Haier AE072FEBHA, AE092FEBHA, AE072FEBIA, AE092FEAHA, AE092FEBIA Installation Manual

...
0 (0)
No.
0010571036 C
Please read this manual carefully before using. Please keep this manual carefully and safely.
Ceiling Concealed Duct type
INSTALLATION MANUAL
CONTENTS
1 2 3-6 7-8 9-11 12-13 14 15
MRV Intelligent Network
Indoor Air Conditioning
Caution
Auto Restart function for C-MRV models
Haier Auto Restart function: when the unit power drops down suddenly, the unit microprocessor will store the previous working condition and when the power is on again, the unit will run as this memory.
Auto Restart function is designed basically on the MRV whole system, but it is suitable for each indoor unit individually.
If some of indoor units power cut down, but the outdoor unit and the other indoor units still work, maybe problems will happen such as freezing at cooling mode and overload protection at heating mode on those indoor units without power.
Reason
When one or some indoor units power drops down and the other indoor units are still work, the indoor units without the power, will keep the previous working condition before the power is off. And expansion valve keeps open at a kind of opening rate condition as the previous requirement, so there is refrigerant flowing in the exchanger, but the indoor fan stops working. If the units work at cooling mode, the indoor units without the power will maybe make freezing. If the unit works at heating mode, maybe the outdoor unit compressor will stop because of the pressure or temperature protection. This is our design basically on Auto Restart function currently. Haier, Herewith, solemnly informs our customers, installers, distributors, etc. when making
installation, please make sure when the power is shut down whether artificially or accidentally, the whole system including outdoor unit and all the indoor units must be off. If you do not make the installation as our indication, Haier will not be responsible for any problem resulting from this.
Interpretation of four symbols:
:
WARNING : A potentially hazardous situation, which, if not avoided,could result in serious injury or death
: Operation so marked must be avoided at all cost, or serious damage to equipment or fatal injury to operator may result.
CAUTION : A potentially hazardous situation, which, if not avoided, may result in minor or moderate injury or damage to the equipment
Operation so marked is not allowed, or serious damage to equipment or fatal injury to operator may result.
The following instructions must be followed to avoid potential hazards. Written instructions should be available at hand any time for convenient reference. This operation manual should always be attached to this appliance even if the appliance is transferred.
1
Safety cautions
Entrusted installation Installation should be entrusted with after-sale servicemen. Self-installation is likely to cause water leakage, shock and fire, etc.
Installation should be done according to this installation manual. Inappropriate installation may lead to water leakage, shock and fire, etc.
Connection of the earth wire The earth wire should not be connected to gas pipes, water pipes, lightning rods or telephone wires. Poor earth may lead to shocks.
After-sale servicemen should take measures to avoid refrigerant leakage. Refrigerant leak may cause anoxia when a certain density is reached. If the room is small, make sure to have sound safety measures to avoid anoxia accidents.
Installation site The site must be firm enough to withstand the weight of the air conditioner to prevent falling. During installation, if refrigerant leakage occurs, ventilation measures must be taken. When refrigerant meets with fire, hazardous gas will be produced. After installation, make sure that there is no refrigerant leakage. Refrigerant, if meeting with heaters and stoves, etc in the room, may produce hazardous gas. The installation of the electric part should be conducted by qualified professionals and done according to the installation manual. Special return circuit must be used. Insufficient capacity return circuit and inappropriate installation may lead to fire accidents. Specific cables should be used for the wiring. To avoid external tension of the cables, the terminals should be firmly fixed. Inappropriate connection and fixture may lead to fire accidents.
Electric leak breaker should be installed. Without it, shock accidents may occur. Do not install at places where inflammable gas leak may occur. Gas leakage may lead to fire accident.
In order to discharge the condensed water, the installation of the drainpipe should be done in accordance with the manual instructions. The drainpipe should be treated for heat isolation. Inappropriate treatment may lead to water leakage in the room.
Test run After indoor units are installed,all cassettes hinded models should be tested.when the units are confirmed to be normal,other fitments can be installed.
Caution
!
Warning
!
!
!