The power wiring should always follow NEC and local codes, with respect to the unit’s, rating plate. See
installation manual for additional information. Main power connection is 208/230V/1PH~60HZ.
The communicating cable, which connects between the indoor and outdoor units must meet all NEC and
local codes, with respect to the unit’s rating plate. We recommend using 14 AWG/4 conductor Stranded THHN
6
ФФ V cable.
Pipe length and elevation
Pipe size
Unit
Gas inch
(mm)
Liquid inch
(mm)
9K 3/8’’ (Ф9.52) 1/4’’ (Ф6.35)
12K/18K 1/2’’ (Ф12.7) 1/4’’ (Ф6.35)
Max. Total length for all rooms
Standard
length
(m)
(5)
16.5ft
Dual-zone(m)Tri-zone(m) Quad-zone(m)
Max.
Elevation
B (m)
(10)
33ft
Max.
Length
A (m)
(15)
50ft
Additional
refrigerant
(g/m)
(20)
0.2 oz/ft
(30)100ft (45)150ft (60)200ft
2XWGRRUXQLW
$
2LOWUDS
,QGRRUXQLW
%
NOTES:
Capacity test is based on standard length and maximum allowance length is based on reliability.
Oil trap should be installed per (3-5 meters)10-15ft.
Outdoor connections are ¼” (Ф6.35 mm) liquid and 3/8” (Ф9.52 mm) gas, therefore a reducer is
11
Service Manual VMH SerieSHeat Controller, Inc.
Hi
Compound meter
Pressure
7.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as indicated below:
● Pressure in the system rises.
● Operating current rises.
● Cooling or heating efficiency drops.
● Moisture in the refrigerant circuit may freeze and block capillary tubing.
● Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and
evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections and outdoor unit
connections with a soft brush to check for leakage on the connecting points of the piping. If air bubbles
come out, the connections have leaks and those connection points must be tightened. Recheck to
ensure all leakage points are tightened properly and not leaking.
1. Air purging with vacuum pump
Vacuum
pump
Vacuum
pump
(Indoor unit)
-0.1MPa
Handle Lo
Charge hose
(Liquid side)
(Gas side)
Manifold valve
Lo
Charge hose
(Outdoor unit)
Two-way valve
Close
Three-way valve
Close
gauge
Handle Hi
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and
3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Conduct evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If
12
Heat Controller, Inc. VMH SerieSService Manual
the pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage
points. Once the meter indicates -0.1mpa, fully close the handle Lo valve of the manifold valve and stop
the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5
minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
comes out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a
little higher than the atmospheric pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3). Air purge by open the valves on the charging cylinder and the charge set. Purge the air by loosening
the flare nut on the 2-way valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3
times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check for gas leakage by checking the flare connections using the soap water method.
5). Discharge the refrigerant by closing the valve on the charging cylinder and discharging the refrigerant
by loosening the flare nut on the 2-way valve approximately 45° until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position.
13
Service Manual VMH SerieSHeat Controller, Inc.
7). Replace the valve stems nuts and the service port cap that were previously removed.
Be sure to use a torque wrench to tighten the service port cap to a torque of 18N·m.
Be sure to check for gas leakage using soap water.
3. Adding the refrigerant if the pipe length >(5m)16.5ft
Electronic scale
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. Because refrigerant is R410A, turn the cylinder upside down, ensuring the bottom is upward,
to create a liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air
(be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner in the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with the proper amount (refer to
table) liquid refrigerant.
14
Heat Controller, Inc. VMH SerieSService Manual
6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose
from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the
hose.
7). Replace the valve stem caps and the service port that were previously removed.
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage using soap water.
7.5 Adding the refrigerant due to loss of charge
Electronic scale
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. Because the refrigerant is R-410A,
turn the cylinder upside down, such that the bottom is upward, to ensure a liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air
(Do not vent refrigerant into the atmosphere).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner in the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant, (refer to
the gauge and the pressure of the low side).
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
15
Service Manual VMH SerieSHeat Controller, Inc.
side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air
conditioner before disconnecting the hose.
7). Replace the valve stem caps and the service port that were previously removed.
.
Use torque wrench to tighten the service port cap to a torque of 18N
m.
Be sure to check for gas leakage using soap water.
7.6 Replacing the indoor unit
1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the open position
Remove the valve stem caps and confirm that the valve stems are in the open position.
Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds
and then close it quickly.
4). Set the 2-way valve to the closed position.
5). Operate the air conditioner in the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
16
Heat Controller, Inc. VMH SerieSService Manual
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts.
Use a torque wrench to tighten the 3-way valves service port cap to a torque of 1.8 N.m.
Be sure to check for gas leakage using soap water.
7). Remove the defective indoor unit and install the new indoor unit. Follow the next set of procedures to
charge.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on
the 2-way valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage using soap water.
5). Discharge the refrigerant into charging cylinder.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
17
Service Manual VMH SerieSHeat Controller, Inc.
2-way valve approximately 45° until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position
Be sure to use a hexagonal wrench to operate the valve stems.
7). Replace the valve stems nuts and the service port cap that were previously removed.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage using soap water.
7.7 Replacing the outdoor unit
1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the open position.
2). Connect the vacuum pump to 3-way valve’s service port.
3). Evacuate for approximately one hour. Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
6). Remove the defective outdoor unit and install the new unit. See the following instructions for
re-charging the new unit.
18
Heat Controller, Inc. VMH SerieSService Manual
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. Because the refrigerant is R-410A, turn the cylinder upside down, such that the bottom is
upward, to ensure a liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air
(Do not vent refrigerant into the atmosphere).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at
a time (approximately (150g),5oz. each time) , operating the air conditioner in the cooling cycle. Wait
approximately 1 minute and then repeat the procedure as needed.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way
valve’s service port immediately
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
6). Replace the valve stem caps and the service port that were previously removed.
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage using soap water.
19
Service Manual VMH SerieSHeat Controller, Inc.
No.SW1
Display
Remark
Amendatory capacity demand code
Evaporator outlet temp. for 1# indoor unit
Actual data is measured, however due to display limitations
Condenser pipe temp.
the digital display shows “0.5”, it means the compressor
8. Electronic control function
8.1 Abbreviations
T1: Indoor ambient temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet.
T3: Coil temperature of outdoor heat exchanger
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Ts: Set point temperature.
8.2 Electric control working environment.
8.2.1 Input voltage: 230V.
8.2.2 Input power frequency:60Hz.
8.2.3 Indoor fan normal working amperage. is less than 1A.
8.2.4 Outdoor fan normal working amperage. is less than 1.5A.
8.2.5 Four-way valve normal working amperage. is less than 1A.
8.2.6 Swing motor: 12V DC.
8.3 Outdoor unit’s digital display
There is a digital display tube in outdoor PCB.
Digital display functions:
• In standby , the LED displays “- -”
• When compressor is operating, the LED displays the running frequency,
• In defrosting mode, The LED displays “dF” or alternatively displays between running frequency and
“dF”(each displays 2s)
• In compressor pre-heating, The LED displays “- -”
• In protection or malfunction modes, the LED displays the associated error code or protection code.
8.4 Outdoor unit point check function
There is a check switch in outdoor PCB.
Push the switch SW1 to check the states of unit when the unit is running. The digital display will display the
following each time the SW1 switch is preserved.
Pressed
10
11
Indoor unit capacity demand code
1
Outdoor unit running mode code Off:0, Cooling:1, Heating:2
2
3
Outdoor unit fan motor state Off:0, Low speed:1, High speed:2
4
5
Evaporator outlet temp. for 2# indoor unit
6
Evaporator outlet temp. for 3# indoor unit
7
Evaporator outlet temp. for 4# indoor unit
8
9
Ambient temp.
Compressor discharge temp. Actual data is measured, however due to display limitations
if the temp. is lower than -9 degrees, the digital display will
show “-9”. If the temp. is higher than 70 degrees, the digital
display will show “70”. If the indoor unit is not connected, the
digital display tube will show: “- -“.
if the temp. is lower than 0 degrees, the digital display will
show “0”. If the temp. is higher than 99 degrees, the digital
display will show single digit and a tens digit. For example if
20
Heat Controller, Inc. VMH SerieSService Manual
connected, the digital display tube will show: “- - “.
12
Inverter current
AD data
EXV open angle for 1# indoor unit
Actual data, divide this number by 8 for actual angle valve is
open.
15
EXV open angle for 3# indoor unit
18
Indoor unit number
The indoor unit can communicate with outdoor unit well.
19
The last error or protection code
00 means no malfunction
21
Ambient temp. of 1# indoor unit
Actual data
22
Condenser pipe temp. of 1# indoor unit
Actual data
――
Check point over
discharge temp. is 105 degree. If the indoor unit is not
13
14
16
17
20
23
24 Condenser pipe temp. of 2# indoor unit Actual data
25 Ambient temp. of 3# indoor unit Actual data
26
27 Ambient temp. of 4# indoor unit Actual data
28 Condenser pipe temp. of 4# indoor unit Actual data
29
EXV open angle for 2# indoor unit Actual data divide 8
Actual data divide 8
Actual data divide 8
EXV open angle for 4# indoor unit
Power supply of outdoor unit AD data (AD data*472/255=actual data)
frequency value Actual data
Ambient temp. of 2# indoor unit Actual data
Condenser pipe temp. of 3# indoor unit Actual data
The following items from 6.4.1 to 6.4.6 are for the explanation of the point check functions.
8.4.1 Frequency of compressor:
Display Frequency of compressor (Hz)
30 30
-- Stand by
60 60
8.4.2 Running mode:
Display Corresponding mode
0 Off
1 Cooling mode
2 Heating mode
8.4.3 Capacity demand:
Cooling mode
Capacity 2000-
2500
Corresponding
Code
1 2 3 4 5 6 7 8 9 >=10
Heating mode
Capacity 2000-25
Corresponding
Code
00
1 2 3 4 5 6 7 8 9-10 >=11
Note:
The capacity is just for reference.
2000-
2500
2000-25
00
3000-
3800
3000-38
00
4500-
5000
4500-50
00
5000-
5500
5500-61
00
5500
-6100
6100-70
00
6100-
7000
6100-70
00
7000-
7500
7000-75
00
7500-
8000
7500-80
00
>7500
>8000
21
Service Manual VMH SerieSHeat Controller, Inc.
8.4.4Number of indoor units – displays how many indoor units the outdoor unit is communicating with.
Display Quantity of indoor unit
1 1
2 2
3 3
4 4
8.4.5 Opening degree of electronic expansion valve:
Actual opening degree value equals the display data divided 8
8.5 Protection
8.5.1 Three minutes delay at restart for compressor.
8.5.2 Temperature protection of compressor discharge.
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 216°F<T5< 239°F (102°C<T5<115°C), the frequency or the compressor will decrease to a lower level
every 2 minutes until it reaches F1.
---If T5>239°F(T5>115°C) for 10 seconds, the compressor will stop and restart till T5<194°F (T5<90°C).
8.5.3 Low voltage protection
VOLTAGE
VOLREL1
VOLREL2
VOLREL3
VOLLIMT1
VOLLIMT2
VOLLIMT3
No limit
VOLFRE1
VOLFRE2
Off
Model VOLLIMT1 VOLLIMT2 VOLLIMT3 VOLREL1 VOLREL2 VOLREL3 VOLFRE1 VOLFRE2
A-VMH18DC-1 230 200 120 260 210 135 62 54
A-VMH27TC-1 245 220 120 265 240 135 78 45
A-VMH36QC-1 200 185 120 210 195 135 54 42
Note: if the low voltage protection occurs and does not resume within 3min, it will keep the protection after
the machine is restarted.
22
Heat Controller, Inc. VMH SerieSService Manual
8.5.4 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited per the table below.
Cooling mode:
Current frequency(Hz) Current limit value(A) Frequency limit
COOL_F10 ICOOLLMT6
COOL_F9 ICOOLLMT5
COOL_F8 ICOOLLMT4
COOL_F7 ICOOLLMT3
COOL_F6 ICOOLLMT2
COOL_F5 ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL,the AC will display the failure for 30 seconds and stop. The AC will restart 3
minutes later and re-check.
The compressor frequency will decrease to COOL_F4 and
then run at COOL_F4 for 3 minutes.
After that, the frequency will be adjusted according to the
capacity demand, then rise to the next level up every 3
minutes (When the frequency>COOL_F4 via capacity
demand).
Heating mode:
Current frequency(Hz) Current limit value(A) Frequency limit
HEAT_F12 IHEATLMT8 The compressor frequency will decrease HEAT _F4 and
HEAT_F11 IHEATLMT7
HEAT_F10 IHEATLMT6
HEAT_F9 IHEATLMT5
HEAT_F8 IHEATLMT4
HEAT_F7 IHEATLMT3
HEAT_F6 IHEATLMT2
HEAT_F5 IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT,the AC will display the failure for 30 seconds and stop. The AC will restart 3
minutes later and re-check.
then run at HE AT_F4 for 3 minutes.
After that, the frequency will be adjusted according to the
capacity demand, then rise to the next level up every 3
minutes (When the frequency>Heat_F4 via capacity
demand).
23
Service Manual VMH SerieSHeat Controller, Inc.
Model
RECOILINFRE
8.5.5 Indoor / outdoor units communication protection
If any indoor unit can not receive the feedback signal from the outdoor unit for 2 minutes, the AC will stop
and display the failure code.
8.5.6 High condenser coil temp. protection.
When T3>149°F(T3>65°C) for 3 seconds, the compressor will stop while the indoor fan and outdoor fan will
continue.
When T3<126°F(T3<52°C), the protection will release and the compressor will restart after 3 minutes.
8.5.7 Outdoor unit anti-freezing protection
When T2B<32°F(T2B<0°C) for 4 minutes, the indoor unit capacity demand will be zero and resume to
normal when T2B>50°F(T2B>10°C).
8.5.8 Oil return
Running rules:
1. If the compressor frequency remains lower than RECOILINFRE for 2hours,the AC will increase the
frequency to RECOILFRE for 3mins and then resume to the former frequency.
A-VMH18DC-1 45
A-VMH27TC-1 45
A-VMH36QC-1 40
2. During the oil return process, the EXV and indoor units continue with the current running mode, the
frequency will not be limited by the compressor discharge temp. or the current.
8.5.9 Compressor preheating functions
----Preheating permitting condition:
If T4(outdoor ambient temperature) T4<37.4°F(T4<3°C) and newly powered on or if T4<37.4°F(T4<3°C)
and compressor has stopped for over 3 hours, the compressor’s crank case heater will begin to operate.
----Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, heats the
compressor without it operating via the crankcase heater.
----Preheating release condition:
If T4>41°(T4>5°C) or the compressor starts running, preheating function will stop.
8.5.10 Compressor crankcase heater
When T4<37.4°(T4<3°C) and the compressor is not running, the crankcase heater will be active.
When T4≧41°(T4≧5°C) or the compressor starts up, the crankcase heater will stop working.
24
Heat Controller, Inc. VMH SerieSService Manual
9. Troubleshooting
9.1 Indoor Mini-Split error code explanations:
Indoor Error
Code
E0
E1 Indoor/ outdoor unit communication error ——
E2 Zero-crossing signal error ——
E3 Indoor fan speed has been out of control ——
E5
E6 Open circuit or short circuit of T1 or T2 temperature sensor ——
P0 IPM module protection or IGBT over-strong current protection P4
P1 Voltage protection E5
P2 Temperature protection of compressor top P0,P1,P2
P3 Outdoor temp. too low protection(Optional for some models) ——
P4 Inverter compressor drive protection E7, P7
P5 Mode conflict ——
LED STATUS
Indoor EEPROM malfunction ——
Open circuit or short circuit of outdoor temperature sensor or outdoor
EEPROM malfunction
Corresponding
Outdoor Error code
E0,E1,E2,
E3,E4,E6
Indoor Ceiling Cassette error codes:
Operation Timer De-frost Alarm LED STATUS
★
X X
X
X X X
★ ★
★
★
★
X X X Open or short circuit of T1 temperature sensor
★
★
X X
X X Indoor / outdoor units communication error
X X Indoor EEPROM malfunction
X X Open or short circuit of T3 or T4 temperature sensor
X
★ ★ ★ ★
★
X
X Open or short circuit of T2 temperature sensor
★
Full-water malfunction
IPM module protection
Voltage protection
Temperature protection of compressor top.
Mode conflict
★
X Inverter compressor drive protection
★ flash at 2.5Hz, light, X extinguished.
25
Service Manual VMH SerieSHeat Controller, Inc.
coil outlet temp. sensor or connector of
r or connector of
coil outlet temp. sensor or connector of
board and
Temperature protection of
9.2 Outdoor unit error code explanation:
Outdoor
Error
Code:
E0 Outdoor EEPROM malfunction E5
Indoor unit A’s
E1
sensor is defective
Indoor unit B’s coil outlet temp. sensor or connector of
E2
sensor is defective
Indoor unit C’s coil outlet temp. senso
E3
sensor is defective
Indoor unit D’s
E6
sensor is defective
E4 Open or short circuit of outdoor unit temperature sensor E5
LED STATUS
Corresponding Indoor
Mini-Split error code
E5
E5
E5
E5
E5 Voltage protection P1
E7
P0
P1 High pressure protection (Only for A-VMH-36QC-1) P2
P2 Low pressure protection (Only for A-VMH-36QC-1) P2
P3 Current protection of compressor ——
P4 IPM module protection P0
P6 High temperature protection of condenser ——
P7 Inverter compressor drive protection P4
PF PFC module protection (A-VMH36QC-1) ——
Communication malfunction between IPM
outdoor main board
Temperature protection of compressor discharge or
compressor top.
For A-VMH-36QC-1 it means
compressor discharge
P4
P2
26
Heat Controller, Inc. VMH SerieSService Manual
9.3 Trouble shooting
9.3.1 Indoor unit trouble shooting
9.3.1.1 Indoor EEPROM malfunction
Shut off the power supply and
turn it on 1 minute later. Is it
still displaying the error code?
Yes
If the EEPROM chip
is welded on PCB,
replace the PCB
directly. Otherwise,
check whether the
EEPROM chip
plugged in PCB well?
Yes
Replace the indoor PCB.
No
EEPROM: a read-only memory chip whose contents can be erased and reprogrammed using a pulsed
Insert the EEPROM well
Re-insert the EEPROM well
voltage.
(EERROM chip may be solid for some models)
27
Service Manual VMH SerieSHeat Controller, Inc.
Check wiring on the outdoor
minal follow the
iring diagram. Are all wires
s wit h
Are
no. of outdoor units
Measure Vs, is it moving
(Vs is the voltage between
Turn off the all indoor
Is PFC power LED lamp
Are number of indoor units
heck on the
nt (18). (2
zone, 4
Is Main board
lamp on?
Is all the wiring
between terminal
and Indoor PCB
Change the
wer on by remote
the E1
error code ended
after 3 minutes?
eactor
hange Outdoor Main
outdoor unit PCB
9.3.1.2 Indoor / outdoor units communication error
Power off , then Power on the A/C by the
Breaker. Did E1 error code turn off?
No
and indoor ter
w
connected correctly?
Yes
Turn on all indoor unit
the remote controller.
correct? Refer to PIC 5.
Yes
units. Is IPM power LED
Yes
No
No
change
IPM
Yes
No
Reconnect the wiring
Reconnect the wiring
alternately between positive
value and negative value?
Yes
A:
No
No
Yes
off? Refer PIC 3.
Yes
“"
Yes
correct? C
outdoor check poi
for dual zone, 3 for tri
for qua zone). Refer PIC 5.
No, fist time
Change
assembly(include wiring) totally
No
change
PFC
Reconnect the wiring
Is the r
connecting well?
C
PCB
No, second time
Yes
Yes
No
No No
E1 error problem solved.
SEE A
Indoor PCB
Po
controller, has
Yes
28
Heat Controller, Inc. VMH SerieSService Manual
check how many indoor units are
Pic 1: Measure the voltage of L2 to S (Vs), is it
moving alternately between positive value and
negative value?
PIC 3: IPM (For dual/tri/quad-zone)
PIC4: Main board LED when power on and unit standby.
PIC 2, Check the wiring.
PFC (quad-zone only)
PIC 5: check point bottom,
press 18 times to
connected.
29
Service Manual VMH SerieSHeat Controller, Inc.
Correct the connections
Shut off the power supply, rotate the fan
rubbing/obstructions?
9.3.1.3 Zero-crossing signal error
Check if the connections and
power supply is normal?
Indoor PCB is defective.
Replace indoor PCB.
are normal?
Yes
No
Correct the connections. Turn on the unit
Correct the connections. Turn on the
when the power supply is within 90-110% of
unit when the power supply is good.
rated voltage on unit’s rating plate.
9.3.1.4 Indoor fan speed has been out of control(DC fan motor)
Shut off the power supply and
turn it on 5 seconds later. Is it
still displaying the error code?
Yes
No
The unit operates normally.
Shut off the power supply, rotate the fan by hand. Does
by hand. Does it rotate freely with any
it rotate properly?
Yes
Check the wires of fan motor.
Are all the connections good?
Yes
Check the voltage between port
1 and 6 of fan motor connector,
is it 310V?
No
Replace indoor main PCB. Is it
still displaying the error code?
No
No
Correct the connections.
No
Replace indoor fan
per wiring diagram.
The unit operates normally.
motor.
Yes
DC motor voltage input and output
5
4
6
1
3
2
NO. Color Signal Voltage
1 Red VDC310V
2 --- --- ---
3 White Vcc 15V
4 Blue FG 0.3V
5 Yellow Vsp 0-7.5V
6 Black GND 0V
30
Heat Controller, Inc. VMH SerieSService Manual
9.3.1.5 Indoor fan speed has been out of control(AC fan motor)
Shut off the power supply
and turn it on 5 seconds
later.Is it still displaying
the error code?
Yes
No
The unit operates normally.
Shut off the power
supply, rotate the cross
fan by hand. Does it
rotate properly?
freely?
Yes
Check the wires of
fan motor. Are all the
connections good?
Yes
Check the resistance value of
indoor fan motor, is it normal?
Yes
Replace indoor PCB.
No
No
Disassembly the
connection between
fan and motor, check if
the bearing is normal?
Correct the connections
Correct the connections.
per wiring diagram.
No
No
Yes
Replace indoor fan motor.
Replace the bearing.
31
Service Manual VMH SerieSHeat Controller, Inc.
Correct the connections per
Is
Is
9.3.1.6 Open or short circuit of temperature sensor.
Check the connections
between temperature
sensor and PCB. Are
the connections good?
No
Correct the connections.
wiring diagram.
Yes
Check the resistance value
of the sensor via Appendix