Haier HC18D2VAR, HC36D2VAR, HC24D2VAR, HC42D2VAR, HC30D2VAR User Manual

Installation & Operation Manual
Central Air Conditioner
13 SEER 1.5 to 3.5 Ton Models: HC18D2VAR
HC30D2VAR HC42D2VAR
HC24D2VAR
HC36D2VAR
No.0010578572
The information contained in this booklet is subject to change without notice.
! WARNING
service or maintenance possibly resulting in fire, electrical shock, pr operty damage, personal injury or death. This product is designed and manufactured to permit installation in accordance with National Codes. It is the installer's responsibility to install the product in accordance with National Codes and/or prevailing local codes and regulations. The manufacturer assumes no responsibility for equipment installed
in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations r egarding the introduction and disposal of refrigerants in this unit. Failure to follow these regulations may harm
the environment and can lead to the imposition of substantial fines. Because these regulations may vary due to the passage of new laws we suggest that any work on this unit be done by a certified technician. Should you have any questions please contact the local EPA office. The manufacturer's warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto, or in conjunction with the air conditioner. You should be aware that the use of unauthorized
components, accessories or devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or
injury resulting from the use of such unauthorized components, accessories or devices. Attach the service panel to the outdoor unit securely. If the service panel is not attached securely, it could result in a fire or an electric shock due to dust, water, etc. These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment,
service or maintenance possibly resulting in fire, electrical shock, pr operty damage, personal injury or death. This product is designed and manufactured to permit installation in accordance with National Codes. It is the installer's responsibility to install the product in accordance with National Codes and/or prevailing local codes and regulations. The manufacturer assumes no responsibility for equipment installed
in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations r egarding the introduction and disposal of refrigerants in this unit. Failure to follow these regulations may harm
the environment and can lead to the imposition of substantial fines. Because these regulations may vary due to the passage of new laws we suggest that any work on this unit be done by a certified technician. Should you have any questions please contact the local EPA office. The manufacturer's warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto, or in conjunction with the air conditioner. You should be aware that the use of unauthorized
components, accessories or devices may adversely affect the operation of the air conditioner and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or
injury resulting from the use of such unauthorized components, accessories or devices. Attach the service panel to the outdoor unit securely. If the service panel is not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
Message to Owner
These instructions should be carefully read and kept near the product for future reference. While the instructions are addressed primarily to the installer, useful maintenance information is included. Have your installer acquaint you with the operating characteristics of the product and periodic maintenance requirements.
TABLE OF CONTENT
1.Introduction ---------------------------------------------------------------------------------------
2.Nomenclature for Model Number -------------------------------------------------------------
3.Specification -------------------------------------------------------------------------------------
4.Unit Inspection -----------------------------------------------------------------------------------
5.Equipment Protection From Environment ----------------------------------------------------
6.Installation ----------------------------------------------------------------------------------------
6.1. General ---------------------------------------------------------------------------------------
6.2.Unit clearances ------------------------------------------------------------------------------
6.3.Refrigerant piping ---------------------------------------------------------------------------
6.4.Electrical wiring -----------------------------------------------------------------------------
7.System Startup -----------------------------------------------------------------------------------
8.Operation ----------------------------------------------------------------------------------------
9.Miscellaneous -----------------------------------------------------------------------------------
9.1.Replacement parts --------------------------------------------------------------------------
9.2.Troubleshooting guide ---------------------------------------------------------------------
1 1 2-3 4 4 4 4 5 5
10 11 12 12 12 12
9.3.Wiring diagram -----------------------------------------------------------------------------
1.INTRODUCTION
This manual contains the installation and operating instructions for your new air conditioner. Improper installation can result in unsatisfactory operation or dangerous conditions. Carefully read this manual and any instructions packaged with separate equipment required to make up the system prior to installation. Give this manual to the owner and explain its provisions. The owner should retain this manual for future reference.
2.NOMENCLATURE FOR MODEL NUMBER
H Brand symbol - H: Haier C System type - C: Air conditioner; R: Heat pump. 24 Nominal capacity in (000) Btu/h D SEER designation. D=13, E=14 2 Design series. 2 - 2nd Generation V Electric: V=208/230-1-60; C=208/230-3-60, D=460-3-60, Y=575-3-60 A Body style
12
R Reserved Example: HC24D2VAR
1
3.SPECIFICATION
Cooling
Capac ity SEE R CFM
80 85 90 95 10 0 10 5 11 0 11 5
HC18 D2VAR HB2400 VD 1M 20 M
1700 0 13 67 0 1921 0 1864 9 1802 0 1700 0 1674 5 1649 0 1623 5 1598 0
HC24 D2VAR HB2400 VD 1M 20 H
2300 0 13 90 0 2599 0 2523 1 2438 0 2300 0 2265 5 2231 0 2196 5 2162 0
HC30 D2VAR HB3600 VD 1M 22 L
2900 0 13 112 5 3277 0 3181 3 3074 0 2900 0 2856 5 2813 0 2769 5 2726 0
HC36 D2VAR HB3600 VD 1M 22 H
3500 0 13 124 0 3955 0 3839 5 3710 0 3500 0 3447 5 3395 0 3342 5 3290 0
HC42 D2VAR HB4800 VD 1M 22 L
4100 0 13 148 0 4633 0 4497 7 4346 0 4100 0 4038 5 3977 0 3915 5 3854 0
ARI data of indoo r
Outdoo r
Indoo r
Coo ling Capac ity with different outdoo r temperature
Indoorfan
speed
The dimensions for the condensing unit are illustrated in Figure 1. Physical and electrical specifications are provided in Table 1 for 13 SEER systems respectively.
The Figure 2 show a schematic of the cooling only system.
Figure 1
D
W
H
Table 1:
MODEL: HC18D2VAR HC24D2VAR HC30D2VAR HC36D2VAR HC42D2VAR Unit Supply Voltage
Normal Voltage Range Compressor Brand
Minimum Circuit Amps Max Fuse or Max CKT. BKR.
(HACR per NEC )
15 20 25 30 30 Rated Load Amps 5.4 8.0 10.1 11.8 13.2 Compressor Locked Running Amps 36.0 53.5 61.0 78.0 78.0 Full Load Amps 0.86 0.86 1.4 1.6 1.6 Fan Motor Rated HP 1/8 1/8 1/4 1/3 1/3 Nominal RPM 1000 1000 1075 1120 1120 Liquid Line OD - In (mm) 3/8"[9.52] 3/8"[9.52] 3/8"[9.52] 3/8"[9.52] 3/8" [9.52] Vapor Line OD - In (mm) 3/4"[19.05] 3/4"[19.05] 3/4"[19.05] 7/8"[22.2] 7/8"[22.2] R-22 Charge -Oz (g) 84.81[2400] 84.81[2400] 123.67[3500] 137.81[3900] 141.34[4000] Net Dimensions - In (mm) 21 1/2"*21 1/2"*23 3/8" 21 1/2"*21 1/2"*26 7/8" 24 1/4"*24 1/4"*23 3/8" 241/4"*24 1/4"*26 7/8" 24 1/4"*24 1/4"*30 3/8" W*D*H Shipping Dimensions - In (mm) 23" *23" *25 " 23"*23"*28 1/2" 26 7/8"*26 7/8"*25" 26 7/8"*26 7/8"*28 1/2" 26 7/8"*26 7/8"*32" W*D*H Net Weight - Lbs (kg) 143[65] 150[68] 176[80] 187[85] 198[90] Approx Shipping Weight - Lbs (kg) 158[72] 165[75] 192[87] 202[92] 214[97]
Model:HC18-42D2VAR
7.6 10.9 14.0
[547* 547*595]
[585* 585*637]
[547* 547*683]
[585* 585*725]
208/230 60Hz 1PH
197 - 253 Bristol
[
[616* 616*595]
682* 682*637]
16.4
[616 *616*683] [616 *616*771]
[682*682*725] [682*682*813]
18.1
Table 2:System Cooling Capacity
2
Figure 2
Central Air Conditioner Refrigerant Circuit
RVICE PORT
SERVICE VALVE
SE
COMPRESSOR
INDOOR COIL
R O
T A
ROPAV
E
DRIER(optional)
DISTRIBUTOR
SE
SE
RVICE VALVE
RVICE PORT
R ES
NEDNOC
OUTDOOR COIL
!Warning - The drier is strongly recommended to be installed by installer and replaced once two
years. This will give your equipment great help in long life.
3
4.UNIT INSPECTION
This product has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully. If damage is found, report immediately to the transportation agency.
5.EQUIPMENT PROTECTION FROM ENVIRONMENT
The metal parts of the unit may be subject to rust or corrosion in adverse environmental conditions. This oxidation could shorten the unit life. Salt spray or mist in seacoast areas, sulphur or chlorine from lawn watering systems and various chemical contaminants from industries such as paper mills and petroleum refineries are especially corrosive.
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure.
Avoid having lawn sprinkler heads spray directly on the unit cabinet. In coastal areas, locate the unit on the side of the building away from the waterfront. Shielding provided by fence or shrubs may give some protection.
Regular maintenance will reduce the buildup of contaminants and help to protect the unit's finish.
! WARNING - Disconnect all electrical power to the unit before servicing. Disconnect power to both the indoor and outdoor units. NOTE: There may be more than one electrical disconnect switch. Failure to shut off power can cause electrical shock resulting in personal injury or death.
Frequent washing of the cabinet, fan blade and coil with fresh water. Regular cleaning and waxing of the cabinet with good automobile polish. A good liquid cleaner may be used several times a year to remove matter that will not wash off with water.
The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.
6.INSTALLATION
6.1.GENERAL
These units are designed for outdoor installations. They can be mounted on a slab or rooftop. It is important to consult your local code authorities at the time the first installation is made.
Check following points before attempting any installation:
Structural strength of supporting members. Clearances and provision for servicing. Power supply and wiring. Location for minimum noise, where operating sounds will not disturb owner or neighbors. Location where there is no risk of combustible gas leakage. Location where external water drainage cannot collect around the unit. Location where roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level. Don't locate unit in an area where excessive snow drifting may occur or accumulate.
4
Provide a level concrete slab. T o prevent transmission of noise or vibration, slab should not be connected to building structure. Some sort of sound-absorbing material should be placed between the condenser and the slab. A good material to use is rubber and cork pad.
For rooftop application, make sure the building construction can support the weight and that proper consideration is given to the weather-tight integrity of the roof. The condensing unit contains moving parts and can vibrate. Therefore, sound is also a consideration in rooftop applications.
! WARNING - Install the unit securely in a place that can bear the weight of the unit. When installed in an insufficiently strong place, the unit could fall causing injury.
6.2.UNIT CLEARANCES
10" Min.
10"
10"
Service Access 18" Min.
10" Min.
Service Access 18" Min.
Figure 3
The minimum clearances for the unit are illustrated in Figure 3. Condenser air enters from three sides. Air discharges upward from the top of the unit. Refrigerant tube and electrical connections are made from the service access area. The most common application will find the unit best located about 10" from back wall with connection side facing the wall. This application minimizes exposed tubing and wiring, minimizing the space for youngsters to run around the unit with subsequent damage to the tubing or wiring.
In more confined application spaces, such as corners provide a minimum of 10" clearance on all air inlet sides. For service access to the compressor and control box, allow 18" minimum clearance. Ensure top is unobstructed. If units are to be located under an overhang, there should be a minimum of 36" clearance and provision made to deflect the warm discharge air out from the overhang.
In order to have an unrestricted air flow, owners should be advised to avoid lawn mower discharge toward the unit depositing debris on the fin coil surface reducing the unit efficiency.
6.3.REFRIGERANT PIPING
The refrigerant piping is very important as it affects the proper operation and efficiency of the air conditioning system. Note the following guidelines:
5
OUTDOOR UNIT
INVERTED LOOP
LIQUID LINE
OUTDOOR UNIT
PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1/2" FRO EVERY 10' OF LINE
INDOOR UNIT ABOVE OR LEVEL TO OUTDOOR UNIT
LIQUID LINE
INDOOR UNIT
A
6'
INDOOR UNIT
50' MAX.
SUCTION LINE
70' MAX.
SUCTION LINE OIL TRAP WHEN INDOOR UNIT IS 4 FEET OR MORE BELOW OUTDOOR UNIT
OUTDOOR UNIT
ADDITIONAL SUCTION LINE OIL TRAP FOR EACH 20 FOOT RISE OF PIPE
LIQUID LINE
INDOOR UNIT
INDOOR UNIT BELOW OUTDOOR UNIT
B-1
B-2
Figure 4
Only refrigeration-grade copper piping (dehydrated and sealed) should be used. Take extreme care to keep the refrigerant tubing clean and dry prior to and during installation. If in doubt, blow out the tubing with dry nitrogen to remove any chips or debris before connection. Always keep tubing sealed until it is in place and the connections are to be made. Refrigerant piping should be as short as possible, with a minimum of elbows or bends, to avoid capacity loss and increased operating costs. Refrigerant lines must be adequately supported. If metal strapping is used to secure the tubing, do not allow the strapping to directly contact the tubing. Use a closed cell insulation to separate the strapping from the tubing. Do not kink or twist the tubing. Refrigerant piping should not be installed in a cement slab, as this limits access to the refrigerant should a leak be suspected. To ensure good oil return to the compressor, it is important to pitch the horizontal suction line toward
the compressor, approximately 1/2" for every 10' of line.
Line Insulation
Suction line requires insulation in order to prevent condensation from forming on the piping and to prevent heat gain caused by surrounding air. Generally 3/8" wall thickness of Armflex or equivalent is satisfactory . In severe application (hot, high humidity areas) greater thickness may be required. Apply the line insulation by sliding it on the sealed tuing before cutting and making connections.
Liquid line does not necessarily need insulation, however, if they are exposed to high ambient temperatures (i.e. kitchen, boiler rooms, hot attics & rooftop surface), then, they should be insulated. Make sure to use the proper size tubing for the liquid line to prevent liquid refrigerant flashing to a vapor within the liquid line.
Do not allow the vapor line and liquid line to touch together. This would cause an undesirable heat transfer resulting in capacity loss and increased power consumption.
6
Refrigerant Line Sizing
Check the following table (Table 3) for correct suction and liquid line sizes for any combination of the unit size and the maximum refrigerant line length.
Refrigerant Line Length (Ft) Unit Size 0 - 24 25 - 49 50 - 74 (Ton) Line Outside Diameter (In)
Suction Liquid Suction Liquid Suction Liquid
Seer
1.5 3/4 3/8 3/4 3/8 7/8 1/2
2.0 3/4 3/8 3/4 3/8 7/8 1/2
2.5 3/4 3/8 3/4 3/8 7/8 1/2
3.0
3.5
7/8 7/8
3/8
3/8
1 1/8 1 1/8
3/8 3/8
1 1/8
1 1/8
1/2 1/2
13
13 13
13 13
Table 3:Refrigerant Line Sizing
The factory charge is sufficient for 25 feet of standard liquid line. For longer or shorter liquid line lengths, adjust the charge as follows: 1/4" Line +/- 0.3 oz. Per foot 5/16" Line +/- 0.4 oz. Per foot 3/8" Line +/- 0.6 oz. Per foot 1/2" Line +/- 1.2 oz. Per foot
Vertical Separation between Indoor and Outdoor Units Maximum allowable vertical separations between indoor and outdoor units are illustrated in Figure 4-A and Figure 4-B. It's 70' when the indoor unit is below the outdoor unit (Figure 4-A ), and 50' when
the indoor unit is above the outdoor unit (Figure 4-B ).
To ensure good oil return to the compressor when the indoor unit is below the outdoor unit, suction line oil trap should be used as illustrated in Figure 4-A .
Tubing Connections
! CAUTION - Use extreme caution in removing the caps from the suction and liquid line fittings, as
there is pressure present. A fitting is on the liquid line to remove pressure.
! CAUTION - Condensing units are charged with refrigerant. Condensing unit liquid and suction valves are closed to contain the charge within the unit. Do not force the valve stem against the retaining ring. If the valve stem is backed out past the retaining ring, system pressure could force the valve stem out of the valve body and possibly cause personal injury.
! CAUTION - The piston is in the accessory bag. Don't forget to take it out and put into the indoor liquid pipe orifice. Instructions on the field tubing connections and valve opening procedure are as follow:
7
1.Tubing should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contamination from entering the system.
2.Make sure that both refrigerant stop valves at the outdoor unit are closed.
3.Push the tubing into the fitting until it stops. This prevents flux from getting into the system.
4.Remove the cap and Schrader valve core from the service port to protect the valve seals.
5.Wrap a wet rag around the valve stub before brazing.
6.Braze the joints of interconnecting tubing. Flow dry nitrogen into the shutoff valve port and through the tubing while brazing.
7.After brazing quench with a wet rag to cool the joint. Reinstall the Schrader core in the valve, if removed for brazing.
8.Pressurize the lines to 150 psi maximum with dry nitrogen. Check for leaks at all joints with liquid detergent. If a leak is found, repair it after removing the nitrogen. Repeat the process and re-ckeck.
9.Do not purge the lines with refrigerant. Evacuate the lines and indoor coil.
Refrigerant Metering Devices
Replace the existing indoor unit fixed orifice with the orifice supplied with the outdoor unit.
See table 4 for the fixed orifice size for each unit.
Table 4
outdoor model
HC18D2
HC24D2
HC30D2
HC36D2
VAR
VAR
VAR
VAR
Fixed orifice size
indoor model
HB2400VD1M20
HB2400VD1M20
HB3600VD1M22
HB3600VD1M22
orifice size
057
062
071
078
HC42D2
VAR
HB4800VD1M22
8
083
Evacuation
All new installations must be evacuated to a deep vacuum in order that all noncondensible gases and moisture are removed prior to charging the system. Air in a system causes high condensing pressure, which increases power consumption and reduces performance. The presence of moisture in a system can render it inoperable in a very short time. Proper evacuation assures a dry , uncontaminated system. Here is the recommended evacuation procedure:
1.Connect vacuum pump to both liquid and suction valve service ports.
2.Evacuate the interconnecting tubing and indoor coil to 500 microns or less for a minimum of 30 minutes. Close the valve to the vacuum pump and wait 15 minutes. Vacuum should not rise above 800 microns. If unable to obtain 500 microns, or vacuum rises above 800 microns over 15 minutes period, discontinue evacuation, pressurize and check for leaks. Repair any leaks found and repeat the step 2.
3.Close valve to the vacuum pump and stop pump.
4.When sure of a tight, well evacuated system, charge with refrigerant.
Charging the System
(For systems with capillary tube or fixed orifice metering device)
Before checking the system charge, make sure that the outdoor unit and indoor coil must be an approved match per the unit specification. The indoor conditions should be within 2 F of the desired comfort conditions.
! WARNING - Do not vent refrigerant to the atmosphere! It is a violation of federal law to do so. If the refrigerant needs to be removed from a system to correct the charge inside, always use a recovery or recycling device.
! WARNING - To prevent personal injury, wear safety glasses and gloves when handling refrigerant.
9
1.Fully open both shutoff valves.
2.Connect service gage manifold to the valve service ports, being sure to evacuate lines.
3.Startup the system (Refer to the Section 7 - "System Startup"). Run system at least 10 minutes to allo pressure to stabilize.
4.T emporarily install thermometer on suction (large) line near condensing unit. Be sure of good contact between thermometer and line. Wrap thermometer with insulating material to assure accurate reading.
5.Refer to Table 5 for proper system superheat. Add charge to lower superheat. Remove charge to raise superheat. Carefully remove gage lines.
System Superheat
Ambient Return Air Temperature ( F) Temperature At 65 70 75 80 85 Condenser Inlet ( F) 60 17 25 30 33 37 65 13 19 26 32 35 70 5 14 20 28 32 75 5 10 17 25 29 80 5 12 21 26 85 5 10 17 20 90 7 12 18 95 5 5 5 100 5 5
Table 5:System charging table by superheat
6.4.ELECTRICAL WIRING
! WARNING -
A means of strain relief must be installed to this appliance at the electrical service entrance.
Make sure that interconnecting wires between indoor and outdoor units meet the standards, codes and regulations. Incomplete connection or fixing of the wire could result in a fire.
A means of strain relief must be installed to this appliance at the electrical service entrance. Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet. It could cause a fire or an electric shock due to defective contact,
defective insulation, exceeding the permissible current, etc.
Perform electrical work according to the installation manual and be sure to use an exclusive circuit. If the capacity of the power circuit is insufficient or there is incomplete electrical work, it
could result in a fire or an electric shock. Ground the unit. Do not connect the ground to a gas pipe, water pipe, lighting rod or telephone ground. Defective grounding could cause an electric shock.
Electrical installation will consists of power supply wiring to the condensing unit and control wiring between thermostat, indoor unit and the condensing unit. All wiring must be in accordance with National Electrical Code and/or local ordinances that may apply.
(See unit wiring diagram furnished with this instruction).
Note: Some states need the power supply wiring within special tybe be careful to use the waterproof tube when installation the outdoor unit power supply wiring.(See the Figure 5)
Figure 5-1 Figure 5-2
10
The condensing unit rating plate and the tables of "Physical and Electrical Specifications / Outdoor Units" (T able 1 and 2) provide pertinent data necessary for the selection of proper size electrical service and over-current protection devices.
Table 6 provides data on the minimum copper wire size as a function of supply wire length and circuit ampacity.
Copper Wire Size - AWG
(1% Voltage Drop)
Supply Circuit Supply Wire Length - Ft Ampacity 50 100 150 200 15 14 10 8 6 20 12 8 6 4 25 10 8 6 4 30 10 6 4 4 35 8 6 4 3 40 8 6 4 2 45 6 4 3 2 50 6 4 3 1
Table 6: Minimum Wire Size Based on N.E.C. for 60 C Type Copper Conductors Below 100
Ampacity.
The owner should be made familiar with the location of the over-current protection, the proper size for this application and the proper procedure for disconnecting power service to the unit.
The condensing unit control wiring requires a 24 Volt minimum, 25 VA service from the indoor transformer as shown on the wiring diagram.
7.SYSTEM STARTUP
1.Turn thermostat to "OFF", turn on power supply at disconnect switch.
2.Turn temperature setting as high as it will go.
3.Turn fan switch to "ON". Indoor blower should run. Be sure it is running in the right direction.
4.Turn fan switch to "AUTO". Turn system switch to "COOL" and turn temperature setting below room temperature. Unit should run in cooling mode.
5.Check to see if compressor and outdoor fan are running correctly?
6.Check the refrigerant charge (see Instructions under "Charging the System").
7.Replace service port caps. Service port cores are for system access only and will leak if not tightly capped.
8.Check unit for tubing and sheet metal rattles.
9.Instruct the owner on operation and maintenance. Leave this "Installation and Operating Manual" and the "Use and Care Manual" with owner.
11
8.OPERATION
Most single phase units are operated without start relay or start capacitor. Such systems should be off for a minimum of 5 minutes before restarting to allow equalization of pressures. The thermostat should not be moved to cycle unit without waiting 5 minutes. To do so may cause the compressor to stop on an automatic open overload device or blow a fuse. Poor electrical service can cause nuisance tripping in overloads or blow fuses.
The compressor has an internal overload protector. Under some conditions, it can take up to 2 hours for this overload to reset. Make sure overload has had time to reset before condemning the compressor.
9.MISCELLANEOUS
9.1. Replacement Parts
Contact your local distributor for a complete parts list.
9.2. Troubleshooting Guide Refer to the troubleshooting guide (Table 6) included in this manual.
9.3. Wiring Diagram
Refer to the appropriate wiring diagram included in this manual.(P14)
Table 6:Troubleshooting Guide
! WARNING - Disconnect all electrical power to the unit before servicing. Disconnect power to
both the indoor and outdoor units. NOTE: There may be more than one electrical disconnect switch. Failure to shut off power can cause electrical shock resulting in personal injury or death.
12
Symptom Possible Cause Remedy
Power off or loose electrical connection Make sure main switch is ON. Check and tighten all connections. Incorrect thermostat setting Set thermostat correctly No cooling Defective contactor Check for 24V at contactor coil. Open circuit breaker of blown fuses Reset or replace Defective transformer Check wiring - Replace it. Interconnecting low voltage wiring damage Replace thermostat wiring Dirty filters Clean & replace Indoor air blockage Check supply registers and return grills for blockage. Blocked outdoor coil Clear away leaves and other debris Improperly sized unit Recalculate load Insufficient Cooling Improper airflow Check - should be 400CFM/Ton Incorrect refrigerant charge Charge correctly per instruction. Air, non-condensibles or moisture in system Recover refrigerant, evacuate & recharge, add filter drier Incorrect voltage At compressor terminals, voltage must be within 10% of rating plate volts when unit is running. Water on floor or in furnace Blocked condensate drain and "P" trap Remove blockage
Run or start capacitor defective Replace Loose connection Check and tighten all connections. Condenser fan runs, Compressor stuck, grounded or open Wait for 2 hours for overload to reset. compressor doesn't motor winding, open internal overload Replace compressor if still open. Low voltage condition At compressor terminals, voltage must be within 10% of rating plate volts when unit is running. Low voltage condition Add start kit components Incorrect voltage At compressor terminals, voltage must be within 10% of rating Compressor plate volts when unit is running. short-cycling Defective overload protector Replace - check for correct voltage Refrigerant undercharge Add refrigerant Register sweat Low evaporator airflow Increase blower speed or reduce restriction - replace air filter Restriction in liquid line, Replace defective components High head - Low metering device or filter drier vapor pressures Flowrator piston size too small Change to correct size piston Incorrect capillary tubes Change coil assembly Blocked outdoor coil Clear away leaves and other debris High head - High Refrigerant overcharge Correct system charge or normal vapor Condenser fan not running Repair or replace pressures Air, non-condensibles or Recover refrigerant, evacuate & moisture in system recharge, add filter drier Low head - High Flowrator piston size too large Change to correct size piston vapor pressures Defective compressor valves Replace compressor Incorrect capillary tubes Replace coil assembly Low vapor - cool Low evaporator airflow Increase blower speed or reduce restriction - replace air filter compressor - iced Operating below 65 F outdoors Add low ambient kit evaporator coil Moisture in the system Recover refrigerant, evacuate & recharge, add filter drier High vapor Excessive load Recheck load calculation pressure Defective compressor Replace Fluctuating head Air or non-condensibles in system Recover refrigerant, evacuate & recharge. and vapor pressures Pulsing noise at Air or non-condensibles in system Recover refrigerant, evacuate & recharge metering device or liquid line
13
HC18-42D2VAR
Air Conditioner Wiring Diagram
BCR
COM
L1
BK
BK
L2
BK
1
NC NO
BL
OPTIONAL
ELECTRIC HE A TER KIT
FL
BK
BK
FL
RD
RD
RD
BR
BL
PU
3
2
5
4
2
3
1
3
2
1
RD
PU
BK
2 4 6
8
GR
RD
BL
RD
R
CBLG
HEAT CONTROL
RD RD
TL
RD
RD
WH
6
7
5
4
5BL4
BL
W2
RESISTANCE
INDOOR FAN CONTROL
5
BRK
BK
WH
1 3
BR
BCAP
5
7
BR
BL
TRAN
BK
230
BK
L1
208
COM
RD
L2
OR
YL/GR
Optional Low & High Pressure Switches
OFM
6
BR
R
M
S
BR
BK
208/230V
60Hz 1PH
L1
L2
GND
IBM
S
M
R
GR
PU
BK-HI
3
RD-LO
RD
C
H
YL
C
6
R
BK
BK
L1
WH
L2
H
S
C
RD
RD
CC
4
RD
GND
BL
YL
C
P2
YL
2
YL
YL
Y
COMPRESSOR
PU
Compress or
P1
Protect 3 Min. Time Delay
LPS
HPS
24VAC COMMON
208/230V 60Hz 1PH
1) Confirm system selection. Optional components may be field or factory installed.
2) If LPS and/or HPS not installed or removed, a jumper wire must be present across circuit for system to operate.
3) For proper system operation, consult indoor unit and outdoor unit installation instructions to confirm system match up and blower speed selection.
4) Alternate double pole contactor used on some systems.
5) Only one start assist method to be used at a time, consult outdoor unit installation instructions for application information. Use only factory approved accessories.
6) Optional OFM components may connect capacitor common and motor common, for reciprocating compressor there may have crankcase heater consult outdoor unit installation instructions for details. Select the running capacitor(one or dual) and connect. If IFM or OFM only have one capacitor wire, connect Com wire to capacitor.
7) Indoor unit shipped without optional electric heater kit. To install optional heater kit, remove power pig tail up to 9 pin plug. Install heater kit and connect with mating 9 pin plug. Run system power connections directly to electric heater kit power terminals. Consult heater kit installation instructions for complete details.
BL
P3
BL
0010526552
LINE VOLTAGE FACTORY STANDARD FIELD INSTALLED OPTIONAL LOW VOLTAGE FACTORY STANDARD FIELD INSTALLED OPTIONAL
TL
USE COPPER CONDUCTORS ONLY WARNING CABINET MUST BE PERMANENTLY GROUNDED AND ALL WIRING TO CONFORM TO I.E.C.,N.E.C.,C.E.C., C.L.C. AND LOCAL CODES AS APPLICAB LE . REPLACEMENT WIRE MUST BE THE SAME GAGE AND INSULATION TYPE AS ORIGINAL WIRE.
COMPONENT CODES BCR - BL OWER CONTROL RELA Y BCAP - RUN CAPACITOR BLOWER MOTOR CC - COMPRESSORCONTACTOR CCH - CRANKCASE HEATER (OPTIONAL)
6
CHS - CRANKCASE HEATER SWITCH (OPTIONAL) CMPR - COMPRESSOR
6
HPS - HIGH PRESSURE SWITCH
BR
WH
LPS - LOW PRESSURESWITCH IBM - INDOOR BLOWER MOTOR OFM - OUTDOOR FAN MOTOR RCAP - RUN CAPACITOR COMPRESSOR RVS - REVERSING VALVE SOLENOID STCAP - START CAPACITOR (OPTIONAL) STRLY - START RELAY (OPTIONAL) STRTH - START THERMISTOR (OPTIONAL) TRAN - TRANSFORMER 230/208 SELECTABLE
COLOR CODES BK - BLACK BL - BLUE GY - GRAY BR - BROWN GR- GREEN OR - ORANGE PU - PURPLE RD - RED VI - VIOLET WH - WHITE YL - YELLOW
WH
BR
W
Y
W G
R C
1
­S H R
LED
AUTO
ON
S
HEAT
W
-
OFF
HA
COOL
1
CA
N
TS
A
HEAT
F
RHS-2
OFF COOL
S W
-
2
14
Made in P.R.C.
Loading...