WARNING: IF THE INFORMATION
IN THESE INSTRUCTIONS IS NOT
FOLLOWED EXACTL Y, A FIRE OR
EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance.
- What to do if you smell gas
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the fire department.
- Installation and service must be performed by a
qualified installer, service agency, or the gas
supplier.
Installers Guide
Underwriters
Laboratories Listed
READ THIS MANUAL BEFORE INSTALLING OR
OPERATING THIS APPLIANCE. THIS INSTALLERSGUIDE MUST BE LEFT WITH APPLIANCE FOR
FUTURE REFERENCE.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN
CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR
ASSIST ANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIED INST ALLER, SERVICE AGENCY , OR THE
GAS SUPPLIER.
1.This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where not prohibited
by local codes.
2. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases, unless a certified kit is used.
Printed in U.S.A. Copyright 2005,
Heat & Glo, a brand of Hearth & Home Technologies Inc.
20802 Kensington Boulevard, Lakeville, MN 55044
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 481 1534, 5000162, 5016609, 5076254, 51 13843, 5191877, 5218953, 5263471,
5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195,
6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, D320652,
D445174, D462436; (Canada)1297749, 2195264, 2225408; or other U.S. and foreign patents pending.
Please contact your Heat & Glo dealer with any
questions or concerns. For the number of your nearest
Heat & Glo dealer, please call 1-888-427-3973.
1Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
SAFETY AND WARNING INFORMATION
READ and UNDERSTAND all instructions carefully
!
before starting the installation. FAILURE TO
FOLLOW these installation instructions may result
in a possible fire hazard and will void the warranty.
Prior to the first firing of the fireplace, READ the
!
Using Your Fireplace section of the Owners Guide.
DO NOT USE this appliance if any part has been
!
under water. Immediately CALL a qualified service
technician to inspect the unit and to replace any part
of the control system and any gas control which has
been under water.
THIS UNIT IS NOT FOR USE WITH SOLID FUEL.
!
Installation and repair should be PERFORMED by a
qualified service person. The appliance and venting
!
system should be INSPECTED before initial use
and at least annually by a professional service
person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding
material, etc. It is IMPERATIVE that the unit’s
control compartment, burners, and circulating air
passageways
adequate combustion and ventilation air.
BE KEPT CLEAN to provide for
These units MUST use one of the vent systems
described in the Installing the Fireplace section of
!
the Installers Guide. NO OTHER vent systems or
components MAY BE USED.
This gas fireplace and vent assembly MUST be
!
vented directly to the outside and MUST NEVER be
attached to a chimney serving a separate solid fuel
burning appliance. Each gas appliance MUST USE
a separate vent system. Common vent systems are
PROHIBITED.
INSPECT the external vent cap on a regular basis to
!
make sure that no debris is interfering with the air
flow.
The glass door assembly MUST be in place and
!
sealed, and the trim door assembly MUST be in
place on the fireplace before the unit can be placed
into safe operation.
DO NOT OPERATE this appliance with the glass
!
door removed, cracked, or broken. Replacement of
the glass door should be performed by a licensed
or qualified service person. DO NOT strike or slam
the glass door.
Always KEEP the appliance clear and free from
!
combustible materials, gasoline, and other
flammable vapors and liquids.
NEVER OBSTRUCT the flow of combustion and
!
ventilation air. Keep the front of the appliance
CLEAR of all obstacles and materials for servicing
and proper operations.
Due to the high temperature, the appliance should
be LOCATED out of traffic areas and away from
!
furniture and draperies. Clothing or flammable
material SHOULD NOT BE PLACED on or near the
appliance.
Children and adults should be ALERTED to the
!
hazards of high surface temperature and should
STAY AWAY to avoid burns or clothing ignition.
Y oung children should be CAREFULL Y SUPERVISED
when they are in the same room as the appliance.
The glass door assembly SHALL ONLY be
!
replaced as a complete unit, as supplied by the gas
fireplace manufacturer. NO SUBSTITUTE material
may be used.
DO NOT USE abrasive cleaners on the glass door
!
assembly. DO NOT ATTEMPT to clean the glass
door when it is hot.
Turn off the gas before servicing this appliance. It is
recommended that a qualified service technician
!
perform an appliance check-up at the beginning of
each heating season.
Any safety screen or guard removed for servicing
!
must be replaced before operating this appliance.
DO NOT place furniture or any other combustible
!
household objects within 36 inches of the fireplace
front.
2
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
TABLE OF CONTENTS
Safety and Warning Information ................................................ 2
Service Parts Lists ..................................................................... 4
Section 1: Approvals and Codes............................................... 7
Step 12 Before Lighting the Fireplace ....................................... 28
Step 13 Lighting the Fireplace .................................................. 28
After the Installation..................................................................... 28
Climate Control ........................................................................... 28
Section 4: Maintaining and Servicing Your Fireplace......... 29
Î = Contains updated information.
3Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Service Parts
GEM36
(NG , LP) Exploded Parts Diagram
(GN, PL) Vue éclatée des pièces
Beginning Manufacturing Date: 7-02
Ending Manufacturing Date: ______
10
1
4
2
3
5 Log set assembly
9
6
7
Part number list on following page.
*
La liste des numéros de pièce se
*
trouve à la page suivante.
4
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
8
Service Parts List / Liste des pièces de rechange
GEM36
IMPORTANT: THIS IS DATED INFORMA TION. The most current information is located on your dealers VIP site. When order-
ing, supply serial and model numbers to ensure correct service parts. / IMPORT ANT : L'information fournie dans cette brochure
n'est valide que pendant une courte période. Les sites VIP des distributeurs disposent des renseignements les plus récents.
Lors d'une commande, veuillez fournir les numéros de série et de modèles pour un remplacement adéquat des pièces.
ITEM /
PIÈCE
1Heat Shield / Pr otection(Bouclier) de Chaleur370-130
2Glass Door Assembly / Porte en verreGLA-GEM36
3L og Grate / Grille de Bûche
4B urner / Brûl eur
5L og Se t Assembly / Jeu de BûchesLOGS-GEM36
6L og 1 / Bûche 1SRV370-700
7L og 2 / Bûche 2SRV370-701
8L og 3 / Bûche 3SRV370-702
9L og 4 / Bûche 4SRV582-705
10Top Heat Shi eld / Protection(Boucli er) de Chaleur Supérieure370-140
Flue Restrictor 1-1/4" diameter / Restricteur de conduite de cheminée370-259
Flue Restrictor 1-1/2" d i a meter / Restricteur de condui te de cheminée370-260
Junction Bo x / Bo îti er de dé r ivat ion
3V Adaptor Plug / 3V Boucho n d'adapteur593-593A
DESCRIPTION
SERIAL #
/ N° DE SÉRIE
PRE 002330771
POST 002330771
PRE 002330771
POST 002330771
PRE 5-04
POST 5-04
PART NUMBE R
/ N° DE PIÈCE
370-360A
370-361A
SRV370-279A
SRV370-380A
383-250A
4021-013
Battery Pack / Paquet de Batteri e(Pi le)593-594A
Fan Kit / Module de ventilateurGFK-160A
Mineral Wool / Laine mi nérale050-721
Fiberglass Rope / Corde de fibre de verre060-455
Golden Embers / Braises doréesGE-93
Vermiculite Embers / Vermiculite BraisesMYSTIC-EMBERS
Temp la te / Gab ari tGEM36-TEMPLATE
ACCESSORIES / ACCESSOIRES
Wall S witch Kit, Off -w hite / Interr up teur mural, b lanc c r èmeWS K-21
Wall Switch Ki t, W hi te / Interrupteur mural, blancWSK-21-W
Multi-functional Wall Switc h / L e Commutateur de Mur multi-fonctionnelWSK-MLT
Heat-Out Kit / Chauffe-hors TrousseHEAT-OUT
Heat-Zone Kit / Trousse de chauffe-zoneHEAT-ZONE
Trim Door Mesh / Écran porte de garnitureMESH-GEM36
LP Conversion Kit / Module d e conversion PLLPK-GEM36
Fiber Patch Kit / La Trousse de Pièce de fibreSRV-PACK
5Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Service Parts
GEM36
Intermittent Pilot Ignition
Valve Assembly
11
12
(NG , LP) Exploded Parts Diagram
(GN, PL) Vue éclatée des pièces
9
10
5
Beginning Manufacturing Date: 7-02
Ending Manufacturing Date: ______
7
8
18
19
17
16
ITEM /
PIÈCE
1
2
2
3
4
5
6
7
7
8
9
10
11
12
13
14
15
16
17
18
19
19
13
14
ON/O F F R ock er Switch / Interrup teur à ba s cule MA RCHE/ARR ÊT060-521A
Valve NG / Valve GN750-500
Valve LP / Valve PL750-501
Flexible Gas Connector / Tuyau à gaz flexible567-301A
Module / Module593-592
Wire Assembly / Module de fil593-590A
Rheostat Assembly / Assemblée de Rhéostat100-510A
Pilot Assembly NG / Module de veilleuse GN370-510A
Pilot Assembly LP / Module de veilleuse PL370-511A
Pilot Bracket / Parenthèse Pilote370-165
Ground Strap / C ourroie de Raison(Terre)385-512
Valve B rac k e t / P a re nthè s e d e Valve37 0 - 1 5 5
Flex Ball Valve Assembly / Fléchir l'Assemblée de Soupape de Balle302-320A
Contro l Panel / Tableau de commande ava nt370 -153
Flame Control Knob / Flamber le Bouton de Contrôle571-531
Rheostat K nob - Black / Bouton de Rhéostat - Noir100-512
Shutte r R od / Tige d'Obtura teur370-350
Temp Sensor / Détecteur de température107-531
Orifice Bracket / Parenthèse d'Orifice370-120
Ha nd le / P oi g née319-167
Burner Orifice NG (#32C) / Orifice de brûleur GN (#32C)582-832
Burner Orifice LP (#50C) / Orifice de brûleur PL (#50C)582-850
20 inch Wire Harness / Harnais de fil107-559A
Pilo t S up p o rt / Pi lo te r le S outi e n385-120
1
DESCRIPTION
6
2
4
3
15
SERIAL #
/ N° DE SÉRIE
PART NUMBER
/ N ° D E P IÈCE
6
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
1
Approvals and
Codes
Appliance Certification
The Heat & Glo fireplace model discussed in this Installers
Guide has been tested to certification standards and listed
by the applicable laboratories.
Certification
MODEL: GEM36
LABORA TORY : Underwriters Laboratories
TYPE: Direct Vent Gas Fireplace Heater
ST ANDARD:
Installation Codes
The fireplace installation must conform to local codes. Before
installing the fireplace, consult the local building code
agency to ensure that you are in compliance with all
applicable codes, including permits and inspections.
In the absence of local codes, the fireplace installation must
conform to the National Fuel Gas Code ANSI Z223.1 (in
the United St ates) or the CAN/CGA-B149 Installation Codes
(in Canada). The appliance must be electrically grounded
in accordance with local codes or, in the absence of local
codes with the National Electric Code ANSI/NFPA No. 70
(in the United St ates), or to the CSA C22.1 Canadian Electric
Code (in Canada).
ANSI Z21.88-2000•CSA2.33-M98•UL307B
High Altitude Installations
U.L. Listed gas appliances are tested and approved without requiring changes for elevations from 0 to 2,000 feet in
the U. S. A. and in Canada.
When installing this appliance at an elevation above 2,000
feet, it may be necessary to decrease the input rating by
changing the existing burner orifice to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above a
2000 foot elevation in the U.S.A. or 10% for elevations
between 2000 and 4500 feet in Canada. If the heating value
of the gas has been reduced, these rules do not apply . To
identify the proper orifice size, check with the local gas
utility.
If installing this appliance at an elevation above 4,500 feet
(in Canada), check with local authorities.
These models may be installed in a bedroom or bed-sitting
room in the U.S.A. and Canada.
Heat & Glo Quality Systems
registered by SGS ICS
7Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
2
Getting Started
Introducing the Heat & Glo Gas Fireplaces
Heat & Glo direct vent gas fireplaces are designed to operate with all combustion air siphoned from outside of the
building and all exhaust gases expelled to the outside.
The information contained in this Installers Guide, unless
noted otherwise, applies to all models and gas control
systems. Gas fireplace diagrams, including the dimensions,
are shown in this section.
Pre-install Preparation
This gas fireplace and its components are tested and safe
when installed in accordance with this Installers Guide.
Report to your dealer any parts damaged in shipment,
particularly the condition of the glass. Do not install any
unit with damaged, incomplete, or substitute parts.
The vent system components and trim doors are shipped
in separate packages. The gas logs may be packaged
separately and must be field installed.
Read all of the instructions before starting the
installation. Follow these instructions carefully during
the installation to ensure maximum safety and benefit.
Failure to follow these instructions will void the
owner’s warranty and may present a fire hazard.
The Heat & Glo Warranty will be voided by , and Heat & Glo
disclaims any responsibility for, the following actions:
• Installation of any damaged fireplace or vent system
component.
• Modification of the fireplace or direct vent system.
• Installation other than as instructed by Heat & Glo.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not manufactured and approved by Heat & Glo, not withstanding
any independent testing laboratory or other party approval
of such component part or accessory .
ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE
HAZARD.
When planning a fireplace installation, it’s necessary to
determine:
• Where the unit is to be installed.
• The vent system configuration to be used.
• Gas supply piping.
• Electrical wiring.
• Framing and finishing details.
• Whether optional accessories—devices such as a fan,
wall switch, or remote control—are desired.
If the fireplace is to be installed on carpeting or tile, or on
any combustible material other than wood flooring, the
fireplace should be installed on a metal or wood panel that
extends the full width and depth of the fireplace.
8
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
8-5/32” (207.2mm)
42-13/16”
(1087.4mm)
36-3/16” (919.1mm)
18-3/32”
(459.6mm)
17-1/2” (444.8mm)
Ø8” (203mm)
41” (1041mm)
3”
(76.2mm)
(908.9mm)
5-3/16”
(131.9mm)
35-25/32”
TOP STANDOFFS
TRIM DOOR
37-3/4” (958.9mm)
TOP VENT
COLLARS
30-5/32”
(766mm)
(114.3mm)
2”
(50.8mm)
4-1/2”
HEAT-ZONE
KNOCKOUTS
HEAT -OUT
KNOCKOUT
GAS LINE
ACCESS
GAS
CONTROLS
Figure 1. Diagram of the GEM36
RATNG PLATES
AND LABELS
ELECTRICAL
ACCESS
ORIFICE
ACCESS PANEL
9Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
12” MIN. (304.8mm)
B
Installing the Fireplace
3
Constructing the Fireplace Chase
A chase is a vertical box-like structure built to enclose the
gas fireplace and/or its vent system. V ertical vents that run
on the outside of a building may be, but are not required to
be, installed inside a chase.
CAUTION: TREA TMENT OF FIRESTOP SPACERS AND
CONSTRUCTION OF THE CHASE MA Y V ARY WITH THE
TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT
SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL
BUILDING CODES. THEREFORE, YOUR LOCAL BUILDING CODES MUST BE CHECKED TO DETERMINE THE
REQUIREMENTS FOR THESE STEPS.
Factory-built fireplace chases should be constructed in the
manner of all outside walls of the home to prevent cold air
drafting problems. The chase should not break the outside
building envelope in any manner.
This means that the walls, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air
infiltration barriers should be installed in the chase as per
regional codes for the rest of the home. Additionally , Heat &
Glo recommends that the inside surfaces be sheetrocked
and taped for maximum air tightness.
T o further prevent drafts, the firestop s should be caulked to
seal gaps. Gas line holes and other openings should be
caulked or stuffed with insulation. If the unit is being installed on a cement slab, we recommend that a layer of
plywood be placed underneath to prevent conducting cold
up into the room. Be sure to include spark arrestors for
woodburning units if they are required.
THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL
CLEARANCES TO THE FIREPLACE ARE MAINT AINED
AS SPECIFIED WITHIN THIS INST ALLERS GUIDE.
Step 1. Locating the Fireplace
The following diagram shows space and clearance requirements for locating a fireplace within a room.
Clearance Requirements
The top, back, and sides of the fireplace are defined by
stand-offs. The minimum clearance to a perpendicular wall
extending past the face of the fireplace is 12” (304.8 mm).
The back of the fireplace may be recessed 17 1/2” (437.5 mm)
into combustible construction.
A
E
C
1/2” MIN. (13mm)
ABCD E
41-1/2”18”39”50.5”72”
Figure 2. Fireplace Dimensions, Locations,
and Space Requirements
* See Figure 3.
**The clearance to the ceiling is measured from the
top of the unit, excluding the standoffs.
The distance from the unit to combustible construction
is to be measured from the unit outer wrap surface to
the combustible construction, NOT from the screw heads
that secure the unit together.
For minimum clearances, see the direct vent termination
clearance diagrams on pages 19 and 20 in this manual.
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Step 2. Framing the Fireplace
Fireplace framing can be built before or after the fireplace is
set in place. Framing should be positioned to accommodate wall coverings and fireplace facing material. The diagram below shows framing reference dimensions.
Shows center of 10” x 12” vent framing
holes for top and rear venting. The center
of the hole is one (1) inch (25.4mm) above
the center of the horizontal vent pipe.
T
U
O
-
T
A
E
H
CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS AND WALL COVERING
DET AILS BEFORE FRAMING .
Framing should be
constructed of 2 X 4
lumber or heavier.
1/2” CLEARANCE
FROM BOTH SIDES
OF FIREPLACE
TO COMBUSTIBLE
FRAMING
MEMBER
C
D
E
A................. 41-1/2”
B........................ 43”
A
C................. 17-1/2”
D................. 54-1/2”
F
E.** ......... 22-15/16”
F.* ............... 49-1/2”
*Studs labeled “F” are necessary if installing the optional Arched Gem
Stone Kits (BKMS6052, BEMS6052, GRS6052)
**Heat-Out framing is 12 inches wide by 10 inches tall, opposite of vent
framing. Center of Heat-Out framing is 1-1/16 inch LOWER than the
center of the Heat-Out pipe.
1/2” CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE
These models are approved to use DVP-series direct vent
pipe components and terminations (see Figures 4 and 5).
Approved vent system components are labeled for identification. This pipe is tested and listed as an approved component of the fireplace. The pipe is tested to be run inside
an enclosed wall. There is no requirement for inspection
openings at each joint within the wall. There is no required
pitch for horizontal vent runs. NO OTHER VENTING SYS-TEMS OR COMPONENTS MA Y BE USED.
Detailed installation instructions are included with each vent
termination kit and should be used in conjunction with this
Installers Guide.
The flame and ember appearance may vary based on the type
of fuel burned and the venting configuration used.
VERTICAL
TERMINATION
Identifying Vent Component s
The vent systems installed on this gas fireplace may include one, two, or three 90° elbow assemblies. The relationships of vertical rise to horizontal run in vent configurations using 90° elbows MUST BE strictly adhered to. The
rise to run relationships are shown in the venting drawings
and tables. Refer to the diagrams on the next several pages.
NOTE: Two 45° elbows may be used in place of one
90° elbow. Rise to run ratios in the vent system must
be followed if 45° elbows are used.
STORM COLLAR
Î
HORIZONTAL
TERMINATION
T erminations Kits
WALL FIRESTOP
90 DEGREE
ELBOW
ROOF FLASHING
PIPE LENGTH
CEILING
FIRESTOP
PVK-80
DVP-TVHW
DVP-TRAP
SERIES
Figure 5.Vent System Component s and Termination Kits
13Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
STRAIGHT UP
VERTICAL VENTING
V (FT.)
40' MAX. (12.4 M)
NOTE: On vertical venting
configurations install the
vertical baffle found in your
manual bag per the flue
restrictor instructions in
this section.
CAP
1-1/4” & 1-1/2”
DIAMETER
V
Figure 8. Flue Restrictor
Pilot Shield Adjustment
Figure 6.
Straight Up Vertical Venting
Flue Restrictor Instructions
1. Locate the flue restrictors inside the unit to the left of the
control panel. There are two each of 1-1/4” diameter and
1-1/2” diameter. Use the following table to determine which
restrictors to use for the vent run.
Note: When venting this unit with high vertical (8 feet or
more) with very little horizontal the pilot shield will need to
be bent down in the closed position as shown in Figure 9.
PILOT
BRACKET
PILOT SHIELD
PILOT SHIELD SHOULD BE
CLOSED AND TOUC HING
THE PILOT BRACKET
Figure 9
Note: When venting this unit with long horizontal runs
and/or multiple elbows, the pilot shield will need to be in
the opened position as in Figure 10.
Í
Í
2. See Figure 7 for restrictor installation. Insert each restrictor in one of the 3” exhaust collars as shown.
FLUE
RESTRICTOR
FLUE
RESTRICTOR
Figure 7
14
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
PILOT SHIELD
BEND PILOT SHIELD UP 3/8”
TO ALLOW AIR FL OW TO
FEED THE PILOT FLAME
Figure 10
VENTING WITH ONE (1) 90° ELBOW
V
V
V
V
V (FT.) H (FT.)
1.5' MIN. (.457m) 3' MAX. (.912m)
2.5' MIN. (.762m) 6' MAX. (1.82m)
3.5' MIN. (1.06m) 9' MAX. (2.73m)
4.5' MIN. (1.37m)12' MAX. (3.64m)
5.5' MIN. (1.67m)15' MAX. (4.55m)
6.5' MIN. (1.98m) 18' MAX. (5.46m)
7.5' MIN. (2.28m)21' MAX. (6.37m)
8.5' MIN. (2.59m)24' MAX. (7.28m)
V = 40’ MAX. (12.2m)
4.5' MIN. (1.37m)12' MAX. (3.64m)
NOTE: H + H1 = 24' MAX. (7.28m)
V + V
+ H + H1= 64' MAX. (19.5m)
1
H
1
VENTING WITH THREE (3) 90° ELBOWS
V
1
H
V
1
H
1
V (FT.) H + H1 (FT.)
2' MIN. (.609m)3' MAX. (.912m)
2.5' MIN. (.762m)6 ' MAX. (1.82m)
3.5' MIN. (1.06m) 9' MAX. (2.73m)
4.5' MIN. (1.37m) 12' MAX. (3.64m)
H +H
= 20' MAX. (6.2m)
1
NOTE: V+V
+H +H
1
= 64' MAX. (19.5m)
1
H
Figure 13. Venting with three 90° elbows
16
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
B. Installing Vent Components
Venting Out the Top Vent
The glass must be taken off again for positioning the logs
when the unit is finally installed in place and finished around
it. Re-install the glass door . Attach vent system to the top
starting collars.
1. Att ach the First Vent Component to the
Starting Collars
T o attach the first vent component to the st arting collars of
the fireplace:
• Make sure that the fiberglass rope ring supplied in the
manual bag seals between the first 8 inch (203mm) vent
component and the outer fireplace wrap (see Figure 14).
OUTER
WRAP
FIRST VENT COMPONENT
WARNING: ENSURE THA T THE FIBERGLASS
!
GASKET SUPPLIED WITH THE FIREPLACE
SEALS BETWEEN THE FIRST VENT COMPONENT
AND THE OUTER FIREPLACE WRAP .
2. Continue Adding V ent Component s
• Continue adding vent components snap-locking, locking
each succeeding component into place.
• Ensure that each succeeding vent component is securely fitted and locked into the preceding component in the
vent system. Securing pipe sections with a maximum of
two screws is recommended.
• 90° elbows may be installed and rotated to any point
around the preceding component’s vertical axis. If an elbow does not end up in a locked position with the preceding component, attach with a minimum of two (2)
sheet metal screws.
FIBERGLASS ROPE
RING
Figure 14. Fiberglass Rope Ring
Refer to Cinch Pipe (DVP) and T ermination Cap installation
instructions.
3. Install Support Brackets
Refer to Cinch Pipe and Termination Cap installation
instructions.
17Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
4. Install Firestops
For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.
NOTE: Model DVP-TRAP does not need an exterior
firestop on an exterior combustible wall.
To install firestops for horizontal runs that pass through
either interior or exterior walls:
• Cut a 10-inch by 12-inch (254mm X 305mm) hole through
the wall.
NOTE: The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.
• Position the firestops on both sides of the hole previ-
ously cut and secure the firestops with nails or screws.
• The heat shields of the firestops MUST BE placed to-
wards the top of the hole.
• Continue the vent run through the firestops.
For Vertical Runs - One ceiling firestop is REQUIRED at
the hole in each ceiling through which the vent passes.
T o install firestops for vertical runs that pass through ceilings:
• Position a plumb bob directly over the center of the vertical vent component.
• Mark the ceiling to establish the centerpoint of the vent.
• Drill a hole or drive a nail through this centerpoint.
• Check the floor above for any obstructions, such as wiring or plumbing runs.
• Reposition the fireplace and vent system, if necessary,
to accommodate the ceiling joists and/or obstructions.
• Cut an 10-inch X 10-inch (254mm X 254mm) hole through
the ceiling, using the centerpoint previously marked.
• Frame the hole with framing lumber the same size as the
ceiling joists.
NOTE: There must be NO INSULA TION or other
combustibles inside the framed firestop opening.
10"
INTERIOR
WALL S HI ELD
Figure 15. 10" x 12" Hole and Vent Pipe
HEAT SHIELD
TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT
12"
10" (254mm)
10" (254mm)
CHIMNEY
HOLE
EXISTING CEILING
JOISTS
CEILING
NEW
FRAMING
MEMBERS
Figure 17. 10" x 10" Hole & New Framing Members
If the area above the ceiling is NOT an attic, position and
secure the ceiling firestop on the ceiling side of the previously
cut and framed hole.
NOTE: There must be NO INSULA TION or other
combustibles inside the framed firestop opening.
If the area above the ceiling IS an attic, position and secure
the firestop on top of the previously framed hole.
NOTE: Keep insulation away from the vent pipe at least
1 inch (25mm).
NAILS (4 REQUIRED)
RAFTER
C. V ent Termination
For Horizontal Terminations - To attach and secure the
termination to the last section of horizontal vent refer to the
Cinch Pipe and Termination Cap installation instructions.
• Push and snap-lock the ends as described at the beginning of the Installing V ent Components section.
• The termination kit should pass through the wall firestops
from the exterior of the building.
• Adjust the termination cap to its final exterior position on
the building.
WARNING: THE TERMINA TION CAP MUST BE
POSITIONED SO THA T THE ARROW IS POINT -
!
ING UP .
CEILING
CEILING FIRESTOP
Figure 19. Attic Firestop
For trapezoidal cap termination kits:
• Using screws secure the cap to the exterior wall through
the flanges in the cap.
WARNING: VENTING TERMINALS SHALL
!
NOT BE RECESSED INTO A W ALL OR SIDING. VENT TERMINATION CLEARANCES MUST
BE FOLLOWED TO AVOID FIRE DANGER. SEE
VENT TERMINA TION MINIMUM CLEARANCES DIAGRAM ON THE FOLLOWING P AGE.
S = 6" .......................... clearance from sides of elec-
(See Note 5)
trical service
T = 12"......................... clearance above electrical
(See Note 5)
service
** a vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings
and serves both dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on
a minimum of 2 sides beneath the floor, or meets Note 2.
NOTE 1: On private property where termination is less than 7 feet
above a sidewalk, driveway, deck, porch, veranda or balcony, use of
a listed cap shield is suggested.
NOTE 2: Termination in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum
between termination caps. 2. All mechanical air intakes within 10 feet
of a termination cap must be a minimum of 3 feet below the termination
cap. 3. All gravity air intakes within 3 feet of a termination cap must be
a minimum of 1 foot below the termination cap.
Figure 21. Vent Termination Minimum Clearances
NOTE 3: Local codes or regulations may require different
clearances.
NOTE 4: T ermination caps may be hot. Consider their proximity to
doors or other traffic areas.
NOTE 5: Location of the vent termination must not interfere with
access to the electrical service.
WARNING: In the U.S: V ent system termination is NOT permitted
in screened porches. You must follow side wall, overhang and
ground clearances as stated in the instructions.
In Canada: Vent system termination is NOT permitted in screened
porches. Vent system termination is permitted in porch areas
with two or more sides open. You must follow all side walls,
overhang and ground clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper performance of the fireplace when the venting system does not meet
these requirements.
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE
INSTALLED.
20
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
V
2 FT.
MIN.
TERMINATION
CAP
HORIZONTAL
OVERHANG
20 INCH MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
ERTICAL
WALL
IS X/ 12
WARNING: MAJOR U.S. BUILDING CODES
!
SPECIFY MINIMUM CHIMNEY AND/OR
VENT HEIGHT ABOVE THE ROOF TOP. THESE MINIMUM HEIGHTS ARE NECESSARY IN THE INTEREST OF SAFETY. SEE THE PREVIOUS DIAGRAM
FOR MINIMUM HEIGHTS, PROVIDED THE TERMINA TION CAP IS A T LEAST 20 INCHES FROM A VERTICAL WALL AND 2-FEET BELOW A HORIZONT AL
OVERHANG.
NOTE: This also pertains to vertical vent systems installed on the outside of the building.
T o seal the roof hole, and to divert rain and snow from the
vent system:
• Attach a flashing to the roof using nails, and use a nonhardening mastic around the edges of the flashing base
where it meets the roof.
Roof PitchH (min.) ft.
flat to 6/121.0
6/12 to 7/121.25
over 7/12 to 8/121.5
over 8/12 to 9/122.0
over 9/12 to 10/122.5
over 10/12 to 1 1/123.25
over 1 1/12 to 12/124.0
over 12/12 to 14/125.0
over 14/12 to 16/126.0
over 16/12 to 18/127.0
over 18/12 to 20/127.5
over 20/12 to 21/128.0
Figure 22. Minimum Height from Roof to
Lowest Discharge Opening
For Vertical Terminations - To locate the vent and install
the vent sections:
• Locate and mark the vent centerpoint on the underside
of the roof, and drive a nail through the centerpoint.
• Make the outline of the roof hole around the centerpoint
nail.
• The size of the roof hole framing dimensions depend on the
pitch of the roof. There MUST BE a 1-inch (25.4mm) clearance from the vertical vent pipe to combustible materials.
• Mark the roof hole accordingly.
• Cover the opening of the installed vent pipes.
• Cut and frame the roof hole.
• Use framing lumber the same size as the roof rafters
and install the frame securely . Flashing anchored to the
frame must withstand heavy winds.
• Continue to install concentric vent sections up through
the roof hole (for inside vent installations) or up past the
roof line until you reach the appropriate distance above
the roof (for outside terminations).
• Attach a storm collar over the flashing joint to form a
water-tight seal. Place non-hardening mastic around the
joint, between the storm collar and the vertical pipe.
• Slide the termination cap over the end of the vent pipe
and snap into place.
Step 4. Positioning, Leveling and
Securing the Fireplace
The diagram below shows how to properly position, level,
and secure the fireplace.
NAILING TABS
(BOTH SIDES)
Figure 23. Proper Positioning,
Leveling and Securing of a Fireplace
• Place the fireplace into position.
• Level the fireplace from side to side and front to back.
• Shim the fireplace with non-combustible material, such
as sheet metal, as necessary.
• Secure the fireplace to the framing by nailing or screwing.
21Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Step 5. Installing the Optional Heat-Out
or Heat-Zone Kits
Heat-Out Kit
Step 6 The Gas Control System
WARNING: THIS UNIT IS NOT FOR USE WITH
!
SOLID FUEL.
1. Remove the Heat-Out knockout from the fireplace and
discard it (see Figure 24).
2. Center the rear collar around the exposed hole and attach it to the fireplace with 3 screws. NOTE: Remove the
bottom knockout on the collar for typical 2 x 4 or 2 x 6 wall
construction. See Figure 24.
3. Cut and frame a 12” wide x 10” tall (305 x 254mm) hole in
the exterior wall. The center of the hole will be 22-15/16”
(583mm) above the base of the fireplace. See Figure 3.
4. Install the interior firestop with the hole towards the top.
Secure the firestop to wall framing members.
Reference the Heat-Out kit instructions for the remaining
installations steps.
NOTE: There must be NO INSULA TION or other combustibles inside the framed firestop opening.
HEAT-ZONE
KNOCKOUTS
HEAT-OUT
KNOCKOUT
The type of gas control system used with this model is
Intermittent Pilot Ignition.
Intermittent Pilot Ignition System
This system includes millivolt control valve, standing pilot,
thermopile/thermocouple flame sensor, and piezo ignitor .
WARNING: 110-120 VAC MUST NEVER BE
!
CONNECTED TO A CONTROL VALVE IN A
MILLIVOL T SYSTEM.
WARNING: CONTINUOUS 110-120 VAC SER-
!
VICE MUST BE WIRED DIRECTL Y TO THE FIREPLACE JUNCTION BOX.
Intermittent Pilot Ignition
FLAME SENSOR
ROD
REAR COLLAR
BOTTOM
KNOCKOUT
Figure 24
Heat-Zone Kit
1. Remove the knockout from the top of the fireplace and
discard it (see Figure 24).
2. Center the duct collar around the exposed hole and attach it to the fireplace with 3 screws. NOTE: Do this BE-FORE final positioning of the fireplace.
3. Determine the location for the air register/fan housing
assembly.
Reference the Heat-Zone kit instructions for the remaining
installations steps.
Figure 25. Gas Controls System
22
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Step 7. The Gas Supply Line
Step 8. Gas Pressure Requirements
NOTE: Have the gas supply line installed in accordance
with local building codes by a qualified installer approved and/or licensed as required by the locality . (In
the Commonwealth o f Massachusetts installation must
be performed by a licensed plumber or gas fitter).
NOTE: Before the first firing of the fireplace, the gas
supply line should be purged of any trapped air.
NOTE: Consult local building codes to properly size
the gas supply line leading to the 1/2 inch (13mm)
hook-up at the unit.
This gas fireplace is designed to accept a 1/2 inch
(13 mm) gas supply line. To install the gas supply line:
• A listed (and Commonwealth of Massachusetts approved)
1/2 inch (13mm) tee-handle manual shut-off valve and a
listed flexible gas connector are connected to the 1/2
inch (13mm) inlet of the control valve. NOTE: If substituting for these components, please consult local codes
for compliance.
• Locate the gas line access hole in the outer casing of
the fireplace.
• The gas line may be run from either side of the fireplace
provided the hole in the outer wrap does not exceed 2 1/2”
in diameter and it does not penetrate the actual firebox.
• The gap between the supply piping and gas access hole
can be plugged with non-combustible insulation to prevent cold air infiltration.
• Open the fireplace lower grille, insert the gas supply line
through the gas line hole, and connect it to the shut-off valve.
• When attaching the pipe, support the control so that the
lines are not bent or torn.
• After the gas line installation is complete, all connections must be tightened and checked for leaks with a
commercially-available, non-corrosive leak check solution. Be sure to rinse off all leak check solution following
testing.
Pressure requirements for Heat & Glo gas fireplaces are
shown in the table below .
Maximum Inlet14.0 inches14.0 inches
Gas Pressurew.c.w.c.
Manifold3.5 inches10.0 inches
Pressurew.c.w.c.
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
provided on the inlet and outlet side of the gas control for a
test gauge connection to measure the manifold pressure.
Use a small flat blade screwdriver to crack open the screw
in the center of the tap. Position a rubber hose over the tap
to obtain the pressure reading.
The fireplace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of one-half (1/2) psig (3.5 kPa).
The fireplace must be isolated from the gas supply piping
system by closing its individual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than one-half (1/2) psig (3.5 kPa).
WARNING: DO NOT USE AN OPEN FLAME TO
!
CHECK FOR GAS LEAKS.
• At the gas line access hole, use insulation to re-pack
the space around the gas pipe.
• Insert insulation from the outside of the fireplace and
pack the insulation tightly to totally seal between the
pipe and the outer casing.
23Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
LOW VOLTAGE
SEE NOTE 1
NEUTRAL
TRANSFORMER OUTLE T
PLUG-IN
3V TRANSFORMER
IGNITION
MODULE
(3V)
ON/OFF
WALL SWITCH
VALVE
GROUND
JUNCTION BOX
IGNITOR
MODULE
FLAME SPARKER /
SENSOR
OPTIONAL
BATTERY
BACK-UP
LOW VOLTAGE
SEE NOTE 1
REMOTE
CONTROL
HOT
R
T
A
ON/OFF
SWITCH
3V
O
R
R
E
M
N
F
S
3
V
BLACK
OPTIONAL
BATTERY
BACK-UP
RED
BROWN
BROWN
ORANGE (IG N I T OR )
I
WHITE (SENSO R )
S
BLACK
ORANGE
GREEN
NOTE 1: Ignition module, valve, pilot and wall switch operate on 3 volts.
120 VAC is required at junction box unless equipped with battery back-up.
SPARK TO
PILOT IGNITOR
GROUND TO
FIREPLACE
CHASSIS
PILOT ASSEMBLY
AND VALVE ASSEMBLY
MUST BE GROUNDED
(COMMON GROUND
WITH FIREPLACE
CHASSIS)
Figure 26. Intermittent Pilot Ignition (IPI) Wiring Diagram
Step 9. Wiring the Fireplace
Intermittent Pilot Ignition (IPI) Wiring
3 V olt Transformer
This appliance comes with a factory installed 3 volt transformer.
Operation with Battery Back-up
This appliance comes with a factory installed battery backup.
Appliance Requirements
This appliance requires that 1 10-120 VAC be wired to the
factory installed junction box. Maintain correct polarity when
wiring the junction box.
WARNING: DO NOT CONNECT 110-120 VAC
!
TO THE GAS CONTROL VALVE OR THE APPLIANCE WILL MALFUNCTION AND THE
V AL VE WILL BE DESTROYED.
Optional Accessories
Optional remote control kits require that 110-120 VAC be
wired to the factory installed junction box before the fireplace is permanently installed.
Wall Switch
Position the wall switch in the desired position on a wall.
Run a maximum of 25 feet (7.8 m) or less length of 18
A.W.G. minimum wire and connect it to the fireplace ON/
OFF switch pigtails.
WARNING: DO NOT CONNECT 110-120 V AC
!
TO THE WALL SWITCH OR THE CONTROL
V AL VE WILL BE DESTROYED.
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS
CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERA TION AFTER SERVICING .
Heat-Zone and Heat-Out kits are approved with this fireplace as heat management accessories.
24
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
SPEED CONTROL
(RHEOSTAT)
TEMPERATURE
SENSO R SWIT CH
Figure 27. Fan Wiring Diagram
FAN
JUNCTION BOX
Step 10. Finishing
Figure 28 shows the minimum vertical and corresponding
maximum horizontal dimensions of fireplace mantels or other
combustible projections above the top front edge of the
fireplace. See Figures 2 and 3 for other fireplace clearances.
Only non-combustible materials may be used to cover the
black fireplace front.
WARNING: WHEN FINISHING THE FIREPLACE,
!
NEVER OBSTRUCT OR MODIFY THE AIR INLET/OUTLET GRILLES IN ANY MANNER.
CEILING
1 IN. TYPICAL
12”
COMBUSTIBLE
SHEATHING
FIREPLACE
HEADER
TOP FRONT
EDGE OF FIREPLACE
NON-COMBUSTIBLE
SHEATHING
5”
4”
3”
2”
1”
13 IN. MINIMUM FROM TOP
OF ARCH OPENING TO
FIRST MANTEL PROJECTION
13 IN. MINIMUM NON-COMBUSTIBLE
SHEA T HING AB OVE FIREP LACE
11”
10”
9”
8”
7”
6”
ARCH OPENING
31 IN MINIMUM
CLEARANCE
CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS
AND THE FIREPLACE SURROUND (TOP AND SIDES)
ARE SEALED, A 300° F. MINIMUM SEALANT MATERIAL MUST BE USED. THESE JOINTS ARE NOT REQUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE
MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF
NEEDED) CAN BE APPLIED AS F ACING TO THE FIREPLACE SURROUND. SEE THE DIAGRAM BELOW .
FINISH WALL MATERIAL
MUST BE NON-COMBUSTIBLE
- TOP AND SIDES
NON-COMBUSTI BLE
41-1/2”
42”
TOP OF ARCH
OPENING
Figure 28.
Î
Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles above Fireplace
HIGH TEMPERATURE (3000F / 1490C MIN.)
TOP & SIDES SEAL JOINT
Figure 29. Sealant Material
WARNING: A 8” minimum hearth extension
!
is required to protect combustible floor construction in front of the fireplace. This hearth must
be constructed of non-combustible material and
extend the width of the fireplace.
Í
25Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Facing Requirements
Facing Thickness from 3/4” to 1-1/4”
Facing material within this thickness range can be brought
to 1/2” behind the door top and sides. These non-combustible finishing materials must never overlap or obstruct the
air outlet/inlet grille areas.
Facing Thickness greater than 1-1/4”
For facing material greater than 1-1/4” a template should be
constructed to provided the finishers with a guide so as to
leave a 1/8” gap between the finishing materials and the
door. See Figure 31 to construct the facing template.
NON-COMBUSTIBLE
MATERIAL*
HEADER
41-1/2”
*The fireplace requires a concrete board (or
other non-combustible material) extending from
the header to the floor and extending from framing stud to framing stud. 42” HT x 41-1/2” WD
42”
R39-7/8”
29-1/8”
21-1/2”
1-5/16”
3-1/8”
1-5/16”
38”
Figure 31. Facing Template Dimensions
NON-COMBUSTIBLE
BOARD
Ø
3/8”
24-5/16”
Figure 30.
IMPORTANT INSTALLATION NOTE
Please note that there are four holes or dots on the template to assist in positioning the template. These holes or
dots should line up with the door mounting holes on the unit
to ensure proper placement of the door after finishing materials are installed.
FACING TEMPLATE
Figure 32. Position of board and template
26
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Step 1 1. Inst alling T rim, Logs,
and Ember Material
Installing the Trim
Combustible materials may be brought up to the specified
clearances on the side and top front edges of the fireplace,
but MUST NEVER overlap onto the front face. The joints
between the finished wall and the fireplace top and sides
can only be sealed with a 300° F . (149° C) minimum sealant.
WARNING: WHEN FINISHING THE FIREPLACE,
!
NEVER OBSTRUCT OR MODIFY THE AIR INLET/
OUTLET GRILLES IN ANY MANNER.
Install optional marble and brass trim surround kits as
desired. Marble, brass, brick, tile, or other non-combustible
materials can be used to cover up the gap between the
sheet rock and the fireplace.
Do not obstruct or modify the air inlet/outlet grilles. When
overlapping on both sides, leave enough space so that the
bottom grille can be lowered and the trim door removed.
Positioning the Logs
If the gas logs have been factory installed they should not
need to be positioned. If the logs have been packaged
separately, refer to the instructions that accompany the
logs. Save the log instructions with this manual.
If sooting occurs, the logs might need to be repositioned
slightly to avoid excessive flame impingement.
Placing the Ember Material
• Save the remaining ember materials for use during fireplace servicing.
• Replace the glass door and a front trim door on the unit.
• Pull out and latch the glass clips into the groove on the
glass frame.
LATCHES
(BOTH BOTTOM
AND TOP)
GLASS
ASSEMBLY
Figure 34. Glass Assembly
Glass Specifications:
GEM42: CERAMIC
Note shutter
position
Ember material is shipped with this gas fireplace. T o place
the ember material:
• Pull the four glass latches out of the groove on the glass
frame. Remove glass door from the unit (see Figure 33).
• Embers CANNOT be placed directly over ports. Care
should be taken not to cover the lighting trail of ports
(from back to front).
• Place dime size pieces of mineral wool embers about 1/2
Î
inch apart near port holes in burner top. Do NOT press
embers into burner ports. Cover the top of the burner
with a single layer of ember material. For best performance do NOT place embers on the ports at the rear of
the burner (Figure 33). Failure to follow this procedure
will likely cause lighting and sooting problems.
EMBER
PLACEMENT
REMOVE 2
SCREWS
Figure 35.
Burner Removal
Note the position of the shutter and shutter stop bracket
(Figure 35). This will need to be re-set after replacing the
burner.
Remove the burner from the fireplace as shown in Figure
35. Remove the burner assembly by first removing the
screws (2) that secure it behind the burner surface. Slide
the adjustable shutter towards the rear of the fireplace
(closed position). Lift the burner up and towards you to
remove.
Í
Í
Í
Figure 33
27Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Step 12. Before Lighting the Fireplace
Before lighting the fireplace, be sure to do the following:
Remove all paperwork from underneath the fireplace.
Review safety warnings and cautions
• Read the Safety and Warning Information section at
the beginning of this Installers Guide.
Double-check for gas leaks
• Before lighting the fireplace, double-check the unit for
possible gas leaks.
Double-check vent terminations and front grilles for
obstructions.
• Before lighting the fireplace, double-check the unit for
possible obstructions that could be blocking the vent terminations or the front grilles.
Double-check for faulty components
• Any component that is found to be faulty MUST BE replaced with an approved component. T ampering with the
fireplace components is DANGEROUS and voids all warranties.
A small amount of air will be in the gas supply lines. When
first lighting the fireplace, it will take a few minutes for the
lines to purge themselves of this air. Once the purging is
complete, the fireplace will light and will operate normally.
Subsequent lightings of the fireplace will not require this
purging of air from the gas supply lines, unlessthe gasvalve has been turned to the OFF position, in which
case the air would have to be purged.
NOTE: The fireplace should be run 3 to 4 hours on the initial
start-up. Turn it of f and let it cool completely. Remove and
clean the glass. Replace the glass and run the fireplace for
an additional 8 hours. This will help to cure the products
used in the paint and logs.
Air Shutter Setting
This fireplace has an adjustable air shutter (which controls
the primary air) factory set for the minimum vertical vent run
(see Figure 36). If your installation has more than the
minimum required vertical vent length, adjustment of the air
shutter may be necessary to obtain optimal flame
appearance. This should be adjusted by a qualified
installer at the time of installation.
The air shutter handle has a gap maintainer clip factory
installed which needs to be removed to make any
adjustments. By pushing the air shutter handle in, you will
be closing the air shutter. Care should be taken when
adjusting the air shutter so as not to cause the fireplace to
soot. If sooting occurs the air shutter will need to be opened
by pulling the handle out.
Step 13. Lighting the Fireplace
You’ve reviewed all safety warnings, you’ve checked the
fireplace for gas leaks, you know the vent system is
unobstructed, and you’ve checked for faulty components.
Now you’re ready to light the fireplace.
WARNING: PLEASE REFER TO THE USER’S
!
MANUAL FOR ALL CAUTIONS, SAFETY,
AND WARNING INFORMATION PERTAINING TO
THE LIGHTING AND OPERATION OF THE
FIREPLACE.
After the Installation
LEAVE THIS INSTALLA TION MANUAL WITH
!
THE APPLIANCE FOR FUTURE REFERENCE.
Step 14. Climate Control
During this break-in period it is recommended that some
windows in the house be opened for air circulation. This will
help avoid setting off smoke detectors, and help eliminate
any odors associated with the fireplace’s initial burning.
GAP MAIN TAINER CLIP
AIR SHUTTER
HANDLE
Figure 36.
28
Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
This model is equipped with a baffle which will allow you to
control the usable heat output. The baffle control lever is located at the lower left corner of the unit behind the lower grille.
MORE HEA T : Pull handle down and push back to close the
damper.
LESS HEA T: Pull handle forward and push up to open the
damper.
BAFFLE
CONTROL
LEVER
Figure 37.
4
Maintaining and Servicing Your Fireplace
Fireplace Maintenance
Although the frequency of your fireplace servicing and maintenance will depend on use and the type of installation, you
should have a qualified service technician perform an appliance check-up at the beginning of each heating season.
See the table below for specific guidelines regarding each
fireplace maintenance task.
IMPORT ANT : TURN OFF THE GAS BEFORE SERVICING
YOUR FIREPLACE.
Replacing old ember material
Frequency: Once annually , during the checkup.
By: Qualified service technician.
Task: Brush away loose ember material near the burner.
Replace old ember material with new dime-size and shape
pieces. Save the remaining ember material and repeat this
procedure at your next servicing. For more information, see
Placing Ember Material.
Cleaning Burner and Controls
Frequency: Once annually .
By: Qualified service technician.
Task: Brush or vacuum the control compartment, fireplace
logs and burner areas surrounding the logs.
Cleaning Flame Sensor Rod (IPI Systems)
Frequency: Periodically .
By: Qualified service technician.
Task: Make a visual check of the straight flame sensor rod
(see Figure 25). Use emery cloth to carefully remove any
existing film or white deposits.
By: Qualified service technician/Home owner.
T ask: Make a visual check of your fireplace’ s flame patterns.
Make sure the flames are steady - not lifting or floating. The
thermopile/thermocouple tips should be covered with flame.
See Figure 25.
Checking Vent System
Frequency: Before initial use and at least annually
thereafter, more frequently if possible.
By: Qualified service technician/Home owner.
Task: Inspect the external vent cap on a regular basis to
ensure that no debris is interfering with the flow of air. Inspect
entire vent system for proper function.
Cleaning Glass Door
Frequency: After the first 3 to 4 hours of use. As neces-
sary after initial cleaning.
By: Home owner.
Task: Remove and clean glass after the first 3 to 4 hours of
use. Af ter the initial cleaning, clean as necessary , particularly after adding new ember (flame colorant) material. Film
deposits on the inside of the glass door should be cleaned
off using a household glass cleaner . NOTE: DO NOT handle
or attempt to clean the door when it is hot and DO
NOT use abrasive cleaners.
29Heat & Glo • GEM36 • 370-900 Rev. O • 2/05
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.