HEAT-ZONE-WOOD AIR DUCT KIT
Ceiling Register
Wall Register
Floor Register
Two Duct Kits
Ceiling Register
12" (305mm) minimum clearance
from register to ceiling
Part No: HEAT-ZONE-WOOD
APPROVALS
The Heat-Zone-Wood air duct kit is approved to
use on EPA Fireplaces 7100FP, North Star and
Constitution.
INTRODUCTION
The Heat-Zone-Wood accessory kit conveys warm
air from the replace through air duct(s) to remote
locations in the same room or other rooms of the
building. See Figure 1. One or two Heat-Zone
kits can be installed on the replace.
Possible Air Duct Runs / Locations
PRELIMINARY PREPARATION
1. Contents of kit:
• 16” Snap Lock Starter pipe - cut to
desired length (See Figure 2 on page 2).
• Mounting Plate
• Adapter
• Fan Housing Assembly
• Return Air Grille
• Gasketing
• Variable Speed Wall Rheostat
• Fastener Package
If any parts are missing or damaged, contract your dealer
before starting installation. DO NOT install a damaged kit.
1445 North Highway
Colville, WA 99114
7015-114 September 5, 2003 Page 1 of 4
Figure 1
www.quadrare.com
2. This kit is tested and safe when installed in
Adapter
Mounting
Plate
Starter Pipe
Knockout
Cut a
3
"
(
7
6
m
m
)
ho
l
e
in
in
su
l
a
t
io
n
3-13/16"
(97mm)
3-1/8" (79mm)
C
L
accordance with this installation manual. It is your
responsibility to read all instructions before starting installation and to follow these instructions
carefully during installations.
3. Installation of this kit MUST by performed by a
qualied service technician.
4. The Heat-Zone-Wood kit is carefully engineered
and must be installed only as specied. If you
modify it or any of its components you will void
the warranty and you may possibly cause a re
hazard. Installation must be done according to
applicable local, state, provincial and/or national
codes.
5. CAUTION: ALL wiring should be done by a
qualied electrician and shall be in compliance
with local codes and with the National Electric
Code ANSI/NFPA No. 70-current (in the United
States) or with the current CSC22.1 Canadian
Electric Code (in Canada).
6. Plan the location of the replace and warm air
duct run(s).
DUCT RUN REQUIREMENTS
MAXIMUM Duct Run = 40-ft (12m)
MINIMUM Duct Run = 36” (914mm)
DUCTING MATERIAL
6 inch (152mm) B-Vent Only
DO NOT DUCT into existing furnace plenum
Figure 2
Run Length Cut Pipe
20 - 40 ft (6-12m) 2” (51mm)*
*A minimum of 2” (51mm) pipe must be used to
cover the raw insulation to prevent it tfrom blowing
out through the Return Air Grille.
10 - 20 ft (3 - 6m) 8” (203mm)
3 - 10 ft (1 - 3m) No cut needed**
**Use full 16” (406mm) as supplied
Figure 3
MINIMUM CLEARANCE TO COMBUSTIBLES
1 inch (25mm) from the B-Vent
1
/2 inch (13mm) from top & bottom of outlet box
0 inch (0mm) from the sides of outlet box
12” (305mm) from wall register to ceiling*
*(See Figure 1 on page 1).
INSTALLATION
1. Remove the knockout or cover plate from the top of
the replace and discard it. See Figure 2.
2. Cut a 3” (76mm) hole in the insulation board as per
the dimensions shown in Figure 2.
3. Determine the necessary length of starter pipe from
the following table and cut as required. See Figure 3.
4. The starter pipe is shipped at. After cutting to the
required length, manually roll the pipe together and
snap lock into place. NOTE: It is important the pipe
length be adhered to or it will affect the performance of your replace.
7015-114 September 5, 2003 Page 2 of 4
5. On the Mounting Plate, hand bend the tabs downward. Slide the tabs over the outside of the starter
pipe. Secure with 4 sheet metal screws included in
fasteners package. Figure 4
6. Slide the starter pipe into the replace, matching
the holes in the plate to the holes in the replace.
7. Place the Adapter on the Mounting Plate lining up
holes. Using the 4 sheet metal screws included in the
kit, secure the Adapter and Mounting Plate into re-
Figure 4