“Ce manuel est disponible en Français sur demande”
R1
SAFETY NOTICE
PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INST ALL AND USE YOUR NEW BOILER. FAILURE T O FOLLOW INSTRUCTIONS MA Y RESUL T IN PROPERTY DAMAGE, BODIL Y INJURY, OR EVEN DEA TH.
FOR USE IN THE U.S. AND CANADA. SUIT ABLE FOR INST ALLA TION IN MOBILE HOMES
IF THIS HARMAN PELLET BOILER IS NOT PROPERL Y
FOLLOW INSTALLATION DIRECTIONS.
CONT ACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INST ALLA TION INSPECTION
REQUIREMENTS IN YOUR AREA.
CONT ACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIP AL BUILDING DEP ARTMENT , FIRE DEP ARTMENT, FIRE
PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FOR A PERMIT .
CETTE GUIDE D'UTILISA TION EST DISPONIBLE EN FRANCAIS. CHEZ VOTRE CONCESSIONNAIRE DE HARMAN STOVE
COMP ANY.
SA VE THESE INSTRUCTIONS
INST ALLED, A HOUSE FIRE MA Y RESUL T . FOR YOUR SAFETY ,
R4
3
Table of Contents
Assembly4
Venting8
Installation11
Operation20
Maintenance2 7
Troubleshooting31
Feeder Parts32
Specifications3 3
Wiring Diagram3 4
Parts List & Options3 5
Warranty36
Testing Label37
Quick Reference Start-UpBack Cover
Please read this entire manual before you install and use your new
boiler . Failure to follow instructions may result in
property damage, bodily injury , or even death.
SAVE THESE INSTRUCTIONS
Harman S tove Company
352 Mountain House Road
Halifax, P A 17032
4
Assembly
nt
C
n B
He
W
ere
nt
C
n B
He
W
ere
ombustio
ombustio
ESP Probe
ESP Probe
lue TunnelWeldme
lue Tunne l Weldme
ater Coil OptionShownH
ater Coil Option Shown H
*Removed w/ DomesticHot
*Re mo ved w/ Domest ic Ho t
Blank Cover*
Blank Cover*
Pressure Relief Valve
Pressure Relief Valve
Aquastat Well
Aquastat Well
Temperature /PressureGauge
Tempera t ure / Pressu re Gauge
Firebox & Ash
Doo r Handles
Firebox & Ash
QTY (5)
QTY (5)
Doo r Handle s
Thumb Screws(3)
Thumb Screws (3)
½”MPT BoilerDrain
(Not Shown)
½”MPT Bo iler Drain
(Not Shown)
Outdoor Air Temperature Sensor Wiring :
Heat Exchan ger
Cleanout Rod Handles
Heat Exchan ger
Cleanout Rod Handles
Access Cover To Secondary Ash Chamber
Remove Cover to accessnuts tofasten Flue
Access Cover To Secondary Ash Chamber
Tunnel Weldment to the Ash Chamber.
Remove Cover to access nuts to fasten Flue
Tunnel Weldment to the Ash C hamber.
5
Assembly
Boiler Kit Materials: (Refer to pages 4 & 5)
List of items contained within the boiler kit shipped with the
unit.
Installation of the Flue Tunnel Weldment,
Combustion Blower and Wiring, ESP and Heat
Shield:
Step 1: First install the flue tunnel weldment by aligning
the (4) studs up with the (4) holes in the ash
chamber base.Fasten the (4) nuts and lock washers
provided, to the studs by removing the access cover on
the secondary ash chamber.
Step 2: Place the combustion motor onto the flue tunnel
weldment and tighten the (3) wing screws provided.
Step 3: Insert the Exhaust Sensing Probe (ESP) into
the 1/8" hole provided on the flue pipe stub. Fasten
with the (1) #8x1/2" TEK screw also provided. ESP
will be taped to the sheet metal jacket for shipping
purposes.
Step 4: Connect the flex conduit 90 degree elbow(Not
Shown) to the heat shield in the hole provided. Then
connect the (3) wires from the combustion blower with
the (3) wires in the flex conduit by using the push-on
connectors and matching the wire colors as follows:
Red to Black, White to White and Green to Green.
Step 5: Place Heat Shield over combustion blower and
align the swell latches with the holes in the sheet metal
and tighten.
6
Assembly
After assembly of the flue tunnel weldment, combustion
blower assembly with wiring and heat shield, the boiler can
now be installed.
1. Install the control board cover as well as the access
cover located on the feeder cover.
2. Install the spring handles provided with the unit on
the ash door, firebox door and the heat exchanger cleanout
rod handles. (Fasten handles by turning them counterclockwise and pushing inward simultaneously).
3. Install 1/2” MPT boiler drain in the fitting as
shown.
Note: Use teflon pipe thread sealant or teflon
tape on ALL threads before connections are made.
4. Install 3/4” MPT pressure relief valve as shown.
5. Install the 1/2” MPT aquastat well in fitting as
shown, then place aquastat in the well and fasten with a zip
tie.
6. Install the 1/2” MPT temperature/pressure gauge in
fitting as shown.
7. Locate and install outside air temperature sensor.
Location of this sensor should be on the north side of the
home or building and out of direct sunlight. Use the cat
cable supplied with the boiler to attach sensor to the
terminals located on the hopper. (Place at the back side just
above and to the right of the main power connection box)
The wires can be connected to the sensor with the connectors supplied. Wire nut or butt splice connectors could also
be used. The connections at the boiler can be done with the
two 1/4” female push on connectors supplied.
8. Fasten conduit to the ash base with the clamps
provided.
Floor Protection:
The striped area indicates the minimum required floor
protection area if the PB105 is going to be placed on a
combustible floor . It requires 30” X 55” of non combustible floor protection as shown below . 6” of the floor
protection must be in front of the boiler as shown. Flooring must be a minimum of 26 gauge sheet metal. Floor
protection must also be provided under any horizontal run
of vent pipe equal to the outside diameter of the venting
plus 2” to each side.
MINIMUM NON-COMBUSTIBLE FLOOR PROTECTION AREA
Non-Combustible
Floor Protector
Design:
The first thing that needs to be done is deciding where and
how the boiler will be installed.
Things that need to be taken into consideration are the
intended use of the boiler for example, is the boiler going to
be used as your primary heating system or is it going to be
used as a secondary or backup heating system. If it is to be
used in conjunction with an existing oil or gas boiler system
will it be piped in parallel or in series? The answers to these
and other questions can be determined by talking to your
certified dealer or a qualified HV AC or plumbing contractor . This will insure that the boiler is installed and piped to
accommodate your needs and expectations.
Consideration must be given to the venting as well as
electrical and clearance requirements. (Clearances must be
maintained to combustibles and also for service)
Example: 4” type “L” or “PL” vent pipe has an outside
diameter of 4-1/2” + 2” on each side equals a protected
floor area of 8-1/2” wide underneath the horizontal run.
After the boiler is set into place the venting can be done.
Make sure fans are not used in the fuel storage area, unless
they are installed so as not to create a negative pressures in
the room where the solid fuel burning appliance is located
7
Assembly
When installing the PB105 in a mobile home several
requirements must be followed:
1. The unit must be bolted to the floor .
2. The unit must be connected to outside air .
3. Floor protection and clearances must be followed.
4. Unit must be grounded to the metal frame of the mobile
home.
8
INSTALLATION IS TO BE PERFORMED BY A
QUALIFIED INSTALLER.
NOTE: All installation clearances and restrictions
must be adhered to.
NOTE:Use only 4” diameter type “L” or “PL” venting
system. Be sure to inspect and clean exhaust venting
system frequently.
Venting
Requirements for Terminating the V enting
W ARNING: V enting terminals must not be recessed
into a wall or siding.
NOTE: Only PL vent pipe wall pass-throughs and
fire stops should be used when venting through combustible materials.
NOTE: Always take into consideration the ef fect
the prevailing wind direction or other wind currents will
cause with flyash and /or smoke when placing the termination.
In addition, the following must be observed:
A. The clearance above grade must be a minimum
of 18".
1
B. The clearance to a window or door that may
be opened must be a minimum of 48" to the side, 48"
below the window/door, and 12" above the window/
1
door.
( with outside air installed, 18” )
C. A 12" clearance to a permanently closed window is recommended to prevent condensation on the
window .
D. The vertical clearance to a ventilated soffit located above the terminal within a horizontal distance of
2 feet (60 cm) from the center-line of the terminal must
be a minimum of 18".
E. The clearance to an unventilated soffit must be
a minimum of 12".
F . The clearance to an outside corner is 1 1" from
center of pipe.
G . The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90
cm) above a gas meter/regulator assembly when measured from the horizontal center-line of the regulator .
1
I. The clearance to service regulator vent outlet
must be a minimum of 6 feet.
1
J. The clearance to a non-mechanical air supply
inlet to the building or the combustion air inlet to any
other appliance must be a minimum of 48”.
1
K. The clearance to a mechanical air supply inlet
must be a minimum of 10 feet.
1
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a
paved driveway located on public property must be a
minimum of 7 feet.
M. The clearance under a veranda, porch, deck
or balcony must be a minimum of 12 inches.
1,2
1,3
NOTE: The clearance to vegetation and other
exterior combustibles such as mulch is 36” as measured
from the center of the outlet or cap. This 36” radius
continues to grade or a minimum of 7 feet below the
outlet.
1
Certain Canadian and or Local codes or regula-
tions may require different clearances.
2
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two
single family dwellings and serves both dwellings.
3
Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the
floor.
NOTE: Where passage through a wall, or partition
of combustible construction is desired, the
installation shall conform to CAN/CSA-B365. (if
in Canada)
V
= Vent terminal
Fixed
Closed
Openable
A
Openable
= Air supply inlet
Fixed
Closed
Inside
Corner
Detail
= Area where terminal is not permitted
Fig. 2
9
Venting
10
Fig. 3
Venting
Venting
Venting
Use 4” pellet vent pipe to vent your PB105.
A combustion blower is used to extract the combustion
gases from the firebox. This creates a negative pressure in
the firebox and a positive pressure in the venting system as
shown in Fig. 4. The longer the vent pipe and more elbows
used in the system, the greater the flow resistance. Because
of these facts we recommend using as few elbows as possible and 30 feet or less of vent pipe. The maximum horizontal run should not exceed 18 feet.
Be sure to use wall and ceiling pass through fittings (which are approved for pellet vent pipe ) when
going through combustible materials. Be sure to use astarting collar to attach the venting system to the stove. The
starting collar must be sealed to the stove flue collar
with high temp silicone caulking or aluminum tape, and
screwed into the stove flue collar at least three (3)
places.
4” T ype “L” or
“PL” Vent pipe
Fig. 5
This is the minimum venting configuration.
+
-
Fig. 4
Vent Pipe
4” pellet vent pipe (also known as PL vent) is constructed
of two layers with air space between the layers. This air space
acts as an insulator and reduces the outside surface temperature to allow a minimum clearance to combustibles of 1 inch.
In Canada the minimum clearance to combustibles is 3 inches.
The sections of pipe lock together to form an air tight
seal in most cases; however, in some cases a perfect seal is
not achieved. For this reason and the fact that the PB105
operates with a positive vent pressure, we specify that all
joints within the structure should also be sealed with
clear silicone.
NOTE:Use only 4” diameter type “L” or “PL” venting
system. Be sure to inspect and clean exhaust venting
system frequently.
The minimum vent configuration is a 90o or T ee on a
starter collar and a 24” length horizontal through an exterior
wall. A cap or other bird screen on the end should direct
the flue gasses down and away from the structure. See Fig.
5.
The maximum horizontal length is 18 feet. The minimum termination height above the exterior grade is 18”. The
maximum total length of any configuration is 30 feet*.
* ( see venting graph on page 9 for exceptions )
NOTE: Cleanout Tee’s should always be used on the
transitions to horizontal pipe to allow easy access for
cleaning.
The venting graph allows for (one) 90 deg. or T ee fitting in any configuration.
If more 90’s, T’s, or 45’ s are needed the total length
must be adjusted to allow for the added restriction.
Up to four (4) additional 90’s, Tee’s, or equivalent
45’ s can be added as long as the overall length is adjusted
in accordance with the values listed below .
( See the venting graph on page 9.)
Each Vertical ---- 90 deg. or T subtract 2.5 feet
Each Vertical ---- 45 deg. subtract 1.5 feet
Each Horizontal - 90 deg. or T subtract 5.0 feet
Each Horizontal - 45 deg. subtract 2.5 feet
Any exterior venting (vent pipe exposed to outside ambiant temperatures) should be kept to a minimum, due to potential condensation problems.
This is especially important in high humidity cold
weather climates, such as maritime areas, lake shores, and
low river valleys.
11
Venting Installation
Chimneys taller than 20’ above the connection will re-
quire a draft test to determine if the draft is too high.
Note: The High Burn Draft should not exceed .85
IWC. Some form of a restrictor plate may be required at the
top of high chimneys to reduce the draft. See page 19 for
the Draft T est procedure.
The PB105 Boiler may be used and installed into an
existing masonary or Class A metal chimney .
Certain Canadian and Local Codes may require that
the chimney be fully relined.
It Can Not be installed in a chimney serving another
appliance.
The chimney should be cleaned and or inspected before installation.
Creosote - Formation and Need for Removal - When wood is burned slowly, it produces tar and other organic vapors,
which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue
of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an
extremely hot fire. The pellet vent pipe should be inspected at least twice monthly during the heating season to determine
if a creosote buildup has occurred. If creosote has accumulated it should be removed to reduce the risk of a chimney fire.
Guidance on minimizing creosote formation and the need for periodic creosote removal: The chimney should be
inspected during the heating season to determine if a creosote build-up has occurred. If a significant layer of creosote has
accumulated (3mm or more) it should be removed to reduce the risk of a chimney fire.
12
Inlet Cover part#
1-10-09542
Outside Air Pipe
Outside Air Pipe
Knockout
Knockout
Feeder Cover
Feeder Cover
Fig. 7
Installation
Outside Air
Outside air is optional, although it may be required
by some building codes. The benefit of outside air is
higher efficiency and reduced venting restrictions mainly
noticed in small and very tight houses.
T o install outside air, use 2 3/4”" I.D.galvinized steel
flex pipe, part # 2-00-08544 ( 12’ 6” length) or part #
2-00-08545 ( 25’ length) See Fig. 6. There is a breakaway hole on the rear panel which must be removed
before connecting the flex pipe. See Fig. 7. The pipe
Fig. 6
should be run outside and terminate 3 feet or more below or 1 foot or more to the side of the vent pipe outlet.
Never terminate the outside air above the vent pipe outlet. The maximum length of this pipe is 20 feet. Inlet
cover part number 1-10-09542 should be used to keep
birds, rodents etc.out of the inlet pipe. See Fig.6.
NOTE: If outside air is installed, the inlet cover
should not be placed in an area where drifting of
snow or ice will build up, blocking the intake air
supply.
The Outside Air knockout is located on the face
of the Feeder Cover. It is pre-cut except for several
small tabs. There is also a filler plate screwed to the
inside to cover the top of the hole after the Outside Air
Pipe has been installed. This will allow for removal of
the Feeder Cover without disconnecting the Outside Air
Pipe. See Fig. 7.
Only metal Intake Flex should be used for the
Outside Air Supply connection.
Only a screened or rodent protected Outside Air
Intake cover should be used as an outside weather cover.
The Outside Air Intake Pipe is inside the Feeder
Cover and to the right of the feeder motor. The 2 3/4”
steel flex pipe is made to slide over the outside of the Air
Intake Pipe.See Fig. 8. It should be held into place with
some silicone, foil tape, or a hose clamp.
(not supplied)
Outside Air Inlet Pipe
Outside Air Inlet Pipe
Hopper/Feeder Swing
Hopper/Feeder Swing
Plate Knob
Plate Knob
Fig. 8
Heat Reclaiming Ventilation System
(HRV)
When installing in a house with a Heat Reclaiming
Ventilation System (HRV) be sure the system is balanced and is not creating a negative pressure in the house.
NOTE: If the boiler is installed with the outside air system no adjustments to the HRV should be
necessary.
13
Main Wiring Installation
14
NOTE: If other sources of electrical power are to be used ( such as a generator ) for normal operation or emergency operation, this
T o install power to the boiler first remove the cover on the 4” X 4” junction box located on the back of the unit. There are several knockout holes
provided for the incoming main power wires. Also, a knockout hole can be used for the auxiliary output overheat zone (if used).
The minimum recommended circuit is 6 AMP - 120 VAC - 60 HZ. This boiler should be the only appliance on the circuit. If a 15 AMP circuit breaker
is used at the distribution box, the boiler must be protected with an in-line fuse rated at 6 AMP .
This boiler should never be powered by the use of an extension cord.
The recommended high and low voltages are, 130 V.A.C. 60 Hz maximum high voltage, and 113 V.A.C. 60 Hz minimum low voltage.The furnace will
continue to operate at voltages as low as 105 V.A.C. , although it can not be guaranteed that automatic ignition will occur.
source should be checked before installation. Many generators and inverters may not supply 120V.A.C. 60Hz. power stable enough to operate
the control board properly. (Control board damage could occur).
Installing Duct
Installation
15
Installing Duct/Air Conditioning
Boilers intended to be connected to an existing boiler or boiler system shall:
1. Be capable of being installed without interfering with the normal delivery of heated water from the original boiler to the radiation
system.
2. Be capable of being installed to operate as intended without affecting the operation of the electrical and mechanical safety controls
of the original boiler.
3. Provide, upon completion of the installation, for a change over from one fuel to the other without requiring the manual adjustment of
any controls or components other than the thermostats.
4. Be compatible with the operation of a service water-heating coil within the original boiler without bypassing the operation of the
solid-fuel boiler.
5. Have provision for preventing, or adequate water capacity within the boiler to prevent, damage to the boiler from loss of circulation
due to electrical power failure.
6. Be capable of being installed without changing the function of the control or rewiring of the original boiler. A wiring interconnection
is permitted. The electrical system of both boilers shall be powered from a single branch circuit without exception.
(CAN/CSA-B366.1-M91)
Installation
16
Installation
17
Installation
18
Installation
19
Draft Bolt Location
Viewing Window
Installation
Air wash Slot
Fig. 9
Draft T est Procedure
After the venting is completed, the firebox low draft
will need to be checked and possibly adjusted. After removing the 3/8” bolt from the draft hole shown in Fig. 9,
insert the draft meter tube. The hopper lid must be latched
during this test. (It is recommended that the draft meter
have a scale of 0 to 1” WC.)
Turn the feed adjuster to “T est”. this will start the combustion blower and allow you to check and record the High
Draft ______ - IWC date _______ (There is no adjustment for the High Draft)
After the first 60 seconds the “T est” mode lowers the
combustion blower voltage to the Low Burn voltage. (The
“T est” mode cycles the voltage from high to low every 60
seconds).During this lowered voltage cycle the Low BurnDraft must be checked and adjusted if necessary . The
recommended low draft setting should be between -.25 &
-.35 IWC. Depending on the amount of vertical rise, it may
not be possible to get a low draft reading in this range. In
this case, a maximum low draft of -.55 is acceptable.
The adjustment screw is through the small hole to the
right of the Igniter Light. See Fig. 10. Adjusted Low Draft
is __________ -IWC.
Don’t forget to turn the feed adjuster back to #4.
20
Operation
Power Light
Indicates power to the
control board.
Status Light
Will be lit anytime ther e is a
call for heat.
Overheat Saftey Zone Light
Indicates that the boiler
water temperature has
reached 205 Degree F.
Combustion Blower Light
Indicates Power to
combustion blower
Feed Motor Light Indicates
Power to the feed motor.
Igniter Light
Indicates power to the
igniter
Feed adjuster
Sets the maximum feed rate
Test
Combustion blower , feed motor
and safety dump zone are fully
energized for the first minute.
Combustion blower alternates
from high to low every minute.
Lighting Mode Selector
Switched between Auto and
Manual lighting
Mode Selector/Min Temp
Dial
Used to turn the boiler on or
off and set the desired
minimum operating
temperautre of the boiler.
Dealer Diagnostic Port
For dealer maintenance only.
Requires special DDM
monitor supplied to Harman
Dealers exclusively.
Max Temp dial
The “Max Temp Dial” is used to set the desired
maximum operating temperature of the boiler.
Status light error messages:
1 Blink: Indicates control board self diagnostic failure. This
requires a manual reset by cycling the main power off for a
few seconds and re-connect.
3 Blinks: Indicates ESP (Exhaust Sensing Probe) failure. This
requires a manual reset by cycling the main power off for a
few seconds and re-connect.
5 Blinks: (In Auto Light Mode Only)
Indicates that the igniter has failed to light the fire after 40
Minutes. To reset - Turn the Mode Selector/Min. Temp. to
OFF and then back to the desired temperature.
6 Blinks : Indicates that the control has calculated poor or
incomplete combustion occurring for 25 or more minutes.
A six blink status may be set if the stove is allowed to run out
of pellets. To reset, turn Mode Selector/Min Temp dial to
"OFF" then back on to the desired temperature. If the unit
was not out of pellets, see Troubleshooting section, Page 31,
for more details.
7 Blink: Boiler water over heat saftey shut down (210 Degree
Farenheit) This requires a manual reset by cycling the main
power off for a few seconds and re-connect.
Mode Selector/Min. Temp.
Used to turn the boiler on or off and set the desired minimum
operating temperautre of the boiler.
Max. Temp./ Min. Temp. Water Temperature Settings
See “Setting the boiler temperature” found on page 21.
OFF Mode
Turning the Mode Selector/Min.T emp. to OFF will shut down
the boiler.
21
Operation
Setting The Boiler Temperature
Without the Outdoor Air T emperature Sensor Installed
simply turn the Max. T emp. water temperature dial to the
desired setting. The control and the boiler will then perform to achieve and maintain the set temperature.
mode switch, on or off. T urning the knob fully counterclockwise is the “OFF” position while turning the knob
clockwise past the 120 degree position is the “ON”
position.
With The Outdoor Air T emp - Sensor Installed
above.
mode setting (on or off) now also has the function of
setting the minimum boiler water temperature. This would
be the lowest boiler water temperature that you want to
have based on the following factors.
NOTE:
Although the full operational scale of the boiler water
temperature setting is from 120 to 185 degrees F, in
most cases it would not be recommended to maintain a
boiler temperature less than 140 degrees F.
T o set the maximum boiler water temperature,
The Min. T emp. Knob simply becomes the boiler
Maximum boiler temp setting is as described
The MIN. TEMP . knob in addition to being the
1.) Outdoor Air T emperature (OA T)
2.) Domestic Hot W ater Use
a.) Hot W ater Coil Option
b.) Indirect Hot W ater Storage
3.) Overall Volume of the Heating System
Control Board Operation
Aquastat Sensor - This sensor is located in the
aquastat well on the top of the water jacket. This sensor
along with the outdoor air sensor is what the control board
uses to regulate the feed rate based on these two observed
conditions. (Boiler T emp. & Outdoor Air T emperature)
Outdoor Air Temp. Sensor (OAT) - This sensor
is located outside the building (on the north side of the
house and out of direct sunlight). The Outdoor Air Sensor
is used to perform hot water reset based on outdoor air
temperatures.
When the OA T sensor is installed, at zero degrees F
(outside temperature), the boiler will operate at the temperature set on the MAX. TEMP . knob. The boiler water
temperature will decrease by 1 degree F . for every 1
degree F . in temperature rise of the outdoor air .
NOTE: Pellet Boiler Outdoor Air Reset Operation
Graph located on page 22.
22
The PB105 is designed to withstand lower return water
temperatures however, extended return temperatures
below 130 degrees F can cause condensation in the
secondary ash chamber area and also in the venting
system both of which could cause damage in these
areas.
One Exception to this would be summertime operation with
a domestic hot water coil option. The boiler water temperature could be maintained at a lower temperature since there
would be no load from the heating system and recovery
would be quick.
NOTE:
If the system is run at the lower temperature settings,
conditions of the firebox, boiler tubes, secondary ash
chamber and venting should be monitored closely. If
any indications show excess condensation the boiler
water temperature will need to be increased until
condensation does not occur.
* No change in boiler tem perature after reaching mini mum s etpoint t emp
Degree
Water Temp
Degree
* No change in boiler tem perature after reaching mini mum s etpoint t emp
Degree
Degree
Water Temp
5180
0185
5180
65120
60125
55130
50135
45140
40145
35150
30155
25160
20165
65120
60125
55130
50135
45140
40145
35150
OAT
OAT
Pellet Boil er Outdoor Ai r Reset Operat i on
Pellet Boil er Outdoor Ai r Reset Operat i on
Example # 1
Example # 1
1 degree for every 1 degree in t em perat ure rise of the OA
1 degree for every 1 degree in t em perat ure rise of the OA
Mi n set @ 12 0
Mi n set @ 12 0
Max set @ 185
Max set @ 185
30155
15170
25160
20165
15170
0185
10175
10175
Water Temp
Water Temp
5175
0180
5175
65150
60150
55150
50150
45150
40150
35150
30150
25155
20160
65150
60150
55150
50150
45150
40150
35150
OAT
OAT
Example # 2
Example # 2
Mi n set @ 15 0
Mi n set @ 15 0
Max set @ 180
Max set @ 180
30150
15165
25155
20160
15165
0180
10170
10170
23
Operation
S tarting A Fire Automatically
1. Turn Mode Selector to "OFF".
This resets the control in addition to turning it off.
2. Clean burnpot with scraper, if necessary .
This is usually a weekly maintenance procedure.
Cleaning the burn pot with the scraper with a small
amount of new fuel in the bottom is not a problem. First,
scrape the ashes on the front of the burn pot into the ash
pan. Then scrape the hole grid surface downward into
the burn pot. When the stove is ignited these scrapings
will be pushed out by the feeder .
Scrape burnpot to remove any carbon
bu i ld- up t ha t m ay have occ urr e d
Scraping can be done while in operation if
perf orm ed through the firebox door
opening
NOTE: To minimize the amount of stress placed
on the hopper swing plate hinges, opening of the
hopper swing plate should be done when the hopper fuel level is low whenever possible.
3. Fill hopper with pellets.
When filling the hopper check for excessive fines in
the bottom of the hopper. Fines are small pieces of broken
pellets (sawdust). Fines do not flow easily and often
build up on the hopper funnel bottom angles. These fines
can be pushed into the feeder opening and then fill the
hopper with pellets. As the system works, they will be
burned.
24
Operation
4. If starting after an empty hopper, turn
Feed Adjuster to "TEST" (for one 60
second cycle).
the auger tube and also allow you to check
the motors for operation. NOTE: The auger
motor will not operate with any of the
doors open.
5. Turn Feed Adjuster to #4.
If this is your first fire or you are trying
different pellets, set the feed adjuster to #4,
This is a conservative number and will probably need to be increased if maximum BTU
output is desired. After you know a feed rate
setting that works well for your application,
use that setting.
This will purge pellets into
6. Flip the Igniter Switch up into the "AUTO"
position.
7. Turn the MAX. TEMP. Dial on the
control board to the desired temperature. This
setting must always be higher then the MIN.
TEMP. setting.
WARNING: HOT WHILE IN OPERATION.
KEEP CHILDREN, CLOTHING, AND
FURNITURE A WAY. CONTACT MA Y CAUSE
SKIN BURNS.
25
Operation
8. T urn the MIN. TEMP. Dial on the control board to
the desired Minimum temperature. This will start the
lighting process if the temperature at the aquastat sensor is
less than the set temperature on the MAX TEMP. dial.
The PB105 is more than just an automatic ignition pellet
boiler . The automatic system will allow the fire size to be
adjusted to match the heating needs and even put the fire
out if necessary . If heat is needed after the fire is out, the
PB105 will automatically re-ignite and adjust the fire size
to match the heating need.
Fig. 12
7. Open hopper swing plate as shown in Fig.
13 (See “NOTE” on page 23.)
9. Fill hopper with pellets and remove ashes as
required.
Type of Fuel
Use pelletized wood only . The lower the ash
content of the pellets the less cleaning that will be needed
of the heat exchanger surfaces. The cleaner these surfaces
are kept, the more efficient the boiler will be.
NOTE: Do not burn garbage, gasoline, naphtha,
engine oil, or other inappropriate materials in the
PB105.
Stor e pellets in the manufacturer’s wrapping
until needed to prevent pellets from absorbing
moisture. Do not store fuel within the appliance
installation clearances, or within the space required
for fueling, ash removal, and other routine
maintenance operations.
Lighting A Fire Manually
Lighting the fire manually will not be necessary unless
the igniter in the burnpot fails.
Follow steps 1 through 5 of the instructions for
automatic lighting.
6. Flip the Igniter Switch Down into the
"MANUAL-LIGHT" position. See Fig. 12.
Fig. 13
8. Fill burnpot with pellets as shown.
See Fig. 14. Only fill level with the front
edge. ( ------- DO NOT OVERFILL ------- )
Fig. 14
9. Have matches or other ignition source
ready.
10. Apply starting gel as shown in Fig.15
26
Operation
Fig. 15
NOTE: Stirring the starting gel into the pellets usu-
ally allows the fire to become established quicker.
11. Turn Mode Selector to desired MIN
TEMP setting.
This will start the combustion blower and allow the
ESP to control the fire in relation to the MAX TEMP Dial
setting. (The MAX TEMP dial setting must always be set
above the MIN TEMP setting) Once the fire is well established the MAX TEMP dial can remain on any temperature
setting desired.
NOTE: When the Switch is set to Manual igniter
position the boiler will function as in auto igniter except
the fire will not be allowed to go out. It will only be
allowed to go to a minimum burn rate between the times
the aquastat is calling for heat. This rate is about 1.1
pound of fuel per hour.
CAUTION: A vapor flash could occur if too much
time is allowed to pass before lighting the starting gel.
CAUTION: Care must be taken not to get starting
gel on your hands or clothing. Serious burns could occur
during the lighting process.
CAUTION: Never try to apply more starting gel to
an already burning fire, or a fire with smoldering pellets.
"NEVER USE GASOLINE, GASOLINE-TYPE
LANTERN FUEL, KEROSENE, CHARCOAL
LIGHTER FLUID, OR SIMILAR LIQUIDS TO
ST ART OR "FRESHEN UP " A FIRE IN THIS FURNACE. KEEP ALL SUCH LIQUIDS WELL AWAY
FROM THE FURNACE WHILE IN USE".
12. Light The Starting Gel With A Match.
13. Close The Doors
The fire will light and the PB105 will adjust the fire to
proper level according to the MAX TEMP dial setting.
Solid-fuel burning appliances need to be cleaned frequently because soot, creosote, and ash may accumulate. If
you suspect a chimney/vent pipe fire do the following:
1. Call the fire department.
2. Remove fuel from the burn pot using the burnpot scraping tool to scrape the pellets into the ash pan.
3. Remove the ash pan from the unit and take outside. Do
not place ash pan on a combustible material.
4. Turn of f circuit breaker at unit.
5. Do not use the unit until a qualified person has inspected
your appliance and venting.
Fig. 16
27
Burnpot cleaning:
The burnpot should be cleaned no less than once a week.
For best operation the burnpot should be cleaned every time the
hopper is filled with pellets. The fire does not have to be out to
scrape the burnpot although it is recomended the boiler be on
minimum burn at the time of cleaning.
Note: Scraping can be done while in operation if performed throug the firebox door opening. See Fig. 17
Use the flat end of the scraper provided to scrape down
over the holed surface of the burnpot grate. See Fig. 18. It is
not necessary to clean out the scrapings from this cleaning because they will be pushed out the next time the auger operates.
Note: Make a special effort to scrape the bottom inside corners of the burnpot where the auger tube enters the
burnpot. Carbon deposits can build up over time in this area
that may cause a restriction to the flow of pellets into the
burnpot.
Note: An old long shank scr ewdriver with the end sharpened is an ideal aid in the removal of these deposits.
Cleaning the burnpot air chamber:
This area only needs to be cleaned twice a heating season,
unless excessive buildup is noticed during scheduled cleanings.
There is a cover on the front of the burnpot to gain access
to the air chamber and igniter. The cover is held into place by
two thumb screws. Loosen the thumb screws and remove the
cover. See Fig. 19. The air chamber can be cleaned of any ash
that has fallen through the holes during operation and cleaning.
Also at this time, remove the feeder assembly cover and remove
any fines that may have accumulated.
NOTE: ALWAYS REMEMBER TO CLOSE THE
CLEANOUT COVER AFTER CLEANING.
Feeder Chamber (Fig. 20):
This chamber may get a buildup of fines from the feeder
mechanism movement. This area should be checked and cleaned
at least once a year.
To remove the feeder cover:
• Lossen the 5/16" wing nut.
• Slide the cover off of the threaded stud and lift upward.
• Inspect and clean the inner chamber if necessary . See Fig. 20.
• Reinstall the cover making certain it is centered on the feeder
body and tighten as tightly as you can by hand.
28
Ash D oo r
Ash D oo r
Maintenance
Ash Pan
Ash Pan
Ash Pan Handle
Ash Pan Handle
Ash Door Handle
Ash Door Handle
S ec o ndary Ash C hamber Ac c ess Co ver
S ec o ndary Ash C hamber Ac c ess Co ver
Ash Removal
It is recommended to remove the ashes when the boiler
is not in operation. This lessens the chances of coming in
contact with hot surfaces. Ashes can be removed while in
operation but, extra care must be taken.
Open Ash Door
Lift the latch and open the door as shown in fig. 21.
NOTE: Keep hopper lid, hopper swing plate, fir ebox door
and ash pan door closed during operation and maintain
all seals in good condition.
Remove Ash Pan
Always wear gloves to remove ash pan. Grab the ash
pan by the finger hold and pull it out of the boiler. Lift the ash
pan by the finger hold and use it for carrying the ash pan.
Close the ash door before disposing the ashes
Fig. 21
Disposal of Ashes
Ashes should be placed in a metal container with a
tight fitting lid. The closed container of ashes should be placed
on a non-combustible floor or on the ground, well away
from all combustible materials, pending final disposal. If ashes
are disposed of by burial in soil or otherwise locally dispersed,
they should be retained in the closed container until all cinders
have thoroughly cooled.
Soot and Flyash: Formation and Need for
Removal
The products of combustion will contain small
particles of flyash. The flyash will collect in the exhaust venting
system and restrict the flow of the flue gases. Incomplete
combustion, such as occurs during startup, shutdown, or
incorrect operation of the room heater will lead to some
soot formation which will collect in the exhaust venting system.
The exhaust venting system should be inspected at least twice
monthly to determine if cleaning is necessary .
29
Maintenance
Cleaning
This cleaning should be done after each ton of pellets
used. The frequency of this cleaning will be directly related to
the quality and the ash content of the pellets being used. Keep
in mind that the cleaner the heat exchanger surface is kept,
the higher the heat transfer efficiency will be.
Due to it’s ease of restarting it is recommended that the
boiler be OFF and COOL before cleaning.
Start by pulling the (3) heat exchanger cleanout rods by
pulling and pushing these rods vigorously severl times. It will
remove any fly ash built up on the heat exchanger tubes. This
can also be done at any time during the operation of the boiler
to maintain higher efficiencies. Make sure that these rods are
pushed in at all times.
Cleaning Steps
-Open hopper swing plate to access burnpot and also
the firebox. W ith a wisp brush, wire brush, stiff bristled paint
brush or a soot vac, clean the firebox walls and any fly ash
that has accumilated on the ledges of the burnpot, or burnpot
opening. At this time you can scrape and clean the burnpot
and fines cleanout area. Be careful not to damage the igniter
located inside the burnpot.
-Open firebox door and vaccum ash from ledges and
ash deflector. You can also clean the firebox door viewing
glass using a typical glass cleaner and soft cloth.
30
r
r
d
Latch (2)
d
d
Latch (2)
Latch (2)
Combustio n
Combustio n
Blower Moto
Blower Moto
Thumb Screws (3 Total)
Thumb Screws (3 Total)
HeatShiel
HeatShiel
Heat Shiel
ESP Probe
Maintenance
should attempt to clean the combustion blower .
disconnected during the cleaning process.
See Fig. 23. Hold the motor head with one hand and the blower
plate handle with the other hand. Pull outward on the plate
handle until the complete unit comes loose. Now rotate the
plate counter-clockwise about 1/8 turn. This will allow the
complete assembly to be removed from the blower chamber.
Fig. 22
sealing overlap. See Fig. 24.
will throw the fan blade out of balance or it may rub the
inner chamber, which may affect the performance of the
boiler. Any horizontal and vertical flue pipe directly above
the unit should be cleaned at this time
boiler is the first place fly ash will settle, due to the slowing of flue gas velocity through horizontal pipe. Cleaning
of horizontal venting pipes is very important to the efficiency of this boiler.
Fig. 23
of the flue tunnel (this is the hole that goes up into the flue
pipe). See Fig. 24.
same area. CARE MUST BE TAKEN NOT TO DAMAGE THE ESP PROBE DURING CLEANING. Bending
of the ESP probe will make it difficult to remove if it should
become necessary. See Fig. 24.
The furnace MUST be OFF and COOL before you
The wire to the combustion blower doesn’t need to be
Loosen the three (3) thumb screws about 4 turns each.
Clean the blower fan blades and the blower plate
NOTE: Be carefull not to bend the fan blades, this
NOTE: The horizontal flue pipe directly above the
Clean the flue outlet throat as well as the inner chamber
NOTE: The ESP probe sensing tip extends into this
Sealing Overlap
Sealing Overlap
5” Double
5” Double
Bladed Fan
Bladed Fan
Fig. 24
Combustion Blower Cleaning
Remove the combustion blower heat shield.There
are two latches that hold the shield in place . See Fig. 22
Flip the latches up and pull the shield away from the furnace.
It can not be fully removed, it can only be moved down over
the wire until it hangs on the junction box.
Clean the boiler blower plate, sealing overlap. See Fig
24. Make sure there are no fly ash buildups that may block
the easy flow of flue gasses into the combustion blower inlet
hole. ( A flashlight may be necessary. )
Cleaning the T ube heat Exchangers:
The heat exchanger tubes have external handles that
operate the cleaning mechanisms. See picture on page 29.
This cleaning should be done at least once a week, although it can be done as often as desired. The cleaner the
heat exchangers are, the more efficient the boiler will be.
This cleaning can be done at any time and in any mode of
operation.
CAUTION: Inspect flue pipes, flue pipe joints and
flue pipe seals regularly to ensure that smoke and
flue gases are not entering the home.
31
FEEDER DOES NOT FEED
1. No pellets in hopper .
2. Firebox draft may be too low for low draft
pressure switch in feeder circuit to operate.
Check for closed doors, loose or missing
gasket on doors or hopper lid, or a faulty pressure switch.
3. Feed motor will not run until ESP
senses 170 deg. F. Maybe you did not put
enough pellets in the burn pot before lighting the
fire manually .
4. Something is restricting flow in the hopper or
causing the slide plate to stick.
5. Feed motor has failed.
PARTIALLY BURNED PELLETS
1. Feed rate too high.
2. Draft too low. (Check burn pot clean-out slide
and door gasket).
3. Burn pot or heat exchanger tubes may need
to be cleaned.
4. Combination of all the above.
5. #6 status blink: A 6 blink control board status
indication is caused by poor or incomplete
combustion. The Automatic Ignition circuit board
has the ability to track the combustion through
feed settings and ESP temperatures. When the
control board has calculated poor or incomplete
combustion, it will shut down the unit as a safety
feature. (Poor or incomplete combustion is a
contributer of creosote which may cause a
chimney fire)
A 6 blink status may be caused by several things:
1. Blocked or partially blocked flue.
2. Blocked or partially blocked inlet air .
a. Backdraft damper on the inlet pipe may be
stuck closed.
b. If outside air is installed, the inlet cover may
be blocked.
3. The air chamber under the burnpot may be
filled with fines and small bits of ash.
4. The holes in the burnpot may be getting filled
with ash or carbon buildup.
5. Combustion blower fan blades may need
cleaned.
6. There is no fuel in the hopper .
SMOKE SMELL
Seal the vent pipe joints and connection to stove
with silicone.
FIRE HAS GONE OUT
1. No pellets in hopper .
2. Draft setting is too low .
3. Something is restricting fuel flow.
4. Feed motor or combustion blower has failed.
5. Power failure or blown fuse.
32
SMOKE IS VISIBLE COMING OUT OF VENT
1. Air-fuel ratio is too rich.
A. Feed rate too high.
B. Draft too low caused by a gasket leak.
LOW HEAT OUTPUT
1. Feed rate too low
2. Draft too low because of gasket leak.
3. Poor quality or damp pellets
4. Combination of 1 and 2.
Cleaning Burn Pot
Whenever your boiler is not burning, take the
opportunity to scrape the burn pot to remove
carbon buildup. A vacuum cleaner is handy to
remove the residue. Be sure the boiler is cold
if you use a vacuum.
Carbon buildup can be scraped loose with
the fire burning using the special tool provided
with your stove. Scrape the floor and sides of the
burn pot. The carbon will be pushed out by the
incoming fuel. Always wear gloves to do this.
Removing Ashes
Ashes can be removed while in operation,
but extra care must be taken and always wear
gloves.
Maximum Feed Adjuster settings are not
needed in most cases. O 6n4-0. boirs a of the
#4)methinTwmende rem bem Tw[(Mheat by the)TjT*9-0.0012 Tc-0.018utp1 Tboiler requ(tdurn poESPal tn wireal ts of the)TjT*-0.0011 T6-0.0351 Th you fromre O 6inle-f(tdugloves.)Tj2.1818 -1.0(KeepBe sure the fre becad car takdirtet leak.)Tj/FTj Tf18 4 0 56 254.c-0m/Cs9 csTfscn0009 8-0.0062 TcFomig Ashes
Feeder Parts
33
Specifications
34
Wiring Diagram
Wiring Diagram
35
Parts List
ITEM NUMBERDESCRIPTION
0-88-00248RUBBER GROMMET (Hopper Lid - 7' Needed)
0-88-881001" WHITE GASKET W/PSA SINGLE PL Y (Access Plate - 2' Needed)
1" WHITE GASKET W/PSA SINGLE PL Y (FDR Swing Plate - 5' Needed)
0-88-882501" WHITE GASKET W/PSA DOUBLE PL Y (Firebox Door - 3.5' Needed)
1" WHITE GASKET W/PSA DOUBLE PL Y (Flue - 1.5' Needed)
1-10-00330IGNITER ASY
1-10-07210BURN POT WELDMENT
1-10-09330CIRCUIT BOARD PLA TE W/LABEL
1-10-72129ASH P AN
1-10-73416COMBUSTION BLOWER MOUNT
2-00-73362CONTROL COVER
3-00-08534FLAME GUIDE
3-00-677154UL CAM BLOCK
3-10-050601/2" PIPE THREAD MALE DRAIN
3-10-77382SAFETY RELIEF VAL VE
3-10-78422PRESSURE/TEMP GAUGE
3-10-935111WELL
3-20-00607THERMOST A T EXTENSION
3-20-00744THERMISTER PROBE
3-20-025832 PAIR TWISTED CA T 3 CABLE (100 FT .)
3-20-05630CIRCUIT BOARD
3-20-09302FEED MOTOR - 6 RPM
3-20-09302BFEED MOTOR BLADE
3-20-3433PRESSURE SWITCH
3-20-494476 A MP FUSE
3-20-502221COMBUSTION BLOWER BLADE
3-20-72180AQUA TEMP SENSOR/OUTDOOR AIR TEMP . SENSOR
3-20-72181OUTDOOR AIR EXTENSION TCP
3-20-72195WIRING HARNESS
3-21-08639COMBUSTION BLOWER
3-31-015CONTROL BOARD SHAFT (3)
3-31-199110SWELL LA TCH
3-31-3014CAM BLOCK BEARING
3-31-605CONTROL BOARD KNOB (3)
3-31-721961/2-13 THREAD RED NYLON KNOB
3-40-00086-31/2" SPRING HANDLE
3-44-00409BURN POT GASKET
3-44-3755013/8' X 1/2" SILICONE GASKET W/PSA (Hopper to Feeder - 1.5' Needed)
3-44-535001/2" ROUND GASKET (Ash Door - 5.5' Needed)
3-50-00565AUGER
3-90-07205OWNERS MANUAL
4-00-00042DOOR HANDLE
36
Warranty
HARMAN GOLD WARRANTY
6 YEAR TRANSFERABLE LIMITED
WARRANTY (Residential)
1 YEAR LIMITED W ARRANTY (Commercial)
Harman Stove Company warrants its products to be free from defects in material or workmanship, in normal use and
service, for a period of 6 years from the date of sales invoice and for mechanical and electrical failures, in normal use and
service, for a period of 3 years from the date of sales invoice.
If defective in material or workmanship, during the warranty period, Harman Stove Company will, at its option, repair or
replace the product as described below.
The warranty above constitutes the entire warranty with respect to Harman Stove Company products. HARMAN STOVE
COMPANY MAKES NO OTHER WARRANTY, EXPRESSED OR IMPLIED, INCLUDING “ANY” WARRANTY OF
MERCHANT ABILITY, OR W ARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. No employee, agent, dealer , or
other person is authorized to give any warranty on behalf of Harman Stove Company . This warranty does not apply if the product
has been altered in any way after leaving the factory. Harman Stove Company and its agents assume no liability for “resultant
damages of any kind” arising from the use of its products. In addition, the manufacturer and its warranty administrator shall be
held free and harmless from liability from damage to property related to the operation, proper or improper, of the equipment.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.
THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the user’s manual.
THESE WARRANTIES WILL NOT APPLY if abuse, accident, improper installation, negligence, or use beyond rated
capacity causes damage.
HOW TO MAKE A CLAIM - Any claim under this warranty should be made to the dealer from whom this appliance was
purchased. Then contact is made with manufacturer, giving the model and serial numbers, the date of purchase, your dealer’s
name and address, plus a simple explanation of the nature of the defect. Extra costs such as mileage and overtime are not
covered. Nuisance calls are not covered by these warranties.
THIS WARRANTY IS LIMITED TO DEFECTIVE PARTS - REPAIR AND/OR REPLACEMENT AT
HARMAN STOVE COMPANY’S OPTION AND EXCLUDES ANY INCIDENTAL AND CONSEQUENTIAL
DAMAGES CONNECTED THEREWITH.
WARRANTY EXCLUSIONS: Failure due, but not limited to, fire, lightning, acts of God, power failures and/or surges,
rust, corrosion and venting problems are not covered. Damage and/or repairs including but not limited to; remote controls,
filters, fuses, knobs, glass, ceramic brick panels, ceramic fiber afterburners, combustion packages, door packing, tile, ceramic
log sets, paint, batteries or battery backups and related duct work are not covered. Also excluded from this warranty are
consumable or normal wear items including but not limited to; flame guides, grates, coal bars, afterburner hoods, fire brick,
gaskets. Additional exclusions for corn stoves are burn pot housing weldment, burn pot grate weldment (pellet or corn),
burnpot front plate (pellet or corn), burnpot front plate lock, corn auger extension, ceramic insert, and ceramic insert plate.
Additional or unusual utility bills incurred due to any malfunction or defect in equipment and the labor cost of gaining access to
or removal of a unit that requires special tools or equipment are not covered. Maintenance needed to keep the stove in “good
operating condition” is not covered. This includes, but is not limited to, cleaning, adjustment of customer controls and
customer education. Labor, materials, expenses and/or equipment needed to comply with law and/or regulations set forth by
any governmental agencies are not covered.
This Warranty provides specific legal rights and the consumer may have other rights that vary from state to state.
In the event of change in ownership, the remaining portion of this warranty may be transferred to the new owner by
sending the new owner information and a transfer fee of $25.00 US to the Harman Stove Company.
PLEASE READ THE LITERATURE BY THE MANUF ACTURER FOR THE VARIOUS ACCESSOR Y DEVICES.
THE MANUF ACTURER WARRANTS THESE ACCESSOR Y DEVICES, NOT HARMAN STOVE COMP ANY OR
THEIR WARRANTY ADMINISTRA T OR. FUR THERMORE, THESE ACCESSOR Y DEVICES MUST BE INSTALLED
AND USED ACCORDING TO THE RECOMMENDATIONS OF THE MANUF ACTURER.
REMEDIES - The remedies set forth herein are exclusive and the liability of seller with respect to any contract or sale or
anything done in connection therewith, whether in Contract, in tort, under any warranty, or otherwise, shall not, except as
herein expressly provided, exceed the price of the equipment or part of which such liability is based.
CLARIFY - The above represents the complete warranty, which is given in connection with stoves, manufactured by
Harman Stove Company. No other commitments, verbal or otherwise, shall apply except by a written addendum to this
warranty.
37
Testing Label
38
NOTES
39
Quick Reference ( Auto-Light )
1 Turn Mode Selector to OFF .
2 Use heat exchanger cleanout rods to clean the heat exchanger tubes.**
3 Scrape the air holes in the burnpot.**
4 Fill the hopper with pellets.
5 T urn Feed Adjuster to “T est”.*
6 Check the Combustion Blower and Feeder Motor for operation.*
7 T urn Feed Adjuster back to the #4 setting.
8 T urn the MAX TEMP dial to the desir ed temperature.
9 Turn MIN TEMP dial to the desired settings.*
10 Flip the igniter switch to Auto.*
The boiler will ignite if the temperature of the boiler water is less than the
temperature set on MAX TEMP dial..
*See the section on Operation for information
about Manual Lighting and Emergency Power.
**See the section on Maintenance for more details
about cleaning.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.