Heat Controller B-VMH09FC-1, B-VCH18FC-1, B-VMH18FC-1, A-VCH27TC-1, B-VMH12FC-1 User Manual

...
INSTALLATION
MANUAL
Indoor Models:
B-VCH12FC-1
B-VCH18FC-1 B-VMH09FC-1 B-VMH12FC-1 B-VMH18FC-1
Version C
InverterFlex
High Wall and Ceiling Cassettes
Outdoor Models:
A-VCH18DC-1
A-VCH27TC-1
A-VMH36QC-1
Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
Installation Manual VMH SerieS Heat Controller, Inc.
CONTENTS
SAFETY PRECAUTIONS
Warning ...........................................................................................................................................2
Caution ............................................................................................................................................2
Nomenclature Combinations...............................................................
INSTALLATION INSTRUCTIONS
Selecting installation place...............................................................................................................3
Wall-mounted type ...........................................................................................................................3
Accessori e s ......... . . . . . . . . . . . ...................
Four-way cassette type ................................................................................................................9
Duct & Ceiling type .......................................................................................................................12
Outdoor unit installation ........................................
......... . . . . . . . . . . . ................... . . . . . . . . . . . ................4
........................................................................23
REFRIGERANT PIPE CONNECTION
Refrigerant pipe connection ..........................................................................................................24
..............................................4
ELECTRICAL WORK
Electrical work .................. ...........................................................................................................25
AIR PURGING
Air purging with vacuum pump .....................................................................................................27
Safety and leakage check ............................................................................................................29
TEST RUNNING
Test running ..................................................................................................................................30
Read This Manual
Inside you will find many helpful hints on how to install and test the air conditioner properly. All the illustrations and specifications in the manual are subject to change without prior notice for product improvement. The actual shape should prevail.
CAUTION
Contact an authorised service technician for repair or maintenance of this unit. Contact an authorised installer for installation of this unit. The air conditioner is not intended for use by young children or infirmed persons without supervision. Young children should be supervised to ensure that they do not play with the air conditioner. If the power cord is to be replaced, replacement work shall be performed by authorised personnel only. Installation work must be performed in accordance with the national wiring Standards by authorised personnel only.
2
Heat Controller, Inc. VMH SerieS Installation Manual
SAFETY PRECAUTIONS
ead the fol low SAFETY PRECAUTIONS carefu lly before installation. lectric al work must be installed by a licensed elect rician. Be sure to use the correct rating
f the power p lug and main circuit for the model to be instal led.
ncorrec t installation due to ignoring of the instr uction will cause harm or damage.
The serio usness is classif ied by the followin g indications.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
The items to be followed are classified by the symbols:
Symbol with background white denotes item that is PROHIBITED from doing.
WARNING
1) Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock fire.
2) Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock fire.
3) Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall, water leakage, electrical shock fire.
4) Install at a strong and firm location which is able to withstand the set s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
5) For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock fire.
6) Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7) Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
8) When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
9) Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
,
CAUTION
1) This equipment must be earthed and installed with earth leakage current breaker. It may cause electrical shock if grounding is not perfect.
2) Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.
3) Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
3
Installation Manual VMH SerieS Heat Controller, Inc.
NOMENCLATURE
Outdoor Models:
A - VMH18DC - 1
Outdoor Inverter Multi-Zone
Heat
Pump
Mini-Split
Indoor Models:
B - VMH09FC - 1
Indoor Inverter Heat
M=Mini-Split high wall mount C=Ceiling cassette
Pump
Capacity 09=09kBtu/H* 12=12kBtu/H 18=18kBtu/H
*not available in ceiling cassette
Nominal Capacity 18=18kBtu/H 27=27kBtu/H 36=36kBtu/H
Voltage Code 1=208/230V-60hz-1PH
Design
Series
D=Dual Zone T-Tri-Zone Q-Quad Zone
Flexible Matching capabilities
4
Heat Controller, Inc. VMH SerieS Installation Manual
Combinations
Unit A
Unit B
9k
12k
18k
9k
9k
9k
12k
Combinations
Unit A
Unit B
Unit C
9k — —
12k — —
18k — —
9k
9k
9k
12k
9k
18k
12k
12k — TRI (1x3)
9k
9k
9k
Combinations
Unit A
Unit B
Unit C
Unit D
9k — —
12k — —
18k — —
9k
9k — —
9k
12k — —
9k
18k — —
12k
12k — —
12k
18k — —
18k
18k — —
9k
9k
9k
9k
9k
12k — 9k
9k
18k
9k
12k
12k
12k
12k
12k
QUA(1x4)
9k
9k
9k
9k
Unit combinations
NOTE: The total capacity of indoor air handlers can not exceed the nominal capacity of the outdoor unit.
The minimum quantity of indoor air handlers is one on any outdoor unit, whether it is a dual, tri, or quad zone.
Indoor unit combinations for A-VMH18DC-1
Comb.
Dual(1x1)
Dual (1x2)
Indoor unit combinations for A-VMH27TC-1
Comb.
TRI (1x1)
TRI (1x2)
Indoor unit combinations for A-VMH36QC-1
Comb.
QUA (1x1)
QUA (1x2)
QUA (1x3)
Available indoor models:
High Wall Mount Ceiling Cassette
9k B-VMH09FC-1 N/A
12k B-VMH12FC-1 B-VCH12FC-1
18k B-VMH18FC-1 B-VCH18FC-1
5
Installation Manual VMH SerieS Heat Controller, Inc.
INSTALLATION INSTRUCTIONS
NOTE: Indoor units shown can be replaced with ceiling cassettes.
More th an 15 cm
More th an 12 cm
2
1
3
Air fil ter
Remot e con troller
Air fil ter
Remot e con troller
Air fil ter
Remot e contr oll er
One-Two One-Thr ee One-Fou r
One-Fiv e
5
Remot e con troller
Air f il ter
Loop a conne cti ve cable
Remot e contr oll er
Air out
Air f il ter
4
6
CAUTIONS
This illustration is fo r explanation purposes only. The actual shape of your ai r condtioner may be slightl y different. Copper li nes must be insulated independently
CAUTION
NOTE : Ceiling cas settes come w ith an opti onal wall mou nted wirele ss thermo stat that c an take the pla ce of the wirel ess remo te controll er.
6
Heat Controller, Inc. VMH SerieS Installation Manual
7. Installation Details
7.1 Wrench torque sheet for installation
Outside diameter Torque Additional tightening torque
mm inch
N.m
N.m
Ф6.35 1/4 15(153kgf.cm) 16(163kgf.cm)
Ф9.52 3/8 25(255kgf.cm) 26(265kgf.cm)
Ф12.7 1/2 35(357kgf.cm) 36(367kgf.cm)
7.2 Connecting the cables
The power wiring should always follow NEC and local codes, with respect to the units, rating plate. See
installation manual for additional information. Main power connection is 208/230V/1PH~60HZ.
The communicating cable, which connects between the indoor and outdoor units must meet all NEC and
local codes, with respect to the unit’s rating plate. We recommend using 14 AWG/4 conductor Stranded THHN
6
Ф Ф V cable.
Pipe length and elevation
Pipe size
Unit
Gas inch
Liquid inch
(mm)
9K 3/8’’ (Ф9.52) 1/4’’ (Ф6.35)
12K/18K 1/2’’ (Ф12.7) 1/4’’ (Ф6.35)
Max. Total length for all rooms
(mm)
Standard
length
(m)
(5)
16.5ft
Dual-zone(m) Tri-zone(m) Quad-zone(m)
(30)100ft (45)150ft (60)200ft
Max.
Elevation
B (m)
(10)
33ft
Max.
Length
A (m)
(15)
50ft
2XWGRRUXQLW
2LOWUDS
,QGRRUXQLW
$
%
Additional
refrigerant
(g/m)
(20)
0.2 oz/ft
NOTES:
• Do not exceed 50 ft. (15m) per each indoor unit.
• Minimum pipe lenght of 10ft (3m) is required for each indoor unit.
• Oil trap should be installed per (3-5 meters) 10-15 ft., where outdoor unit is located above indoor unit.
• Outdoor connections are 1/4” (f6.35 mm) liquid and 3/8” (f9.52 mm) gas, therefore a are nut adapter is provided with all 12/18k indoor sections.
7
Installation Manual VMH SerieS Heat Controller, Inc.
INSTALLATION INSTRUCTIONS
1. Selecting Inst allatio n Place
More than 6 in.(15cm)
Read completely, then follow step by step.
Indoor unit
More than 5 in.(12cm)
More than 5 in.(12cm)
Do not expo se the indoor unit to heat or steam . Select a pl ace where there are no obstacles in front or a round the unit. Make sure t hat condensation drainage can be conven iently routed away. Do not inst all near a doorway.
More than 6.5 ft.(2.0m)
Fig. 1
Ensure th at the proper clearance is maintained per F ig.1. Use a stud fi nder to locate studs to prevent u nnecessary damage to the wall. Variati ons in pipe length may require adjustment t o refrigerant charge. There sho uld not be any direct sunlight. Otherwise , the sun will fade the plastic cab inet and
affect its ap pearance . If unavoidable, sunlight pr eventi
on should b e taken into consideration.
Outdoor unit
More than 1 ft.(30cm)
If an awnin g is built over the outdoor unit to prevent d irect sunlight or rain exposure,
More than 1 ft.(30cm)
make sure t hat heat radiation from the condens er is not restricted.
Ensure th at the clearance is maintained per Fig 2.
More than 2 ft.(60cm)
Do not plac e animals and plants in the path of the air in let or outlet. Take the air co nditioner weight into account and selec t a place where noise and vibration will not be a n issue.
More than 6.5 ft.(200cm)
Fig. 2
Clearance
Select a pl ace so that the warm air and noise from the air con ditioner do not disturb neighbors.
Outlet
Inlet
A 11” (280mm)
Outlet
7.5ft (>2300)
Fig.13
3.5ft (>1000)
3.5ft (>1000)
Fig.14
Ground
3.5ft (>1000)
3.5 ft (>1000)
8
Loading...
+ 17 hidden pages