Heat & Glo Heat-Zone-Gas Air Duct Kit Installation & Operation Instructions

Heat-Zone-Gas Air Duct Kit
- Installation & Operation Instructions -
The flexible duct in this Heat-Zone-Gas air duct kit is manufactured and marked to the requirements of UL­181, Class I air duct.
INTRODUCTION
The Heat-Zone-Gas accessory kit conveys warm air from the fireplace through air duct(s) to remote locations in the same room or other rooms of the building. See Figure 1. One or two Heat-Zone-Gas kits can be installed on the fireplace.
Possible Air Duct Runs/Locations
PRELIMINARY PREPARATION
Contents of kit:
DESCRIPTION SERVICE PART NO.
20 Ft Length of 6" Round Duct 659-200 Fan Housing Assembly 659-001A Junction Box 659-122 Variable Wall Rheostat BC10 Air Register 659-150 Register Adaptor Frame-Thick 695-125 Fireplace Duct Collar 659-125 Duct Adaptor (Round to Oval) 659-129 Hardware Bag 659-90 0 A
If any parts are missing or damaged, contact your Dealer before starting installation. DO NOT install a damaged kit. Be sure to also reference the fireplace Installers Guide.
Ceiling Register
Wall Register
Floor Register
Figure 1
Printed in U.S.A. Copyright 2005 Hearth & Home Technologies Inc., 20802 Kensington Boulevard, Lakeville, MN 55044
1
Two Duct Kits
659-900J 9/05
This kit is tested and safe when installed in accordance with this installation manual. It is your responsibility to read all instructions before starting installation and to follow these instructions carefully during installation.
Installation of this kit MUST be performed by a qualified service technician.
The Heat-Zone-Gas kit is carefully engineered and must be installed only as specified. If you modify it or any of its components you will void the warranty, and you may possibly cause a fire hazard. Installation must be done according to applicable local, state, provincial, and/or national codes.
CAUTION: All wiring should be done by a qualified electrician and shall be in compliance with local codes and with the National Electric Code ANSI/NFPA No. 70­current (In the United States), or with the current CSC22.1 Canadian Electric Code (in Canada).
Plan the location of the fireplace and the warm air duct run(s).
Figure 2
NOTE: If the fan housing is installed in a 2 x 4 wall, the
front of the housing will protrude approximately 1/2 - in. (13mm) out of the wall. See Figure 3.
MAXIMUM Duct Run = 20-ft. (6.1m) for useful heat output.
MINIMUM Duct Run = NA - for runs out from the fireplace to adjacent room OR down to the room below.
MINIMUM Duct Run = 31-in. (787mm) top of fireplace to room above.
INSTALLATION
Install the Heat-Zone-Gas kit following instruc­tions in the fireplace Installer's Guide.
FAN & ELECTRIAL CONNECTIONS
The fan and electrical connections must be accessible for servicing per local code requirements.
Mount and secure the fan housing assembly to framing members so the front surface is 1/4 -in. (6mm) below the finished wall or floor surface. Use the adjustable mounting brackets and screws provided in the kit. See Figure 2. NOTE: The brackets can be rotated 180o and mounted to the back side of the 2 x 4 if necessary.
2 x 4 Wall
Fan Housing
1/2 - in.
Figure 3
(13mm)
Install the air duct run. NOTE: Fold outer poly layer of flexible duct back to maintain clearance to combus­tibles on the fireplace. Secure liner to the collar with clamp provided.
2
Loading...
+ 1 hidden pages