Haier ADH125M1ERG, ADH071M3ERG, ADH105H1ERG, ADH140M1ERG, ADH125H1ERG Operation Manual And Installation Manual

...
DUCT TYPE AIR CONDITIONER OPERATION MANUAL AND INSTALLATION MANUAL
Contents
Original instructions
No. 0150519050
Keep this operation manual for future reference.
This product must only be installed or serviced by qualified personnel. Please read this manual carefully before installation.
Cautions Safety Precautions Parts and Functions Heating Mode Care and Maintenance Troubleshooting Accessories Precaution for Installation Is The Unit Installed Correctly Installation Procedure Move and scrap the air conditioning ----- 26
ADH105M1ERG ADH125M1ERG ADH140M1ERG
ADH071M1ERG ADH071M3ERG ADH090M1ERG
ADH105H1ERG ADH125H1ERG ADH140H1ERG ADH160H1ERG
ADH200H1ERG ADH250H1ERG
3 5 8
10
11 12 14 16 17 18
2
Your air conditioning product is marked with this symbol.This means that electrical and electronic products shall not be mixed with unsorted household waste.Do not try to dismantle the system yourself:the dismantling of the air conditioning system,treatment of the refrigerant,of oil and of other part must be done by a qualified installer in accordance with relevant local and national legislation.Air conditioners must be treated at a specialized treatment facility for reuse, recycling and recovery.By ensuring this product is disposed of correctly,you will help to prevent potential negative cons­equences for the environment and human health.Please contact the installer or local authority for more information. Battery must be removed from the remote controller and dis­posed of separately in accordance with relevant local and national legislation.
DISPOSAL REQUIREMENTS:
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.Do not vent into the atmosphere. Refrigerant type:R410A GWP:2088 GWP=global warming potential Please fill in with indelible ink,
1 the factory refrigerant charge of the product 2 the additional refrigerant amount charged in the field
and 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product charging port(e.g.onto the inside of the stop value cover). A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refrigerant charge of the product:see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging
IMPORTANT INFORMATION REGA­RDING THE REFRIGERANT USED
Haier Industrial Park,Qianwangang Road,Eco-Tech Development Zone,Qingdao 266555,Shandong,P.R.C.
A
B
C
D
kg
kg
kg
R410A
WARNING
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities,
or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
The appliances are not intended to be operated by means of an external timer or separate remote-control system. Keep the appliance and its cord out of reach of children less than 8 years. The A-weighted sound pressure level is below 70 dB. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial
use by lay persons
Air conditioner working temperature: cooling 10~43 degree, heating -15~24 degree.
3
Cautions
Disposal of the old air conditioner
Before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air conditioner in order to avoid the risk of child entrapment.
It must be noticed that air conditioner system contains refrigerants, which require specialized waste disposal. The valuable materials contained in a air conditioner can be recycled. Contact your local waste disposal center for proper disposal of an old air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the pipework of your air conditioner does not get damaged prior to being picked up by the relevant waste disposal center, and contribute to environmental awareness by insisting on an appropriate, anti-pollution method of disposal.
Disposal of the packaging of your new air conditioner
All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to the environment.
The cardboard box may be broken or cut into smaller pieces and given to a waste paper disposal service. The wrapping bag made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon.
All these valuable materials may be taken to a waste collecting center and used again after adequate recycling.
Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal services nearest to your house.
Safety Instructions and Warnings
Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.
Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
Installation shall be done by professional people, don't install unit by yourself.
For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.
Always remember to unplug the air conditioner before opening inlet grill. Never unplug your air conditioner by pulling on the power cord. Always grip plug firmly and pull straight out from the outlet.
All electrical repairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of danger for the user of the air conditioner.
Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner's tubes with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant spurts out and gets into eyes, it may result in serious eye injuries.
Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet and swing louver.
Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
The User's Guide contains very important observations relating to the assembly, operation and maintenance of the air conditioner. We recommend that you read this instruction manual carefully before using your air conditioner to gain full advantage of the functions and to avoid malfunction due to mishandling or incorrect operation. The precautions described below are WARNINGS and CAUTIONS. These are very important precautions concerning safety. Be sure to observe all of them without fail. The manufacturer does not accept responsibility for any damages that may arise due to non-observation of the following instruction.
4
Cautions
If the air conditioner appears to be operating abnormally (smell of something burning, etc.), switch the air conditioner off at the main switch and contact the dealer where you purchased the air conditioner. Continued
operation under such circumstances may result in a failure, electric shock or fire. Only use a qualified installer for installation of the air conditioner. Incorrect installation may result in a water leakage, electric shock or fire. Ask your dealer to carry out improvements, repairs and maintenance. Incorrect improvements, repairs and maintenance may result in a water leakage, electric shock or fire. Never remove any fixed coves on the indoor or outdoor unit. Removal of the covers may expose fast moving fan blades or electrical components operating at a hazardous voltage. Contact with the blades or high voltage components may result in injury or electric shock. Precaution against refrigerant leakage. If the air conditioner is to be installed in an unventilated room it is necessary to take proper measures to ensure that the allowable refrigerant concentration per cubic metre cannot be exceeded, should a refrigerant leak occur. If the allowable refrigerant concentration is exceeded, drowsiness or asphyxiation due to oxygen deficiency may occur. For installation of separately sold component parts, ask a specialist only. Be sure to use separately sold component parts designated by Haier. Incomplete installation performed by yourself may result in a water leakage, electric shock or fire. Ask your dealer to move and reinstall the air conditioner. Incomplete installation may result in a water leakage, electric shock or fire. Never insert any objects into the openings in the indoor or outdoor unit. This may damage the product or result in injury or death to the person inserting the object. When the air conditioner is used in combination with burners or heaters, ensure sufficient ventilation. Insufficient ventilation may result in an oxygen deficiency accident. Regularly check the quality of the foundation blocks. If they are left in a damaged condition, the unit may fall and result in injury.
Do not place or use a flammable spray can near the air conditioner. Doing so may result in a fire. To clean the air conditioner, stop the operation and switch the power off at the main switch. Otherwise, an electric
shock and injury may result. Do not expose the indoor unit or remote controller to rain or moisture. Water or other fluids on the electrical components may result in fire or electric shock. Always replace any blow fuse with a fuse of the same specification. The use of the wrong type fuse may allow the electrical wiring to overheat and catch on fire. If the correct type of fuse continues to blow contact your installer or electrician. Do not place a burner or heater in a place directly exposed to the airstream from the air conditioner. Incomplete combustion of the burner or heater may result.
Do not wash the air conditioner with water. An electric shock may result. Do not install the air conditioner in an area where flammable gas may be present. If the gas leaks out and stays
around the air conditioner, a fire may break out.
Avoid prolonged exposure of your body to direct streams of cold air. Your physical condition may deteriorate.
WHAT TO DO BEFORE OPERATING YOUR SYSTEM FOR THE FIRST TIME
Carefully read the operation manual supplied with your controller. Be sure to follow the operation instructions to ensure the system functions correctly. Ensure that your installer shows you the location of the main power switch of the air conditioning system. This switch is normally located adjacent to the outdoor unit or in the fuse box switchboard. The main switch must be turned on at least 6 hours before the air conditioner is operated to warm up the compressor. Failure to do so may result in damage to the compressor which will not be covered by warranty. Ensure that there are no obstacles near the air outlet of the outdoor unit. Obstacles such as plants, boxes, fences, etc. may result in declined performance and increased running noises. Ensure the air filter is installed in the return air grille.
5
Safety Precautions
Before starting to use the system, read carefully this "SAFETY PRECAUTIONS" to ensure a proper operation of the system. Safety precautions described here are classified to " WARNING" and " CAUTION". Precautions which are shown in the column of " WANING" means that an improper handing could lead to a grave result like a death, serious injury, etc. However, even if precautions are shown in the column of " CAUTION", a very serious problem could occur depending on situation. Make sure to observe these safety precautions faithfully because they are very important information to ensure the safety. Symbols which appear frequently in the text have following meanings.
Strictly prohibited.
Observe instructions faithfully.
Provide a positive grounding.
When you have read through the manual, keep it always at hand for read consultation. If the operator is replaced, make sure to hand over this manual to the new operator.
CAUTIONS FOR INSTALLATION
ON
OFF
WARNING
CAUTION
The system should be applied to places as office, restaurant, residence and the like.
The system should be installed by your dealer or a professional installer.
When you need some optional devices such as a humidifier, electric heater, etc., be sure to use the products which are recommended by us. These devices should be attached by a professional installer.
Applic ation to inferior en vironment such as an engi ne er i ng sh op , c ould cau se equip me nt malfunction and serious injury or death.
Installation by yourself is not encouraged because it could cause such problems as water leakage, electrical shock or fire accident by some improper handing.
Installation by yourself is not encouraged because it could cause such problems as water leakage, electrical shock or fire accident by some improper handing.
Do not install nearby the place where may have leakage of flammable gas.
Depending on the place of installation, a circuit breaker may be necessary.
Drain pipe should be arranged to provide a positive draining.
If the gas leaks and gathers around, it may cause the fire.
Unless the circuit breaker is installed, it could cause electrical shocks.
Where strong winds may prevail, the sys tem should be fixed securely to prevent a collapse.
Install on the place where can endure the weight of air conditioner.
Make sure the system is grounded.
If the pipe is arranged improperly, furniture or the likes may be damaged by leaked water.
Bodily injury could result by a collapse. Bodily injury could result by a careless installation. Grounding cable should never be connected to
a gas pipe, city water pipe, lightning conductor rod or grounding cable of telephone. If the grounding cable is not set properly, it could cause electric shocks.
WARNING
CAUTIONS FOR TRANSFER OR REPAIR
Modification of the system is strictly prohibited. When the system needs a repair, consult your dealer.
When the air conditioner is relocated, contact your dealer or a professional installer.
Improper practice of repair could cause water leakage, electric shock or fire.
Improper practice of installation could cause water leakage, electric shock or fire.
Do not wash the air conditioner with water.
Do not in stall the system where the air outlet reaches directly the flora and fauna.
Make sure to use a fuse of proper electric rating.
Do not operate the system while the air outlet grill is removed.
It is strictly prohibited to place a container of combustible gas or liquid near the air conditioner or to spray it directly with the gas or liquid.
Neither stand on the air conditioner nor place something on it.
Do not use the power switch to turn on or off the system.
Do not touch the air outlet section while the swing louver is operating.
Do not use such equipment as a water heater, etc. around the indoor unit or the wire controller.
ON
OFF
It could cause electric shocks. It will not be good for their health. Use of steel or copper wire in place of a fuse is
strictly prohibited because it could result in a trouble or fire accident.
There is a risk of injury.It could cause a fire accident.There are risks of falling or injury by collapsed
object.
It could cause a fire or water leakage. There is a risk of injury. If the system is operated at the vicinity of such
equipment which ge nerates ste am, condensed water may drip during cooling operation or it could cause a fault current or short-circuit.
When operating the system simultaneously with a combu stion appara tus, indo or air must b e ventilated frequently.
Check occasionally the support structure of the unit for any damage after a use of long period of time.
Insufficient ven tilation could cause an ox ygen deficiency accident.
If the structure is not repaired immediately, the unit could topple down to cause a personal injury.
When cleaning the system, stop the operation and turn off the power switch.
Do not put water containers on the unit such as a flower vase, etc.
Cleaning should never be done while the internal fans are running with high speed.
If the water enters into the unit and damages the electric insulation material, it may cause electric shock.
WARNING
CAUTION
CAUTIONS FOR OPERATION
You should refrain from exposing your body directly to cool wind for a long time.
Do not poke the air inlet or outlet with a bar, etc. When any abnormal condition (scorching smell or
others) is found, stop the operation immediately and turn off the power switch. Then consult your dealer.
It could affect your physica l condition or cause some health problems.
Since the internal fan is operating with a high speed, it could cause an injury.
If you continue the operation without removing the cause, it could result in a trouble, electric shock or fire.
The system should never be used for any other purposes than intended such as for preservation of food, flora and fauna, precision devices or work of art.
Do not handle switches with a wet hand. Com bustion appa ratus shou ld n ot be place d
allowing a direct exposure to wind of air conditioner.
Incomplete combustion could occur on the apparatus.
It could cause electric shocks.It could cause deterioration of food or other
problems.
6
Safety Precautions
1. Applicable ambient temperature range:
The machine is adaptive in following situation
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on the indoor PC board is broken please change it with the type of T 3.15A /250V(For ADH105, ADH125,ADH140M1ERG);or the type T5A /250V(For ADH071M1ERG,ADH071M3ERG,ADH090M1ERG).T8A/250V(For
ADH105/125/140/160H1ERGADH200H1ERG/ADH250H1ERG)
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be: H05RN-F 3G 4.0mm
2
(outdoor unit 1UH071/090/105N1ERG),
or H05RN-F 3G 6.0mm2 (outdoor unit 1UH125/140/160P1ERG), or H05RN-F 5G 4.0mm2 (outdoor unit 1UH125/140P1EK) or H05RN-F 5G 4.0mm2 (outdoor unit 1UH200/250W1ERK); The connecting cable should be: H05RN-F4G 2.5mm2; All the cables shall have got the European authentication certificate. During installation, when the connecting cables break off, it must be assured that the grounding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.
10.1 FOR ADH071M1ERG, ADH090M1ERG, we can get the 4 different ESP through adjust the indoor unit PCB SW1-4 and SW1-5, please refer below:
Attention: Cut off the power supply to adjust the SW1-4, and SW1-5, or else the operation is invalid.
10.2 For ADH071M3ERG, ADH105M1ERG, ADH125M1ERG, ADH140M1ERG, ADH105H1ERG, ADH125H1ERG, ADH140H1ERG,ADH160H1ERG,ADH200H1ERG,ADH250H1ERG,You can select 10 levels static pressure ,2 level is the
factory default static pressure level.For different models, even the static pressure level is the same; the actual static pressure value is differentstatic pressure selection need achieved by wired controller, refer wired controller's manual to get details
40 72 100 120 150 180 210 230 250
300
7
Safety Precautions
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB min. DB/WB
max. DB/WB min. DB/WB
max. DB/WB min. DB/WB
max. DB/WB min. DB/WB
32/23 C 18/14 C
46/24 C 10/6 C
27 C 15 C
24/18 C
-15 C
ADH200H1ERG ADH250H1ERG
SW1
(1) (2) (3) (4) (5) (6) (7) (8)
Static pressure
10 Pa 30 Pa 50 Pa
70 Pa
OFF OFF OFF ON ON OFF ON ON
- - - - - -
- - - - - -
- - - - - -
- - - - - -
For AD105/125/140M1ERG,ADH071M3ERG,ADH105/125/140/160/200/250H1ERG,static pressure level selection can also /be achieved by Infrared remote controller,method is: Step a: set the Infrared remote controller at condition:FAN mode,fan speed high. Step b:then aim the remote controller at the infrared remote receiver RE-02,press HEALTH button 4+N times(1 N
10,integer) within 12 seconds,then the receiver will beep N+1 times,the static pressure level N is been set successfully. Note:For Infrared remote controller YR-HBS01, need press ON/OFF button make the controller's at OFF status first,then open the button cover press FRESH button will enter FAN mode interface.
ADH105M1ERG ADH125M1ERG ADH140M1ERG
ADH105H1ERG ADH125H1ERG ADH140H1ERG ADH160H1ERG
40 50 60 80 100 120 150 180 200
250
Static pressure level ( N)
External static pressure
1
2
3 4 5
6
30 40 50 60 70
80 7 8 9
10
90
100
110
120
(pa)
ADH071M3ERG
25 37 50 70 90 100 110 120 130
150
(Factory default)
ADH071M1ERG
ADH105M1ERG ADH125M1ERG ADH140M1ERG
ADH090M1ERG
ADH105H1ERG ADH125H1ERG ADH140H1ERG ADH160H1ERG
ADH071M3ERG
8
Parts and Functions
ADH250H1ERG ADH200H1ERG
The pump drain opening
Electrical components Case
Drain pan
Evaporator
Air outlet frame
Air outlet frame
Drain pan
Evaporator
The pump drain opening
Electrical components Case
Air outlet frame
Fan
Drain pan
The drain opening
Electrical components Case
9
Parts and Functions
1118
1330
DRAIN 25 OD
ELECTRICAL BOX
NOTE:
1.Open the cover 1, disconnect the four bolts(1-4) and take out the fan motor assembly.
2.Open the cover plate 2 and the coamng,disconnect the six screws(A-F) and take out the evaporaor assembly
959 1221 FIXED MTG CTRS
OVERALL 1394
ELECTRICAL BOX
ELECTRICAL BOX
966.5 OA
38.5
39
screw
A
B
C
DRAIN 25 OD
COAMING
THE COVER PLATE 2
BOLT
1
2
3
4
THE COVER PLATE 1