This appliance may be constructed with a vertical or horizontal direct vent termination system.
Electrician: Please refer to page 14 for wiring instructions.
Plumber:Please refer to page 6 and 13 for gas connection information.
Framer:Please refer to page 7 for framing specifications.
Heatilator
1915 W. Saunders Street
Mt. Pleasant, IA 52641
A Division of Hearth Technologies Inc.
GC150 HEAT CIRCULATING SERIES GAS APPLIANCE
OWNER’S MANUAL
AND INSTALLATION INSTRUCTIONS
MODELS: GC150, GC150L, GC150E, GC150LE
WARNING: If the information in
these instructions is not followed
exactly, a fire or explosion may result
causing property damage, personal
injury or death.
-Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
-WHAT TO DO IF YOU SMELL GAS
lDo not try to light any appliance.
lDo not touch any electrical switch.
lDo not use any phone in your
building.
lImmediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
lIf you cannot reach your gas sup-
plier, call the fire department.
This manual must be used for installation of the
GC150 Series Gas Appliance and retained by the
homeowner for operating and maintenance
instructions.
-Installation and service must be performed
by a qualified installer, service agency or
the gas supplier.
2-99221322L
GC150 SERIES DIRECT VENT GAS APPLIANCE
Table of Contents
I.Listings and Code Approvals.....................................................................................................................3
II.Description of the Fireplace System..........................................................................................................3
III.Fireplaces System Components and Dimensions.....................................................................................4
VIII. Trouble Shooting.....................................................................................................................................25
1. Please read these installation instructions completely before beginning installation procedures. Failure
to follow them could cause a fireplace malfunction
resulting in serious injury and/or property damage.
2. Always check your local building codes prior to
installation. This installation must comply with all
local, regional, state and national codes and regulations.
3. Installation and repair should be done by a qualified
service person. This appliance should also be
inspected annually by a qualified service person.
More frequent inspections/cleaning may be required
due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment,
burners and circulating air passage ways of the
appliance be kept clean.
4. The GC150 fireplace is a vented gas fireplace. Do
not burn wood or other material in this appliance.
5. NEVER leave children unattended when there is a
fire burning in the fireplace.
6. This fireplace may be vented horizontally through an
outside wall or vertically above the roof line and
must not be connected to a chimney flue servicing a
solid fuel burning appliance.
7. NEVER use gasoline, gasoline-type lantern fuel,
kerosene, charcoal lighter fluid, or similar liquids in
this fireplace. Keep any flammable liquids a safe
distance from the fireplace.
8. While servicing this fireplace, always shut off all
electricity and gas to the fireplace. This will prevent
possible electrical shock or burns. Also, make sure
the unit is completely cooled before servicing.
9. During any pressure testing of the gas supply piping
system that exceeds test pressures of 1/2 psig, this
appliance and its individual shut-off valve must be
disconnected from the piping system. If test pressures equal to or less than 1/2 psig are used in pressure testing the gas supply piping system, this appliance must be isolated from the piping system by
closing its individual manual shut-off valve during
testing.
10. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part
of the control system and any gas control which has
been under water.
11. Be sure to provide adequate clearances around the
air openings into the combustion chamber and adequate accessibility clearances for servicing and
proper operation.
12. The appliance and its individual shutoff valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2 psi (3.5 kPa).
13. Provisions shall be made to provide adequate
combustion and ventilation air.
14. The appliance area shall be kept clear and free from
combustible materials, gasoline and other flammable
vapors and liquids.
15. The flow of combustion and ventilation air should
not be obstructed.
GC150 SERIES DIRECT VENT GAS APPLIANCE
I. LISTINGS AND CODE APPROVALS
Certification
The GC150 Series Vented Gas Fireplace has been
tested in accordance with the ANSI standard ANSI
Z21.50-1998lCGA 2.22-M98 and has been listed by
Warnock Hersey for installation and operation as
described in these Installation and Operating
Instructions. All components are A.G.A. or UL safety
certified.
Local codes
Check with your local building code agency prior to installing this appliance to ensure compliance with local
codes, including the need for permits and follow-up
inspections. This installation must conform with local
codes or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1-latest edition, in
the U.S.A. and the CAN/CGA B149, Installation Codes,
in Canada.
A manufactured home installation must conform with
the Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280, or, when such a
standard is not applicable, the Standard for
Manufactured Home Installations, ANSI Z225.1/NFPA
5 0 1 A .
Optional components
This gas appliance has been tested and listed for use
with the optional components listed on page 4. Many
optional components may be purchased separately
and installed at a later date. However, installation of
a remote control or fan kit will require electrical power.
To avoid costly reconstruction, electrical power should
be connected to the unit at the time of the initial fireplace installation for possible addition of these accessories at a later date.
Fuel
Any additions, changes or conversions required in
order for the appliance to satisfactorily meet the application needs must be made by a Heatilator distributor
using factory specified and approved parts.
This product is manufactured to use natural gas and
is available in propane gas. In the event your appliance must be converted to either natural gas from
propane or to propane gas from natural you must use
a proper conversion kit.
If any assistance is required during installation please
contact your local dealer or contact Heatilator
Technical Services Department, 1915 W. Saunders
Street, Mt. Pleasant, Iowa 52641.
HEATILATOR®is a registered trademark of
Heatilator, a Division of Hearth Technologies Inc.
II. DESCRIPTION OF THE FIREPLACE SYSTEM
The GC150 is a vented gas fireplace. Combustion air is supplied from outside, not from inside the house as with
other types of fireplaces. While a significant amount of heat is created by the GC150, it is not intended to be and,
therefore, should not be used as a heater.
This HEATILATOR fireplace system consists of the
following:
1. Fireplace
2. Venting System
3. Termination
Optional components include:
1. Trim kits
2. Fan kit
3. Remote control
Note: Illustrations throughout these instructions
reflect typical installations and are for design purposes only. Actual installation may vary slightly due
to individual design preferences. However, minimum and maximum clearances must be maintained
at all times.
The illustrations and diagrams used throughout
these installation instructions are not drawn to scale.
Tools and building supplies normally required for installation:
Tools:Building Supplies:
SawWall-finishing materials
PliersFraming material
HammerFireplace surround
Phillips screwdriverHigh Temp. Caulking
Tape measureMaterial (300° F+)
Plumb line
Level
Drill and Bits
Square
Note: Operation of a direct vent fireplace
may be sporadic in high wind situations.
1-99321322L
GC150 SERIES DIRECT VENT GAS APPLIANCE
III. FIREPLACE SYSTEM COMPONENTS
The table below is a list of only those components
which may be safely used with this fireplace. An
illustration of each component can be found on
page 5.
(Natural gas models may be converted to propane gas using the CKP
conversion kit)
CKPNatural gas to propane gas conversion kit
BC10Fan motor rheostat control
BC11Automatic Variable Blower Control
CSDirect vent cap shield (for horizontal termination)
CV7Vertical termination cap
EL4545 degree elbow
FK4Fan kit
FS6Firestop spacer (for vertical termination)
RC4Remote control (standing pilot)
RC5Remote control (electronic ignition)
RF6Roof Flashing (for vertical termination)
1243SSteep Pitch Roof Flashing
TA2Horizontal termination kit including one termination cap, one starter elbow (15942),
(Must be the elbow closest to unit
when horizontal venting begins.)
Termination Cap
VK24
Vent Section
2-99621322L
INSTALLATION AND REPAIR SHOULD BE DONE BY A QUALIFIED SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A QUALIFIED SERVICE PERSON.
MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY
FROM FURNITURE AND DRAPERIES.
WARNING!
THIS APPLIANCE MAY ONLY USE THE DIRECT VENT CHIMNEY SYSTEM DESIGNED FOR USE
WITH THE UNIT AND MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVICING A SEPARATE SOLID FUEL OR GAS FUEL BURNING APPLIANCE.
GC150 SERIES DIRECT VENT GAS APPLIANCE
IV. PRE-INSTALLATION PREPARATION
A. GAS PRESSURE
For natural gas, the minimum inlet gas supply pressure is
4.5 inches water column, and the maximum inlet gas pressure is 7.0 inches water column, for the purpose of input
adjustment. Input rate is 22,500 Btu/hr. For propane gas,
the inlet gas supply pressure must be at least 11.0 inches
water column and a maximum 14.0 inches water column.
(See CKP Natural Gas to Propane Gas Conversion Kit
installation instructions.)
A 1/8" NPT plugged tapping is provided on the gas control
valve, near the outlet to the main burner immediately
upstream of the gas supply connection to the appliance,
accessible for a test gage connection .
Optimum manifold pressure is 3.5 inches water column for
natural gas and 10.5 inches water column for propane gas.
C. FIREPLACE LOCATIONS AND
SPACE REQUIREMENTS
This appliance may be installed along a wall, across a
corner or use an exterior chase. The GC150 Series
may be installed at a height level with the floor, or it
can be raised up from the floor to enhance its visual
impact. Figure 1 illustrates a variety of ways the
appliance may be located in a room. These appliances are also certified for installation in a bedroom
or bed/sitting room in the U.S.
B. HIGH ALTITUDE INSTALLATION
For U.S. installation, units are tested and approved for elevations from 0-2000 feet.
When installing this unit at an elevation above 2000 feet,
United States codes require a decrease of the input rating
by changing the existing burner orifice to a smaller size.
Input should be reduced 4 percent for each 1000 feet
above sea level. Check with the local gas utility for proper
orifice size identification. This unit uses a .093in. /2.36
mm. orifice size on natural gas versions and a .056 in./1.42
mm. orifice size on propane gas converted versions.
Consult your local gas company for assistance in determining the proper orifice for your location or refer to ANSI
Z223.1-latest edition, Appendix F.
CAUTION:
DO NOT EXPOSE THE UNIT TO THE
ELEMENTS (SUCH AS RAIN, ETC.).
D. CLEARANCES
The following clearances to combustibles must be
maintained: Minimum clearances to the top standoffs
of the unit - 0", floor - 0", back - 1/2", sides - 1/2", top
of the hood to ceiling - 30". Minimum clearances to
venting are as follows: Horizontal runs require a 3"
minimum air space on the top and a 1" minimum air
space on the sides and bottom of the vent section.
Vertical rise sections require a 1" minimum air space
completely around the vent sections.
Fireplace Locations and Clearances
Figure 1
GC150 SERIES DIRECT VENT GAS APPLIANCE
WARNING!
AIR SLOTS ON THIS APPLIANCE CANNOT, IN ANY WAY, BE COVERED AS IT
MAY CREATE A FIRE HAZARD.
E. FRAMING THE FIREPLACE
Note: If an optional fan (FK4) or hand held remote
control (RC4 or RC5) are to be used, wiring must
be done prior to finishing to avoid reconstruction.
Note: The remote wall switch must be wired prior
to applying the finishing material in order to avoid
reconstruction.
The GC150 Series Gas Appliance will fit a framed
opening of 40" w X 161⁄2" d X 301⁄8" h.
Figure 2 - Framing the Fireplace
Figure 2a
Framing the Fireplace
F. FINISHING MATERIALS
Only non-combustible materials may be used to
cover the black surfaces of the fireplace front.
Combustible Finishing Material. Material made of
or surfaced with wood, compressed paper, plant
fibers, plastics, or any material capable of igniting
and burning, whether flame proofed or not, plastered
or unplastered.
Non-combustible Finishing Material. Material
which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or combination thereof.
High Temperature Sealant Material. Sealants that
will withstand high temperatures (300° F+); General
Electric RTV103 (Black), or equivalent. Rutland, Inc.
Fireplace Mortar #63, or equivalent.
After completing the framing and applying the finishing material (dry wall) over the framing, a non-combustible sealant, one-half inch wide maximum, must
be used to close off any gaps at the top and sides
between the fireplace and facing to prevent cold air
leaks. See Figure 3.
Figures 2 and 2a show a typical framing of this fireplace assuming combustible materials are used. All
required clearances to combustibles around the fireplace must be adhered to. A 1/2" air clearance must
be maintained at the back and sides of the firebox
assembly. A minimum of 38” is required to the bottom of a 7” mantle. Anything greater than 7” must be
42” above the base of the unit. Any framing on top of
the fireplace must be above the top standoffs. Vent
sections for a horizontal run require a 3" minimum air
space on top and a 1" minimum air space on the
sides and bottom. Vertical rise sections require a 1"
minimum air space completely around the vent sections.
Flue outside diameter: 8"
Minimum firestop framing: 10" X10"
Face of header to the center of the firestop spacer
(FS6) framing: 8
7
/
8"
Figure 3
Finishing Materials
Note:The outside walls of the home around the
fireplace should be insulated and finished as
one would any other outside wall, while maintaining the 1/2"air clearance around the firebox.
12-98721322K
GC150 SERIES DIRECT VENT GAS APPLIANCE
V. STEP-BY-STEP INSTALLATION OF
THE FIREPLACE SYSTEM
WARNING!
BEFORE STARTING, DO THE FOLLOWING:
1. WEAR GLOVES AND SAFETY GLASSES FOR PROTECTION.
2. KEEP HAND TOOLS IN GOOD CONDITION. SHARPEN CUTTING EDGES AND MAKE SURE TOOL
HANDLES ARE SECURE.
3. ALWAYS MAINTAIN THE MINIMUM AIR SPACE REQUIRED TO THE ENCLOSURE TO PREVENT FIRE.
STEP 1 - Positioning the Firebox
This fireplace may be placed on a smooth combustible or noncombustible continuous, flat surface. When the appliance is
installed directly on carpeting, tile or other combustible material
other than wood flooring, the appliance shall be installed on a
metal or wood panel extending the full width and depth of the appliance.
Slide the unit into position and level the fireplace from sideto-side and front-to-back. Shim with non-combustible material,
such as sheet metal, as necessary.
Secure the fireplace by bending out the nailing flanges located on
each side of the fireplace and nailing the unit to the framing. See
Figure 4.
STEP 2 - Termination
Two types of termination are available for this appliance, horizontal and vertical. For vertical termination, skip section A and
advance to section B on page 11.
A. Horizontal Termination
Minimum combustible clearances to the vent on a horizontal run
is 3" on top and 1" on the bottom and sides. These clearances
must be maintained at all times. The maximum horizontal run
allowed for venting is 26 feet. The maximum vertical rise allowed
for horizontal termination is 25 feet. See Figure 5.
1. Assembling vent sections. Attach either a VE12 (starter
elbow), VE16, VE20 or straight vent section (depending upon
your specific installation) to the top of the appliance. Secure
with the three screws supplied. Use only vent supplied and
listed for use with this appliance and the appropriate number of
direct vent sections. MAINTAIN MINIMUM CLEARANCESOR GREATER AROUND THE VENT SYSTEM. Do not pack
air spaces with insulation or other material.
a. Using elbows. The first elbow used with horizontal termination must be starter elbow 15942. The maximum horizontal
distance this vent system may reach is 26'. No more than 3elbows may be used. A single vertical-to-horizontal elbow is
already calculated into the allowable 26' run. Each additional
elbow reduces the maximum horizontal distance by three feet.
Example, by using three total elbows, the maximum horizontal
distance has been reduced to twenty feet (3 - 1 = 2 elbows X 3'
= 6'; 26' max. - 6' of elbows = 20' of horizontal run).
AB
Figure 4
Nailing Flanges
Figure 5 - Horizontal Length
Note: The horizontal run of vent must have a
1/4" rise for every 1 ft. of run towards the termination. Never allow the vent to run downward. This could cause high temperatures
and may present the possibility of a fire.
1-99821322L
b. Amount of venting required. Due to the many
different combinations that can be used when constructing venting, the number of vent sections
required can only be determined by the installer.
1-99921322L
GC150 SERIES DIRECT VENT GAS APPLIANCE
4. Venting through the wall. Horizontal venting
must terminate within the shaded area shown in
Figure 5 on the previous page. For example, if
your vertical rise is the minimum one foot, venting
can terminate anywhere between 16 inches and 3
feet.
The last section of vent may require cutting, depend-
ing upon wall thickness and appliance location. The
end of the vent must penetrate the exterior wall. Cut
the pipe so the outer vent section extends past the
exterior wall by 1" and the inner vent section extends
past the exterior wall by 21⁄2". See Figure 8.
2. Preparing the wall for interior wall shield. A
hole measuring 10" wide X 12" high must be cut
and framed in the exterior wall where venting will
be terminated. If the wall being penetrated is constructed of non-combustible material, i.e. masonry
block or concrete, a 9" diameter port is acceptable.
The hole must be positioned so the vent system
will have a 1/4" rise for every 12" of run AND be
perpendicular to the wall. See Figure 6. The
height of the hole must be located to meet all local
and national codes and not be easily blocked or
obstructed. The minimum height to the top of the
exterior wall hole is 45” from the base of the unit.
This figure will increase by the length of each verti-
cally positioned vent section added to the venting
system.
3. Interior Wall Shield. An interior wall shield
must be installed each time the venting system
penetrates a wall. This shield has been designed
to maintain the minimum clearances needed for
the venting system and prevent cold air infiltration.
After the venting hole has been cut and framed,
secure an interior wall shield into position with four
1" fasteners, one in each corner. Bend out the
tabs located on the inner portion of the wall shield
and use a 1/2" screw to secure each tab to the
penetrating pipe. See Figure 7. (1/2" screws are
used to avoid penetrating the inner pipe.)
Note: Horizontal runs will require the use of
one Vent Support (VS4) for every 3' of vent.
Note: Exterior wall thickness must be a minimum of 4" to a maximum of 231⁄2”.
Figure 6
Exterior Wall Hole
Figure 7
Interior Wall Shield
Figure 8
Venting Through the Wall
NOTE: IF THE TERMINATION CAP IS SURROUNDED BY VINYL SIDING OR IS LOCATED BELOW A VINYL SOFFIT, A VINYL
SHIELD MUST BE USED TO PREVENT DAMAGE TO THE VINYL.
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.