Heat & Glo HEAT-ZONE-WOOD Installation and operation guide

HEAT-ZONE-WOOD AIR DUCT KIT
Ceiling Register
Wall Register
Floor Register
Two Duct Kits
Ceiling Register
12" (305mm) minimum clearance from register to ceiling
Part No: HEAT-ZONE-WOOD
APPROVALS
The Heat-Zone-Wood air duct kit is approved to use on EPA Fireplaces 7100FP, North Star and Constitution.
INTRODUCTION
The Heat-Zone-Wood accessory kit conveys warm air from the replace through air duct(s) to remote locations in the same room or other rooms of the building. See Figure 1. One or two Heat-Zone kits can be installed on the replace.
Possible Air Duct Runs / Locations
PRELIMINARY PREPARATION
1. Contents of kit:
• 16” Snap Lock Starter pipe - cut to desired length (See Figure 2 on page 2).
• Mounting Plate
• Adapter
• Fan Housing Assembly
• Return Air Grille
• Gasketing
• Variable Speed Wall Rheostat
• Fastener Package
If any parts are missing or damaged, contract your dealer before starting installation. DO NOT install a damaged kit.
1445 North Highway Colville, WA 99114
7015-114 September 5, 2003 Page 1 of 4
Figure 1
www.quadrare.com
2. This kit is tested and safe when installed in
Adapter
Mounting Plate
Starter Pipe
Knockout
Cut a
3
"
(
7
6
m
m
)
ho
l
e
in
in
su
l
a
t
io
n
3-13/16" (97mm)
3-1/8" (79mm)
C
L
accordance with this installation manual. It is your responsibility to read all instructions before start­ing installation and to follow these instructions carefully during installations.
3. Installation of this kit MUST by performed by a qualied service technician.
4. The Heat-Zone-Wood kit is carefully engineered and must be installed only as specied. If you modify it or any of its components you will void the warranty and you may possibly cause a re hazard. Installation must be done according to applicable local, state, provincial and/or national codes.
5. CAUTION: ALL wiring should be done by a qualied electrician and shall be in compliance with local codes and with the National Electric Code ANSI/NFPA No. 70-current (in the United States) or with the current CSC22.1 Canadian Electric Code (in Canada).
6. Plan the location of the replace and warm air duct run(s).
DUCT RUN REQUIREMENTS
MAXIMUM Duct Run = 40-ft (12m) MINIMUM Duct Run = 36” (914mm)
DUCTING MATERIAL
6 inch (152mm) B-Vent Only DO NOT DUCT into existing furnace plenum
Figure 2
Run Length Cut Pipe 20 - 40 ft (6-12m) 2” (51mm)*
*A minimum of 2” (51mm) pipe must be used to cover the raw insulation to prevent it tfrom blowing
out through the Return Air Grille.
10 - 20 ft (3 - 6m) 8” (203mm) 3 - 10 ft (1 - 3m) No cut needed**
**Use full 16” (406mm) as supplied
Figure 3
MINIMUM CLEARANCE TO COMBUSTIBLES
1 inch (25mm) from the B-Vent 1
/2 inch (13mm) from top & bottom of outlet box 0 inch (0mm) from the sides of outlet box 12” (305mm) from wall register to ceiling* *(See Figure 1 on page 1).
INSTALLATION
1. Remove the knockout or cover plate from the top of the replace and discard it. See Figure 2.
2. Cut a 3” (76mm) hole in the insulation board as per the dimensions shown in Figure 2.
3. Determine the necessary length of starter pipe from the following table and cut as required. See Figure 3.
4. The starter pipe is shipped at. After cutting to the required length, manually roll the pipe together and snap lock into place. NOTE: It is important the pipe
length be adhered to or it will affect the perfor­mance of your replace.
7015-114 September 5, 2003 Page 2 of 4
5. On the Mounting Plate, hand bend the tabs down­ward. Slide the tabs over the outside of the starter pipe. Secure with 4 sheet metal screws included in fasteners package. Figure 4
6. Slide the starter pipe into the replace, matching the holes in the plate to the holes in the replace.
7. Place the Adapter on the Mounting Plate lining up holes. Using the 4 sheet metal screws included in the kit, secure the Adapter and Mounting Plate into re-
Figure 4
Loading...
+ 2 hidden pages