Heat & Glo Heat-Zone-Gas Air Duct Kit Installation & Operation Instructions

Page 1
Heat-Zone-Gas Air Duct Kit
- Installation & Operation Instructions -
The flexible duct in this Heat-Zone-Gas air duct kit is manufactured and marked to the requirements of UL­181, Class I air duct.
INTRODUCTION
The Heat-Zone-Gas accessory kit conveys warm air from the fireplace through air duct(s) to remote locations in the same room or other rooms of the building. See Figure 1. One or two Heat-Zone-Gas kits can be installed on the fireplace.
Possible Air Duct Runs/Locations
PRELIMINARY PREPARATION
Contents of kit:
DESCRIPTION SERVICE PART NO.
20 Ft Length of 6" Round Duct 659-200 Fan Housing Assembly 659-001A Junction Box 659-122 Variable Wall Rheostat BC10 Air Register 659-150 Register Adaptor Frame-Thick 695-125 Fireplace Duct Collar 659-125 Duct Adaptor (Round to Oval) 659-129 Hardware Bag 659-90 0 A
If any parts are missing or damaged, contact your Dealer before starting installation. DO NOT install a damaged kit. Be sure to also reference the fireplace Installers Guide.
Ceiling Register
Wall Register
Floor Register
Figure 1
Printed in U.S.A. Copyright 2005 Hearth & Home Technologies Inc., 20802 Kensington Boulevard, Lakeville, MN 55044
1
Two Duct Kits
659-900J 9/05
Page 2
This kit is tested and safe when installed in accordance with this installation manual. It is your responsibility to read all instructions before starting installation and to follow these instructions carefully during installation.
Installation of this kit MUST be performed by a qualified service technician.
The Heat-Zone-Gas kit is carefully engineered and must be installed only as specified. If you modify it or any of its components you will void the warranty, and you may possibly cause a fire hazard. Installation must be done according to applicable local, state, provincial, and/or national codes.
CAUTION: All wiring should be done by a qualified electrician and shall be in compliance with local codes and with the National Electric Code ANSI/NFPA No. 70­current (In the United States), or with the current CSC22.1 Canadian Electric Code (in Canada).
Plan the location of the fireplace and the warm air duct run(s).
Figure 2
NOTE: If the fan housing is installed in a 2 x 4 wall, the
front of the housing will protrude approximately 1/2 - in. (13mm) out of the wall. See Figure 3.
MAXIMUM Duct Run = 20-ft. (6.1m) for useful heat output.
MINIMUM Duct Run = NA - for runs out from the fireplace to adjacent room OR down to the room below.
MINIMUM Duct Run = 31-in. (787mm) top of fireplace to room above.
INSTALLATION
Install the Heat-Zone-Gas kit following instruc­tions in the fireplace Installer's Guide.
FAN & ELECTRIAL CONNECTIONS
The fan and electrical connections must be accessible for servicing per local code requirements.
Mount and secure the fan housing assembly to framing members so the front surface is 1/4 -in. (6mm) below the finished wall or floor surface. Use the adjustable mounting brackets and screws provided in the kit. See Figure 2. NOTE: The brackets can be rotated 180o and mounted to the back side of the 2 x 4 if necessary.
2 x 4 Wall
Fan Housing
1/2 - in.
Figure 3
(13mm)
Install the air duct run. NOTE: Fold outer poly layer of flexible duct back to maintain clearance to combus­tibles on the fireplace. Secure liner to the collar with clamp provided.
2
Page 3
V
ROUND AIR DUCT: Attach the 6" round air duct (sup-
plied in the kit) to the fireplace collar with sheet metal screws and run the duct to the fan housing. Att ach the round-to-oval adapter to the fan housing and the air duct to the adapter. See Figure 4.
OV AL AIR DUCT: Attach the round-to-oval adapter to the fireplace starting collar with sheet metal screws and a 6" oval duct to the adapter. Complete the duct run and attach the oval duct to the fan housing. NOTE: 6" metal oval air duct is NOT provided with this kit but can be purchased from an HV AC supplier.
ROUND and OV AL DUCT: A combination of 6" round and 6" oval air duct can be used in the duct run. Oval duct components must be purchased from an HV AC supplier.
Install the variable speed (with "OFF" setting) wall Rheo­stat in a convenient location. This switch will control the HEA T-ZONE-GAS fan operation.
Remove duct cover. Wire 1 10 V AC service TO the wall Rheostat and FROM the wall Rheostat to the fan junc­tion box. Use wire nuts to secure the 1 10 VAC service wires to the hot and neutral fan wires and screw the 110 VAC ground wire to the fan box. See Wiring Dia­gram - Figure 5.
Screw the duct cover to the fan box. Screw the register adapter frame and the air register to
the fan housing.
Support duct at intervals of no greater than four feet, with no more than 1/2" sag between supports as re­quired by local code. NOTE: Secure the duct so that clearance to the fireplace outer wrap is maintained. T ape all seams with aluminum t ape (1-1/4" minimum width, or as specified by local codes).
Fan Housing
Round to Oval Adapter
6" Round Air Duct
Figure 5
Figure 4
USE WIRE NU TS TO
SECURE THE 110 VAC
SERVICE WIRES TO THE HOT
AND NEUTRAL FAN WIRES
Complete the fireplace installation per instructions.
OPERATION
Start the fireplace per instructions and allow it to warm up.
Turn the wall Rheostat "ON" and adjust the variable speed based upon desired air flow at the air duct regis­ter.
MAINTENANCE
Service and maintain the gas fireplace per instructions. Keep the air register(s) clean and free of any blockage.
WIRE 110
AC SERVICE
FAN BOX
FAN
GROUND
SCREW
RHEOSTAT
BLACK HOT
WHITE NEUT RAL
COPPER GROUND
RHEOSTAT JUNCTION BOX
DUCT
COVER
BLACK
WHITE
GROUND
3
Loading...