The power wiring should always follow NEC and local codes, with respect to the unit’s, rating plate. See
installation manual for additional information. Main power connection is 208/230V/1PH~60HZ.
The communicating cable, which connects between the indoor and outdoor units must meet all NEC and
local codes, with respect to the unit’s rating plate. We recommend using 14 AWG/4 conductor Stranded THHN
6
ФФ V cable.
Pipe length and elevation
Pipe size
Unit
Gas inch
(mm)
Liquid inch
(mm)
9K 3/8’’ (Ф9.52) 1/4’’ (Ф6.35)
12K/18K 1/2’’ (Ф12.7) 1/4’’ (Ф6.35)
Max. Total length for all rooms
Standard
length
(m)
(5)
16.5ft
Dual-zone(m)Tri-zone(m) Quad-zone(m)
Max.
Elevation
B (m)
(10)
33ft
Max.
Length
A (m)
(15)
50ft
Additional
refrigerant
(g/m)
(20)
0.2 oz/ft
(30)100ft (45)150ft (60)200ft
2XWGRRUXQLW
$
2LOWUDS
,QGRRUXQLW
%
NOTES:
Capacity test is based on standard length and maximum allowance length is based on reliability.
Oil trap should be installed per (3-5 meters)10-15ft.
Outdoor connections are ¼” (Ф6.35 mm) liquid and 3/8” (Ф9.52 mm) gas, therefore a reducer is
11
Service Manual VMH SerieSHeat Controller, Inc.
Hi
Compound meter
Pressure
7.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as indicated below:
● Pressure in the system rises.
● Operating current rises.
● Cooling or heating efficiency drops.
● Moisture in the refrigerant circuit may freeze and block capillary tubing.
● Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and
evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections and outdoor unit
connections with a soft brush to check for leakage on the connecting points of the piping. If air bubbles
come out, the connections have leaks and those connection points must be tightened. Recheck to
ensure all leakage points are tightened properly and not leaking.
1. Air purging with vacuum pump
Vacuum
pump
Vacuum
pump
(Indoor unit)
-0.1MPa
Handle Lo
Charge hose
(Liquid side)
(Gas side)
Manifold valve
Lo
Charge hose
(Outdoor unit)
Two-way valve
Close
Three-way valve
Close
gauge
Handle Hi
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and
3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Conduct evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If
12
Heat Controller, Inc. VMH SerieSService Manual
the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage
points. Once the meter indicates -0.1mpa, fully close the handle Lo valve of the manifold valve and stop
the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5
minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
comes out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a
little higher than the atmospheric pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3). Air purge by open the valves on the charging cylinder and the charge set. Purge the air by loosening
the flare nut on the 2-way valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3
times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check for gas leakage by checking the flare connections using the soap water method.
5). Discharge the refrigerant by closing the valve on the charging cylinder and discharging the refrigerant
by loosening the flare nut on the 2-way valve approximately 45° until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position.
13
Service Manual VMH SerieSHeat Controller, Inc.
7). Replace the valve stems nuts and the service port cap that were previously removed.
Be sure to use a torque wrench to tighten the service port cap to a torque of 18N·m.
Be sure to check for gas leakage using soap water.
3. Adding the refrigerant if the pipe length >(5m)16.5ft
Electronic scale
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. Because refrigerant is R410A, turn the cylinder upside down, ensuring the bottom is upward,
to create a liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air
(be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner in the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with the proper amount (refer to
table) liquid refrigerant.
14
Heat Controller, Inc. VMH SerieSService Manual
6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose
from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the
hose.
7). Replace the valve stem caps and the service port that were previously removed.
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage using soap water.
7.5 Adding the refrigerant due to loss of charge
Electronic scale
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. Because the refrigerant is R-410A,
turn the cylinder upside down, such that the bottom is upward, to ensure a liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air
(Do not vent refrigerant into the atmosphere).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner in the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant, (refer to
the gauge and the pressure of the low side).
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
15
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.