Haier CA0070AANB, CA0035AANB, CA0035MANB, CA0070MANB Installation & Operation Manual

HAIER CHILLER
Air Cooled Module Water Chiller
Installation, operation and technical manual
Heat pump / Cooling only R22 refrigerant 33KW, 65KW 3PH, 380V~400V, 50Hz
Haier Commercial Air Conditioning
MANUAL CODE: SYJS-012-06REV.0 2006-5-10
HAIER CHILLER
TABLE OF CONTENTS
1. Nomenclature……………………………………………………………………………………………………..3
2. Product character…………………………………………………………………………………………………3
3. Specifications……………………………………………………………………………………………………..5
4. Dimension data…………………………………………………………………………………………………...7
5. Installation and debugging………………………………………………………………………………………8
6. Safety precaution…………………………………………………………………………………………………9
7. Refrigerant circuit……………………………………………………………………………………………….10
8. Water system installation diagram…………………………………………………………………………….11
9. Auxiliary electric heating function control. ……………………………………………………………………12
10. Water pump operation control(valid when water pump and the unit controlled simultaneously)……….12
11. The terminal simultaneous control…………………………………………………………………………….12
12. Wiring diagrams…………………………………………………………………………………………………13
13. Wired controller functions………………………………………………………………………………………15
14. Operation introduction………………………………………………………………………………………….19
15. External wiring of UHR-820 type control board………………………………………………………………22
16. Control functions………………………………………………………………………………………………...23
17. Controller specs………………………………………………………………………………………………....25
18. Malfunction and troubleshooting……………………………………………………………………………....25
19. Water quality management………………………………………………………………………………….....26
20. Daily maintenance……………………………………………………………………………………………....26
HAIER CHILLER
1. Nomenclature
Code Explanation for chiller
1 2 3 4 5 6 7 8 9 10
Chiller
system Compressor type
Capacity
(KW)
Product type
Unit
character Suitable voltage Design number
C Hermetic scroll A 1 0 6 9 R22 A
Air cooled
A
100-115V/60Hz 1
Fixed frequency
A-G
Hermetic rotary B 0 2 3 7 R407C B
Water cooled
W
220-240V/50Hz 2
Inverter H-Q
Hermetic single screw C 0 0 1 2 R134a C 100V/50Hz 3 DC inverter R-Z Hermetic twin screws D
Heat
pump
R123 D 220V/60Hz 4
Hermetic reciprocating E R22 M 110V/50-60Hz 5 Hermetic absorption F R407C N 220V/50-60Hz 6 Semi-hermetic scroll G R134a P 127V/60Hz 7 Semi-hermetic single screw H
Cooling
only
R123 Q 240V/50Hz 8
Semi-hermetic twin screws I
110-220V/50-60H z
9
Semi-hermetic reciprocating J 380-400V/50Hz N Semi-hermetic absorption K 415V/50Hz M Semi-hermetic centrifugal L Opened M
2. Product character
a. Installation conveniently, no need the special machine room and water tower; can be installed on the
roof or out of the room. Widely application for cinema, hospital, hotel, school, commercial building, etc.
b. Utilize flexible scroll compressor. And adopts dual compressors in parallel technology. The master unit
will control both compressors run or stop due to the water outlet temp. Optimum refrigerant distribution technique and minimum-deformation design. Adoption of rolling bearing and non-lubricated bearing. Excellent heating effect at low temperature. Broad range of working temperature and suitability for high condensation temperature.
c. Shell & Tube and U type inner grooved finned coil heat exchanger.
High efficient water side heat exchanger: in cooling, the water side heat exchanger is as evaporator; in heating, it is as condenser. The freezed water flows outside of the pipe, and the refrigerant flows in the pipe. Optimum design, reliable operation, reasonable structure, perfect performance.
d. Central control technology, indoor unit be connected with controller by dual core non-polar wire. The
indoor units can be controlled individually or simultaneously, more convenient, more energy saving. One central air conditioning system can include max. 8 sets (65 series) or 16 sets (100 series) of module unit. Through the dip switch on PCB you can set unit No. of every module unit, and every unit is connected by RS485 port. Compact structure, convenient for electric installation.
e. Fan coil simultaneous control technology: indoor fan coil can be controlled individually or centrally.
HAIER CHILLER
Every indoor unit is connected to the individual controller or central controller through dual-core non-polar wire to realize the cental control. When one indoor starts up, the central air conditioning system will start up automatically. When all indoors arrive the set temperature, the master unit will stop. Energy saving.
f. Auto check technology: The system can check the operation status automatically; all kinds of sensors
will transmit the operation parameters to the chip. By pressing the buttons, all the parameters can display on the liquid crystal screen. When the unit occurs failure in operation, the failure will display on the LED so that the malfunction can be solved soon.
g. Password control function: According to the user setting, the password control function can be used.
Therefore the control to the unit will be more reliable and more flexible.
h. Equipped with RS-485 physical connector, perfect network communication ability.
i. Module structure design, the system can be produced or transported as module unit. Every system is
independent, and they are spare part for each other, however which cooling circuit is abnormal, the other systems do not be affected by the abnormal system, and furthermore they will run in shape. Module structure can reduce the cost of transport and installation greatly, more convenient.
j. Heat exchanger of air side is designed much larger, enlarge heat transmission area, lower the
temperature drop of transmission. Consequently, the chiller can run in cool mode even at high temperature of 45celsius degree in summer, and also can run in heat mode at low ambient temperature of –15celcius degree in winter with good performance.
k.
Safety and protection devices: phase reverse protection device, high and low pressure switch, freeze protection device, overheat protection device, overload protection device, etc. Also, with Timer ON/OFF, AUTO operation, defrosting, etc. functions.
HAIER CHILLER
3. Specifications
Model CA0035AANB/CA0035MANB CA0070AANB/CA0070MANB
KW 33 65
KW 35 (only for CA0035AANB) 70 (only for CA0070AANB) Total power input KW 10.1 20.2 Start current A 142 142 Running current A 17.5 35
A 22.5 45 Recommended circuit breaker A 6A 500V 6A 500V Power supply 3PH, AC380V, 50Hz 3PH, AC380V, 50Hz
11
fully automation fully automation Appearance colour ivory white ivory white Capacity control step 1 2
Safety&functional protection
model type/manufacture COP quantity set 1 2 power input KW 10.7 10.7 rated power KW 10.1 10.1 power supply running current A 15 15 starting current A 142 142
oil type MINERAL MINERAL oil charge ml 3000 3000
crankcase heater W 40*2 40*2 weight kg 71 71 rated speed rpm 2900(50Hz) 2900(50Hz) type axial flow axial flow quantity set 1 2 rated power KW 0.75 0.75 running current A 2.5 2.5 Air flow m3/h 13000 13000 Fan speed rpm 720 720 length mm 2215 2215 width mm 1100 1100
hermetic scroll / DAIKIN
3.17
3PH, 380V, 50Hz
water-lackage delay protection,high and low pressure switch,
freeze protection device, overheat protection device, overload
protection device,phase sequence protection,digital display
controller
JT335DA-Y1L
Compressor
Fan
External dimension
Running control method
Nominal cooling capacity Nominal heating capacity
Max. running current (in the electric control box)
Number of power supply circuit
HAIER CHILLER
height mm 1920 1920 Refrigerant charge kg 10 10*2 Refrigeration system (circuit quantity) 1 2 Refrigeration control method
Water flow m3/h 6 12 Water resistance kPa 80 80
mm 65 65 Noise level DB/(A) 63 65 Net weight kg 560 800 Running weight kg 660 925 Casing
cross finned coil, inner grooved copper pipe&dydrophilic aluminum finned coil
polyester painted galvanized steel plate, ivory white
thermostatic expansion valve
shell & tube heat exchanger, working pressure 1.0MPa
Air side heat exchanger
Water pipe diameter
Water side heat exchager
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. The noise level is measured at 2meter in front of the unit, 1.5 meter high to the ground. When starting up the complete unit, the compressor will start up one by one and will not start up together.
In the unit there are two protector, air breaker for compressor motor is GV2-M22C,whose parameter is overload current:20~25A,short circuit current:327A,415V; air breaker for fan motor is GV2-M08C, whose parameter is overload current:2.5~4A,short circuit current:51A,400V.
The permitted range of voltage is 380±10%
Nominal working condition (cooling ):water inlet temp. 12℃, water outlet temp. 7℃, ambient temp. 35 Nominal working condition (heating ):water inlet temp. 40℃, water outlet temp. 45 ℃, ambient temp. (DB)7℃, (WB)6℃
HAIER CHILLER
4.Dimension data
4.1 Installation dimension
2:31
3231
2711 +?JNOCIIHJF >KIE,
2491+>KHNOHJF >KIE,
:6
2131
2211
641
3:1
361
461
461
361
5- 29
ACOEM HJIEO
ACOEM @POIEO
=KPJDCOHKJ
?JNOCIIHJF >KIE
46. 81;
HAIER CHILLER
4.2 Foundation dimension
4.2.1 The bearing capacity of the foundation shall be designed according to the unit's operation weight.
4.2.2 The foundation can be beam channel (designed by the installer according to the unit outline dimension) or concrete structure, and the surface of the foundation shall be flat.
4.2.3 A 10~20mm rubber anti-vibration cushion shall be used between unit and foundation.
4.2.4 The unit can be fixed on the foundation by using anchor bolt with 16 or 18mm diameter.
5. Installation and debugging
5.1 Freight Check
All the units are tightly fastened on the wooden pallet by the bolts. Before leaving factory, the units are all checked and pre-filled with refrigerant and refrigerant oil, both of which are the precise amount the unit operation needs. When user receives the product, he shall check it carefully to confirm if there is product damage in transportation and to confirm all the pre-ordered parts are received. If there is any damage, he shall immediately inform the transportation person and claim for compensation according to relevant clauses. If there is problem except for surface damage, he shall immediately inform our company.
5.2 Transportation
In order to be convenient to carry the unit, the user shall use forklift or crane. When using crane, there shall be proper partition to protect the top and side panel of the unit (as Figure shown). During carrying, the unit shall be kept level, and the gradient shall not exceed 30°. Try to avoid units damage due to improper operation.
2711
2381
2131
?
?
?/? QHER;
LMENEO GKIE
211B211
461
311
361
HAIER CHILLER
5.3 Unwrap the packaging
After putting the unit on the site, cut the packing strap and remove the outer crate. Unscrew the tightening bolt and remove the wood pallet from the bottom of the unit.
5.4Selection of Installation Place
5.4.1 The installation place shall be plane, the foundation surface shall be flat, and the supporting surface can bear the operating weight of the unit.
5.4.2 The unit shall not be installed in a place where there is too much dust, corrosive gas, high humidity or insects gathers easily, fallen leaves and other contaminative matters.
5.4.3 There shall be over 1.5m space around the unit to be convenient for ventilation and maintenance.
5.4.4 Try to keep the unit away from sunshine and rain, it is recommended to cover the unit with shed, but be sure there is a space over 3m above the air outlet for releasing heat easily.
5.4.5 An anti-vibration cushion about 10-20mm shall be equipped between the unit and the foundation. After adjusting length, fasten the anchor bolt.
5.4.6 For the heat pump unit, there shall be a drain for the condensate.
5.4.7 The installation and thermal insulation of the water pipes of the air conditioning system shall be designed and instructed by the professionals and shall implement the relevant regulations of the Installation Standard for HV & AC.
5.4.8 The external water pipe system must be equipped with anti-vibration hose, water filter, electronic water cleaner, check valve, drain valve, discharging valve, stop valve and expansion tank, etc. The expansion tank shall be installed 1-1.5m higher than the system top, and its capacity is about 1/10 of the total water amount of the system. The air release valve shall be installed between the top of the system and the expansion tank, and the water tank and the pipe shall be thermal insulated.
5.4.9 The water supply system must match the water pump with proper water flow and proper head to ensure the supply for the unit normally.
5.4.10 The unit must be equipped with a water filter in front of the water inlet pipe and use the mesh with 16~40-mesh filter.
5.4.11 The anti-vibration hose must be used between water pump and unit, between water pump and water pipe of system. At the same time, the pipes and the water pump shall have bracket to prevent the unit from receiving force.
5.4.12 leaning and heat preservation of system must be done before connecting the pipe with the unit.
5.4.13 Recommend that maintemance space among units should be over 400mm.
6.Safety Precautions
6.1The system pressure and electric parts will cause danger to the installation and maintenance of the air conditioner, so only the authorized personnel with qualification can perform the installation, operation and maintenance of the air conditioner.