Heatiator GDST3831I User Manual

Page 1
Models: GDST3831I
Owner’ s Manual
Installation and Operation
NOTICE
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
WARNING: If the information in these instructions is not followed exactly, a fi re or explosion may result causing property damage, personal injury, or death.
DO NOT store or use gasoline or other fl am- mable vapors and liquids in the vicinity of this or any other appliance.
• What to do if you smell gas
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas suppli­er’s instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed by a qualifi ed installer, service agency , or the gas supplier.
This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the manufactured home construction and safety standard,
Title 24 CFR, Part 3280 or Standard for Installation in Mobile Homes, CAN/CSA Z240MH, in Canada.
This appliance is only for use with the type(s) of gas indicated on the rating plate.
• Read, understand and follow these instructions for safe installation and operation.
DO NOT
DISCARD
• Leave this manual with party responsible for use and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter.
See Table of Contents for location of additional Commonwealth of Massachusetts requirements.
Installation and service of this appliance should be performed by qualifi ed personnel. Hearth & Home Technologies suggests NFI certifi ed or factory trained professionals, or technicians supervised by an NFI certifi ed professional.
1Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 2
Read this manual before installing or operating this appliance.
Not Not for for use use with with solid solid fuel.fuel. ((Ne Ne doit doit pas pas entre entre utilise utilise avec avec un un combustible combustible solide).solide).
This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes, codes, if if any; any; if if not, not, follow follow ANSI ANSI Z223.1Z223.1 in in the the USA USA or or CAN/CGA CAN/CG A B149 B149 installation installation codes. codes. (Installer (Installer l’appareil l’appareil selon selon les les codes codes ou ou reglementsreglements
locaux locaux ou, ou, en en l’absence l’absence de de tels tels reglements, reglements, selon selon les les codes codes d’installation d’installation CAN/CGA-B149.)CAN/CGA-B149.)
Type Type o f of Gas Gas (Sorte (Sorte De De Gaz)Gaz)::
NNAATURALTURAL GASGAS
MADE MADE IN IN USAUSA
Minimum Minimum Permissible Permissible Gas Gas Supply Supply for for Purposes Purposes of of Input Input Adjustment.Adjustment. Approved Approved Minimum Minimum (De (De Gaz) Gaz) AcceptableAcceptable 0.00.0 in in w.c.w.c. (Po. (Po. Col. Col. d’eau)d’eau) Maximum Maximum Pressure Pressure (Pression)(Pression) 0.00.0 in in w.c.w.c. (Po. (Po. Col. Col. d’eau)d’eau) Maximum Maximum Manifold Manifold Pressure Pressure (Pression)(Pression) 0.00.0 in in w.c.w.c. (Po. (Po. Col. Col. d’eau)d’eau) Minimum Minimum Manifold Manifold Pressure Pressure (Pression)(Pression) 0.00.0 in in w.c.w.c. (Po. (Po. Col. Col. d’eau)d’eau)
Model:Model:
(Modele):(Modele):
SerialSerial
(Serie):(Serie):
ANSI ANSI Z21XX-XXXX Z21XX-XXXX · · CSA CSA 2.XX-MXX 2.XX-MXX · · UL307BUL307B
XXXXXXXXXXXXXXXX
IN IN CANADACANADA ALTITUDE:ALTITUDE: 0-0000 0-0000 FT.FT. 0000-0000FT.0000-0000FT. MAX. MAX. INPUT INPUT BTUH:BTUH: 00,00000,000 00,00000,000 MIN. MIN. INPUT INPUT BTUH:BTUH: 00,00000,000 00,00000,000 ORIFICE ORIFICE SIZE:SIZE: #XXXXX#XXXXX #XXXXX#XXXXX
XXXXXXXXXXXXXXXX
Total Total Electrical Electrical Requirements: Requirements: 000Vac, 000Vac, 00Hz., 00Hz., less less than than 00 00 AmperesAmperes
Heat & Glo, a brand of Hearth & Home Technologies, Inc. 7571 215th Street West, Lakeville, MN 55044
Please retain this owner’s manual for future reference.
A. Congratulations
Congratulations on selecting a Heatilator gas fi replace, an elegant and clean alternative to wood burning fi replaces. The Heatilator gas fi replace you have selected is designed to provide the utmost in safety, reliability, and effi ciency.
This owner’s manual should be retained for future reference. We suggest that you keep it with your other important documents and product manuals.
The information contained in this owner’s manual, unless noted otherwise, applies to all models and gas control systems.
As the owner of a new fi replace, you’ll want to read and carefully follow all of the instructions contained in this owner’s manual. Pay special attention to all cautions and warnings.
Homeowner Reference Information
Your new Heatilator gas fi replace will give you years of durable use and trouble-free enjoyment. Welcome to the Heatilator family of fi replace products!
We recommend that you record the following pertinent information about your fi replace.
Model Name: ___________________________________________ Date purchased/installed: __________________ Serial Number: __________________________________________ Location on fi replace: _____________________ Dealership purchased from: _______________________________ Dealer Phone: __________________________ Notes: _______________________________________________________________________________________ _____________________________________________________________________________________________
Listing Label Information/Location
Type of Gas
Gas and Electric Information
The model information regarding your specifi c fi replace can be found on the rating plate usually located in the control area of the fi replace.
Model Number
Serial Number
Heatilator • GDST3831I • 2127-900 Rev. K • 7/122
Page 3
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
A. Congratulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
B. Limited Lifetime Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1 Listing and Code Approvals
A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
B. Tempered Glass Specifi cations . . . . . . . . . . . . . . . . . . . . . 7
C. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 7
E. Non-Combustible Materials Specifi cation. . . . . . . . . . . . . . 7
F. Combustible Materials Specifi cation . . . . . . . . . . . . . . . . . 7
G. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
H. Requirements for the Commonwealth of Massachusetts . . 8
User Guide
2 Operating Instructions
A. Gas Fireplace Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
B. Your Fireplace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
C. Fan Kit (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
D. Clear Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
E. Decorative Doors and Fronts . . . . . . . . . . . . . . . . . . . . . . 10
F. Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
G. Remote Controls, Wall Controls and Wall Switches . . . . . 10
H. Before Lighting Fireplace . . . . . . . . . . . . . . . . . . . . . . . . . 10
I. Lighting Instructions (IPI) . . . . . . . . . . . . . . . . . . . . . . . . . 11
J. After Fireplace is Lit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
K. Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . 12
3 Maintenance and Service
A. Maintenance Tasks-Homeowner . . . . . . . . . . . . . . . . . . . 13
B. Maintenance Tasks-Qualifi ed Service Technician . . . . . . 14
Installer Guide
4 Getting Started
A. Typical Appliance System. . . . . . . . . . . . . . . . . . . . . . . . . 16
B. Design and Installation Considerations . . . . . . . . . . . . . . 17
C. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . 17
D. Inspect Appliance and Components . . . . . . . . . . . . . . . . . 17
5 Framing and Clearances
A. Selecting Appliance Location . . . . . . . . . . . . . . . . . . . . . . 18
B. Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . 19
C. Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
D. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 20
6 Termination Locations
A. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 21
B. Continue Adding Vent Components . . . . . . . . . . . . . . . . . 23
C. Install Support Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7 Vent Information and Diagrams
A. Approved Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
B. Vent Table Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
C. Use of Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
D. Measuring Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
E. Use of Flex Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
F. Vent Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8 Vent Clearances and Framing
A. Pipe Clearances to Combustibles . . . . . . . . . . . . . . . . . . 31
B. Wall Penetration Framing . . . . . . . . . . . . . . . . . . . . . . . . . 31
C. Install the Ceiling Firestop . . . . . . . . . . . . . . . . . . . . . . . . 32
D. Install Attic Insulation Shield . . . . . . . . . . . . . . . . . . . . . . . 33
9 Appliance Preparation
A. Securing and Leveling the Appliance . . . . . . . . . . . . . . . . 34
10 Installing Vent Pipe
A. Assemble Vent Sections. . . . . . . . . . . . . . . . . . . . . . . . . . 35
B. Assemble Slip Sections . . . . . . . . . . . . . . . . . . . . . . . . . . 36
C. Securing the Vent Sections . . . . . . . . . . . . . . . . . . . . . . . 36
D. Disassemble Vent Sections . . . . . . . . . . . . . . . . . . . . . . . 37
E. Installing Decorative Ceiling Components . . . . . . . . . . . . 37
F. Installing Metal Roof Flashing . . . . . . . . . . . . . . . . . . . . . 38
G. Assemble and Install Storm Collar . . . . . . . . . . . . . . . . . . 38
H. Installing Vertical Termination Cap . . . . . . . . . . . . . . . . . . 39
I. Installing Decorative Wall Components . . . . . . . . . . . . . . 39
J. Heat Shield Requirements for Horizontal Termination . . . 39
K. Install Horizontal Termination Cap . . . . . . . . . . . . . . . . . . 40
11 Gas Information
A. Fuel Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
B. Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
C. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . 41
3Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 4
12 Electrical Information
A. Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
B. Intellifi re Ignition System Wiring . . . . . . . . . . . . . . . . . . . . 42
C. Optional Accessories Requirements . . . . . . . . . . . . . . . . 42
D. Electrical Service and Repair . . . . . . . . . . . . . . . . . . . . . . 42
E. Junction Box Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 44
F. Wall Switch Installation for Fan (Optional) . . . . . . . . . . . . 44
13 Finishing
A. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 45
B. Facing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
C. Splatter Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
14 Appliance Setup
A. Remove Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . 48
B. Remove the Shipping Materials . . . . . . . . . . . . . . . . . . . . 48
C. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
D. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
E. Lava Rock, Mystic Embers and Glowing Ember
Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
F. Install the Log Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . 49
G. Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
H. Install Trim Kits and Surrounds . . . . . . . . . . . . . . . . . . . . 51
I. Air Shutter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
15 Troubleshooting
A. Intellifi re Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . 52
16 Reference Materials
A. Appliance Dimension Diagram . . . . . . . . . . . . . . . . . . . . . 54
B. Vent Components Diagrams . . . . . . . . . . . . . . . . . . . . . . 55
C. Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
D. Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
= Contains updated information.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/124
Page 5
B. Limited Lifetime Warranty
g
y
y p
p
y
y
y
y
Hearth & Home Technologies Inc.
LIMITED LIFETIME WARRANTY
Hearth & Home Technologies Inc., on behalf of its hearth brands (”HHT”), extends the following warranty for HHT gas, wood, pellet, coal and electric hearth appliances that are purchased from an HHT authorized dealer.
WARRANTY COVERAGE:
HHT warrants to the original owner of the HHT appliance at the site of installation, and to any transferee taking ownership of the appliance at the site of installation within two years following the date of original purchase, that the HHT appliance will be free from defects in materials and workmanship at the time of manufacture. After installation, if covered compo­nents manufactured by HHT are found to be defective in materials or workmanship during the applicable warranty period, HHT will, at its option, repair or replace the covered components. HHT, at its own discretion, may fully discharge all of its obligations under such warranties by replacing the product itself or refunding the verified purchase price of the product itself. The maximum amount recoverable under this warranty is limited to the purchase price of the product. This warranty is subject to conditions, exclusions and limitations as described below.
WARRANTY PERIOD:
Warranty coverage begins on the date of original purchase. In the case of new home construction, warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent, authorized HHT dealer/ distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following the date of product shipment from HHT, regardless of the installation or occupancy date. The warranty period for parts and labor for covered components is produced in the following table.
The term “Limited Lifetime” in the table below is defined as: 20 years from the beginning date of warranty coverage for gas appliances, and 10 years from the beginning date of warranty coverage for wood, pellet, and coal appliances. These time periods reflect the minimum expected useful lives of the designated components under normal operating conditions.
Warranty Period HHT Manufactured Appliances and Venting
Parts Labor Gas Wood Pellet
1 Year
2 years
3 years
ears 1 year X X Castings and baffles
5
7 years 3 years X X X
10
ears
Limited
Lifetime
1 year X Burners, logs and refractory
3 yearsXXXXX Firebox and heat exchanger
XXXXXXX
XXX
XXXXX Factor
X Molded refractor
XFire
EPA
Wood
Coal Electric Venting
Components Covered
All parts and material except as
covered by Conditions,
Exclusions, and Limitations
listed
Igniters, electronic components,
lass
and
-installed blowers
ots and burnpots
Manifold tubes,
HHT chimne
and termination
anels
90 Days
4021-645C 12-29-10 Page 1 of 2
XXXXXXX
See conditions, exclusions, and limitations on next page.
All replacement parts
be
ond warranty period
5Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 6
B. Limited Lifetime Warranty (continued)
WARRANTY CONDITIONS:
 7KLVZDUUDQW\RQO\FRYHUV++7DSSOLDQFHVWKDWDUHSXUFKDVHGWKURXJKDQ++7DXWKRUL]HGGHDOHURUGLVWULEXWRU$OLVWRI
++7DXWKRUL]HGGHDOHUVLVDYDLODEOHRQWKH++7EUDQGHGZHEVLWHV  7KLVZDUUDQW\LVRQO\YDOLGZKLOHWKH++7DSSOLDQFHUHPDLQVDWWKHVLWHRIRULJLQDOLQVWDOODWLRQ  &RQWDFW\RXULQVWDOOLQJGHDOHUIRUZDUUDQW\VHUYLFH,IWKHLQVWDOOLQJGHDOHULVXQDEOHWRSURYLGHQHFHVVDU\SDUWVFRQWDFW
WKHQHDUHVW++7DXWKRUL]HGGHDOHURUVXSSOLHU$GGLWLRQDOVHUYLFHIHHVPD\DSSO\LI\RXDUHVHHNLQJZDUUDQW\VHUYLFH
IURPDGHDOHURWKHUWKDQWKHGHDOHUIURPZKRP\RXRULJLQDOO\SXUFKDVHGWKHSURGXFW  &KHFNZLWK\RXUGHDOHULQDGYDQFHIRUDQ\FRVWVWR\RXZKHQDUUDQJLQJDZDUUDQW\FDOO7UDYHODQGVKLSSLQJFKDUJHV
IRUSDUWVDUHQRWFRYHUHGE\WKLVZDUUDQW\
WARRANTY EXCLUSIONS:
7KLVZDUUDQW\GRHVQRWFRYHUWKHIROORZLQJ  &KDQJHVLQVXUIDFHILQLVKHVDVDUHVXOWRIQRUPDOXVH$VDKHDWLQJDSSOLDQFHVRPHFKDQJHVLQFRORURILQWHULRUDQG
H[WHULRUVXUIDFHILQLVKHVPD\RFFXU7KLVLVQRWDIODZDQGLVQRWFRYHUHGXQGHUZDUUDQW\
 'DPDJHWRSULQWHGSODWHGRUHQDPHOHGVXUIDFHVFDXVHGE\ILQJHUSULQWVDFFLGHQWVPLVXVHVFUDWFKHVPHOWHGLWHPV
RURWKHUH[WHUQDOVRXUFHVDQGUHVLGXHVOHIWRQWKHSODWHGVXUIDFHVIURPWKHXVHRIDEUDVLYHFOHDQHUVRUSROLVKHV
 5HSDLURUUHSODFHPHQWRISDUWVWKDWDUHVXEMHFWWRQRUPDOZHDUDQGWHDUGXULQJWKHZDUUDQW\SHULRG7KHVHSDUWV
LQFOXGHSDLQWZRRGSHOOHWDQGFRDOJDVNHWVILUHEULFNVJUDWHVIODPHJXLGHVOLJKWEXOEVEDWWHULHVDQGWKHGLVFRORU-
DWLRQRIJODVV
 0LQRUH[SDQVLRQFRQWUDFWLRQRUPRYHPHQWRIFHUWDLQSDUWVFDXVLQJQRLVH7KHVHFRQGLWLRQVDUHQRUPDODQGFRP-
SODLQWVUHODWHGWRWKLVQRLVHDUHQRWFRYHUHGE\WKLVZDUUDQW\
 'DPDJHVUHVXOWLQJIURPIDLOXUHWRLQVWDOORSHUDWHRUPDLQWDLQWKHDSSOLDQFHLQDFFRUGDQFHZLWKWKHLQVWDOODWLRQ
LQVWUXFWLRQVRSHUDWLQJLQVWUXFWLRQVDQGOLVWLQJDJHQWLGHQWLILFDWLRQODEHOIXUQLVKHGZLWKWKHDSSOLDQFHIDLOXUHWR
LQVWDOOWKHDSSOLDQFHLQDFFRUGDQFHZLWKORFDOEXLOGLQJFRGHVVKLSSLQJRULPSURSHUKDQGOLQJLPSURSHURSHUD-
WLRQDEXVHPLVXVHFRQWLQXHGRSHUDWLRQZLWKGDPDJHGFRUURGHGRUIDLOHGFRPSRQHQWVDFFLGHQWRULPSURSHUO\ LQFRUUHFWO\SHUIRUPHGUHSDLUVHQYLURQPHQWDOFRQGLWLRQVLQDGHTXDWHYHQWLODWLRQQHJDWLYHSUHVVXUHRUGUDIWLQJ FDXVHGE\WLJKWO\VHDOHGFRQVWUXFWLRQVLQVXIILFLHQWPDNHXSDLUVXSSO\RUKDQGOLQJGHYLFHVVXFKDVH[KDXVWIDQVRU IRUFHGDLUIXUQDFHVRURWKHUVXFKFDXVHVXVHRIIXHOVRWKHUWKDQWKRVHVSHFLILHGLQWKHRSHUDWLQJLQVWUXFWLRQV LQVWDOODWLRQRUXVHRIFRPSRQHQWVQRWVXSSOLHGZLWKWKHDSSOLDQFHRUDQ\RWKHUFRPSRQHQWVQRWH[SUHVVO\DXWKRUL]HG DQGDSSURYHGE\++7PRGLILFDWLRQRIWKHDSSOLDQFHQRWH[SUHVVO\DXWKRUL]HGDQGDSSURYHGE\++7LQZULWLQJ
DQGRULQWHUUXSWLRQVRUIOXFWXDWLRQVRIHOHFWULFDOSRZHUVXSSO\WRWKHDSSOLDQFH  1RQ++7YHQWLQJFRPSRQHQWVKHDUWKFRPSRQHQWVRURWKHUDFFHVVRULHVXVHGLQFRQMXQFWLRQZLWKWKHDSSOLDQFH  $Q\SDUWRIDSUHH[LVWLQJILUHSODFHV\VWHPLQZKLFKDQLQVHUWRUDGHFRUDWLYHJDVDSSOLDQFHLVLQVWDOOHG
 ++7¶VREOLJDWLRQXQGHUWKLVZDUUDQW\GRHVQRWH[WHQGWRWKHDSSOLDQFH¶VFDSDELOLW\WRKHDWWKHGHVLUHGVSDFH,QIRUPD-
WLRQLVSURYLGHGWRDVVLVWWKHFRQVXPHUDQGWKHGHDOHULQVHOHFWLQJWKHSURSHUDSSOLDQFHIRUWKHDSSOLFDWLRQ&RQVLGHU-
DWLRQPXVWEHJLYHQWRDSSOLDQFHORFDWLRQDQGFRQILJXUDWLRQHQYLURQPHQWDOFRQGLWLRQVLQVXODWLRQDQGDLUWLJKWQHVVRI
WKHVWUXFWXUH
This warranty is void if:
 7KHDSSOLDQFHKDVEHHQRYHUILUHGRURSHUDWHGLQDWPRVSKHUHVFRQWDPLQDWHGE\FKORULQHIOXRULQHRURWKHUGDPDJLQJ
FKHPLFDOV2YHUILULQJFDQEHLGHQWLILHGE\EXWQRWOLPLWHGWRZDUSHGSODWHVRUWXEHVUXVWFRORUHGFDVWLURQEXEEOLQJ
FUDFNLQJDQGGLVFRORUDWLRQRIVWHHORUHQDPHOILQLVKHV  7KHDSSOLDQFHLVVXEMHFWHGWRSURORQJHGSHULRGVRIGDPSQHVVRUFRQGHQVDWLRQ  7KHUHLVDQ\GDPDJHWRWKHDSSOLDQFHRURWKHUFRPSRQHQWVGXHWRZDWHURUZHDWKHUGDPDJHZKLFKLVWKHUHVXOWRIEXW
QRWOLPLWHGWRLPSURSHUFKLPQH\RUYHQWLQJLQVWDOODWLRQ
LIMITATIONS OF LIABILITY:
 7KHRZQHU¶VH[FOXVLYHUHPHG\DQG++7¶VVROHREOLJDWLRQXQGHUWKLVZDUUDQW\XQGHUDQ\RWKHUZDUUDQW\H[SUHVVRU
LPSOLHGRULQFRQWUDFWWRUWRURWKHUZLVHVKDOOEHOLPLWHGWRUHSODFHPHQWUHSDLURUUHIXQGDVVSHFLILHGDERYH,QQR
HYHQWZLOO++7EHOLDEOHIRUDQ\LQFLGHQWDORUFRQVHTXHQWLDOGDPDJHVFDXVHGE\GHIHFWVLQWKHDSSOLDQFH6RPHVWDWHV
GRQRWDOORZH[FOXVLRQVRUOLPLWDWLRQRILQFLGHQWDORUFRQVHTXHQWLDOGDPDJHVVRWKHVHOLPLWDWLRQVPD\QRWDSSO\WR\RX
7KLVZDUUDQW\JLYHV\RXVSHFLILFULJKWV\RXPD\DOVRKDYHRWKHUULJKWVZKLFKYDU\IURPVWDWHWRVWDWH(;&(3772
7+((;7(173529,'('%</$:++70$.(612(;35(66:$55$17,(627+(57+$17+(:$55$17<
63(&,),('+(5(,17+('85$7,212)$1<,03/,(':$55$17<,6/,0,7('72'85$7,212)7+(
(;35(66(':$55$17<63(&,),('$%29(
4021-645C 12-29-10 Page 2 of 2
Heatilator • GDST3831I • 2127-900 Rev. K • 7/126
Page 7
1
1
Listing and Code Approvals
A. Appliance Certifi cation
MODELS: GDST3831I LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Direct Vent Gas Appliance Heater STANDARD: ANSI Z21.88-2007 • CSA 2.33a-2007
This product is listed to ANSI standards for “Vented Gas Appliance Heaters” and applicable sections of “Gas Burn­ing Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”.
NOTICE: This installation must conform with local codes. In the absence of local codes you must comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada.
NOT INTENDED FOR USE AS A PRIMAR Y HEAT SOURCE.
This appliance is tested and approved as either supplemen­tal room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
C. BTU Specifi cations
Models
(U.S. or Canada)
GDST3831I (NG)
GDST3831I (LP)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
Maximum
Input
BTU/h
21,000 14,700 44 18,900 13,200 45 20,000 55 18,000 56
Minimum
Input
BTU/h
Orifi ce
Size
(DMS)
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
• In CANADA: Reduce input rate 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.
Check with your local gas utility to determine proper orifi ce size.
B. Tempered Glass Specifi cations
Hearth & Home Technologies appliances manufactured with tempered glass may be installed in hazardous loca­tions such as bathtub enclosures as defi ned by the Con- sumer Product Safety Commission (CPSC). The tempered glass has been tested and certifi ed to the requirements of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing Certifi cation Council SGCC# 1595 and 1597. Architectur- al Testing, Inc. Reports 02-31919.01 and 02-31917.01).
This statement is in compliance with CPSC 16 CFR Sec- tion 1201.5 “Certifi cation and labeling requirements” which refers to 15 U.S. Code (USC) 2063 stating “…Such certifi cate shall accompany the product or shall otherwise be furnished to any distributor or retailer to whom the product is delivered.”
Some local building codes require the use of tempered glass with permanent marking in such locations. Glass meeting this requirement is available from the factory. Please contact your dealer or distributor to order.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC and UL763 shall be
considered non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed pa­per, plant fi bers, plastics, or other material that can ignite and burn, whether fl ame proofed or not, or plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA C22.1.
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
7Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 8
Note: The following requirements reference various Massachuset ts and national codes not contain ed in this document.
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addi­tion, the installing plumber or gas fi tter shall observe that a battery operated or hard wired carbon monoxide detec­tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fu­eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur­ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Inspection
The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob­serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fu-
eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro­vide the parts for venting the fl ue gases, but identifi es “special venting systems”, the following requirements shall be satisfi ed by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor­dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu­eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB­STRUCTIONS”.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/128
• The referenced “special venting system” instructions
shall be included with the appliance or equipment in­stallation instructions; and
• The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that sys­tem shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Ap­proved side wall horizontally vented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Common­wealth of Massachusetts requirements.
Page 9
2
2
Operating Instructions
User Guide
A. Gas Fireplace Safety
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
If you expect that small children or vulnerable adults may come into contact with this fi replace, the following precau- tions are recommended:
• Install a physical barrier such as:
- A decorative fi rescreen.
- Adjustable safety gate.
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
• Never leave children alone near a hot fi replace, whether operating or cooling down.
• Teach children to NEVER touch the fi replace.
• Consider not using the fi replace when children will be present.
Contact your dealer for more information, or visit:www. hpba.org/safety-information.
T o prevent unintended operation when not using your fi re- place for an extended period of time (summer months, vacations, trips, etc):
• Remove batteries from remote controls.
• Turn off wall controls.
• Unplug 3 volt adapter plug and remove batteries on IPI models.
B. Your Fireplace
WARNING! DO NOT operate fi replace before read- ing and understanding operating instructions. Failure
to operate fi replace according to operating instructions could cause fi re or injury.
Figure 2.1 General Operating Parts
DECORATIVE DOORS
(NOT SHOWN)
SECTION 2.E.
CLEAR SPACE
SECTION 2.D.
FIXED GLASS ASSEMBLY
SECTION 14.G.
HEARTH
MANTEL
9Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 10
C. Fan Kit (optional)
If desired, a fan kit may be added. Contact your dealer to order the correct fan kit.
D. Clear Space
WARNING! DO NOT place combustible objects in front of the fi replace or block louvers. High temperatures may start a fi re. See Figure 2.2.
A void placing candles and other heat-sensitive objects on mantel or hearth. Heat may damage these objects.
3 FT. IN FRONT OF FIREPLACE
CLEAR SPACE
Figure 2.2 Clear Space
F. Fixed Glass Assembly
See Section 14.G.
G. Remote Controls, Wall Controls and Wall
Switches
Follow the instructions supplied with the control installed to operate your fi replace:
For safety:
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
See your dealer if you have questions.
H. Before Lighting Fireplace
Before operating this replace for the rst time, have a qualifi ed service technician:
• Verify all shipping materials have been removed from inside and/or underneath the fi rebox.
• Review proper placement of logs, ember material and/or other decorative materials.
• Check the wiring.
• Check the air shutter adjustment.
• Ensure that there are no gas leaks.
• Ensure that the glass is sealed and in the proper position and that the integral barrier is in place.
WARNING! Risk of Fire or Asphyxiation! DO NOT op­erate fi replace with fi xed glass assembly removed.
E. Decorative Doors and Fronts
WARNING! Risk of Fire! Install ONLY doors or fronts approved by Hearth & Home Technologies. Unapproved doors or fronts may cause fi replace to overheat.
This fireplace has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the fi replace with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
For more information refer to the instructions supplied with your decorative door or front.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1210
Page 11
I. Lighting Instructions (IPI)
The IPI system may be operated with two D-cell batteries. When using batteries, unplug the transformer. To prolong battery life, remove them when using the transformer.
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a re or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an
intermittent pilot ignition (IPI) device which automatically lights the burn­er. DO NOT try to light the burner by hand.
B. BEFORE LIGHTING, smell all around
the appliance area for gas. Be sure to smell next to the fl oor because some gas is heavier than air and will settle on the fl oor.
WHA T TO DO IF YOU SMELL GAS
DO NOT try to light any appliance.
DO NOT touch any electric switch; do not use any phone in your building.
WARNING:
DO NOT CONNECT LINE VOLT­AGE (110/120 VAC OR 220/240 V AC) TO THE CONTROL VALVE.
Improper installation, adjustment, al­teration, service or maintenance can cause injury or property damage. Re­fer to the owner’s information manual provided with this appliance.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
If not installed, operated, and main­tained in accordance with the manufac­turer’s instructions, this product could expose you to substances in fuel or fuel combustion which are known to the State of California to cause can­cer, birth defects, or other reproductive harm.
Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
For additional information on operating your
Hearth & Home Technologies fi replace, please refer to www.fi replaces.com.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas sup­plier, call the fi re department.
C. DO NOT use this appliance if any
part has been under water. Imme­diately call a qualifi ed service tech- nician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
CAUTION:
Hot while in operation. DO NOT touch. Keep children, clothing, furniture, gaso­line and other liquids having fl ammable vapors away.
DO NOT operate the appliance with xed glass assembly removed, cracked or broken. Replacement of the fi xed glass assembly should be done by a licensed or qualifi ed service person.
NOT FOR USE
WITH SOLID FUEL
For use with natural gas and propane. A conversion kit, as supplied by the manufacturer, shall be used to convert this appliance to the alternate fuel.
Also Certifi ed for Installation in a Bedroom or a Bedsitting Room.
For assistance or additional informa­tion, consult a qualifi ed installer, ser- vice agency or the gas supplier.
LIGHTING
INSTRUCTIONS (IPI)
1. This appliance is equipped with an ignition
device which automatically lights the burner.
DO NOT try to light the burner by hand.
GAS
VALVE
2. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the fl oor. If you smell gas, STOP! Follow “B” in the Safety Information located on the left side of this la­bel. If you do not smell gas, go to next step.
3. To light the burner: Equipped with wall switch: Turn ON/OFF switch
to ON.
Equipped with remote or wall control: Press
ON or FLAME button.
Equipped with thermostat: Set temperature to
desired setting.
4. If the appliance does not light after three tries, call your service technician or gas supplier.
TO TURN OFF
GAS TO APPLIANCE
1. Equipped with wall switch: Turn ON/OFF switch
to OFF.
Equipped with remote or wall control: Press
OFF button.
Equipped with thermostat: Set temperature to
lowest setting.
2. Service technician should turn off electric power to the control when performing service.
593-913G
Final inspection by
11Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 12
J. After Fireplace is Lit
Initial Break-in Procedure
• The fireplace should be run three to four hours continuously on high.
• Turn the fi replace off and allow it to completely cool.
• Remove fi xed glass assembly. See Section 14.G.
• Clean fi xed glass assembly. See Section 3.
• Replace the fi xed glass assembly and run continuously on high an additional 12 hours.
This cures the materials used to manufacture the fi re- place.
NOTICE! Open windows for air circulation during fi re- place break-in.
• Some people may be sensitive to smoke and odors.
• Smoke detectors may activate.
K. Frequently Asked Questions
ISSUE SOLUTIONS
Condensation on the glass
Blue fl ames
Odor from fi replace
Film on the glass
Metallic noise
This is a result of gas combustion and temperature variations. As the fi replace warms, this condensation will disappear.
This is a result of normal operation and the fl ames will begin to yellow as the fi replace is al- lowed to burn for 20 to 40 minutes.
When fi rst operated, this fi replace may release an odor for the fi rst several hours. This is caused by the curing of materials from manufacturing. Odor may also be released from nishing materials and adhesives used near the fi replace. These circumstances may require additional curing related to the installation environment.
This is a normal result of the curing process of the paint and logs. Glass should be cleaned within 3 to 4 hours of initial burning. A non-abrasive cleaner such as gas fi replace glass cleaner may be necessary. See your dealer.
Noise is caused by metal expanding and contracting as it heats up and cools down, similar to the sound produced by a furnace or heating duct. This noise does not affect the operation or longevity of the fi replace.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1212
Page 13
3
3
Maintenance and Service
Any safety screen or guard removed for servicing must be replaced prior to operating the fi replace.
When properly maintained, your fi replace will give you many years of trouble-free service. We recommend an­nual service by a qualifi ed service technician.
A. Maintenance Tasks-Homeowner
Installation and repair should be done by a qualifi ed service technician only. The fi replace should be inspected before use and at least annually by a professional service person.
The following tasks may be performed annually by the homeowner. If you are uncomfortable performing any of the listed tasks, please call your dealer for a service ap­pointment.
More frequent cleaning may be required due to lint from carpeting or other factors. Control compartment, burner and circulating air passageway of the fi replace must be kept clean.
CAUTION! Risk of Burns! The fi replace should be turned off and cooled before servicing.
Glass Cleaning
Frequency: Seasonally By: Homeowner Tools Needed: Protective gloves, glass cleaner, drop
cloth and a stable work surface.
CAUTION! Handle fi xed glass assembly with care.
Glass is breakable.
• Avoid striking, scratching or slamming glass
• Avoid abrasive cleaners
DO NOT clean glass while it is hot
• Prepare a work area large enough to accommodate fi xed glass assembly and door frame by placing a drop cloth on a fl at, stable surface.
Note: Fixed glass assembly and gasketing may have res­idue that can stain carpeting or fl oor surfaces.
• Remove door or decorative front from fi replace and set aside on work surface.
• See Section 14.G for instructions to remove fi xed glass assembly.
• Clean glass with a non-abrasive commercially available cleaner.
- Light deposits: Use a soft cloth with soap and water
- Heavy deposits: Use commercial fireplace glass
cleaner (consult with your dealer)
• Carefully set fi xed glass assembly in place on fi replace. Hold glass in place with one hand and secure glass latches with the other hand.
• Reinstall door or decorative front.
Doors, Surrounds, Fronts
Frequency: Annually By: Homeowner Tools needed: Protective gloves, stable work surface
• Assess condition of screen and replace as necessary.
• Inspect for scratches, dents or other damage and repair as necessary.
• Check that louvers are not blocked.
• Vacuum and dust surfaces.
Remote Control
Frequency: Seasonally By: Homeowner Tools needed: Replacement batteries and remote con-
trol instructions.
• Locate remote control transmitter and receiver.
• Verify operation of remote. Refer to remote control operation instructions for proper calibration and setup procedure.
• Place batteries as needed in remote transmitters and battery-powered receivers.
• Place remote control out of reach of children.
If not using your fi replace for an extended period of time (summer months, vacations/trips, etc), to prevent unin­tended operation:
• Remove batteries from remote controls.
• Unplug 3 volt adapter plug on IPI models.
13Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 14
Venting
Frequency: Seasonally By: Homeowner Tools needed: Protective gloves and safety glasses.
• Inspect venting and termination cap for blockage or obstruction such plants, bird nests, leaves, snow, debris, etc.
• Verify termination cap clearance to subsequent construc­tion (building additions, decks, fences, or sheds). See Section 6.
• Inspect for corrosion or separation.
• Verify weather stripping, sealing and fl ashing remains intact.
• Inspect draft shield to verify it is not damaged or missing.
B. Maintenance Tasks-Qualifi ed Service
Technician
The following tasks must be performed by a qualifi ed ser- vice technician.
Gasket Seal and Glass Assembly Inspection
Frequency: Annually By: Quali ed Service Technician T ools needed: Protective gloves, drop cloth and a stable
work surface.
• Inspect gasket seal and its condition.
• Inspect fi xed glass assembly for scratches and nicks that can lead to breakage when exposed to heat.
• Confi rm there is no damage to glass or glass frame. Replace as necessary.
• Verify that fi xed glass assembly is properly retained and attachment components are intact and not damaged. Replace as necessary.
Logs
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves.
• Inspect for damaged or missing logs. Replace as necessary. Refer to Section 14 for log placement instructions.
• Verify correct log placement and no fl ame impingement causing sooting. Correct as necessary.
Firebox
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves, sandpaper, steel wool,
cloths, mineral spirits, primer and touch-up paint.
• Inspect for paint condition, warped surfaces, corrosion or perforation. Sand and repaint as necessary.
• Replace fi replace if fi rebox has been perforated.
Control Compartment and Firebox Top
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves, vacuum cleaner, dust
cloths
• V acuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.
• Remove all foreign objects.
• Verify unobstructed air circulation.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1214
Page 15
Burner Ignition and Operation
Frequency: Annually By: Quali ed Service Technician T ools needed: Protective gloves, vacuum cleaner, whisk
broom, fl ashlight, voltmeter, indexed drill bit set, and a manometer.
• Verify burner is properly secured and aligned with pilot or igniter.
• Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if necessary.
• Replace ember materials with new dime-size pieces. DO NOT block ports or obstruct lighting paths. Refer to Section 14 for proper ember placement.
• Verify batteries have been removed from battery back­up IPI systems to prevent premature battery failure or leaking.
• Check for smooth lighting and ignition carryover to all ports. Verify that there is no ignition delay.
• Inspect for lifting or other fl ame problems.
• Verify air shutter setting is correct. See Section 14 for required air shutter setting. Verify air shutter is clear of dust and debris.
• Inspect orifi ce for soot, dirt and corrosion. Verify orifi ce size is correct. See Service Parts List for proper orifi ce sizing.
• Verify manifold and inlet pressures. Adjust regulator as required.
• Inspect pilot fl ame pattern and strength. See Figure 3.2 for proper pilot fl ame pattern. Clean or replace orifi ce spud as necessary.
• Inspect IPI fl ame sensing rod for soot, corrosion and deterioration. Polish with fi ne steel wool or replace as required.
• Verify that there is not a short in fl ame sense circuit by checking continuity between pilot hood and fl ame sense rod. Replace pilot as necessary.
Figure 3.2 IPI Pilot Flame Patterns
15Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 16
4
4
A. Typical Appliance System
NOTICE: Illustrations and photos refl ect typical installations and are for design purposes only . Illustrations/diagrams are not drawn to scale. Actual product may vary from pictures in manual
Getting Started
HORIZONTAL
TERMINATION CAP
(SECTION 8.A)
NON-COMBUSTIBLE ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE (SECTION 10.C)
VERTICAL TERMINATION CAP
(SECTION 10.C)
STORM COLLAR (SECTION 10.C)
VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS (SECTION 8.C )
Installer Guide
FRAMING/HEADER (SECTION 5.B)
GAS LINE
(SECTION 11.C)
OPTIONAL
WALL SWITCH
ATTIC INSULATION SHIELD (NOT SHOWN) MUST BE USED HERE TO KEEP INSULATION AWAY FROM VENT PIPE IF ATTIC IS INSULATED (SECTION 8.D )
VENT PIPE (SECTION 8 and 10)
FRAMING HEADED OFF IN CEILING JOISTS (SECTION 8.C)
CEILING FIRESTOP ON FLOOR OF ATTIC (SECTION 8.C)
Figure 4.1 Typical System
HEARTH EXTENSION
SURROUND
MANTEL AND MANTEL LEG (SECTION 5.D)
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1216
Page 17
B. Design and Installation Considerations
Heatilator direct vent gas appliances are designed to op­erate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and regulations. Consult insurance carrier, local building inspector, fi re offi cials or authorities having jurisdiction over restrictions, installation inspection and permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping.
• Electrical wiring requirements.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a fan, wall switch, or remote control—are desired.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualifi ed service technician, service agency or your dealer.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Tape measure Framing material Pliers Non-corrosive leak check solution Hammer Phillips screwdriver Gloves Framing square Voltmeter Electric drill and bits (1/4 in.) Plumb line Safety glasses Level Reciprocating saw Manometer Flat blade screwdriver 1/2 - 3/4 in. length, #6 or #8 Self-drilling screws One 1/4 in. female connection (for optional fan). Caulking material (300ºF minimum continuous exposure
rating)
D. Inspect Appliance and Components
• Carefully remove the appliance and components from the packaging.
• The vent system components and decorative doors and fronts may be shipped in separate packages.
• If packaged separately, the log set and appliance grate must be installed.
• Report to your dealer any parts damaged in shipment, particularly the condition of the glass.
Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the installation to ensure maximum safety and benefi t.
WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation. DO NOT install damaged, in- complete or substitute components. Keep appliance dry.
Hearth & Home T echnologies disclaims any responsibility for , and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent
system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock! DO NOT use this appliance if any part has been under
water. Call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and/or gas control which has been under water.
17Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 18
5
5
Framing and Clearances
A. Selecting Appliance Location
When selecting a location for the appliance it is important to consider the required clearances to walls (see Figure 5.1).
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access.
Due to high temperatures, the appliance should be locat­ed out of traffi c and away from furniture and draperies.
NOTICE: Illustrations re ect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation may vary due to individual design preference.
36 in.
914 mm
GDST3831I
36 in.
914 mm
Figure 5.1 Appliance Locations
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1218
Page 19
B. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should enclosed inside the chase.
NOTICE: Treatment of ceiling restops and wall shield restops and construction of the chase may vary with the
type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, you MUST check local building codes to determine the requirements to these steps.
Chases should be constructed in the manner of all out­side walls of the home to prevent cold air drafting prob­lems. The chase should not break the outside building envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase should be insulated. Vapor and air infi ltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infi ltration may be an issue, the inside surfaces may be sheetrocked and taped for maximum air tightness.
To further prevent drafts, the wall shield and ceiling fi re- stops should be caulked with caulk with a minimum of 300ºF continuous exposure rating to seal gaps. Gas line holes and other openings should be caulked with caulk with a minimum of 300ºF continuous exposure rating or stuffed with unfaced insulation. If the appliance is being installed on a cement slab, a layer of plywood may be placed underneath to prevent conducting cold up into the room.
C. Clearances
NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, tile or any combustible material other than wood.
WARNING! Risk of Fire! Maintain specifi ed air space clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent accidental contact.
• The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fi replace or chimney.
• Failure to maintain airspace may cause overheating and a fi re.
HEADER
A
*C
D
GDST3831I
Inches
Millimeters
Note: The header must be installed on end as
A
B
shown in this diagram.
E
I
F
G
H
MINIMUM FRAMING DIMENSIONS
AB *C D E F G H I
Rough
Opening
(Width)
8-5/8 34-3/4 15 38-1/8 31 0 0 1/2 36
Rough
Opening
(Height)
219 883 381 969 787 0 0 13 914
Rough
Opening
(Depth)
Rough
Opening
(Width)
Clearance
to Ceiling
Combustible
Floor
Combustible
Flooring
Ends of
Appliance
Sides of
Appliance
* Adjust framing dimensions for interior sheathing (such as sheetrock)
Figure 5.2 Clearances to Combustibles GDST3831I
19Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 20
D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear­ances as specifi ed. Framing or fi nishing material closer than the minimums listed must be constructed entirely of noncom­bustible materials (i.e., steel studs, concrete board, etc).
TOP VIEW
1/2 in.
Min.
Note: All measurements in inches.
MAX.
12
11
10
9
8
7
6
5
4
3
6
5
4
TOP OF HOOD OR FIREPLACE OPENING
9
8
7
10
11
CEILING
13
12
Figure 5.3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles
FIREPLACE
OPENING
Note: Clearance from opening to perpendicular wall.
Figure 5.5 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)
32
MIN.
3-1/4 in.
SHEETROCK
3.5 in.
Min.
Unlimited
Note: All measurements in inches.
MAX.
10
9
8
7
6
5
4
TOP OF HOOD OR FIREPLACE OPENING
3
2
1
CEILING
18
12
11
32
MIN.
14
8
7
6
5
4
Figure 5.4 Minimum Vertical and Maximum Horizontal Dimensions of Non-Combustibles
AIR SPACE REQUIRED
Figure 5.6 Non-Combustible Zone
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1220
Page 21
6
6
Termination Locations
A. Vent Termination Minimum Clearances
WARNING
Fire Risk. Maintain vent clearance to combustibles as
specifi ed.
DO NOT pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause overheating and fi re.
HORIZONTAL
OVERHANG
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
IS X/ 12
VERTICAL
WALL
6 in. (minimum) up to 20 in.
AB
152 mm/508 mm
20 in. and over 0 in. minimum
18 in. minimum
457 mm
Gas, Wood or Fuel Oil
Termination Cap
B
A *
Gas
Termination
Cap **
If using decorative cap cover(s), t his distance may need to be
*
increased. Refer to the installation instructions supplied with the decorative cap cover.
In a staggered installation with both gas and wood or fuel oil
**
terminations, the wood or fuel oil termination cap must be higher than the gas termination cap.
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
* 3 foot minimum in snow regions
Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening
Figure 6.2 Staggered Termination Caps
21Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 22
O
N
P
C
V
B
J
V
V
= VENT TERMINAL
X
= AIR SUPPLY INLET
B
D
V
V
V
A
F
B
G
M
V
H or i
V
X
H
V
H
E
V
V
A
= AREA WHERE TERMINAL IS NOT PERMITTED
R
Q
V
L
K
Electrical
V
Service
C
V
K
V
A = 12 inches.................clearances above grade, veranda,
porch, deck or balcony
12 inches.................clearance to window or door that may
B =
be opened, or to permanently closed window
C = 18 inches.................clearance below unventilated soffi t
18 inches.................clearance below ventilated soffi t
30 inches .................clearance below vinyl soffits and
electrical service
D = 6 inches...................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas me-
ter/regulator assembly within 3 feet
horizontally from the center-line of the
regulator
G = 3 ft ...........................clearance to gas service regulator
vent outlet H = 9 inches (U.S.A)
12 inches (Canada). clearance to non-mechanical (unpow-
ered) air supply inlet, combustion air
inlet or direct-vent termination i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (powered)
air supply inlet All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below termination.
J = 7 ft. ......................... On public property: clearance above
paved sidewalk or a paved driveway. A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and serves both dwellings.
K = 6 inches................. clearance from sides of electrical
service
L = 12 inches................ clearance above electrical service
Location of the vent termination must not interfere with access to the electrical service.
M =
18 inches ....................clearance under veranda, porch, deck,
balcony or overhang
42 inches ................vinyl or composite overhang
Permitted when veranda, porch, deck or balcony is fully open
on a minimum of 2 sides beneath the fl oor.
Figure 6.3 Minimum Clearances for Termination
Covered Alcove Applications
(Spaces open only on one side and with an overhang)
N = 6 inches ........... non-vinyl sidewalls
12 inches ......... vinyl sidewalls
O = 18 inches ......... non-vinyl soffi t and overhang
42 inches ......... vinyl soffi t and overhang
P = 8 ft.
Q
MIN
1 cap 3 feet 2 x Q 2 caps 6 feet 1 x Q 3 caps 9 feet 2/3 x Q 4 caps 12 feet 1/2 x Q
Q
= # termination caps x 3 R
MIN
Measure vertical clearances from this surface.
Measure horizontal clearances from this surface.
= (2 / # termination caps) x Q
MAX
R
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL
ACTUAL
CAUTION! Risk of Burns! Termination caps are HOT, consider proximity to doors, traffi c areas or where people may pass or gather (sidewalk, deck, patio, etc.). Listed cap shields available. Contact your dealer.
• Local codes or regulations may require different clearances.
• Vent system termination is NOT permitted in screened porches.
• Vent system termination is permitted in porch areas with two or more sides open.
• Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
• Vinyl protection kits are suggested for use with vinyl siding.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1222
Page 23
B. Continue Adding Vent Components
COMBUSTIBLE SURFACE
DIRECTION
UP
HEAT SHIELD
90º ELBOW
WARNING! Risk of Fire! Installation of this appliance may require the use of heat shield 385-290 above the rst 90º elbow in the venting system.
To Install the Heat Shield:
1. Determine if the heat shield is required. Do so by measuring the vertical distance between the top horizontal surface of the elbow to any combustible surface above. If the distance is more than 4 inches, the heat shield is NOT required. If it is 4 inches or less, the heat shield IS REQUIRED. Install per the following steps. See Figure 6.4.
COMBUSTIBLE
SURFACE
CORRECT INCORRECT
Figure 6.5
• If the combustible materials are not in place at the time of install, the elbow heat shield may be screwed to the exhaust pipe (see Figure 6.6). Cut the tabs as shown and bend down. Secure the heat shield to the pipe maintain­ing 3 inch to 4 inch between the pipe and shield.
3 in. MIN.
HEAT
SHIELD
Figure 6.4
(76 mm)
2. Fasten the shield in place using the four pilot holes provided in the part. The shield should be oriented such that the 13-1/8 inch dimension (longest dimension) is running in the same direction the elbow is pointing. The shield should be centered directly above the elbow, and positioned so that it creates a 1/2 inch airspace between the shield and the combustible surface. See Figure 6.5.
SCREW
3 in.
(76 mm)
Figure 6.6
Refer to Cinch Pipe and Termination Cap installation in­structions.
• Continue adding vent components, locking each suc­ceeding component into place.
• Ensure that each succeeding vent component is securely tted and locked into the preceding component in the vent system.
• 90º elbows may be installed and rotated to any point around the preceding component’s vertical axis. If an elbow does not end up in a locked position with the preceding component, attach with a minimum of two (2) sheet metal screws.
C. Install Support Brackets
Refer to cinch pipe and termination cap installation in­structions.
23Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 24
7
7
Vent Information and Diagrams
A. Approved Pipe
This appliance is approved for use with Hearth & Home Technologies a SLP venting system. Refer to Section 16B for vent component information.
DO NOT mix pipe, fi ttings or joining methods from differ- ent manufacturers.
The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli­ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.
Vertical
12 in.
8-1/2 in.
8-1/2 in.
B. Vent Table Key
The abbreviations listed in this vent table key are used in the vent diagrams.
Symbol Description
V
V H H
First section (closest to appliance) of vertical length
1
Second section of vertical length
2
First section (closest to appliance) of horizontal length
1
Subsequent sections of horizontal length
2
C. Use of Elbows
Diagonal runs have both vertical and horizontal vent as­pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows (see Figure 7.1).
Horizontal
Figure 7.1
D. Measuring Standards
Vertical and horizontal measurements listed in the vent diagrams were made using the following standards.
• Pipe measurements are shown using the effective length of pipe (see Figure 7.2).
• Horizontal terminations are measured to the outside mounting surface (fl ange of termination cap) (see Figure
6.1).
• Vertical terminations are measured to bottom of termination cap.
• Horizontal pipe installed level with no rise.
Effective Height/Length
Pipe inchesmm
SLP4 4 102 SLP6 6 152
SLP12 12 305
Effective
Height/ Length
SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 - 6 51 - 152
SLP12A 2 - 12 51 - 305 SLP-FLEX-2 24 610 SLP-FLEX-3 36 914 SLP-FLEX-5 60 1524 SLP-FLEX-10 120 3048
Figure 7.2 SLP Pipe Effective Length
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1224
Page 25
E. Use of Flex Vent
The fl ex vent must be supported with the spacing between support intervals not exceeding 4 feet, with no more than 1/2 inch sag between supports.
A support is required at each change in venting direction, and in any location where it is necessary to maintain the necessary clearance to combustibles. A simple “up and out” installation (Figure 7.3) requires only enough sup­port to maintain the necessary clearance to combustibles. However, the vent attachment point and the fi restop loca- tion are considered to be supports.
3 in. CLEARANCE
FLEX VENT
Figure 7.3
TERMINATION CAP
1 in. CLEARANCE
25Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 26
F. Vent Diagrams
General Rules:
• SUBTRACT 3 ft. from the total H measurement for each 90° elbow installed horizontally.
• SUBTRACT 1-1/2 ft. from the total H measurement for each 45° elbow installed horizontally.
• A maximum of three 90° elbows (or six 45° elbows) may be used in any vent confi guration. Some elbows may be installed horizontally. See Figure 7.6.
• Elbows may be placed back to back anywhere in the system as long as the fi rst 90° elbow is a starter elbow.
• When penetrating a combustible wall, a wall shield restop must be installed.
• When penetrating a combustible ceiling, a ceiling fi restop must be installed.
• Horizontal runs of vent do not require vertical rise; horizontal runs may be level.
1. Top Vent - Horizontal Termination
One Elbow
WARNING**
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-SS termination caps on top vented fi replaces, a one foot minimum vertical vent section is required before
installing fi rst elbow
• When using DVP-TB1 termination cap on top vented replaces, a three foot minimum vertical vent section is required before installing fi rst elbow.
• When using any other cap, a section of vertical pipe (12 inches minimum) MUST be installed prior to attaching a 90° elbow.
Note: There MUST be a 25% reduction in total H when using ex vent except when using the simple up and out installation (see Figure 7.3).
.
H
1
V1 Minimum** H1 Maximum
90 Elbow** 2 ft. 610 mm
1/2 ft.** 152 mm 2 ft. 610 mm 1-1/2 ft.** 457 mm 3 ft. 914 mm 2-1/2 ft.** 762 mm 5 ft. 1.5 m
3-1/2 ft. 1.1 m 7 ft. 2.1 m
4-1/2 ft. 1.4 m 14 ft. 4.3 m
H
Max. =14 ft. (4.3 m)
1
V + H Max. = 40 ft. (12.2 m)
See Warning**
V
1
Figure 7.4
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1226
Page 27
1. Top Vent - Horizontal Termination - (continued) Two Elbows
WARNING**
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-SS termination caps on top vented fi replaces, a one foot minimum vertical vent section is required before
installing fi rst elbow.
• When using DVP-TB1 termination cap on top vented replaces, a three foot minimum vertical vent section is required before installing fi rst elbow.
• When using any other cap, a section of vertical pipe (12 inches minimum) MUST be installed prior to attaching a 90° elbow.
Note: There MUST be a 25% reduction in total H when using ex vent except when using the simple up and out installation (see Figure 7.3).
V1 Minimum** H1 + H2 Maximum
90 Elbow** 1/2 ft. 152 mm
1/2 ft.** 152 mm 1 ft. 305 mm 1-1/2 ft.** 457 mm 2 ft. 610 mm 2-1/2 ft.** 762 mm 4 ft. 1.2 m
3-1/2 ft. 1.1 m 6 ft. 1.8 m
4-1/2 ft. 1.4 m 14 ft. 4.3 m
+ H2 Max. =14 ft. (4.3 m)
H
1
V1 + H1 + H2 Max. = 40 ft. (12.2 m)
See Warning**
Figure 7.5
H
V
1
2
H
1
INSTALLED
HORIZONTALLY
27Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 28
1. Top Vent - Horizontal Termination - (continued)
Three Elbows
Note: There MUST be a 25%
reduction in total H when using ex vent except when using the simple up and out installation (see Figure 7.3).
V1 Minimum** H1 + H2 Maximum V
2
V1 + V2 Min.
90 Elbow** 2 ft. 610 mm * *
1/2 ft.** 152 mm 6 ft. 1.8 m * * 1-1/2 ft.** 457 mm 10 ft. 3 m * * 2-1/2 ft.** 762 mm 12 ft. 3.7 m * *
3-1/2 ft. 1.1 m 14 ft. 4.3 m * *
H
+ H2 Max. =14 ft. (4.3 m)
1
*No specifi c restrictions on this value
EXCEPT V
+ V2 + H1 + H2 cannot exceed 40 ft. (12.2 m)
1
See Warning Below**
H
2
V
2
WARNING**
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-SS termination caps on top vented fi replaces, a one foot minimum vertical vent section is required before
installing fi rst elbow.
• When using DVP-TB1 termination cap on top vented replaces, a three foot minimum vertical vent section is required before installing fi rst elbow.
• When using any other cap, a section of vertical pipe (12 inches minimum) MUST be installed prior to attaching a 90° elbow.
V
1
H
1
Figure 7.6
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1228
Page 29
2. Top Vent - Vertical Termination No Elbow
Note: Use SLP Series
components only.
Note: If installing a vertical vent/termination of f the top of the appliance, the exhaust restrictor may be needed.
V1 = 3 ft. Min. (914 mm) V1 = 50 ft. Max (15 m)
Exhaust restrictor Instructions
1. Center the exhaust restrictor in the open end of the ex­haust outlet and secure through the slots on the exhaust restrictor with the 2-1/4 in. self tapping screws provided in the appliance manual bag.
EXHAUST
RESTRICTOR
V
1
Figure 7.7
Exhaust restrictors are recommended for these verti­cally terminated products which have excessive draft. Exhaust restrictors will compensate for high draft, and restore visual fl ame height. If the vent confi guration has a total vertical of 15-50 feet, an exhaust restrictor may be needed. The exhaust restrictor can be located in the appliance manual bag.
Figure 7.8
29Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 30
Two Elbows
V1 Minimum H Maximum V
2
V1 + V2 Min.
90 Elbow 1-1/2 ft. 457 mm * *
1/2 ft. 152 mm 2 ft. 610 mm * * 1-1/2 ft. 457 mm 3 ft. 914 mm * * 2-1/2 ft. 762 mm 5 ft. 1.5 m * * 3-1/2 ft. 1.1 m 7 ft. 2.1 m * * 4-1/2 ft. 1.4 m 15 ft. 4.6 m * *
V
2
H
1
* No specifi c restrictions on this value EXCEPT V
V
1
H Max. =15 ft. (4.6 m)
+ V2 + H1 cannot exceed 40 ft. (12.2 m)
1
Figure 7.9
Three Elbows
H
2
V1 Minimum H1 + H2 Maximum V
2
V1 + V2 Min.
90 Elbow 1/2 ft. 152 mm * *
1/2 ft. 152 mm 1 ft. 305 mm * * 1-1/2 ft. 457 mm 2 ft. 610 mm * * 2-1/2 ft. 762 mm 4 ft. 1.2 m * * 3-1/2 ft. 1.1 m 6 ft. 1.8 m * * 4-1/2 ft. 1.4 m 14 ft. 4.3 m * *
V
2
* No specifi c restrictions on this value EXCEPT V1 + V2 + H1 + H2 cannot exceed 40 ft. (12.2 m)
H
1
H
+ H2 MAX. =14 ft. (4.6 m)
1
V
1
Figure 7.10
INSTALLED
HORIZONTALLY
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1230
Page 31
8
8
Vent Clearances and Framing
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles:
• Between ceiling fi restops
• Between wall shield fi restops
• Around vent system Failure to keep insulation or other material away from
vent pipe may cause overheating and fi re.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8
in. (111 mm to 194 mm thick).
• If wall thickness is less than 4-3/8 the existing heat shields must be
field trimmed. If wall thickness is greater than 7-5/8 in. a DVP­HSM-B will be required.
2-1/2 in. (64 mm) top clearance at
wall shield firestops
3 in. (76 mm) top clearance
1 in. (25 mm) clearance around vertical sections
Wall
Shield
Firestop
1 in. (25 mm) clearance bottom and sides
Figure 6.1 Horizontal venting clearances to combustible
materials
Heat
Shields
1/2 in. (13 mm) bottom clearance at wall shield firestops
WALL
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must frame a hole for the wall shield fi restop. The wall shield restop maintains minimum clearances and prevents cold air infi ltration.
• The opening must be framed on all four sides using the same size framing materials as those used in the wall construction.
• SLP pipe - A wall shield fi restop must be placed on each side of an interior wall. A minimum 1-1/2 in. (38 mm) overlap of attached heat shields must be maintained.
• See Section 10.L. for information for regarding the in­stallation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom­bustible materials such as concrete, a hole with diameter one in. greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall shield fi restop is only required on one side and no heat shield is necessary.
10 in.
10 in.
B
A*
A* B
38-7/8 in. 37-7/8 in.
* Shows center of vent framing hole for top venting. The center of the hole is
one (1) inch (25.4 mm) above the center of the horizontal vent pipe.
Figure 8.2 Wall Penetration
31Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 32
C. Install the Ceiling Firestop
A ceiling restop MUST be used between oors and attics.
• Frame opening 9 in. x 9 in. (229 mm x 229 mm) whenever the vent penetrates a ceiling/ oor (see Figure 8.3).
• Frame the area with the same sized lumber as used in ceiling/fl oor joist.
• The ceiling fi restop may be installed above or below the ceiling joists when installed with a attic insulation shield. It must be under joists between fl oors that are not insulated. Refer to Figure 8.4.
• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu­lation around the vent. Insulation must be kept back from the pipe to prevent overheating.
ATTIC ABOVE
A
A
Figure 8.3 Installing Ceiling Firestop
INSTALL ATTIC INSULATION SHIELDS
BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
3 FASTENERS
PIPE SLP
PER SIDE
A
9 in. (229 mm)
CEILING FIRESTOP
INSTALLED BELOW CEILING
Figure 8.4 Installing the Attic Shield
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1232
CEILING FIRESTOP
INSTALLED ABOVE CEILING
Page 33
D. Install Attic Insulation Shield
WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies Inc. requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet specifi ed clearance and be se- cured in place.
Flat Ceiling Installation
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.
• Wrap shield around pipe if pipe is already installed in area to be insulated.
• Match the three holes in each side and fasten with three screws to form a tube.
• Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling fi restop.
• Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.
BEND ALL TABS INWARD 90° TO MAINTAIN CLEARANCE AND PREVENT INSULATION FROM FALLING INSIDE
INSERT 3 SCREWS
Figure 8.5 Attic Insulation Shield
LASER-ETCHED CUT LINES
BEND 3 TABS OUTWARD TO FASTEN TO CEILING FIRESTOP-BEND REMAINING TABS INWARD 90 DEGREES TO MAINTAIN CLEARANCE
Vaulted Ceiling Installation
• The attic insulation shield has been laser-etched with cut lines and ceiling pitches to make fi eld trimming easier.
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.
• Cut the attic insulation shield (if application is for vaulted ceiling) using a laser-etched cut line, to fi t your ceiling pitch. Snip cut edge to recreate 1 in. bend tabs all the way around the bottom.
• Wrap shield around pipe if pipe is already installed in area to be insulated.
• Match the three holes in each side and fasten with three screws to form a tube.
• Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling fi restop.
• Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.
33Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 34
9
9
Appliance Preparation
A. Securing and Leveling the Appliance
WARNING! Risk of Fire! Prevent contact with:
• Sagging or loose insulation
• Insulation backing or plastic
• Framing and other combustible materials Block openings into the chase to prevent entry of blown-
in insulation. Make sure insulation and other materials are secured.
DO NOT notch the framing around the appliance standoffs.
Failure to maintain air space clearance may cause overheating and fi re.
NOTICE: Failure to ensure that the fi replace opening is square may result in the decorative front not fi tting properly.
The diagram shows how to properly position, level, and secure the appliance (see Figure 9.1). Nailing tabs are pro­vided to secure the appliance to the framing members.
1. Venting - refer to V ent Clearances and Framing (Section
8) for hole location.
2. Place the appliance into position, making sure to
maintain proper clearance to combustibles.
3. Level the appliance from side to side and front to back. It
is acceptable to use wood shims under the appliance.
4. Fasten the appliance to the fl oor using the pilot holes
located at the bottom of the appliance.
5. Bend out nailing tabs on each side making sure to keep
the nailing tabs fl ush with the framing.
6. Using a framing square, make sure that the sides of
the appliance are square to the bottom as shown in Figure 9.2.
7. Secure the appliance to the framing by using nails
or screws through the nailing tabs. It is acceptable to use plumber strap to secure the unit to the framing if necessary. Be sure to maintain all clearances to combustible material.
NAILING TABS
Figure 9.1 Securing An Appliance
90º
SIDE TO SIDE
FRONT TO BACK
Figure 9.2 Proper Positioning and Leveling of an Appliance
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1234
Page 35
10
10
Installing Vent Pipe
A. Assemble Vent Sections
To attach the fi rst vent component to the starting collars of the appliance:
• Lock the vent components into place by sliding the pipe section onto the collar.
• Align the seam of the pipe and seam of collar to allow engagement. Rotate the vent component to lock into place. Use this procedure for all vent components. See Figure 10.1.
• Slide the gasket over the fi rst vent section and place it ush to the appliance. This will prevent cold air infi ltration. Caulk with a minimum of 300ºF continuous exposure rating may be used to hold the part in place.
• Continue adding vent components, locking each succeeding component into place.
• Ensure that each succeeding vent component is securely tted and locked into the preceding component.
Commercial, Multi-family (Multi-level exceeding two sto­ries), or High-Rise Applications
For Installation into a commercial, multi-family (multi-level exceeding two stories) or high-rise applications: All outer pipe joints must be sealed with high temperature silicone, including the slip section that connects directly to the hori­zontal termination cap.
• Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections. See Figure 10.2
• Only outer pipes need to be sealed. All unit collar, pipe, slip section, elbow and cap outer fl ues shall be sealed in this manner, unless otherwise stated.
Note: Align seams to engage pipe, then rotate counterclockwise to lock
Figure 10.1 Adding Venting Components
Figure 10.2 High Temperature Silicone Sealant
WARNING! Risk of Fire or Explosion! DO NOT break silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals are broken during removal of the termination cap, vent may leak.
35Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 36
B. Assemble Slip Sections
Pilot hole
• Slide the inner fl ue of the slip section into the inner fl ue of the pipe section and the outer fl ue of the slip section over the outer fl ue of the pipe section. See Figure 10.3.
• Slide together to the desired length.
Pilot hole
Figure 10.3 Slip Section Pilot Holes
• Maintain a 1-1/2 in. (38 mm) overlap between the slip section and the pipe section.
• Secure the pipe and slip section with two screws no longer than 1/2 in. (13 mm), using the pilot holes in the slip section. See Figure 10.4.
C. Securing the Vent Sections
• Vertical runs of pipe must be supported every 8 ft. (2.44 m).
• Horizontal sections must be supported every 5 feet (1.52 m).
• Vent supports or plumbers strap (spaced 120º apart) may be used to support. See fi gures 10.5 and 10.6.
• Wall shield fi restops may be used to provide horizontal support.
• Ceiling fi restops have tabs that may be used to provide vertical support.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate. Use vent run supports and connect vent sections per in­stallation instructions. DO NOT allow vent to sag below connection point to appliance.
Figure 10.4 Screws into Slip Section
• Continue adding pipe as necessary following instructions in “Assembling Pipe Sections.”
NOTICE: If slip section is too long, the inner and outer fl ues of the slip section can be cut to the desired length.
NOTICE: When installing a vent system with an HRC termination cap, all pipe system joints shall be sealed using a high temperature silicone sealant.
Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections.
Only outer pipes are sealed, sealing the inner fl ue is not required.
All unit collar, pipe, slip section, elbow and cap outer ues shall be sealed.
Figure 10.5 Securing Vertical Pipe Sections
Figure 10.6 Securing Horizontal Pipe Sections
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1236
Page 37
D. Disassemble Vent Sections
• Rotate either section (see Figure 10.7) so the seams on both pipe sections are aligned as shown in Figure 10.8.
• Pull carefully to separate the pieces of pipe.
• Lower the support box through the hole in the roof until its bottom is at least 2 in. (51 mm) below the ceiling (Figure
10.9).
• Level the support box both vertically and horizontally and temporarily tack it in place through the inside walls into the roof sheathing.
• Use tin snips to cut the support box from the top corners down to the roof line and fold the resulting fl aps to the roof. See Figure 10.10.
• Nail the fl aps to the roof AFTER running a bead of non hardening sealant between the fl aps and the roof.
WARNING! Risk of Fire! Clean out ALL materials from inside the support box and complete the vertical vent run and termination.
LEVEL
Figure 10.7 Rotate Seams for Disassembly
Figure 10.8 Align and Disassemble Vent Sections
E. Installing Decorative Ceiling Components
A decorative ceiling thimble can be installed on a fl at ceil- ing through which the vent passes. The decorative ceiling thimble is used to cover the fi restop.
• Seal the gap between the vent pipe and fi restop using high temperature silicone to prevent cold air infi ltration.
• Install the decorative ceiling thimble by sliding it up to the ceiling and attaching it using the provided screws.
A decorative cathedral ceiling support box can be installed on a cathedral ceiling through which the vent passes.
• Use a plumb-bob to mark the center line of the venting system on the ceiling and drill a small hole through the ceiling and roof at this point. Locate the hole and mark the outline of the cathedral ceiling support box on the outside roof.
• Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box. Cut the hole 1/8 in. (3 mm) larger than the support box outline.
CATHEDRAL CEILING SUPPORT BOX
2 in. (51 mm) MIN. BELOW FINISHED CEILING
CUT HOLE 1/8 in. (3 mm) GREATER IN SIZE THAN PATTERN OF SUPPORT BOX AS IT IS PROJECTED ONTO ROOF LINE
Figure 10.9
Figure 10.10
37Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 38
F. Installing Metal Roof Flashing
Figure 10.13 Assembling the Storm Collar
Figure 10.14 Assembling the Storm Collar Around the Pipe
• See minimum vent heights for various pitched roofs (Figure 10.1 1) to determine the length of pipe to extend through the roof.
• Slide the roof fl ashing over the pipe sections extending through the roof as shown in Figure 10.12.
HORIZONTAL
OVERHANG
CAULK
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
Roof Pitch H (Min.) Ft.
Flat to 6/12........................................1.0*
Over 6/12 to 7/12 ............................1.25*
Over 7/12 to 8/12 ..............................1.5*
Over 8/12 to 9/12 ..............................2.0*
Over 9/12 to 10/12 ............................. 2.5
Over 10/12 to 11/12 ......................... 3.25
Over 11/12 to 12/12 ........................... 4.0
Over 12/12 to 14/12 ........................... 5.0
Over 14/12 to 16/12 ........................... 6.0
Over 16/12 to 18/12 ........................... 7.0
Over 18/12 to 20/12 ........................... 7.5
Over 20/12 to 21/12 ........................... 8.0
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
X
12
ROOF PITCH
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
* 3 foot minimum in snow regions
VERTICAL
WALL
IS X/ 12
Figure 10.12
G. Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during instal­lation. Sheet metal edges are sharp.
• Connect both halves of the storm collar with two screws (see Figure 10.13).
• Wrap the storm collar around the exposed pipe section closest to the roof and align brackets. Insert a bolt (provided) through the brackets and tighten the nut to complete the storm collar assembly . Make sure the collar is tight against the pipe section.
• Slide the assembled storm collar down the pipe section until it rests on the roof fl ashing (see Figure 10.14).
• Caulk around the top of the storm collar (see Figure 10.15).
Figure 10.11 Minimum Height From Roof To Lowest Discharge
Opening
NOTICE: Failure to properly caulk the roof fl ashing and pipe seams may permit entry of water.
• Caulk the gap between the roof fl ashing and the outside diameter of the pipe.
• Caulk the perimeter of the fl ashing where it contacts the roof surface. See Figure 10.12.
• Caulk the overlap seam of any exposed pipe sections that are located above the roof line.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1238
Figure 10.13 Assembling the Storm Collar
Figure 10.14 Assembling the Storm Collar Around the Pipe
Page 39
H. Installing Vertical Termination Cap
• Attach the vertical termination cap by sliding the inner collar of the cap into the inner fl ue of the pipe section while placing the outer collar of the cap over the outer ue of the pipe section.
• Secure the cap by driving three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer fl ue of the pipe (see Figure 10.15).
TERMINATION CAP
(1 of 3)
STORM COLLAR
SCREWS
CAULK
Figure 10.15
I. Installing Decorative Wall Components
A decorative wall thimble can be installed on wall through which the vent passes. The decorative wall thimble is used to cover the fi restop.
• Slide the decorative wall thimble over the last section of horizontal pipe before connecting the termination cap to the pipe.
• Once the pipe section and the termination cap have been connected, slide the wall thimble up to the interior wall surface and attach with screws provided. See Figure
10.16.
J. Heat Shield Requirements for Horizontal
Termination
WARNING! Risk of Fire! To prevent overheating and fi re, heat shields must extend through the entire wall thick­ness.
DO NOT remove the heat shields attached to the wall shield fi restop and the horizontal termination cap (shown in Figure 10.17).
• Heat shields must overlap 1-1/2 in. (38 mm) mini­mum.
There are two sections of the heat shield. One section is factory-attached to the wall shield fi restop. The other section is factory-attached to the cap. See Figure 10.17.
If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat shield overlap when installed, an extended heat shield must be used.
• If the wall thickness is less than 4 in./102 mm (DVP) or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap and wall shield fi restop must to be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained.
• Use an extended heat shield if the fi nished wall thickness is greater than 7-1/4 in. (184 mm).
• The extended heat shield may need to be cut to length maintaining suffi cient length for a 1-1/2 in. (38 mm) overlap between heat shields.
• Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to vent components diagrams in the back of this manual.
• Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.
Important Notice: Heat shields may not be eld constructed.
Figure 10.16 Wall Thimble
39Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 40
K. Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping fl ue section of the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of fl ue telescoping section is required.
Failure to maintain overlap may cause overheating and re.
• Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at outside edges of cap.
• When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149 installation codes and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require in­stallation of a cap shield to prevent anything or anyone from touching the hot cap.
NOTICE: For certain exposures which require superior resistance to wind-driven rain penetration, a fl ashing kit and HRC caps are available. When penetrating a brick wall, a brick extension kit is available for framing the brick.
Note: When using termination c aps w ith fac tory-suppli ed heat shield attached, no additional wall shield fi restop is required on the exterior side of a combustible wall.
HEAT SHIELD OR
EXTENDED
WALL SHIELD
FIRESTOP
INNER VENT
OUTER VENT
Figure 10.17 Venting through the wall
HEAT SHIELD
SLIP SECTION
CAN BE EXTENDED
INTERIOR
HEAT SHIELD
1-1/2 IN. (38 MM) MIN.
OVERLAP
SHEATHING
EXTERIOR
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1240
Page 41
11
11
Gas Information
A. Fuel Conversion
• Make sure the appliance is compatible with available gas types.
• Conversions must be made by a qualified service technician using Hearth & Home T echnologies specifi ed and approved parts.
B. Gas Pressure
• Optimum appliance performance requires proper input pressures.
• Gas line sizing requirements will be determined in ANSI Z223.1 National Fuel Gas Code in the USA and CAN/ CGA B149 in Canada.
• Pressure requirements are:
Gas Pressure Natural Gas Propane
Minimum inlet pressure 5.0 in. w.c. 11.0 in. w.c. Maximum inlet pressure 14.0 in. w.c. 14.0 in. w.c. Manifold pressure 3.5 in. w.c. 10.0 in. w.c.
WARNING! Risk of Fire/Explosion! High pressure will damage valve. Low pressure may cause explosion.
• Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating.
• Install regulator upstream of valve if line pressure is greater than 1/2 psig.
WARNING
Fire Risk. Explosion Hazard. High pressure will damage valve.
• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.
• Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.
Note: Have the gas supply line installed in accordance with local codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualifi ed installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter).
Note: A listed (and Commonwealth of Massachusetts ap­proved) 1/2 in. (13 mm) T-handle manual shut-off valve and fl exible gas connector are connected to the 1/2 inch (13 mm) control valve inlet.
• If substituting for these components, please consult local codes for compliance.
C. Gas Connection
• Refer to Reference Section 16 for location of gas line access in appliance.
• Gas line may be run through knockout(s) provided.
• The gap bet ween supply piping and gas access hole may be caulked with caulk with a minimum of 300ºF continuous exposure rating or stuffed with non­combustible, unfaced insulation to prevent cold air infi ltration.
• Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes.
• Pipe incoming gas line into valve compartment.
• Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve.
WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line.
• A small amount of air will be in the gas supply lines.
WARNING! Risk of Fire or Explosion! Gas build-up dur ­ing line purge could ignite.
• Purge should be performed by qualified service
technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks
or open fl ames.
Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Check all fi ttings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open fl ame. Fittings and connections could have loos- ened during shipping and handling.
WARNING! Risk of Fire! DO NOT change valve settings. This valve has been preset at the factory.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce burner orifi ce 4% for each 1000 feet above 2000 feet.
• In the CANADA: Reduce burner orifi ce 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.
41Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 42
12
12
Electrical Information
A. Wiring Requirements
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.
• Wire the appliance junction box to 110-120 VAC. This is required for use of optional accessories and proper operation of the appliance (Intellifi re ignition).
• A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
• Low voltage and 110 VAC voltage cannot be shared within the same wall box.
WARNING! Risk of Shock or Explosion! DO NOT wire 1 10V to the valve or to the appliance wall switch. Incorrect wiring will damage controls.
B. Intellifi re Ignition System Wiring
• Wire the appliance junction box to 110 VAC for proper operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire IPI controlled appliance junction box to a switched circuit. Incorrect wiring will override IPI safety lockout.
• Refer to Figure 12.2, Intellifi re Pilot Ignition (IPI) Wiring Diagram.
• This appliance is equipped with an Intellifi re control valve which operates on a 3 volt system.
• Plug the 3-volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries (not included) into the battery pack before use.
NOTICE: Batteries should not be placed in the battery pack while using the transformer. Remove batteries before using the transformer, and unplug the transformer before installing the batteries. Battery polarity must be correct or module damage will occur.
C. Optional Accessories Requirements
• This appliance may be used with a wall switch, wall mounted thermostat and/or a remote control.
Wiring for optional Hearth & Home T echnologies approved accessories should be done now to avoid reconstruction. Follow instructions that come with those accessories.
D. Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to dis­connection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with type 105° C rated wire. Wire must have high temperature insulation.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1242
Page 43
IGNITION
MODULE 3 VAC
I
S
INTERMITTENT PILOT IGNITOR
TRANSFORMER
PLUG IN
3 VAC
RED
THERMOSTAT
WIRE ASSEMBLY
BLACK
WIRES (TO BROWN)
BATTERY PACK
HOT
NEUTRAL
Figure 12.1 Intellifi re Ignition Wiring Diagram with Wall Switch or Thermostat
NOTE: 1. Ignition module, valve, pilot, and
wall switch operate on 3 volts. 120 VAC is required at junction box unless equipped with battery back-up.
ORANGE
WHITE
GROUND TO
FIREPLACE
CHASSIS
IGNITION
MODULE 3 VAC
I
S
ORANGE
VALVE
GREEN
INTERMITTENT PILOT IGNITOR
TRANSFORMER
3 VAC
PLUG IN
PLUG IN
BATTERY PACK
HOT
NEUTRAL
REMOTE
Figure 12.2 Intellifi re Ignition Wiring Diagram with Remote Receiver
RED
BLACK
WIRES (TO BROWN)
ORANGE
WHITE
GROUND TO
FIREPLACE
CHASSIS
ORANGE
VALVE
GREEN
43Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 44
E. Junction Box Installation
The junction box must be wired from the INSIDE of the appliance:
• Determine which side of the appliance the junction box is located on.
• Pull the electrical wires from outside the appliance through the knockout making sure to use a Romex connector to fasten the electrical wires to the unit.
• Pull enough wire into the valve compartment to easily reach the junction box location.
• Remove the screw attaching the junction box to the junction box bracket and set it aside.
• Route the wire through the knockout in the junction box bracket.
• Wire the junction box and reattach it to the bracket by inserting the tab in the slot and attaching with screw previously removed. Ensure that a Romex connector is used to attach the electrical wires to the junction box.
ROMEX CONNECTORS
Figure 12.4 Junction Box Detail
NOTICE: DO NOT wire 110 VAC to wall switch.
F. Wall Switch Installation for Fan (Optional)
If the box is being wired to a wall mounted switch for use with a fan (See Figure 12.5):
• The power supply for the appliance must be brought into a switch box.
• The power can then be supplied from the switch box to the appliance using a minimum of 14-3 with ground wire.
• At the switch box connect the black (hot) wire and red (switch leg) wire to the wall switch as shown.
• At the appliance connect the black (hot), white (neutral) and green (ground) wires to the junction box as shown.
• Add a 1/4 in. insulated female connector to the red (switch leg) wire, route it through the knockout in the face of the junction box, and connect to the top fan switch connector (1/4 in. male) as shown.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1244
MINIMUM 14-3 AWG WITH GROUND
JUNCTION BOX
RED
Figure 12.5 Junction Box Wired to Wall Switch or BC10
RED
WHITE
BLACK
RED
BLACK
GREEN
WHITE
GREEN
KNOCKOUT
SWITCH BOX
BLACK WHITE
GREEN
SWITCH
POWER SUPPLY
WIRES
Page 45
13
13
Finishing
A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear­ances as specifi ed. Framing closer than the minimums list- ed must be constructed entirely of noncombustible materi­als (i.e., steel studs, concrete board, etc.) Failure to comply could cause fi re.
Note: All measurements in inches.
MAX.
12
11
10
9
8
7
6
5
4
3
6
5
4
TOP OF HOOD OR FIREPLACE OPENING
Figure 13.1 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles
Note: All
measurements in inches.
MAX.
9
8
7
18
11
10
CEILING
CEILING
13
12
32
MIN.
TOP VIEW
Min.
FIREPLACE
1/2 in.
OPENING
Note: Clearance from opening to perpendicular wall.
Figure 13.3 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)
3-1/4 in.
Min.
Unlimited
B. Facing Material
• Metal front faces may be covered with non-combustible materials only.
• Facing and/or fi nishing materials must not interfere with air fl ow through louvers, operation of louvers or doors, or access for service.
• Facing and/or fi nishing materials must never overhang into the glass opening.
• Observe all clearances when applying combustible materials.
• Seal joints between the fi nished wall and appliance top and sides using a 300 °F minimum sealant. Refer to Figure 13.3.
WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specifi ed in this manual. Overlapping materials could ignite and will interfere with proper operation of doors and louvers.
12
11
10
9
8
7
6
5
2
1
4
TOP OF HOOD OR FIREPLACE OPENING
Figure 13.2 Minimum Vertical and Maximum Horizontal Dimensions of Non-Combustibles
6
5
4
3
32
MIN.
14
8
7
Finish wall material may be combustible - Top and Sides
0 in.
0 in.
High Temperature Sealant (300° F/149° C min.)
Top and Side Seal Joint
Figure 13.4 Noncombustible Facing Diagram
0 in.
45Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 46
C. Splatter Guard
The splatter guard is a piece of corrugated material used to protect the appliance during the installation process before fi nishing work on the whole hearth is complete.
Splatter guards must be removed before appliance is red.
WARNING
Risk of Fire
• Splatter guard must be removed before lighting appliance.
• Before splatter guard is installed:
Close ball valve to prevent accidental lighting.
Step 1. Turn off gas to valve. Red gas shutoff knob is located on ball valve. Disconnect the 3 volt transformer from the junction box. See Figure 13.5.
Figure 13.7 Folding of Right and Left Sides of Splatter Guard
Step 4. Center the splatter guard in front of the unit as shown in Figure 13.8. Place the splatter guard in the unit by guiding the top fl ap into proper position and then con- tinuing to guide the tabs on the side fl aps into the top slot on the left and right sides of the appliance. The top slot is indicated in Figure 13.9 Take care not to bend or break off the tabs.
Figure 13.5 Preparation to Install Splatter Guard
To install the Splatter Guard:
Step 2. Crease fl ap on top side of splatter guard using the scored line as the guide. See Figure 13.5.
Figure 13.6 Folding Top Flap
Step 3. Crease fl aps on left and right sides of splatter guard using the scored line as the guide. See Figure 13.6.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1246
Figure 13.8 Installation of Splatter Guard
TOP SLOT
Figure 13.9 Top slot
Page 47
Step 5. Fold bottom fl ap along score line as indicated in Figure 13.10 and tuck into valve access area of appli­ance. Splatter guard should fi t securely on front of unit.
Figure 13.10 Folding Bottom Flap
Figure 13.13 Securing Tabs Inside Front of Splatter Guard
Once plumbing and wiring are complete on the fi replace, the lower access panel may be closed until the time that the splatter guard must be removed for fi ring the appliance.
Figure 13.11 Prepare to Open Lower Access Panel
Step 6. To open lower access panel of splatter guard, place one hand above score line and place two fi ngers from other hand in the round holes on the front of the splatter guard. See Figure 13.11. Pull out and fold up the panel as shown in Figure 13.12. Disengage the tabs on left and right bottom of splatter guard and fi t them into the square holes. The tabs are now inside the front of the splatter guard; carefully bend them down. See Figure
13.12.
Figure 13.14 Splatter Guard with Lower Access Panel Open
To Close the Lower Access Panel:
Carefully disengage the tabs from the square holes and bend the access panel to its original position. Bend the center bottom fl ap and insert it into the bottom of the ap- pliance.
Figure 13.12 Opening Lower Access Panel
Figure 13.15 Splatter Guard with Lower Access Panel Closed
To Remove the Splatter Guard:
Carefully grab splatter guard on or near the vertical center on the left and right sides. Pull outward gently , but fi rmly, taking care not to tear or remove the inserted tabs.
47Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 48
14
14
Appliance Setup
A. Remove Fixed Glass Assembly
See Section 14G.
B. Remove the Shipping Materials
Remove shipping materials from inside or underneath the rebox.
C. Clean the Appliance
Clean/vacuum any sawdust that may have accumulated inside the fi rebox or underneath in the control cavity.
D. Accessories
Install approved accessories per instructions included with accessories. Contact your dealer for a list of ap­proved accessories.
WARNING! Risk of Fire and Electric Shock! Use ONLY Hearth & Home Technologies-approved optional acces­sories with this appliance. Using non-listed accessories could result in a safety hazard and will void the warranty.
E. Lava Rock, Mystic Embers and Glowing
Ember Placement
WARNING! Risk of Explosion! Follow ember placement instructions in manual. DO NOT place embers directly over burner ports. Replace ember material annually . Improperly placed embers interfere with proper burner operation.
Placing the Ember Material
Ember material is shipped with this gas appliance. T o place the ember material:
• Embers CANNOT be placed directly over ports. Care should be taken not to cover the lighting trail of ports (from back to front).
®
• When placing Glowing Embers should be taken so that the ports are not covered. Place the dime-size ember pieces just in front of the port trail, but not on or in between the ports (see Figure 14.1). Failure to follow this procedure will likely cause lighting and sooting problems.
DO NOT PLACE GLOWING
EMBERS IN THE CIRCLED AREA
onto the burner care
PILOT
= MYSTIC EMBERS
= GLOWING EMBERS
Figure 14.1 Placement of Embers
• Place Lava Rock on areas of base pan away from the burner. Use this material to give the appliance a realistic ash bed.
• Save the remaining ember materials for use during appliance servicing. The embers provided should be enough for 3 to 5 applications.
• Place Mystic Embers on burner and away from the fl ames to give the appliance a realistic ash bed.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1248
Page 49
F. Install the Log Assembly
1
3
2
PILOT
1
2
1
2
3
1
STEP 1. CAUTION! Logs are fragile! Carefully remove the microfoam and packaged logs from the inside of the
replace. See Figure 2. Remove the Mystic Embers and mineral wool and set aside. Remove the packaging from the logs and inspect the logs for damage. To ensure that you are working on the correct side of the appliance, verify that the pilot is on the left side. See Figure 2.
2
Log Set Assembly: LOGS-2126
Models: ST-550T-IPI. GDST3831I
PILOT
1
1
STEP 2. Log #1 (SRV2126-700): Place Log #1 so that the large cutout on the bottom of the log ts over the pilot shield
as shown in Figure 4. The hole in the bottom of Log #1 interlocks with the head of the shoulder screw on the burner.
2
2
STEP 3. Log #2 (SRV2126-701): Place Log #2 as shown in Figure 6 using the shoulder bolt as a guide to align the
log in the proper orientation to the port pattern on the burner.
2126-935
49Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 50
3
3
NOTCH
NOTCH
2
1
3
NOTCH
3
STEP 4. Log #3 (SRV2126-702): Place Log #3 (1 of 2 identical logs) as shown in Figure 7. Align the “Y” of Log #3
with the cutout on Log #2. Rest the bottom of Log #3 in the notch on the ledge on the back side of the basepan.
3
NOTCH
1
3
2
STEP 5. Log #3 (SRV2126-702): Place the remaining Log #3 (2 of 2 identical logs) into the replace so that the bot-
tom of the log rests in the notch on the ledge on the front side of the basepan. Then place the top of Log #3 on top of Log #1 so that the fl at spot is hidden. The complete log set assembly is shown in Figure 11. See the fi replace Owner’s Manual for instructions on how to place the Mystic Embers and Mineral Wool.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1250
Page 51
G. Fixed Glass Assembly
GLASS
ASSEMBLY
LATCHES
(BOTH BOTTOM
AND TOP)
Removing Fixed Glass Assembly
WARNING! Risk of Asphyxiation! Handle fi xed glass assembly with care. Inspect the gasket to ensure it is undamaged and inspect the glass for cracks, chips or scratches.
DO NOT strike, slam or scratch glass.
DO NOT operate replace with glass removed, cracked, broken or scratched.
Replace as a complete assembly.
Removing Fixed Glass Assembly
• Pull the two glass assembly latches out of the groove on the glass frame (see Figure 14.3).
• Remove glass door from the bracket on the top of the rebox.
Replacing Fixed Glass Assembly
• Replace the glass door on the appliance.
• Pull out and latch the two glass assembly latches into the groove on the glass frame.
• Make sure both sides are replaced properly.
H. Install Trim Kits and Surrounds
• Install optional trim kits and/or surrounds using the instructions included with the accessory.
• Use non-combustible materials to cover the gap between the sheet rock and the appliance (if desired).
I. Air Shutter Setting
This appliance has an adjustable air shutter (which con­trols the primary air) factory set for the minimum vertical vent run (see Figure 12.15). If your installation has more than the minimum required vertical vent length, adjust­ment of the air shutter may be necessary to obtain opti­mal fl ame appearance. This should be adjusted by a
qualifi ed installer at the time of installation.
Air Shutter Settings
NG LP
Burner 1/8 in. 3/8 in.
Figure 14.3 Fixed Glass Assembly
51Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 52
15
15
Troubleshooting
With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualifi ed technician in the diagnosis of a problem and the corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed technician. Contact your dealer to arrange a service call by a qualifi ed technician.
A. Intellifi re Ignition System
Symptom Possible Cause Corrective Action
1. Pilot won’t light. The ignitor/module makes noise, but no spark.
2. Pilot won’t light, there is no noise or spark.
a. Incorrect wiring. Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor
are connected to correct terminals on module and pilot assembly.
b. Loose connections or electrical
shorts in the wiring.
c. Ignitor gap is too large. Verify gap of igniter to right side of pilot hood. The gap should be
d. Module. Turn ON/OFF rocker switch or wall switch to OFF position. Remove
a. No power or transformer installed
incorrectly.
b. A shorted or loose connection in wir-
ing confi guration or wiring harness.
Verify no loose connections or electrical shorts in wiring from module to pilot assembly. Verify connections underneath pilot as­sembly are tight; also verify connections are not grounding out to metal chassis, pilot burner, pilot enclosure, mesh screen if present, or any other metal object.
approximately .17 in. or 1/8 in. (3 mm).
ignitor wire “I” from module. Place a grounded wire about 3/16 in. (5 mm) away from “I” terminal on module. Place ON/OFF rocker switch or wall switch in ON position. If there is no spark at “I” terminal module must be replaced. If there is a spark at “I” terminal, module is fi ne. Inspect pilot assembly for shorted sparker wire or cracked insulator around electrode. Replace pilot if necessary .
Verify that transformer is installed and plugged into module. Check voltage of transformer under load at spade connection on module with ON/OFF switch in ON position. Acceptable readings of a good transformer are between 3.2 and 2.8 volts AC.
Remove and reinstall the wiring harness that plugs into module. Verify there is a tight fi t. Verify pilot assembly wiring to module. Re- move and verify continuity of each wire in wiring harness. Replace any damaged components.
3. Pilot sparks, but Pilot will not light.
c. Improper wall switch wiring. Verify that 110/VAC power is “ON” to junction box. d. Module not grounded. Verify black ground wire from module wire harness is grounded to
metal chassis of appliance.
e. Module. Turn ON/OFF rocker switch or wall switch to OFF position. Re-
move ignitor wire “I” from module. Place ON/OFF rocker switch or wall switch in ON position. If there is no spark at “I” terminal module must be replaced. If there is a spark at “I” terminal, module is fi ne. Inspect pilot assembly for shorted sparker wire or cracked insulator around electrode.
a. Gas supply. Verify that incoming gas line ball valve is “open”. Verify that inlet
pressure reading is within acceptable limits, inlet pressure must
not exceed 14 in. W.C. b. Ignitor gap is incorrect. Verify that spark gap from ignitor to pilot hood is .17 in. or 1/8 in (3 mm). c. Module is not grounded. Verify module is securely grounded to metal chassis of appliance. d. Module voltage output / Valve/Pilot
solenoid ohms readings.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1252
Verify battery voltage is at least 2.7 volts. Replace batteries if volt-
age is below 2.7.
Page 53
Intellifi re Ignition System - (continued)
Symptom Possible Cause Corrective Action
4. Pilot lights but contin­ues to spark, and main burner will not ignite. (If the pilot continues to spark after the pilot fl ame has been lit, ame rectifi cation has not occurred.)
a. A shorted or loose connection in fl ame
sensing rod.
b. Poor fl ame rectifi cation or contaminated
ame sensing rod.
c. Module is not grounded. Verify module is securely grounded to metal chassis of
d. Damaged pilot assembly or contami-
nated fl ame sensing rod.
e. Module. Turn ON/OFF rocker switch or wall switch to OFF position.
Verify all connections to wiring diagram in manual. Verify connections underneath pilot assembly are tight. Verify connections are not grounding out to metal chassis, pilot burner, pilot enclosure or screen if present, or any other metal object.
With fi xed glass assembly in place, verify that fl ame is en- gulfi ng fl ame sensing rod on left side of pilot hood. Flame sensing rod should glow shortly after ignition. Verify cor­rect pilot orifi ce is installed and gas inlet is set to pressure specifi cations. Polish fl ame sensing rod with fi ne steel wool to remove any contaminants that may have accumulated on fl ame sensing rod.
appliance. Verify that wire harness is fi rmly connected to the module.
Verify that ceramic insulator around the fl ame sensing rod is not cracked, damaged, or loose. Verify connection from ame sensing rod to white sensor wire. Polish fl ame sens- ing rod with fi ne steel wool to remove any contaminants that may have accumulated on fl ame sensing rod. Verify continuity with a multimeter with ohms set at lowest range. Replace pilot if any damage is detected.
Remove ignitor wire “I” from module. Place ON/OFF rocker switch or wall switch in ON position. If there is no spark at “I” terminal module must be replaced. If there is a spark at “I” terminal, module is fi ne.
53Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 54
16
16
B
C
FRONT VIEW RIGHT VIEW
ELECTRICAL
ACCESS
GAS LINE
ACCESS
LEFT VIEW
A
J
K
D
F
G
H
N
i
L
M
E
Reference Materials
A. Appliance Dimension Diagram
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 5.
Location Inches Millimeters
A 31-1/8 791 B 37-5/8 956 C 21 533 D 30-1/4 768 E1 25 F 2-1/8 54
Figure 16.1 See-Through Dimensions
G 4-1/8 105
Location Inches Millimeters
H 4-1/4 108
I 1-1/2 38
J 8 203 K 8-3/4 222 L 34-1/2 876
M 16 406 N 31-1/4 794
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1254
Page 55
B. Vent Components Diagrams
8-3/4 in. 222 mm
6-5/8 in. 168 mm
SLP45
45° Elbow
Effective
Height/
Length
SLP PIPE
10-7/8 in.
276 mm
6-1/2 in. 165 mm
6 in.
152 mm
6-5/8 in. 168 mm
Effective Height/Length
Pipe
SLP4 4 102
SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 - 6 51 - 152
SLP12A 2 - 12 51 - 305 SLP-FLEX-2 24 610 SLP-FLEX-3 36 914 SLP-FLEX-5 60 1524
SLP-FLEX-10 120 3048
inches mm
6-1/2 in. 165 mm
9-7/8 in. 251 mm
SLP90
90° Elbow
6-1/2 in. 165 mm
9-1/4 in. 235 mm
EFFECTIVE HEIGHT/
LENGTH
SLP-FLEX-PIPE
8-7/8 in.
1-1/2 in.
225 mm
SLP-HVS
Horizontal Pipe
Support
8-11/16 in.
220 mm
8-11/16 in.
220 mm
SLP-FS
Ceiling Firestop
Figure 16.2 SLP Series Vent Components
38 mm
1-1/2 in.
38 mm
12 in.
305 mm
SLP-WS
Wall Shield Firestop
12 in.
305 mm
5-1/2 in. 146 mm
55Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 56
B. Vent Components Diagrams (continued)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.
8 in.
(203 mm)
15-1/8 in. (384 mm)
Heat
Shield
3-15/16 in.
(101 mm)
14-7/16 in.
367 mm
12 in.
(305 mm)
6-11/16 in.
(169 mm)
8 in.
(203 mm)
14-7/16 in.
Horizontal Termination Cap
SLP-TRAP
3-13/16 in.
(97 mm)
SL-2DVP Adapter
367 mm
2-5/16 in.
59 mm
Max
Effective
Length
3-15/16 in.
(101 mm)
5-1/16 in.
(128 mm)
4 in.
102 mm
Term Cap
Trap1
Trap2
Minimum
Effective Length
3-1/8 in. 4-3/4 in.
79 mm 121 mm 5-1/4 in. 9-1/4 in. 133 mm 235 mm
6-3/8 in. 163 mm
8-1/8 in. 206 mm
660 mm
DVP-HSM-B
Extended Heat Shield
Effective Length
4-5/8 in. 117 mm
DVP-2SL Adapter
26 in.
Maximum
4-3/16 in.
106 mm
5-1/16 in.
128 mm
SLP-WT-BK
Wall Thimble-Black
12 in.
305 mm
12-1/2 in.
318 mm
8-1/16 in.
205 mm
SLP-TVHW
Vertical
Termination Cap
Figure 16.3 SLP Series Vent Components
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1256
2-3/4 in.
(70 mm)
9 in.
(229 mm)
11-1/2 in.
(292 mm)
12-1/4 in. (311 mm)
16 in.
(406 mm)
PVK-80
(For use with IPI and DSI appliances only.)
12-1/2 in. (318 mm)
Page 57
B. Vent Components Diagrams (continued)
14-1/16 in.
357 mm
14 in.
356 mm
10-9/16 in.
269 mm
SLP-CCS-BK
Cathedral Ceiling
Support Box-Black
14 in.
356 mm
SLP-FLEX-TRAP
Termination Kit
7-1/2 in. 192 mm
Horizontal
10-3/4 in.
273 mm
6-11/16 in.
169 mm
13 in.
330 mm
1 in.
(25 mm)
14 in.
(356 mm)
13 in.
330 mm
1-5/16 in.
34 mm
SLP-DCF-BK
Ceiling Firestop
Black
7-1/4 in.
(184 mm)
28-1/2 in. 724 mm
13-1/2 in.
343 mm
SLK-SNKD
Snorkel
Termination Cap
10-11/16 in.
271mm
SLP90
SL-2DVP
3/8 in. (10 mm)
1 in. (25 mm)
7-3/4 to 10-3/8 in.
(197 to 264 mm)
DVP-FBHT
Horizontal
Termination Cap
DVP-FBHT
DVP-FBHT
Figure 16.4 SLP Series Vent Components
ASSEMBLY
57Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 58
B. Vent Components Diagrams (continued)
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC­SS termination caps on top vented fi replaces, a one foot minimum vertical vent section is required before installing fi rst elbow.
• When using DVP-TB1 termination cap on top vented replaces, a three foot minimum vertical vent section is required before installing fi rst elbow.
WARNING
15 in.
(381 mm)
8-1/8 in.
(206 mm)
SLP90
13 in.
(330 mm)
Effective Length 5-3/4 to 8-3/8 in.
146 to 213 mm
SLP-HRC-SS
SLP-HRC-ZC-SS
HORIZONTAL TERMINATION CAP
DVP-TB1
SL-2DVP
5-1/2 in. 140 mm
87°
DVP-TB1
8-3/8 in. 213 mm
10-1/2 in.
267 mm
10-7/8 in.
276 mm
Figure 16.5 SLP Series Vent Components
ASSEMBLY
DVP-TB1
HORIZONTAL TERMINATION CAP
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1258
Page 59
B. Vent Components Diagrams (continued)
EFFECTIVE LENGTH 32 IN. (813 mm) MIN. 35 IN. (889 mm) MAX.
Power Vent Inline
PVI-SLP
20-3/4 IN. 527 mm
13-5/8 IN. 346 mm
12-1/2 IN. 318 mm
Optional Wire Harness
DESCRIPTION PART NUMBER
10 ft. PV Wire Harness PVI-WH10 20 ft. PV Wire Harness PVI-WH20 40 ft. PV Wire Harness PVI-WH40 60 ft. PV Wire Harness PVI-WH60 80 ft. PV Wire Harness PVI-WH80 100 ft. PV Wire Harness PVI-WH100
Note: Wire harnesses required to power the PVI-SLP connect to the appliance and are ordered separately from PVI-SLP. Contact your dealer to order.
12-1/2 IN. (318 mm)
13-5/8 IN. (346 mm)
16 IN.
406 mm
4-1/2 IN.
114 mm 9-3/16 IN. (233 mm)
SLP-LPC
SLP Low Profi le Cap
16-11/16 IN.
424 mm
15 IN.
(381 mm)
16-11/16 IN.
(424 mm)
Figure 16.6 Vent Components
59Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 60
C. Service Parts
GDST3831I
Log Set Assembly
3
1
3
31” See Thru Direct Vent Fireplace
2
6
7
8
Beginning Manufacturing Date: Mar 2008
Ending Manufacturing Date: ______
4
5
12
11
10
9
IMPORTANT: THIS IS DA TED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer.
ITEM DESCRIPTION COMMENTS PART NUMBER
Log Set Assembly 1 Log 1 2 Log 2 3 Log 3 4 Sheetrock Ledge 5 Refractory 6 Burner NG, LP 2126-007 7 Base Pan 8 Glass Door Assembly 9 Valve Assembly
10 Junction Box 11 Junction Box Bracket 12 Pilot Shield
Additional service part numbers appear on following page.
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1260
Qty 2 req SRV2126-702
Qty 2 req 2127-017
LOGS-2126 SRV2126-700 SRV2126-701
2126-118
2126-115 GLA-550TR
Refer to valve page
4021-013 2128-128 2126-124
Stocked at Depot
Y
Y
Y
Y
Page 61
#9 Valve Assembly
C. Service Parts
9.2
9.3
9.4
GDST3831I
Beginning Manufacturing Date: Mar 2008
Ending Manufacturing Date: ______
9.1
9.11
9.10
9.5
9.9
9.6
9.8
9.7
IMPORTANT: THIS IS DATED INFORMA TION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer.
ITEM DESCRIPTION COMMENTS PART NUMBER
9.1 Battery Pack 593-594A Y
9.2 3 Volt Transformer 593-593A Y
9.3 Module Wire Assembly 593-590A Y
9.4 Module 593-592 Y
9.5 Valve Bracket
9.6
9.7 Flex Ball Valve Assembly 302-320A Y
9.8 Flexible Gas Connector 530-302A Y
9.9
9.10 3-hole Grommet
9.11
Additional service part numbers appear on following page.
Valve NG 750-500 Y Valve LP 593-501 Y
Orifi ce NG (#44C) Orifi ce LP (#55C)
Pilot Assembly NG Pilot Assembly LP 2 in Jumper Wires
2118-104
582-844 Y 582-855 Y 2118-420 2090-012 Y 2090-013 Y 2012-206
Stocked
at Depot
Y
61Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Page 62
C. Service Parts List GDST3831I
IMPORTANT: THIS IS DA TED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer.
ITEM DESCRIPTION COMMENTS PART NUMBER
Exhaust Restrictor Fiberglass Rope Ring Gasket Assembly
Contains Vent, Seal Cap, Burner Neck, Shutter Bracket and Valve Plate Gaskets
Glass Latch Assembly Lava Rock Mineral Wool Thermostat Wire Surround Overlay (contains overlay for top, bottom and sides) SRV2126-FACE Touch Up Paint
Pkg of 2 33858/2
530-299 045-455
2128-081
2005-790 050-721 2118-170
TUP-GBK-12
Stocked
at Depot
Y
Y
Conversion Kit NG Conversion Kit LP
Pilot Orifi ce NG 593-528 Pilot Orifi ce LP 593-527 Regulator NG NGK-DXV Regulator LP LPK-DXF
Heatilator • GDST3831I • 2127-900 Rev. K • 7/1262
NGK-MS32 LPK-MS32
Y Y Y Y Y Y
Page 63
D. Contact Information
Heatilator, a brand of Hearth & Home Technologies Inc.
7571 215th Street West, Lakeville, MN 55044
www.heatilator.com
Please contact your Heatilator dealer with any questions or concerns.
For the location of your nearest Heatilator dealer,
please visit www.heatilator.com.
- NOTES -
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
NOTICE
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
• Read, understand and follow these instructions for safe installation and operation.
• Leave this manual with party responsible for use and operation.
This product may be covered by one or more of the following patents: (United States) 5328356, 5601073, 5613487, 5647340, 5890485, 5941237, 5947112, 5996575, 6006743, 6019099, 6053165, 6145502, 6170481, 6374822, 6484712, 6601579, 6769426, 6863064, 7077122, 7098269, 7258116, 7470729 or other U.S. and foreign patents pending.
Printed in U.S.A. - Copyright 2012
63Heatilator • GDST3831I • 2127-900 Rev. K • 7/12
Loading...