltage 18 to 28 V DC
Current draw at 28 V DC quiescent in alarm in fault
22 mA 11 mA 16 mA
Relay contacts with latching alarms
switchable voltage, max. switchable current, max. switchable power, max.
30 V DC
1 A
30 W
Degree of protection IP 40
Operating ambient temperature -20°C to +75 °C
Weight 120 g
The ORS 210 has latching alarm functions. Following an alarm , the relay (contacts 4 and 5) remains open until the supply voltage is briefly interrupted.