Heatcontroller A-VFH42PA-1 User Manual

INSTALLATION, OPERATION
& MAINTENANCE MANUAL
InverterFlex® Series
Outdoor Ductless Mini-Split
Heat Pumps
A-VFH24TA-1 A-VFH30QA-1 A-VFH36QA-1
A-VFH42PA-1
Heat Controller • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
TABLE OF CONTENTS
Safety Precautions
Warnings and Cautions............................................. 3
Introduction
Model Nomenclature.................................................4
System Application....................................................5
Installation Instructions
Installation Location Selection............................... 6-7
Outdoor unit installation..........................................8-9
Condensate Drain......................................................9
Refrigerant Line Installation
Refrigerant line set installation............................ 10-15
Leak test, evaluation and release of refrigerant....... 16
Electrical Work
Electrical Precautions.............................................16
Unit wiring........................................................... 17-21
Initial Start Up and Checks
Field charging and Final Inspection ................... 21-23
!
Caution
• Contact an authorized service technician for repair or maintenance of this unit
• Contact an authorized installed for installation of this unit.
• Installation work must be performed in accordance with local and national electrical codes and standards by authorized personnel only
2
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
• Read the follow SAFETY PRECAUTIONS carefully before installation.
• Electrical work must be performed by a licensed electrician. Be sure to use the correct rating of the power cord and main circuit for the model to be installed.
• Incorrect installation due to ignoring the instruction will cause harm or damage.
n The seriousness is classied by the following indications.
WARNING!
!
CAUTION!
!
The items to be followed are classied by the symbols:
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
This symbol denotes procedure that is PROHIBITED.
WARNING!
!
1) Do not install without an authorized servicer/installer.
2) Install according to this installation instruction. If installation is defective, it can cause water leakage or
electrical shock/re.
3) Use the supplied accessories and specied parts for installation.
4) Install the outdoor unit on a raised concrete pad or blocks to provide a solid, level foundation. In a
location with high winds, anchor the unit and provide an air bafe. In snowy areas (for heat pump models), install the outdoor unit on a raised platform higher than drifting snow. Provide snow vents, and awning over the unit.
5) For electrical work, follow local and national electric codes and these installation instructions. An independent must be used. If defects in the electrical work, will cause electrical shock or re.
6) Use the specied cable and connect tightly. Clamp the cable so that no external force will stress the connections. Loose wiring may overheat at the connection points and create a possible re hazard.
7) Wiring routing must be properly arranged so that control board cover is xed properly. If control board cover is not xed perfectly, it will cause overheating at connection point of terminal, re or electrical shock.
8) When charging the unit, take care not to let air/substances other than the specied refrigerant go into refrigeration circuit. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration circuit, explosion and injury.
9) Do not modify the length of the power supply cord or use an extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause re or electrical shock.
CAUTION!
!
1) This equipment must be grounded. It may cause electrical shock if grounding doesn’t comply with local/ national electric codes.
2) Do not install the unit in a place where leakage of ammable gas may occur. If gas leaks and accumulates near the unit, it may cause re.
3) Provide proper condensate drainage per the installation instructions. If not done properly, condensate can destroy personal property and freeze up in improperly on the unit.
3
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Inverter Series System Introduction:
The InverterFlex series allows one outdoor unit to match with up to ve indoor units, depending on capacity. The model nomeclature of the outdoor unit denes the number of available base valves to connect indoor unit. For example a Tri-zone unit can accept up to 3 zones or three indoor units.
Indoor units available for use with these particular outdoor models use the following nomenclature:
A variety of indoor model types can be used with the outdoor unit, including ductless high wall mini-splts, ceiling cassettes, ducted air
handlers, oor/ceiling mount, and console units.
Refer to the indoor Installation, Operation, and Maintenance manuals of each model for further
details. NOTE: Depending on the type of indoor
unit selected, the method of controlling and operating it may vary from a wireless remote
control to a wired wall thermostat/control, or both.
A - V F H 18 D A - 1
B=INDOOR
H=HEAT PUMP
FLEX
Series
V=INVERTER
DASH
CAPACITY
KBTU/H
18 24 30 36 42
0=115V 1=230V
DASH
REVISION
LETTER
TYPE OF INDOOR UNIT
D=Dual (2) Zones
T=Tri (3) Zones Q=Quad (4) Zones P=Penta (5) Zones
B - V F H 09 M A - 1
B=INDOOR
H=HEAT PUMP
FLEX
Series
V=INVERTER
DASH
CAPACITY
BTU/H
09 12 18
0=115V 1=230V
DASH
REVISION
LETTER
TYPE OF INDOOR UNIT
M=Mini-Split Ductless High Wall
C=Ceiling Cassetts
D=Ducted Air Handler
U=Universal Mount (Floor Ceiling
Mount)
F=Floor Mount Console
Outdoor Nomenclature A-VFH18DA-1
Indoor Nomenclature B-VFH09MA-1
EXAMPLE OF TRI-ZONE SYSTEM
Outdoor Unit
Cassette Type Indoor Unit
Wall Mounted Indoor Unit
Duct Type Indoor Unit (Rectangular air outlet)
4
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
Inverter Series System Introduction:
System Selection:
The total capacity of ALL the indoor units can not exceed 150% of the capacity of the outdoor unit. However, we recommend sizing the indoor unit’s total capacity to be less than or equal to 100% of the outdoor unit’s capacity. If sized beyond 100% of the outdoor unit’s capacity, when all the indoor units receive a call for cooling/heating, the entire system will still only be able to achieve the rated capacity. of the outdoor unit The inverter compressor can run at a higher frequency but may not provide full capacity to all indoor units. Sizing above 100% is usually done because one or more indoor units may not be in use the majority of the time.
Additionally, the total capacity of all indoor units cannot be less than 50% of the outdoor unit’s capacity.
System Application:
This system is not designed to be a sole source of heat for a home/building. While the units can operate in low ambient conditions, they cannot provide the full rated capacity for heat at low outdoor temperatures. An additional heat source may be required in areas such as the northern USA and Canada during the winter.
This system must be run in modes that do not conict. For example, one indoor unit cannot be run in cool mode and another indoor unit in heat mode. All indoor units modes must be harmonized for the system to properly operate. The fan mode can run in conjunction with any other mode, while the cooling mode can be run in conjunction with the dehumidication mode. However all other modes must match among the indoor units.
Liquid Receiver
Outdoor Unit
NOTE: The number of indoor units may vary depending on the capacity of the outdoor unit. This is an example of a ve (5) zone system.
Electronic
Expansion Valve
Indoor Unit
Heat Exchanger
Heat Exchanger
System Schematic
Heat Exchanger
Stop Valve
Heat Exchanger
Heat Exchanger
Heat Exchanger
5
Capillary
Compressor
Gas/Liquid Separator
Four Way Valve
Oil Separator
Heating Cooling
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Selecting installation place
Choose a location that places the outdoor unit as close to the indoor unit as possible. The maximum unit separation and vertical lift (distance compressor is above the evaporator) must be taken into account. Do not exceed allowable refrigerant line lengths.
Outdoor unit
• Unit must be installed in a location that does not obstruct the airow and ensures clearance are maintained (Fig. 1)
• If installation location allows the unit to be exposed to strong winds (such as coastal applications), ensure that the unit has a wind barrier. This will assist with preventing strong gusts of wind from entering the unit’s cabinet and interfering with the
Fig. 1
fan operation. (Fig. 2 and Fig. 3)
Fig. 2
Min. 1.5ft. (500mm)
Min. 6.5ft. (2000mm) (Air outlet side)
CorrectIncorrect
Min. 3.5ft.
(1000mm)
Min. 1.5ft.
(500mm)
(Air inlet side)
Min. 1.5ft. (500mm) Space to the wall
Fig. 3
Correct
Incorrect
6
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
Avoid areas where water, snow, or ice may fall from the roof onto the unit.
In climates where snow is a consideration, locate the unit away from areas prone to drifting.
Ensure the location of the unit will not be subject to snow drifts, heavy accumulation of snow or leaves or other seasonal debris. If such a location is unavailable, provide an awning for the unit. (Fig. 4 and Fig. 5)
1. An awning can be built over the outdoor unit
to prevent direct sunlight, rain exposure, or snowfall.
2. Ensure that the awning does not impede the
unit’s required clearances or obstruct air ow.
Rooftop installation
If the outdoor unit is installed on a roof structure, be sure to level the unit.
Ensure the roof structure and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
3. The awning should be at least 2 ft. (0.6m) away from the top of the unit’s housing.
• Ensure free ow of air into and out of the unit. All air
inlet/outlets should be free of obstructions such as walls and shrubs. Minimum clearances should be maintained. (Fig. 1)
• During heating and defrost modes (heat pump
models only), the condensate should be properly drained away from the unit. • Do not locate two or more units in any way that will block discharge air from one unit to another. Be certain that hot air from one unit will not blow into a nearby unit to prevent recirculation or discharge air. (Fig. 6)
Fig. 4
Obstacles
Fence or
Min. 6.5ft (2000mm)
Fig. 6
Min. 1.5ft (500mm)
Min. 1.5ft (500mm)
Fig. 5
Min. 3.5ft (1000mm) (Service space)
• If the outdoor unit is installed on roof structures or external walls, excessive noise and vibration may result, and may also be considered a non­serviceable installation.
• Oil traps must be made in the refrigerant line set (every 10 ft.) when the outdoor unit is located above the indoor unit.
7
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Outdoor Unit Installation
• In a snowy area, slab should be higher than drifting
• Install the outdoor unit on a rigid base (such a concrete slab) to prevent increasing noise level and vibration.
• Use a raised concrete pad or concrete blocks to provide a solid, level surface. Securely anchor the unit down with bolts.
snow.
• See outdoor installation location information on pages 6 and 7 for more details and required clearances.
Anchoring outdoor unit
FIG. 7 18KBTU/H
32.09 in. (815mm)
35.39 in. (899mm)
21.65 in. (550mm)
15.5in. (343mm)
12.44 in. (316mm)
14.88in. (378mm)
Anchor the outdoor unit to the concrete slab with lag bolts or similar size, may vary by model. NOTE: Lag bolts are eld provided and do not come with the unit.
Refer to unit’s mounting footprint for mounting hole locations (Fig. 7 - 10)
23.46 in. (596mm)
FIG. 8 24KBTU/H, 30KBTU/H
35.12 in. (892mm)
37.24 in. (946mm)
22.05 in. (560mm)
8
13.43 in. (341mm)
27.56in. (700mm)
15.59in. (396mm)
14.5in. (368mm)
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
FIG. 9 36KBTU/H
39.13 in. (994mm)
36.22 in. (920mm)
FIG. 10 42KBTU/H
42.8 in. (1087mm) 40 in. (1015mm)
31.06 in. (789mm)
15.55 in. (395mm)
16.81 in. (427mm)
24.62 in. (610mm)
3.78 in. (96mm)
3.78 in.
(96mm)
3.0 in.
(76mm)
6.97 in.
(177mm)
14.57 in. (370mm)
9.02 in. (153mm)
Condensate Drainage
• For heat pump models only.
• Condensate and defrosted water created by the unit operating in heat mode should be routed and drained away from the unit.
• Parts needed for condensate drainage are not
factory supplied; they are commercially available.
• Fit the rubber washer onto the drain connector, then
!
43.43 in. (1103mm)
17.32 in. (440mm)
15.79 in. (401mm)
24.84 in. (631mm)
Fig. 11
Bottom frame
Drain plug
Drain connector
Hose (5/8” (16mm) I.D.
17.72 in. (450mm)
3.9 in.
(99mm)
3.0 in.
(76mm)
4.76 in.
(121mm)
14.25 in. (362mm)
7.52 in. (191mm)
Drain-water hole
insert the drain connector into the hole on the base pan of the outdoor unit. Secure into place. (Fig. 11)
• Connect a locally purchased drain hose. Install
hose to the hose barb end of the drain connector.
• Route the hose to drain location away from
the unit.
• Repeat for each hole on the base of the unit, as needed.
9
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Refrigerant Line Set Installation
Refrigerant Line Set Installation
1. Purchase line sets through a Heat Controller distributor with consideration of the minimum and maximum line lengths. (Page 11)
2. Both liquid and suction lines to be insulated.
3. Connections are made via are nuts.
4. The number of bends and length of refrigerant lines determine the pressure drop which affects capacity and efciency of the system, as well as oil return. Minimize the length and number of bends when possible during installation.
5. Minimum line set length must be maintained, even if the installation does not require it. Extra length that is unnecessary can be coiled up near the outdoor unit (Do not to block air inlets/ outlets).
6. Choose a location that places the outdoor unit as close to the indoor unit as possible to minimize line set lengths.
7. Use only clean, refrigerant grade tubing suitable for R-410A.
8. Avoid installing refrigerant lines on wet/rainy days.
9. Always keep tube ends sealed until the nal connections are to be made.
10. If line sets are being made at the time of installation, rather than being purchased, be sure to:
• Remove burrs from cut ends of the tubing
• Use tube benders to prevent kinking.
• Ensure tube cuts are square in relation to the
end of the tube.
• Use the proper diameter tube and are nut
sizes recommended by the manufacturer.
• Insulate both lines with Amraex or equivalent with a wall thickness of at least 3/8".
• Use copper tubing suitable to withstand pressures for R-410A refrigerant. We recommend a minimum wall thickness of
0.027 in. (0.7mm).
11. The tube size should always be the same
diameter as the connections provided at the of the indoor unit.
Note: On some models, a reducer or an
expander may be shipped with the outdoor unit in order to adapt the line set connection to the proper size to mate with the indoor unit’s connection. Be sure to check for these parts, should you discover that the outdoor units service valve sizes differ from the indoor unit’s connections. If this part is shipped with the outdoor unit, then it is required to be used.
12.Up sizing/downsizing the refrigerant lines/
connections can result in inadequate oil return to the compressor or excessive refrigerant return and will void the warranty.
13.Do not over torque the connections, excessive
force can break the are nut.
14. When routing the line set between the outdoor
and indoor units:
A. Support the tubing adequately to avoid sags
that can trap the oil.
B. Isolate the tubing so it does not transmit
noise from vibration into the structure of the
building. C. Avoid sharp edges that could cut the tubes. D. Trap rises every 10 ft. (5-7m) with a ‘p’
trap, when outdoor unit mounted above the
indoor unit.
10
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
VFH InverterFlex System Line Set Requirements
Indoor Model
Maximum Length
B-VFH09
49.2ft (15m)
B-VFH18/24
82ft (25m)
Dual Zone
Tri-Zone
Quad Zone (L1+L2+L3+L4)
Penta Zone (L1+L2+L3+L4+L5)
Lx
Refrigerant Line Set Installation
Allowable Length and Height of Line Set
Lx = Length of line set
H1
H2
from farthest indoor unit
For systems with only one indoor unit, the maximum line set length (Lx) is:
Outdoor Model Maximum Length (Lx) Max. Elevation Between Outdoor & Indoor Unit (H1) A-VFH18/24/30 32.8ft (10m) 24.6ft (7.5m) A-VFH36/42 82ft (25m) 49.2ft (15m)
For systems with more than one indoor unit, the entire system must pass BOTH requirements below.
Maximum Length Requirement based on Indoor Unit Capacity:
B-VFH12 65.6ft (20m)
Total Allowable Length based on Outdoor Unit Capacity:
Outdoor Model Zoning Based on Actual Number of Indoor Units Installed
(L1+L2)
A-VFH18/24/30 98.4ft
(30m)
A-VFH36/42 104.9ft
(32m)
(L1+L2+L3)
172.25ft (52.5m) 229.6ft (70m) N/A 24.6 ft (7.5m)
157.5ft (48m) 209.9ft (64m) 262.5ft (80m) 49.2 ft(15m)
(See Note 2) Max.
Elevation Between Indoor & Outdoor (H1)
Max. Elevation Difference Between each Indoor Unit (H2)
24.6 ft (7.5m)
11
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
VFH InverterFlex System Line Set Requirements
For systems with only one indoor unit, the maximum line set length (Lx) is:
Outdoor Model Maximum Length (Lx) Max. Elevation Between Outdoor & Indoor Unit (H1) A-VFH18/24/30 32.8ft (10m) 24.6ft (7.5m) A-VFH36/42 82ft (25m) 49.2ft (15m)
For systems with more than one indoor unit, the entire system must pass BOTH requirements below.
Maximum Length Requirement based on Indoor Unit Capacity:
Indoor Model
Maximum Length
B-VFH09
49.2ft (15m)
B-VFH12
65.6ft (20m)
B-VFH18/24
82ft (25m)
Total Allowable Length based on Outdoor Unit Capacity:
Outdoor Model Zoning Based on Actual Number of Indoor Units Installed
(See Note 2) Max.
Elevation Between Indoor & Outdoor (H1)
Max. Elevation Difference Between each Indoor Unit (H2)
Dual Zone
(L1+L2)
Tri-Zone
(L1+L2+L3)
Quad Zone (L1+L2+L3+L4)
Penta Zone (L1+L2+L3+L4+L5)
A-VFH18/24/30
98.4ft
(30m)
172.25ft (52.5m)
229.6ft (70m)
N/A
24.6 ft (7.5m)
24.6 ft (7.5m)
A-VFH36/42 104.9ft
(32m)
157.5ft (48m) 209.9ft (64m) 262.5ft (80m) 49.2 ft(15m)
Lx
An outdoor A-VFH36 is installed with (1) B-VFH18 and (2) B-VFH09 indoor units. Based on the Indoor requirement, the
Refrigerant Line Set Installation
Single Zone Example:
An Outdoor A-VFH18 is installed with (1) B-VFH09 indoor unit. The line set must not exceed 32.8ft (10m) and the indoor unit must not be more that 24.6 ft(7.5m) higher than the outdoor unit.
Multi-Zone Example:
18K indoor unit’s line set can’t exceed 82ft (25m) and each 9K indoor units’ line set can’t exceed 49.2ft (15m). This puts the total system length (L1+L2+L3) at: 82ft (25m) + 49.2ft (15m) + 49.2ft (15m) = 180ft (54.9m). However using the total allowable length requirement, we see that an A-VFH36 Tri-Zone system can’t exceed 157.5ft (48m). Therefore, we must reduce the line set length to some or all of the indoor units. To ensure that the allowable total length requirement is met, let’s reduce the line set for the B-VFH18 unit to 75ft (22.9m) and the B-VHF09 units to 40ft (12.2m) each. Now the total length (L1+L2+L3) requirement is met, as the total = 75ft (22.9m) + 40ft (12.2m) + 40ft (12.2m) = 155ft (47.2m), which is less than the total allowable length of 157.5ft (48m) for an A-VFH36 Tri-Zone system.
Notes:
1. The Max. Allowable Elevation H1 and H2 must also be maintained.
2. The Zoning is based on the actual number of indoor units installed. An outdoor A-VFH42 is capable of having up
to (5) indoor units installed with a max. total line set length of 262.5ft (80m), however if the application is zoned using only (2) indoor heads, the max. total line set length is reduced to 104.9ft (32m) as the actual application is a dual zoned system.
12
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
Refrigerant Line Set Installation
Due to the mix and match nature of the InverterFlex™ system, reducing and/or expansion flare connection subassemblies are provided with some models to accommodate for the different flare connections sizes between indoor and outdoor units.
The subassemblies provided accommodate for most typical applications, however the installing contractor may need to purchase additional subassemblies for certain applications.
A-VFH Outdoor Liquid-Gas Connection Sizes
Liquid Connections 18K 24K 30K 36K 42K
A 1/4” (6.35mm) 1/4” (6.35mm) 1/4” (6.35mm) 1/4” (6.35mm) 1/4” (6.35mm)
B 1/4” (6.35mm) 1/4” (6.35mm) 1/4” (6.35mm) 1/4” (6.35mm) 1/4” (6.35mm)
C n/a 1/4” (6.35mm) 1/4” (6.35mm) 1/4” (6.35mm) 1/4” (6.35mm)
D n/a n/a 1/4” (6.35mm) 3/8” (9.52mm) 1/4” (6.35mm)
E n/a n/a n/a n/a 3/8” (9.52mm)
Gas Connections 18K 24K 30K 36K 42K
A 3/8” (9.52mm) 3/8” (9.52mm) 3/8” (9.52mm) 3/8” (9.52mm) 3/8” (9.52mm)
B 3/8” (9.52mm) 3/8” (9.52mm) 3/8” (9.52mm) 3/8” (9.52mm) 3/8” (9.52mm)
C n/a 3/8” (9.52mm) 3/8” (9.52mm) 1/2” (12.7mm) 1/2” (12.7mm)
D n/a n/a 3/8” (9.52mm) 5/8” (15.9mm) 1/2” (12.7mm)
E n/a n/a n/a n/a 5/8” (15.9mm)
B-VFH Indoor Liquid-Gas Connection Sizes
Subassemblies for A-VFH36QA-1 and A­VFH42PA-1 Outdoor Units:
The A-VFH36QA-1 and A-VFH42PA-1 outdoor units come with a set of copper elbow subassemblies with a female flare nut x male flare fitting.
Indoor Unit Liquid Gas
B-VFH09MA-1
B-VFH12MA-1 B-VFH18MA-1 5/8” (15.9mm)
B-VFH12CA-1 3/8” (9.52mm) B-VFH18CA-1 1/2” (12.7mm)
B-VFH24CA-1 3/8” (9.52mm) 5/8” (15.9mm)
1/4” (6.35mm)
1/2” (12.7mm)
13
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Part #
Flare Nut Size ①
Flare Fitting ②
Length L1
Length L2
06654113
3/8” (9.52mm)
1/4” (6.35mm)
4.37” (111mm)
5.55” (141mm)
06654114
5/8” (15.9mm)
3/8” (9.52mm)
6.92” (176mm)
6.50” (165mm)
Connects to Outdoor Unit
Additional Clearance
≈ 9” (220mm)
L1
L2
Top View
06654110 1/4” (6.35mm) 3/8” (9.52mm) 3.11” (79mm) 3.5” (88mm) 06654111 1/2” (12.7mm) 3/8” (9.52mm) 4.45” (113mm) 4.65” (118mm) 06654112 1/2” (12.7mm) 5/8” (15.9mm) 4.45” (113mm) 4.85” (123mm)
06654120 5/8” (15.9mm) 1/2” (12.7mm) 6.92” (176mm) 5.24” (133mm) 06554121* 3/8” (9.52mm) 1/2” (12.7mm) 4.37” (111mm) 3.74” (95mm) *Note: This subassembly only comes with the A-VFH42PA-1 model.
Flare Nut
Flare Fitting w/Cap
Connects to Line Set
IMPORTANT: Due to the use of these subassemblies on the connections of the outdoor unit, please be
sure to accommodate for about 9” (220mm) of clearance from the side of the unit where the refrigerant lines attach.
Unit Length
Required
Subassemblies for A-VFH24TA-1, A-VFH30QA-1 Outdoor Units:
For models A-VFH24TA-1 and A-VFH30QA-1, two (2) subassemblies consisting of a straight piece of copper with a female flare nut x male flare fitting, are provided to connect any indoor units that have 1/2” (12.7mm) gas connections with the outdoor unit’s 3/8” (9.52mm) gas connections.
14
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
06643008
3/8” (9.52mm)
1/2” (9.52mm)
5.28” (134mm)
Part #
Flare Nut Size ①
Flare Fitting ②
Length L1
Outdoor
Flare Fitting
L1
Indoor
Flare Fitting
L1
Part # Flare Nut Size ① Flare Fitting ② Length L1
Indoor
1/2” Gas
Connection
Flare Nut
Connects to Outdoor Unit Gas Connection
(w/Cap-not shown)
Connects to Indoor Unit
3/8” Gas
Connection
Subassemblies for Indoor Units:
Model B-VFH18MA-1 comes with one (1) subassembly consisting of a straight piece of copper with a female flare nut x male flare fitting, are provided to connect with the outdoor unit’s 3/8” (9.52mm) gas connections.
06643008 3/8” (9.52mm) 1/2” (9.52mm) 5.28” (134mm)
Flare Nut
Connects to Outdoor Unit Gas Connection
(w/Cap-not shown)
Connects to Indoor Unit
1/2” Gas
Connection
Outdoor
3/8” Gas
Connection
Indoor Units also come with Additional Flare Nuts for ease of installation:
Per the chart below, each indoor model comes with one (1) or two (2) flare nuts in the sizes shown.
Indoor Unit Flare Nut
B-VFH09MA-1
B-VFH12MA-1
B-VFH18MA-1 5/8” (15.9mm)
B-VFH12CA-1 3/8” (9.52mm) B-VFH18CA-1 1/2” (12.7mm)
B-VFH24CA-1 3/8” (9.52mm) N/A
1/4” (6.35mm) N/A
15
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Leak Test, Evacuation & Release of Refrigerant
The recommended procedure for leak test, evacuation,
WARNING
It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods and equipment when working on the refrigerant containing parts of the unit. Service should be performed by a QUALIFIED service agency and
certied technicians.
The condensing unit is supplied with a R-410A factory charge—see rating plate and outdoor unit for exact amount. Charge must be added for interconnecting tubing. See Field Charging Section of this manual.
The unit’s service valves are shipped in the closed position and should not be opened until nal connections and evacuation are completed.
and release of refrigerant is outlined below:
1. Complete the nal piping connections to the indoor and outdoor units using line sets equipped with are ttings.
2. Connect a charging manifold to the service ports provided at the service valves.
3. Pressurize the lines and evaporator with nitrogen and leak check all connections with soap bubbles. Repair as necessary any faulty joints. If brazing is required be sure to RELEASE THE NITROGEN FIRST. Re-test as needed.
4. Connect a vacuum pump to the manifold center connection, start the pump and open the manifold valves.
5. Evacuate to 500 microns or less for a minimum of 30 minutes. Close the manifold valves and shut off the pump. Note the vacuum reading and wait 15 minutes. Take a new vacuum reading. A reading of 800 microns or higher indicates the presence of moisture or a leak.
6. Repair as necessary and repeat steps 3, 4 & 5.
7. Conrm that manifold valves are closed and disconnect the vacuum pump.
8. Remove the caps from the services valves. Open the valves to the fully ‘back-seat’ position. Replace service valve caps and tighten.
Electrical Precautions
CAUTION
1. Refer to the unit’s rating plate for power supply voltage. Ensure adequate electrical supply is available.
2. Ensure the air conditioner is properly grounded.
3. Connect wiring to the unit according to the electrical diagram located on the unit.
4. All wiring must comply with local and national electrical codes and be installed by a quali­ed electrician.
5. An individual branch circuit must be available.
6. Properly size the HACR breaker/fuse based on nameplate date.
7. Improper connections and inadequate grounding can cause injury or death.
8. Connect all wiring tightly. Loose wiring may cause overheating at connection points and create a possible re hazard.
9. Match terminal strip numbers/labels and colors between indoor and outdoor wiring. Errone­ous wiring may cause re/shock.
10. Always use strain reliefs and outdoor cable cover to protect wiring.
16
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
Unit Wiring
The contractor is to provide an individual branch
WARNING
• Before performing any electrical work, ensure
all power is off. Electrical shock may occur.
• All outdoor unit’s capacitor’s to discharge
otherwise electrical shock hazard may occur.
Ensure the unit is properly grounded.
circuit for over current protection for the unit as required by code. Some codes may require a disconnect between the indoor and outdoor unit. Run power supply wiring through a weatherproof disconnect box and conduit to the unit connection. Disconnects are required to be within sight and easy reach of the unit (usually within 3 feet). Circuit breakers and disconnect switches should be properly sized based on the required codes and the unit’s nameplate requirements. (Fig.12)
ELECTRICAL WIRING
AND SUPPLY VOLTAGE:
All electrical wiring must be done according to local codes. Additionally installations in the USA, must conform to the current National Electric Code (NEC) and Installations in Canada must conform to current Canadian Electric Code (CEC). Nameplate data indicates the operating voltage, phase, ampacity, maximum over current protection, and minimum voltage.
Model BTUH/H 18 24 30 36 42
POWER (outdoor)
CIRCUIT BREAKER/FUSE (A) 20 30 45 45 50
NOTE: Subject to change. Always refer to unit’s nameplate.
PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase
VOLT 208/230VAC 208/230VAC 208/230VAC 208/230VAC 208/230VAC
Check the unit wiring diagram for the number of conductors required. Ensure that the proper AWG (gauge) and type of wired is used to comply with code and the unit’s nameplate. Route neatly and protect from sharp edges and damage.
Inadequate wiring and/or improper electrical supply will likely result in failure of the compressor and other electrical components and voids the warranty.
Fig. 12
Branch circuit breaker
17
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Electrical Work
Outdoor unit power and communication cable wiring
1. Remove the electrical control cover from the outdoor unit (Fig. 13).
2. Connect power supply wires to the outdoor unit’s terminal strip (Fig. 14-19).
3. Connect the communication cable from the indoor unit to the outdoor unit’s terminal strip on the left side. Repeat for each indoor unit (Fig. 14-19).
4. Connect the ground wire of the communication cable to the ground terminal (Fig. 14-19).
5. To prevent water from entering in the unit, form a loop in the cable (Fig. 13).
6. Insulate any unused conductors with electrical tape, so that they do not touch any other exposed electrical or metal parts.
7. Replace the electrical control cover that was removed in Step 1.
Air inlet (side)
Air outlet
Fig. 13
Air inlet (rear)
Cover
Screw
Loop the cable
Fig. 14
1. The power cable should be placed in the hole under connection cable cover.
2. If connecting two indoor units, the connection cable should be placed in hole A and hole B.
3. If connecting three indoor units, the connection cable should be placed in hole A, B and C.
4. If connecting four indoor unit, the connection cable should be placed in hole A, B, C and D.
5. If connecting ve indoor units, the connecting cables should be places in holes A, B, C, D and E.
18
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
Electrical Work
18KBTU/H
Fig. 15
Fig. 16
24KBTU/H
19
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Electrical Work
Fig. 17
30KBTU/H
Fig. 18
20
36KBTU/H
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
Electrical Work
Fig. 19
42KBTU/H
Field Charging
Unit performance, efciency, and life depends, to a large extent, on a proper system charge. Time spent on getting the charge right at start-up will payoff in the long run. Operating conditions such as voltage, air ow, evaporator coil size, and indoor and outdoor temperature and humidity all have an effect on the system pressures and superheat conditions.
Units are factory charged before shipment. See rating plate on outdoor unit for exact amount.
These units should be critically charged to ensure proper performance. Some systems may require additional charging of refrigerant, depending on line set lengths. If the total line set length is less than the amount in the table below, no additional
KBTU/H
18 32.8 ft. (10m) 24 98 ft. (30m)
30 / 36 131 ft. (40m)
42 166 ft. (50m)
Total allowable length (for all indoor units)
refrigerant is needed.
If the total length or refrigerant lines for all models is greater than the amount shown in the chart, additional refrigerant is needed.
18 - 30 KBTU/H Units
Additional Refrigerant Charge = sum of additional line length* ft (m) times 0.22 oz/ft (20g/m).
36 - 42 KBTU/H Systems
Additional Refrigerant Charge = sum of additional line length* ft (m) times 0.24 oz/ft (22g/m).
*Additional line length is the sum of all the line sets for all indoor units subtracted from the total allowable length shown in the table.
21
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
Field Charging Example
36KBTU/H
Outdoor Unit
OUTDOOR UNIT INDOOR UNIT LINE SET/LENGTH
j 9KBTU/H k 9KBTU/H
36KBTU/H
l 9KBTU/H m 9KBTU/H
Four 9KBTU/H
Indoor Units
a / 30 ft (9m)
b / 35 ft (10.6m)
c / 40 ft (12.2m)
c / 50 ft (15.2m)
Total length of refrigerant line set = a + b + c + d
= 30' (9m)+ 35' (10.6m) + 40’ (12.2m) + 49' (15.2m)
= 154 ft (47m) total
The allowable line length for a 36KBTU/H unit is 131 ft (40m) as shown on the table on page 17. The total line set length for the example installation is 154 ft (47m) which is greater than the allowable length, so additional refrigerant is required.
To calculate the additional refrigerant needed , multiply the additional line length by .024 oz/ft (20g/m) for a 36KBTU/H unit. To get the additional line length, subtract the allowable line length from the total system line length.
CALCULATION EXAMPLE:
Total system line length 154 ft (47m) minus the allowable line length 131 ft (40m) = 23 ft (7m)
To determine the additional refrigerant, the additional line length 23 ft (7m) is multiplied by 0.24 oz/ft (20g/m) = 5.5 oz (154g)
In this example, 5.5 oz (156g) of additional refrigerant is needed for a complete charge.
22
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
Final Inspection
Do a visual inspection of the entire installation. Complete any nal steps and clean up the work areas.
Ensure that all units—indoor and outdoor—are working properly.
IMPORTANT!
All panels must be installed, main power turned on and wiring, refrigerant lines, and condensate drain lines properly connected before operating the unit.
Operation of the unit will depend on the setting of the thermostat on the indoor unit. Refer to the indoor unit’s manual for operating instructions.
Review the system and controls with the homeowner
Ensure that the homeowner is provided with all manuals, warranty card, receipt and any additional documentation that might be available or required.
23
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
This page is left intentionally blank.
24
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
This page is left intentionally blank.
25
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller
This page is left intentionally blank.
26
Heat Controller VFH InverterFlex® - Outdoor Ductless Mini-Split
This page is left intentionally blank.
27
VFH InverterFlex® - Outdoor Ductless Mini-Split Heat Controller

'XHWRRQJRLQJSURGXFWLPSURYHPHQWVVSHFLILFDWLRQVDQGGLPHQVLRQVDUH
VXEMHFWWRFKDQJHDQGFRUUHFWLRQZLWKRXWQRWLFHRULQFXUULQJREOLJDWLRQV'HWHUPLQLQJWKH
DSSOLFDWLRQDQGVXLWDELOLW\IRUXVHRIDQ\SURGXFWLVWKHUHVSRQVLELOLW\RIWKHLQVWDOOHU
$GGLWLRQDOO\WKHLQVWDOOHULVUHVSRQVLEOHIRUYHULI\LQJGLPHQVLRQDOGDWDRQWKHDFWXDOSURGXFW
SULRUWREHJLQQLQJDQ\LQVWDOODWLRQSUHSDUDWLRQV
,QFHQWLYHDQGUHEDWHSURJUDPVKDYHSUHFLVHUHTXLUHPHQWVDVWRSURGXFWSHUIRUPDQFH
DQGFHUWLILFDWLRQ$OOSURGXFWVPHHWDSSOLFDEOHUHJXODWLRQVLQHIIHFWRQGDWHRIPDQXIDFWXUH
KRZHYHUFHUWLILFDWLRQVDUHQRWQHFHVVDULO\JUDQWHGIRUWKHOLIHRIDSURGXFW
7KHUHIRUHLWLVWKHUHVSRQVLELOLW\RIWKHDSSOLFDQWWRGHWHUPLQHZKHWKHUDVSHFLILF
PRGHOTXDOLILHVIRUWKHVHLQFHQWLYHUHEDWHSURJUDPV
:HOOZRUWK$YH-DFNVRQ0,3KZZZKHDWFRQWUROOHUFRP
4/2014
28
Loading...