Haier 3U55S2SR2FA, AB35S2SC1FA, AB25S2SC1FA, 5U105S2SS2FA, AB50S2SC1FA Service Manual

...
SYJS-07-2018 REV.A Edition: 2018-07
R32 Super Match
II
Multi Split
CONTENTS
3. Dimension..............................................................................................................................................................12
3. Dimension..............................................................................................................................................................44
2. Dimension..............................................................................................................................................................71
Part 5 Outdoor Units .............................................................................................................................................105
2. Dimension............................................................................................................................................................117
4. Wiring Connection ...............................................................................................................................................124
5. Piping Diagram ....................................................................................................................................................127
6. Limitation Values on Pipe lnstallation ..................................................................................................................131
7. Combination and the Data ...................................................................................................................................134
9. Sound Pressure level ..........................................................................................................................................163
Part 6 Electric Control and Troubleshooting ......................................................................................................195
1. Indoor PCB Photo................................................................................................................................................196
2. Outdoor unit PCB Photo, Dip Switch Setting and Function .................................................................................206
3. Diagnostic Code ..................................................................................................................................................223
1
Part 1 General Information
1
Model Apperance
Indoor Unit
4-Way Cassette
AB25S2SC1FA AB35S2SC1FA
AB50S2SC1FA AB71S2SG1FA
Low ESP Duct
AD25S2SS1FA AD35S2SS1FA AD25S2SS2FA AD35S2SS2FA
AD50S1SS2FA AD50S2SS2FA AD71S2SS1FA AD71S2SS2FA
Model Apperance
Outdoor Unit
1U71S2SG1FA
3U55S2SR2FA 3U70S2SR2FA
4U75S2SR2FA 4U85S2SR2FA
5U105S2SS2FA
1. Lineup
2
Model Apperance
Indoor Unit Medium Pressure Duct
AD35S2SM3FA
AD50S2SM1FA AD71S2SM1FA
AD71S2SM3FA AD90S2SM3FA
AD105S2SM3FA
AD125S2SM3FA AD140S2SM3FA
3
2. Feature
Clean Design
High Comfort
High Efciency
The outdoor unit takes no screw clean design in the top cover, this design makes people comfort when they are watching the outdoor unit;
New outdoor unit and indoor unit design to get a ultra high SEER/SCOP A+++/A++ which is reaching the world class energy efciency (3U55)
The new outdoor unit takes 550mm diameter large fan design, multi split II outdoor unit can provide same air ow but with lower fan rotation speed, then the sound level reduce 3-4 dB(A) comapred with rst generation multi split outdoor unit;
550mm
4
Installation Friendly
External General Stop Valve
Easy Start Up & Maintenance
The outdoor unit takes external general stop valve in all outdoor unit design, installer can vaccum/charge just one time with no extra dismantlement, save lots of time;
In start up & maintenance, PC monitor can connect with outdoor unit by TD-02, read all indoor unit & outdoor unit running parameter, also with the function to show parameter & curve. When malfunction happens, show failure code.
General stop valve
5
Part 2 Indoor Units-4-Way Cassette Type
3. Dimension..............................................................................................................................................................12
6
1. Feature
Appearance
Energy Efciency
DC Fan Motor
"Spiral" panel
The new 620mm*620mm panel is very t for thestandard decoration panel, won't cover otherthings like light, looks more beautiful;
Compared to conventional AC fan motor, DC fan motor is more efciency.
AC Motor Effciency DC Motor Effciency
“Spiral” concept, “Haier” image;
The new 620mm*620mm panel
20
0
2004 00 6008 00 1000
40
60
80
100
45%
35%
25%
20
0
2004 00 6008 00 1000
40
60
80
100
90%
87.5%
85%
Torque(kgfcm)
Rev(r/min) Rev(r/min)
Torque(kgfcm)
7
Four aps can be controlled individually, airow can be controlled according to end user needs. Increase comfort;
Individual Flap Control
Comfort
Installation Friendly
Easy Access Electrical Box Design
The electrical box is located in the unit, you can just make maintenance by openning the panel .
Horizontal
Adjustable
Downward
corner installation solution
Fixed
8
2. Specication
Item Model AB25S2SC1FA
Function —— Cooling Heating
Capacity W 2600 3200
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h 1.0
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*1
Speed(H-M-L) r/min 690/620/560/500
Fan motor output/input power W 10/15
Air-ows (H-M-L) m³/h 620/520/450/350
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 1
Total area 0.272
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 570*570*260
Package mmxmmxmm 718*680*380
Drainage pipe (Material,I.D/O.D) mm PVC 26/32
Control type(Remote/Wired) Remote YR-HBS01(O) or Wired YR-E17(O)
Fresh air hole dimension mm 95
Electricity Heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 52
Sound pressure level dB(A) 36/33/30/27
Weight(Net/Shipping) kg/kg 17/20
Panel
Panel model(Color) PB-700IB(White)
Dimension
External(L*W*H) mmxmmxmm 700*700*60
Package(L*W*H) mmxmmxmm 740*750*115
Weight(Net/Shipping) kg/kg 2.8/4.8
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
9
Item Model AB35S2SC1FA
Function —— Cooling Heating
Capacity W 3500 4000
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h 1.5
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*1
Speed(H-M-L) r/min 690/620/560/500
Fan motor output/input power W 10/15
Air-ows (H-M-L) m³/h 620/520/450/350
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area 0.544
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 570*570*260
Package mmxmmxmm 718*680*380
Drainage pipe (Material,I.D/O.D) mm PVC 26/32
Control type(Remote/Wired) Remote YR-HBS01(O) or Wired YR-E17(O)
Fresh air hole dimension mm 95
Electricity Heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 52
Sound pressure level dB(A) 36/33/30/27
Weight(Net/Shipping) kg/kg 18.5/22
Panel
Panel model(Color) PB-700IB(White)
Dimension
External(L*W*H) mmxmmxmm 700*700*60
Package(L*W*H) mmxmmxmm 740*750*115
Weight(Net/Shipping) kg/kg 2.8/4.8
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
10
Item Model AB50S2SC1FA
Function —— Cooling Heating
Capacity W 5000 5500
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 2.2
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Axial Fiow*1
Speed (H-M-L) r/min 800/700/600 Fan Motor Output/Input
Power
W 33/50
Air-Flows (H-M-L) m³/h 700/620/500
External Static Pressure pa 0
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 2
Total Area 1.25
Dimension (LxWxH)
External mmxmmxmm 570x570x260
Package mmxmmxmm 718x680x380
Drainage Pipe (Material, I.D/O.D) mm PVC 27/31
Control Type (Remote/Wired) Remote YR-HBS01
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level (H-M-L)
Sound Power Level dB (A) 55
Sound Pressure Level dB (A) 42/37/35
Weight (Net/Shipping) kg/kg 18.5/22
Panel
(Optional)
Panel Model (Color) PB-700KB
Dimension
External (L*W*H) mmxmmxmm 700/700/60
Package (L*W*H) mmxmmxmm 740/750/115
Weight (Net/Shipping) kg/kg 2.8/4.8
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35 (1/4)
Gas mm Φ12.7 (1/2)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27℃DB/19℃WB, indoor temperature (Heating): 20℃DB Outdoor temperature (Cooling): 35℃DB/24℃WB, outdoor temperature (Heating): 7℃DB/6℃WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
11
Item Model AB71S2SG1FA
Function —— Cooling Heating
Capacity W 7100 8000
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed (H-M-L) r/min 650/600/550/500 Fan Motor Output/Input
Power
W 45/50
Air-Flows (H-M-L) m³/h 1260/1070/820/680
External Static Pressure pa 0
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 2
Total Area /
Temp.Scope °C 2.0-7.0
Dimension (LxWxH)
External mmxmmxmm 840*840*204
Package mmxmmxmm 990*990*310
Drainage Pipe (Material, I.D/O.D) mm PVC 26/32
Control Type (Remote/Wired) Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level (H-M-L)
Sound Power Level dB (A) 55
Sound Pressure Level dB (A) 36/33/29/26
Weight (Net/Shipping) kg/kg 27/32
Panel
(Optional)
Panel Model (Color) PB-950KB
Dimension
External (L*W*H) mmxmmxmm 950/950/50
Package (L*W*H) mmxmmxmm 1000/1000/110
Weight (Net/Shipping) kg/kg 6.5/9
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ9.52 (3/8)
Gas mm Φ15.88 (5/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27℃DB/19℃WB, indoor temperature (Heating): 20℃DB Outdoor temperature (Cooling): 35℃DB/24℃WB, outdoor temperature (Heating): 7℃DB/6℃WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
12
3. Dimension
AB25S2SC1FA AB35S2SC1FA AB50S2SC1FA
13
840
840
840
80
5454
80 90
950
950
90 80
168
275
105
288
80
90
90
105
80
80
90
90
80
90
54 54
71
71
191
191
75
128
90 90
105
105
80
128
80
80 80
54 54
90
90
90
105
90
80
183
143
178
152
93
138
AB71S2SG1FA
14
4. Wiring Diagram
AB25S2SC1FA AB35S2SC1FA
TO OUT DOOR
0150523323
BM1-1
BM1-7
BM1-8
TYPE DEFINE
OFFOFF
BM1-2 BM1-3
BTU
B:BLACK
R:RED
W:WHITE
Y/G:YELLOW/GREEN
TEMP.
SENSOR
ROOM
SENSOR
FLOAT
SWITCH
HEATER
PUMP
UP/DOWN
CN9
CN1
CN6
PANNEL
CN4
CN11
CN19
CN13
CN3
ON
CN7
CN21
T5A/250VAC
FUSE
BM3
2
1
3
B
W
R
Y/G
OFF OFF OFF
ON OFF OFF
OFF ON OFF
ON ON OFF
OFF OFF ON
ON OFF ON
OFF ON ON
ON ON ON
9000
12000
18000
24000
28000
36000
48000
60000
NOTE1.DASHED PART ARE OPTIONAL.
2. USER SHOULD NOT TO SET BM1 AND BM3
CH1
OFF OFF
BM1-4
BM1-5
BM1-6
OFF
OFF
CN16
G
CN8
G
TEMP.
PIPING
DC FAN
ROOMCARD
U-HOME
WIRED CONTROLLER
B
A
C
BA
C
REMOTE
CENTRAL
87654321
ON
BM1
OFF
87654321
N
OFF
Room card
available
unavailable
ON
AB25S2SC1FA
AB35S2SC1FA
Default
15
TO OUT DOOR UNIT
SW1-1
TYPE DEFINE
Cassette
Y/G:YELLOW/GREEN
RD:RED WHT:WHITE
BLK:BLACK
******************
.
SENSOR
CN1
CN11
CN19
SW3(BM3)
2 1
3
BLK
WHT
RD
OFF OFF ON
9.0
10.5
NOTE:
1.DASHED PARTS ARE OPTIONAL.
2.USER SHOULD NOT CHANGE THE
DIP SWITCH SW1 SW3 WITHOUT GUIDENCE
3.SW3-5->SW3-8 ARE USED FOR WIRED CONTROLLER
ADRESS SELECT. SW3-1->SW3-4 ARE RESERVED.
CH1
OFF
OFF
TEMP
.
PIPING
DC FAN MOTOR
BA
C
87654321
SW1(BM1)
87654321
N
(SLIM)
Room card
available
ON
Y/G
0150527035
L
WiFi
MODULE
B
A
C
WIRED
CONTROLLER
M
SENSOR
TEMP.
ROOM
ROOM CARD
CN3
CN6
T5A 250VAC
CN16
DRAIN
PUMP
M
CN9
CN10
CN4
FUSE
FLOAT
SWITCH
CN13
INDOOR UNIT
MAIN CONTROL
BOARD
I.R .RECEIVER :
INFRARED REMOTE
RECEIVER .
TEMP.:TEMPERATURE
ON
OFF
ON
62NC
A
B
M
FRESH AIR MOTOR /
EXTERNAL ALARM OUTPUT
(FUNCTION IN FUTURE )
( Contact rating_230VAC,3A)
CAPACITY
(KW)
SW1-2
SW1-3
OFF ON
ON
OFF
ON
ON
12.5
ON
ON
ON
14.0
SW1-4
unavailable
OFF
ON
SW1-5
COOL HEAT
COOL ONLY
HEAT PUMP
SW1-6
SW1-7
SW1-8
OFF
OFF
ON
INDOOR UNIT
TERMINAL BLOCK
CN8
7.1
ON
ON
OFF
ELECTRIC HEATING TERMINAL
RATING_230VAC,3A
CONNECT TO THIRD PARTY RELAY
CN15
ELECTRIC HEATING
THERMOSTAT / FUSE
(INSIDE PANEL,
WITHOUT
DIGITAL
DISPALY)
INFRARED
REMOTE
RECEIVER
CN21
5.0
ON
OFF
OFF
ON
OFF
OFF
3.5
AB50S2SC1FA
16
TO OUT DOOR UNIT
SW1-1
TYPE DEFINE
Cassette
Y/G:YELLOW/GREEN
RD:RED WHT:WHITE
BLK:BLACK
******************
.
SENSOR
CN1
CN11
CN19
SW3(BM3)
2 1
3
BLK
WHT
RD
OFF OFF ON
9.0
10.5
NOTE:
1.DASHED PARTS ARE OPTIONAL.
2.USER SHOULD NOT CHANGE THE
DIP SWITCH SW1 SW3 WITHOUT GUIDENCE
3.SW3-5->SW3-8 ARE USED FOR WIRED CONTROLLER
ADRESS SELECT. SW3-1->SW3-4 ARE RESERVED.
CH1
OFF
OFF
TEMP
.
PIPING
DC FAN MOTOR
BA
C
87654321
SW1(BM1)
87654321
N
(SLIM)
Room card
available
ON
Y/G
0150527033
L
I.R .RECEIVER
(WITH DIGITAL
DISPLAY)
WiFi
MODULE
.
B
A
C
WIRED
CONTROLLER
M
SENSOR
TEMP
.
ROOM
ROOM CARD
CN3
CN6
T5A 250VAC
CN16
DRAIN
PUMP
M
CN9
CN10
CN4
CN14
FUSE
FLOAT
SWITCH
CN13
CN4
CN3
CN2
CN7
CN1
CN6
INTELLIGENT
MOVE EYE DEVICE
M
M
LOUVER
STEP MOTOR4
LOUVER
STEP MOTOR3
M
M
LOUVER STEP
MOTOR2
LOUVER STEP
MOTOR1
INDOOR UNIT
MAIN CONTROL
BOARD
I.R .RECEIVER :
INFRARED REMOTE
RECEIVER .
TEMP.: TEMPERATURE
ON
OFF
ON
62NC
A
B
M
FRESH AIR MOTOR /
EXTERNAL ALARM OUTPUT
(FUNCTION IN FUTURE )
( Contact rating_230VAC,3A)
CAPACITY
(KW)
SW1-2
SW1-3
OFF ON
ON
OFF
ON
ON
12.5
ON
ON
ON
14.0
SW1-4
unavailable
OFF
ON
SW1-5
COOL HEAT
COOL ONLY
HEAT PUMP
SW1-6
SW1-7
SW1-8
OFF
OFF
ON
INDOOR UNIT
TERMINAL BLOCK
CN8
7.1
ON
ON
OFF
ELECTRIC HEATING TERMINAL
RATING_230VAC,3A
CONNECT TO THIRD PARTY RELAY
CN15
ELECTRIC HEATING
THERMOSTAT / FUSE
AB71S2SG1FA
17
5. Air Velocity and Temperature Distribution
2m2m
1m
1m
4m
3m
3m
4m
0m
1.5m/s
1.5m/s
1.0m/s
1.0m/s
0.5m/s
2.7m
2m
1m
0m
0.5m/s
a. Cooling / air velocity distribution
Cooling Blowy angle: 40 Air velocity distribution
b. Cooling / temperature distribution
Cooling Blowy angle:4 0 Temperature distribution
2.7m
27
25
22
27
25
22
4m
3m
2m2m
1m
1m
3m
4m
0m
2m
1m
0m
AB25S2SC1FA AB35S2SC1FA AB50S2SC1FA AB71S2SG1FA
18
c. Heating / air velocity distribution
Heating Blowy angle:70 Air velocity distribution
d.
Heating / temperature distribution Heating
Blowy angle:70
Temper
Ature distribution
2.7m
2m
1m
0m
1.5m/s
1.5m/s
1.0m/s
1.0m/s
0.5m/s
2m2m
1m
1m 3m
3m
4m4m
0m
0.5m/s
22
27
25
22
25
27
2.7m
2m
1m
0m
2m2m
1m
1m 3m
3m
4m4m
0m
19
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
2
5.
0
3
1.
5
4
0.
0
5
0.
0
6
3.
0
8
0.
0
1
00
.0
1
25
.0
1
60
.0
2
00
.0
2
50
.0
3
15
.0
4
00
.0
5
00
.0
6
30
.0
8
00
1
.0
00
0
1
.
0
25
0
1
.
0
60
0
2
.
0
00
0
2
.
0
50
0
3
.
0
15
0
4
.
0
00
0
5
.
0
00
0
6
.
0
30
0
8
.
0
00
1
0
0
.
0
0
0
1
0
2
.0
5
00
1
6
.
0
0
0
2
0
0
.0
0
00
.0
Third octave band frequency Hz
Sound pressure level DB
cooling high
cooling med
cooling low
fan high
fan med
fan low
heating high
heating med
heating low
1/3 octave band noise level-AB50S2SC1FA
Third octave band frequency Hz
Noise level-AB24ES1ERA (S)
8
11
41
71
02
32
62
92
23
53
83
14
44
74
05
35
2
5
3
1.
5
4
0
5
0
6
3
8
0
1
00
1
25
1
60
2
00
2
50
3
15
4
00
5
00
6
30
8
00
1
00
0
1
25
0
1
60
0
2
00
0
2
50
0
3
15
0
4
00
0
5
00
0
6
30
0
8
00
0
1
00
00
1
25
1
00
60
00
0
2
00
00
Sound pressure level DB
wol gnitaeh
elddim gnitaeh
hgih gnitaeh
wol gnilooc
elddim gnilooc
hgih gnilooc
wol naf
elddim naf
hgih naf
6. Sound Pressure level
20
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
2
5
4
0
6
3
1
0
0
1
6
0
2
5
0
4
0
0
6
3
0
1
0
0
0
1
6
0
0
2
5
0
0
4
0
0
0
6
3
0
0
1
0
0
0
0
1
6
0
0
0
Third octave band frequency Hz
1/3 octave band noise level-AB71S2SG1FA
Fan-high
Fan-med
Fan-low
Coo ling-high
Coo ling-med
Coo ling-low
Hea ting-high
Hea ting-med
Hea ting-low
Sound pressure level DB
21
7. Installation
Before Installation
Selection Of Installation Place
<Don't discard any accessories until comp>
(1) Installation place shall meet the following and agreed by customers
(2) Ceiling height Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to foeld setting and installation manual of ornament panel.) (3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced)
• Determine the way tocarry unit toinstallation place.
• Don't remove packing until unit reaches installation place.
• If unpacking is unkavoidable, protect unit properly.
• Place where proper air ow can be ensured.
• Noblock toair ow.
• Water drainage is smpoth.
• Place strong enough to support unit weight.
• Place where inclination is not evident on ceiling.
• Enough space for mainenance.
• Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)
• Indoor and outdoor unit, power cable, inter unit cable are at least 1m away fromT.V. radop. This is helpful to avoid picture disturbance and noise. (Even if 1m iskept, noise can still appear if radio wave is strong)
Model H
AB25S2SC1FA AB35S2SC1FA AB50S2SC1FA 320 AB25S2SC2FA AB35S2SC2FA AB50S2SC2FA 320 AB50S2SF1FA 236 AB71S2SG1FA 257
22
Indoor Unit Panel
AB25S2SC1FA AB35S2SC1FA AB50S2SC1FA
PB-700IB
AB25S2SC2FA AB35S2SC2FA AB50S2SC2FA
PB-620KB
AB50S2SF1FA
AB71S2SG1FA
PB-950KB
(2) Cut an opening in ceiling for installation if necessary. (When ceiling already exists.)
(3) Install a suspending bolt. (Use a M10 bolt)
• Refer to paper pattern for dimension of ceiling hole.
• Connect all pipings (Refrigerant, water drainage), wirings (Inter unit cable) to indoor unit, before installation.
• Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration.
• Contact your real estate dealer
• To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new ceiling, use builtin type bolt or parts prepared in the eld.
• Before going on installing adjust space between ceiling. Note: All the above mentioned parts shall be prepared in eld.
Preparation for the Installation
(1) Position of ceiling opening between unit and suspending bolt.
236
AB25S2SC1FA AB35S2SC1FA AB50S2SC1FA
AB50S2SF1FA AB71S2SG1FA
AB25S2SC2FA AB35S2SC2FA AB50S2SC2FA
Distance between
Distance between
Indoor unit 570mm
Ceiling opening 650mm
Ornament panel 700mm
Indoor unit 840mm
Ceiling opening 890mm
Ornament panel 950mm
suspending bolts 535mm
suspending bolts 765mm
Indoor unit 570mm
Indoor unit 840mm
Ceiling opening 650mm
Ceiling opening 890mm
Ornament panel 700mm
Ornament panel 950mm
Overlap between ceiling and ornament panel shall be 25mm
Overlap between ceiling and ornament panel shall be 25mm
Suspending bolts
Suspending bolts
Ceiling
Ceiling
Ornament panel
Ornament panel
150
130
260
30
Distance between sus
pending bolts 765mm
236
AB50S2SF1FA AB71S2SG1FA
Distance between
Indoor unit 840mm
Ceiling opening 890mm
Ornament panel 950mm
suspending bolts 765mm
Indoor unit 840mm
Ceiling opening 890mm
Ornament panel 950mm Overlap between ceiling and ornament panel shall be 25mm
Suspending bolts
Ceiling
Ornament panel
130
Distance between sus
pending bolts 765mm
23
(5) Remove the washer mounlting ② and tighten the nut above. (6) Remove the paper pattern.
Installation of Indoorunit
(1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern ⑤ onto unit using 3 screws
Fix the corner of the drain pan at piping outlet.
In The Case of New Ceiling
<Aer Inslallalion on the Ceiling>
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))
(4) Check units horizontal level. Watert pump and ating switch is installed inside indoor unit, check four corners of the unit for its level using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem may occur on oating switch, causing water leakage.)
Installation example
Roof
Anchor bolt
Long nut
Suspending bolt
Ceiling
Nut (Prepare in feild)
Washer (Prepared in feild)
Suspending bolts
Fasten (Double nuts)
Insert
Washer fixing pad (Prepared in feild)
[Secure the washer firmly]
Polythene pipe
Screws at the piping outlet is fixed at the cornerof drain pan.
Center of ceiling hole Paper pattern
Screw (Accessory)
Paper pattern
Screw (Accessory)
[Fix the paper pattern]
Level
24
In the Case of Ceiling Already Exisls
(1) Install unit temporally
Put suspending bracket on the suspending bolt. Be sure touse nut and washer at both ends of the bracket. Fix the bracket rmly.
• Outdoor is precharged with refrigerant.
• Be sure tosee the Fig.1, when connecting and removing piping from unit.
• For the size of the are nut, please refer to Table 1.
• Apply refrigerant oil at both inside and outsid of lare nut. Tighten it band tight 3-4 turns then tighten it.
• Use torque specied in Table 1. (Too much force may damage are nut, causing gas leakage).
• Check piping joints for gas leakage. Insulate piping as shown in Fig. below.
• Cover joint of gas piping and insulator 7 with seal.
(2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ).
(3) Proceed with ③ and ④ of "In the case of new ceiling".
Refrigerant Piping (As for outdoor piping, please refer to installalion manual of outdoor unit.)
Apple refrigerant oil
Torque spanner
Medium size seal pad ⑪ (accessory) Cover the piping joint with seal pad)
Clamp
Liquid pipe
Gas pipe
Insulator (accessory) (For liquid pipe)
Insulator (accessory)
For gas pipe
Spanner
Piping joing
Flare nut
Table 1
Pipe Size Tighten Torque A (mm) Flare Shape
φ6.35 1420-1720N.cm (144-176 kgf.cm) 8.3-8.7
9.52 3270-3990N.cm (333-407 kgf.cm) 12.0-12.4
12.7 4950-6030N.cm (490-500 kgf.cm) 12.4-16.6
15.88 6180-7540N.cm (630-770 kgf.cm) 18.6-19.0
19.05 9720-11860N.cm (990-1210 kgf.cm) 22.9-23.3
A
R0.4 - 0.8
90°±0.5°
25
<Caulions for the Drain Waler Lifting Pipe >
Installation height shall be less than 280mm. There should be a right angle with unit, 300mm from unit.
300mm below
1~1.5m
Clamp (accessorry)
Drain hose (accessory)
drain water lifting pipe
Suspending bracket
self-provided stiff pipe
75 below
500 below
(accessory)
220 280 below
500 below
Installation of Waterdrainage Pipe
(1) Install water drainage pipe
• Pipe dia, shall be equal or larger than that of unit piping. (Pipe of polyethylent; size 25mm; O.D 32mm)
• Drain pipe should be short, with a downward slope at least 1/100 toprevent air bag from happening.
• If downward slope can t be made, take other measures to lift it up.
• Keep a distance of 1-1.5m between suspending brackets, tomake water hose straight.
• Use the self-provided stiff pipe and clamp ① with unit. Insert water pipe into water plug until it reaches the white tape. Tighten the clip until head of the screw is less than 4mm from hose.
• Wind the drain hose to the clip using seal pad ⑨ .
• Insulate drain hose in the room.
Apple refrigerant oil
Torque spanner
Medium size seal pad (accessory) Cover the piping joint with seal pad)
Clamp
Liquid pipe
Gas pipe
Insulator (accessory) (For liquid pipe)
Insulator (accessory)
For gas pipe
Spanner
Piping joing
Flare nut
Table 1
Apple refrigerant oil
Torque spanner
Medium size seal pad (accessory) Cover the piping joint with seal pad)
Clamp
Liquid pipe
Gas pipe
Insulator (accessory) (For liquid pipe)
Insulator (accessory)
For gas pipe
Tape (White)
Clamp
Self-provided stiff pipe
Clamp
Large size seal pad
(accessory)
4mm below
(accessory)
Spanner
Piping joing
Flare nut
Table 1
26
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it. If several water hoses join together, do as per following proceedures. Specieations of the water hoses shall meet the requirements for the unit running.
Note:
(2) Check if water drainage is smooth after installation.
• Check whether indoor unit is horizontal with leveler or polythene pipe lled with water, and check that the dimension of the ceiling opening is correct. Take off the lever gauge before install the ornament panel.
• Fasten the screws to make the height difference between the two sides of indoor unit less than 5mm.
• First x it with screws temporally.
• Fasten the two temporally xing screws and other two, and tighten the four screws.
• Connect the wires of synchro-motor.
• Connect the wire of signal.
• If no response of remote controller, check whether the wiring is correct, restart remote controller 10 seconds after shut off power supply.
• Install the panel board in the direction shown in the gure. The incorrect direction will result in water leakage, meanwhile swing and signal receiving are displayed that cannot be connected.
• Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
• Check water drainage in cooling operation.
<Limits of Panel Board Installalion>
After Wiring
300mm below
1~1.5m
Clamp (accessorry)
Over 100
Drain hose (accessory)
drain water lifting pipe
Suspending bracket
self-provided stiff pipe
75 below
500 below
(accessory)
Connect water hoses
with at joint.
220 280 below
500 below
75 below
500 below
Electric control box
Connect with outdoor unit
Terminal block
PCB on indoor unit
Terminal block
Cover of controll box
27
WIRING
• All supplied parts. materials and wiring operation must in appliance with local code and regulations.
• Use copper wire only.
• When make wiring, please refer towiring diagram also.
• All wiring work must be done by qualied electricians.
• A circuit breaker must be installed, which can cut power
• supply toall system.
• See Installation Manual of outdoor unit for specications of wires, circuit breaker, switches and wiring etc.
• Connecting of unit Remove cover of switch box (1), drag wires into rubber tube A, then, after proper wiring with other wires, tighten clamp A. Connect wires of correct pole to the terminal block inside. Wind sea 12 around wires. (Be sure to do that, or, dew may occur).
• Upon connecting, replace control box cover (1) and (2).
Obscrve the following when connecting power supply terminal block. Don't connect wires of different specications to the same terminal block. (Loose wire may cause overheating of circuit) Connect wires of same specications as shown in right Fig.
Connect wires of the same specications at twosides.
Don't connect wires of the same specications at one side.
Don't connect wires of the same specications at one side.
WARNING:
Terminal block
Grounding lead
Cover of control box(1)
In
Out
Rubber tube A
AB25S2SC1FA
Method of water charging Self-provided stiff pipe
Water drainage port for maintenance
(Drain water from this hole)
100mm
Watering can of plastic pipe should be about 100 mm long
Charge water from inspecting hole
Charge water from air outlet
Indoor unit terminal block
Outdoor unit terminal block
Maintenance
Inspecting hole
AB35S2SC1FA AB50S2SC1FA AB25S2SC2FA AB35S2SC2FA AB50S2SC2FA AB50S2SF1FA
AB71S2SG1FA
300mm below
1~1.5m
Clamp (accessorry)
Over 100
Drain hose (accessory)
drain water lifting pipe
Suspending bracket
self-provided stiff pipe
75 below
500 below
(accessory)
Connect water hoses with at joint.
Electric control box
Connect with outdoor unit
Terminal block
PCB on indoor unit
Terminal block
Cover of controll box
220 280 below
500 below
• Remove cover of control box, connect 1PH power to terminal 1 and 2 on terminal block. Use remote controller to operate the unit.
• Note, in this operation, fan will be running.
• Upon conrmation of a smooth water drainage, be sure to cut off power supply.
When Wiring is not Complele
28
Wiring Example
As for outdoor unit circuit, please see installation manual of outdoor unit. Note all electric wires have their own poles, poles must match that on terminal block. Pay special care lo lhe following and check aer inslallalion
Item to the checked Unproper inslallalion may cause
Check
Is indoor unit rmly installed? Unit might fall down, make vibration or noise. Is gas leakage check performed? This may lead togas shortage. Is unit properly insulated? Dew or water drop may occur. Is water drainage smooth? Dew or water drop may occur. Is power voltage meet that stipulated on the
nameplate?
Problem may occur or parts got burned.
Is wiring and piping correctly arranged? Problem may occur or parts got burned. Is unit safely grounded? There might be a danger of electric shock. Is wire size correct? Problem may occur or parts got burned. Are there any obstacles on air inlet and outlet
grill of indoor and outdoor unit?
This may cause poor cooling.
Is record made for piping length and refrigerant charging amount?
It is hard to control refrigerant charging amount.
Attention: After nishing installation, conrm no refrigerant leakage.
- The installation of pipe-work shall be kept to a minimum.
- Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that space is smaller than amin (2m
2
).
- Compliance with national gas regulations shall be observed.
- Mechanical connections shall be accessible for maintenance purposes.
- The minimum oor area of the room: 2m2.
- The maximum refrigerant charge amount: 1.7 kg.
- Information for handling, installation, cleaning, servicing and disposal of refrigerant.
- Warning: Keep any required ventilation openings clear of obstruction.
- Notice: Servicing shall be performed only as recommended by the manufacturer.
29
Unventilated Areas
- WARNING: The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specied.
- WARNING: The appliance shall be stored in a room without continuously operating open ames (e.g.an
operating gas appliance) and ignition sources (e.g. an operating electric heater).
Qualication of Workers
- Specic information about the required qualication of the working personnel for maintenance, service and repair operations.
- WARNING: Every working procedure that affects safety means shall only be carried out by competent persons.
Examples for such working procedures are:
- Breaking into the refrigerating circuit.
- Opening of sealed components
- opening of ventilated enclosures.
Information on Servicing
- Prior to beginning work on systems, safety checks are necessary to ensure that the risk of ignition is minimized.
- Work shall be undertaken under a controlled procedure so as to minimized the risk of ammable gas or vapor being present while the work is being performed.
- Work in conned spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of ammable material.
Checking for Presence of Refrigerant
- The area shall be checked with an appropriate refrigerant detector prior to and during work. The leak detection equipment should be suitable for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
Presence of Fire Extinguisher
- If any hot work is to be conducted, appropriate re extinguishing equipment shall be available to hand. Have a dry powder or CO
2
re extinguisher adjacent to the charging area.
No Ignition Sources
- All possible ignition sources, including cigarette smoking, should be kept sufciently far away from the site of installation, repairing, removing and disposal. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no ammable hazards or ignition risks. "No Smoking" signs shall be displayed.
30
Ventilated Area
- Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
Checks to the Refrigeration Equipment
- Where electrical components are being changed, they shall be t for the purpose and to the correct specication. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations
- The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
- The ventilation machinery and outlets are operating adequately and are not obstructed;
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
Checks to Electrical Devices
- Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
- Initial safety checks shall include:
• That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
• That no live electrical components and wiring are exposed while charging, recovering or purging the system;
• That there is continuity of earth bonding.
Repairs to Sealed Components
- During repairs to sealed components, all electrical supplies shall be disconnected prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
- Ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected, including damage to cables, excessive number of connections, terminals not made to original specication, damage to seals, incorrect tting of glands, etc.
- Ensure that the apparatus is mounted securely.
- Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of ammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specications.
31
Repair to Intrinsically Safe Components
- Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
- Intrinsically safe components are the only types that can be worked on while live in the presence of a ammable atmosphere.
- Replace components only with parts specied by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
Cabling
- Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
Detection of Flammable Refrigerants Removal and Evacuation
- The refrigerant charge shall be recovered into the correct recovery cylinders and the system shall be “ushed” with OFN to render the unit safe. This process may need to be repeated several times.
- Compressed air or oxygen shall not be used for purging refrigerant systems.
- Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to ll until the working pressure is achieved, then venting to atmosphere, and nally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the nal OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
- The vacuum pump is not close to any ignition sources and that ventilation is available.
Charging Procedures
- Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.
- Cylinders shall be kept upright.
- Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to overll the refrigeration system.
- Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak- tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
Decommissioning
- Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail.
- Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant.
- Electrical power must be available before the task is commenced.
32
- Become familiar with the equipment and its operation.
- Isolate system electrically.
- Before attempting the procedure, ensure that:
• mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• all personal protective equipment is available and being used correctly;
• the recovery process is supervised at all times by a competent person;
• recovery equipment and cylinders conform to the appropriate standards.
- Pump down refrigerant system, if possible.
- If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
- Make sure that cylinder is situated on the scales before recovery takes place.
- Start the recovery machine and operate in accordance with manufacturer's instructions.
- Do not overll cylinders. (No more than 80% volume liquid charge).
- Do not exceed the maximum working pressure of the cylinder, even temporarily.
- When the cylinders have been lled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
- Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
Labelling
- Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed.
- Ensure that there are labels on the equipment stating the equipment contains ammable refrigerant.
Recovery
- When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
- Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).
- Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
- The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants.
- A set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak- free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
- The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant waste transfer note arranged.
- Do not mix refrigerants in recovery units and especially not in cylinders.
- If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that ammable refrigerant does not remain within the lubricant.
- The evacuation process shall be carried out prior to returning the compressor to the suppliers.
- Only electric heating to the compressor body shall be employed to accelerate this process.
33
Part 3 Indoor Units -Low Pressure Slim Duct Type
3. Dimension..............................................................................................................................................................44
34
1. Feature
Stylish Design
Comfort
High Efciency
3D Air Flow Air Grille
185Mm Slim Height
Super Silent
185mm body height provide best oor height for room, which is advanced in the industry.
Sound power level is 53DB(A) (3.5kW) , compared with competitors 53DB(A), we already reach top sound level; Note: Sound power data in eurovent;
Dc Fan Motor
AC Motor Efciency
DC Motor Efciency
The air inlet and outlet grill can improve the decoration greatly, further more, the 3D air outlet grill can send the warm air to the ground in winter, avoid the "Cold feet" feeling in winter.
Haier cassette adopts DC fan motor,compared to conventional AC fan motor, DC fan motor is more efciency.
185mm
420mm
20
0
200 400 600 800 1000
40
60
80
100
40%
35%
25%
20
0
200 400 600 800 1000
40
60
80
100
90%
87.5%
85%
Torque(kgfcm)
Rev(r/min) Rev(r/min)
Torque(kgfcm)
35
Design Friendly
Easy Installation
Built In Drain Pump
* Rear or bottom air return, left or right drain outlet * Rear air return (Standard) / Bottom air return (Change on site)
Adjusted Pressure By Wired Controller
We takes DC fan motor design, pressure can be adjusted by wired controller YR-E16A/YR-E16B, so installer don’t need to climb the ladders to adjust pressure; There are four step pressure can be adjusted by wired controller, represent for: 0/10/20/30 pa;
Note: If the installer use wireless controller for duct unit, they need to change the pressure level by PCB dip switch
We have two models as option, one is with drain pump, the other one is with no drain pump, it is easy for the designer to design the product location;
1000mm
0Pa air flow
10Pa air folw
20Pa air folw
30Pa air folw
36
2. Specication
Item Model AD25S2SS1FA
Function —— Cooling Heating
Capacity W 2500 3000
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h 1.0
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed(H-M-L) r/min 850/750/650/600
Fan motor output/input power W 11/15
Air-ows (H-M-L) m³/h 530/460/390/330
External static pressure pa 0/10/20/30
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area 0.11
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 850x420x185
Package mmxmmxmm 1045x540x270
Drainage pipe (Material,I.D/O.D) mm PVC 27/31
control type(Remote/Wired) Wired YR-E17(O) or Remote YR-HBS01(O)
Fresh air hole dimension mm None
Electricity heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 51
Sound pressure level dB(A) 33/30/26/23
Weight(Net/Shipping) kg/kg 16/21
panel
(optional)
Panel model(Color) P1B-890IA/D
Dimension
External(L*W*H) mmxmmxmm
890/190/100
(Outlet panel)/
890/290.5/32.4
(Inlet panel)
Package(L*W*H) mmxmmxmm 938/335/220
Weight(Net/Shipping) kg/kg 4/5
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
37
Item Model AD25S2SS2FA
Function —— Cooling Heating
Capacity W 2500 3000
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed (H-M-L) r/min 850/750/650/600
Fan Motor Output/Input Power W 11/15
Air-Flows (H-M-L) m³/h 530/460/390/330
External Static Pressure pa 0/10/20/30
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 2
Total Area 0.11
Temp.scope °C 2.0-7.0
Dimension (LxWxH)
External mmxmmxmm 850x420x185
Package mmxmmxmm 1045x540x270
Control Type (Remote/Wired)
Wired YR-E17(O)
Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level (H-M-L)
Sound Power Level dB(A) 51
Sound Pressure Level dB(A) 33/30/26/23
Weight (Net/Shipping) kg/kg 15.5/20.5
Panel
(Optional)
Panel Model (Color) P1B-890IA/D
Dimension
External (L-W-H) mmxmmxmm
890/190/100 (Outlet Panel)/ 890/290.5/32.4 (Inlet Panel)
Package (L-W-H) mmxmmxmm 938/335/220
Weight (Net/Shipping) kg/kg 4/5
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting Method Flared
Norminal condition: Indoor temperature (Cooling): 27°C DB/19°C WB, indoor temperature (Heating): 20°C DB Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
38
Item Model AD35S2SS1FA
Function —— Cooling Heating
Capacity W 3500 4000
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h 1.5
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed(H-M-L) r/min 950/850/750/700
Fan motor output/input power W 16/21
Air-ows (H-M-L) m³/h 600/480/420/350
External static pressure pa 0/10/20/30
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area 0.11
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 850x420x185
Package mmxmmxmm 1045x540x270
Drainage pipe (Material,I.D/O.D) mm PVC 27/31
control type(Remote/Wired) Wired YR-E17(O) or Remote YR-HBS01(O)
Fresh air hole dimension mm None
Electricity heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 53
Sound pressure level dB(A) 35/32/29/26
Weight(Net/Shipping) kg/kg 16/21
Panel
(optional)
Panel model(Color) P1B-890IA/D
Dimension
External(L*W*H) mmxmmxmm
890/190/100
(Outlet panel)/
890/290.5/32.4
(Inlet panel)
Package(L*W*H) mmxmmxmm 938/335/220
Weight(Net/Shipping) kg/kg 4/5
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
39
Item Model AD35S2SS2FA
Function —— Cooling Heating
Capacity W 3500 4000
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.5
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed (H-M-L) r/min 950/850/750/700
Fan Motor Output/Input Power W 16/21
Air-Flows (H-M-L) m³/h 600/480/420/350
External Static Pressure pa 0/10/20/30
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 2
Total Area 0.11
Temp.Scope °C 2.0-7.0
Dimension (LxWxH)
External mmxmmxmm 850x420x185
Package mmxmmxmm 1045x540x270
Control Type (Remote/Wired)
Wired YR-E17(O)
Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level (H-M-L)
Sound Power Level dB(A) 53
Sound Pressure Level dB(A) 35/32/29/26
Weight (Net/Shipping) kg/kg 15.5/20.5
Panel
(Optional)
Panel Model (Color) P1B-890IA/D
Dimension
External (L-W-H) mmxmmxmm
890/190/100 (Outlet Panel)/ 890/290.5/32.4 (lnlet Panel)
Package (L-W-H) mmxmmxmm 938/335/220
Weight (Net/Shipping) kg/kg 4/5
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27°C DB/19°CWB, indoor temperature (Heating): 20°C DB Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
40
Item Model AD50S2SS1FA
Function —— Cooling Heating
Capacity W 5000 5500
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 2.2
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*3
Speed (H-M-L) r/min 900/800/700/600
Fan Motor Output/Input Power W 40/55
Air-Flows (H-M-L) m³/h 900/750/600/450
External Static Pressure pa 0/10/20/30
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 2
Total Area 0.21
Dimension (LxWxH)
External mmxmmxmm 1170x420x185
Package mmxmmxmm 1365x540x270
Drainage Pipe (Material,I.D/O.D) mm PVC 27/31
Control Type (Remote/Wired)
Wired YR-E17(O)
Remote YR-HBS01(O) Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise level (H-M-L)
Sound Power Level dB(A) 54
Sound Pressure Level dB(A) 36/34/32/27
Weight (Net/Shipping) kg/kg 22/28
Panel
(Optional)
Panel Model (Color) P1B-890IA/D
Dimension
External (L-W-H) mmxmmxmm
890/190/100 (Outlet Panel)/ 890/290.5/32.4 (lnlet Panel)
Package (L-W-H) mmxmmxmm 938/335/220
Weight (Net/Shipping) kg/kg 4/5
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ12.7(1/2)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27°C DB/19°C WB, indoor temperature (Heating): 20°C DB Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
41
Item Model AD50S2SS2FA
Function —— Cooling Heating
Capacity W 5000 5500
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 2.2
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*3
Speed (H-M-L) r/min 900/800/700/600
Fan Motor Output/lnput Power W 40/55
Air-Flows (H-M-L) m³/h 900/750/600/450
External Static Pressure pa 0/10/20/30
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 2
Total Area 0.21
Dimension (LxWxH)
External mmxmmxmm 1170x420x185
Package mmxmmxmm 1365x540x270
Drainage Pipe (Material,I.D/O.D) mm PVC 27/31
Control Type (Remote/Wired)
Wired YR-E17(O)
Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise level (H-M-L)
Sound Power Level dB(A) 54
Sound Pressure Level dB(A) 36/34/32/27
Weight (Net/Shipping) kg/kg 21.5/27.5
Panel
(Optional)
Panel Model (Color) P1B-890IA/D
Dimension
External (L-W-H) mmxmmxmm
890/190/100 (Outlet Panel)/
890/290.5/32.4 (lnlet Panel)
Package (L-W-H) mmxmmxmm 938/335/220
Weight (Net/Shipping) kg/kg 4/5
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ12.7(1/2)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27°C DB/19°C WB, indoor temperature (Heating): 20°C DB Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
42
Item Model AD71S2SS1FA
Function —— Cooling Heating
Capacity W 7100 7500
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*3
Speed (H-M-L) r/min 1250/1100/1000/900
Fan Motor Output/lnput Power W 48/55
Air-Flows (H-M-L) m³/h 1000/850/750/650
External Static Pressure pa 0/10/20/30
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 3
Total Area 0.11
Temp.Scope °C 2.0-7.0
Dimension (LxWxH)
External mmxmmxmm 1170x420x185
Package mmxmmxmm 1365x540x270
Drainage Pipe (Material,I.D/O.D) mm PVC 25/29
Control Type (Remote/Wired)
Wired YR-E17(O) or
Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise level (H-M-L)
Sound Power Level dB(A) 57
Sound Pressure Level dB(A) 38/35/33/30
Weight (Net/Shipping) kg/kg 24/30
Panel
(Optional)
Panel Model (Color) P1B-1210IA/D
Dimension
External (L-W-H) mmxmmxmm
1210/190/100 (Outlet Panel)/ 1210/290.5/32.4 (Inlet Panel)
Package (L-W-H) mmxmmxmm 1258/335/220
Weight (Net/Shipping) kg/kg 5/6
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ9.52(3/8)
Gas mm Φ15.88(5/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27°C DB/19°C WB, indoor temperature (Heating): 20°C DB Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
43
Item Model AD71S2SS2FA
Function —— Cooling Heating
Capacity W 7100 7500
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*3
Speed (H-M-L) r/min 1250/1100/1000/900
Fan Motor Output/lnput Power W 48/55
Air-Flows (H-M-L) m³/h 1000/850/750/650
External Static Pressure pa 0/10/20/30
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 3
Total Area 0.11
Temp.Scope °C 2.0-7.0
Dimension (LxWxH)
External mmxmmxmm 1170x420x185
Package mmxmmxmm 1365x540x270
Drainage Pipe (Material,I.D/O.D) mm PVC 29
Control Type (Remote/Wired)
Wired YR-E17(O) or
Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise level (H-M-L)
Sound Power Level dB(A) 57
Sound Pressure Level dB(A) 38/35/33/30
Weight (Net/Shipping) kg/kg 23.5/29.5
Panel
(Optional)
Panel Model (Color) P1B-1210IA/D
Dimension
External (L-W-H) mmxmmxmm
1210/190/100 (Outlet Panel)/ 1210/290.5/32.4 (Inlet Panel)
Package (L-W-H) mmxmmxmm 1258/335/220
Weight (Net/Shipping) kg/kg 5/6
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ9.52(3/8)
Gas mm Φ15.88(5/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27°C DB/19°C WB, indoor temperature (Heating): 20°C DB Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
44
3. Dimension
AD25S2SS1FA AD25S2SS2FA AD35S2SS1FA AD35S2SS2FA
420
370
892
850
185
640
90
760
152
A
B
C
AD50S2SS1FA AD50S2SS2FA AD71S2SS1FA AD71S2SS2FA
Unit Model A B C D E F G H I
AD50S2SS1FA AD50S2SS2FA AD71S2SS1FA AD71S2SS2FA
420 1212 370 1170 185 960 90 1080 152
45
4. Wiring Diagram
Y/G:YELLOW/GREEN
NOTE:
1.DASHED PARTS ARE OPTIONAL.
2.
USER SHOULD NOT SET SW01 AND
SW03 WITHOUT GUIDENCE.
3.WHEN ONE WIRED CONTROLLER CONTROL MULTIPLE INDOOR UNIT,
IT CAN CONNECT ANOTHER INDOOR UNIT BY CN22 OR CN22-1.
WHEN TWO WIRD CONTROLLERS CONTROL ONE INDOOR UNIT,
THE WIRED CONTROLLER NEED CONNECT WITH CN22 AND CN22-1.
TEMP.
SENSOR
ROOM
SENSOR
PIPING
TEMP.
ROOMCARD
ROTOM NAF CD
SW03
FUSE
WIRED
CONTROLLER
FLOAT
SWITCH
WIFI
MODULE
PUMP
TO OUT
DOOR UNIT
2
1
3
Y/G
M
12345678
ON
M
B A
C
B
A
C
OFF
0150527034
2
1
3
N L S
B A
C
SW01
12345678
ON
OFF
FRESH AIR MOTOR
(SW01-6 select OFF) /
EXTERNAL ALARM OUTPUT
(SW01-6 select ON)
( Contact rating_230VAC,3A)
M
CN21
Heater_L
CH4
Heater_N
CH2
CN5
CN4
CN34
CN16
CH1
SW01-1
SW01-2
SW01-3
ON
SW01-4
SW01-5
SW01-6
SW01-7
SW01-8
MODEL
OFF
AD71S2SS1(2)FA
OFF
OFF
OFF
ON
ON
OFF
CN13
CN6
CN41
CN22
CN22-1
4.SW03-5
->SW03-08 ARE USED FOR
ADDRESS SETTING ON THE
SITUATION OF ONE WIRED CONTROLLER CONTROL MORE THAN
ONE INDOOR UNIT.
5.REFER TO SERVICE MANUL TO GET MUCH MORE DETAILS
ABOUT THE STATIC PRESSURE LEVEL SETTING.
CN1
AD25S2SS1(2)FA
SW03-1 SW03-2 SW03-3 SW03-4 SW03-5 SW03-6 SW03-7
SW03-8
OFF OFF OFF OFF OFF OFF OFF OFF
FORALL SLIM
DUCT MODEL
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
AD35S2SS1(2)FA
AD50S2SS1(2)FA
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
(WITHOUT
DIGITAL
DISPALY)
INFRARED
REMOTE
RECEIVER
AD25S2SS1FA AD35S2SS1FA AD50S2SS1FA AD71S2SS1FA AD71S2SS2FA
46
5. Airow and Static Pressure Chart
300
400
500
600
ow m3
AIR FLOW AND STATIC PRESSURE CHART
H
0
100
200
300
400
30 Pa 20 Pa 10 Pa 0 Pa
air flow m
3
/h
static pressure (Pa)
H
M
L
500
600
700
h
AIR FLOW AND STATIC PRESSURE CHART
30 Pa 20 Pa 10 Pa 0 Pa
static pressure (Pa)
100
200
300
400
500
600
air flow m
3
/h
H
M
L
0
100
30 Pa 20 Pa 10 Pa 0 Pa
static pressure (Pa)
L
AD25S2SS1FA AD25S2SS2FA
AD35S2SS1FA AD35S2SS2FA
47
500
600
700
800
900
ow m3/h
AIRFLOW AND STATIC PRESSURE CHART
H
0
100
200
300
400
500
600
30 Pa 20 Pa 10 Pa 0 Pa
air flow m
3
/
static pressure (Pa)
H
M
L
0
30 Pa 20 Pa 10 Pa 0 Pa
static pressure (Pa)
500
600
700
800
900
ow m3/h
AIRFLOW AND STATIC PRESSURE CHART
H
0
100
200
300
400
500
600
30 Pa 20 Pa 10 Pa 0 Pa
air flow m
3
/
static pressure (Pa)
H
M
L
0
30 Pa 20 Pa 10 Pa 0 Pa
static pressure (Pa)
300
400
500
600
700
800
900
1000
1100
1200
1300
0pa
10pa
20pa
30pa
40pa
50pa
60pa
70pa
Air flo wm
3
/h
static pressure
Air flow and static pressure chart
AD71S2SG1FA AD71S2SS2FA
L
M
H
AD50S2SS21FA AD50S2SS2FA
AD71S2SS1FA AD71S2SS2FA
48
The Machine Is Adaptive In Following Situation
1. Applicable ambient temperature range:
Cooling
Heating
Max. DB/WB
Min. DB/WB
32/23 °C 18/14 °C
Outdoor Temperature
Max. DB/WB
Min. DB/WB
46/24 °C
18 °C
Heating
Indoor Temperature
Max. DB/WB
Min. DB/WB
27 °C 15 °C
Outdoor Temperature
Max. DB/WB
Min. DB/WB
24/18 °C
15 °C
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualied person.
3. If the fuse on PC board is broken please change it with the type of T3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The breaker of the air conditioner should be all pole switch, and the distance between its two contacts should be no less than 3mm. Such means for disconnection must be incorporation in the xed wiring.
6. The installation height of the indoor unit is recommended from 2.5m to 2.7m.
7. The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the diameter of the wire should be enlarged according to the local wiring standard.
8. The waste battery shall be disposed properly.
9. We can get the 4 different ESP through adjust the indoor unit PCB SW1 4 and SW1 5, please refer below:
SW01 Static
Pressure
[1] [2] [3] [4] [5] [6] [7] [8]
0 0 0Pa 0 1 10Pa 1 0 20Pa 1 1 30Pa
Attention: Cut off the power supply to adjust the SW14, and SW15, or else the operation is invalid.
Parts and Functions
AD25S2SS1FA AD35S2SS1FA AD50S2SS1FA AD71S2SS1FA AD25S2SS2FA AD35S2SS2FA AD50S2SS2FA AD71S2SS2FA
6. Installation
AD25S2SS1(2)FA AD35S2SS1(2)FA AD50S2SS1(2)FA AD71S2SS1(2)FA
49
Selecting the Mounting Position to Install the Indoor Units
After Selecting The Unit Installation Location, Proceed The Following Steps:
Installation Dimension
Indoor Unit Dimensions (Unit:mm)
• Select suitable places where the outlet air can be sent to the entire room, and
convenient to lay out the connection pipe, connection wire and the drainage pipe to outdoor.
• The ceiling structure must be strong enough to support the unit weight.
• The connecting pipe, drain pipe and connection wire shall be able to go though the building
wall to connect between the indoor and outdoor units.
• The connecting pipe between the indoor and outdoor units as well as the drain pipe shall
be as short as possible.
• If it is necessary to adjust the lling amount of the refrigerant, please refer to the installation
manual attached with the outdoor unit.
• The connecting ange should be provided by the user himself.
• The indoor unit has two water outlets one of which is obstructed at the factory (with a
rubber cap).
• Only the outlet not obstructed (liquid inlet and outlet side) will be generally used during
installation. If applicable, both the outlets should be used together.
• An access port must be provided during installation of indoor unit for maintenance.
1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-through tube purchased locally. The wall hole shall be with a outward down slope of at least 1/100.
2. Before drilling check that there is no pipe or reinforcing bar just behind the drilling position. drilling shall avoid at positions with electric wire or pipe.
3. Mount the unit on a strong and horizontal building roof. f the base is not rm, it will cause noise, vibration or leakage.
4. Support the unit rmly.
5. Change the form of the connection pipe, connection wire and drain pipe so that they can go through the wall hole easily.
Unit Model A B C D E F G H I
AD25S2SS1FA AD35S2SS1FA
AD25S2SS2FA AD35S2SS2FA
420 892 370 850 185 640 90 760 152
AD50S2SS1FA AD50S2SS2FA AD71S2SS1FA AD71S2SS2FA
420 1212 370 1170 185 960 90 1080 152
AD25S2SS1FA AD50S2SS1FA AD35S2SS2FA AD71S2SS1FA
AD35S2SS1FA AD25S2SS2FA AD50S2SS2FA AD71S2SS2FA
50
• Each of the air sending duct and air return duct shall be xed on the prefabricated panel of the oor by the iron
bracket. The recommended distance between the edge of the air return duct and the wall is over 150mm.
• The gradient of the condensate water pipe shall keep over 1%.
• The condensate water pipe shall be thermal insulated.
• When installing the ceiling Concealed type indoor unit, the air return duct must be designed and installed as gure
shown
1. Installation of Air sending duct
• This unit uses rounded duct, the diameter of the duct is
180mm.
• The rounded duct needs to add a transition duct to connect
with the air-sending duct of indoor unit, then connect with respective separator. As Figure shown, all the fan speed of any of the separator's air outlet shall be adjusted approximately the same to meet the requirement for the room air conditioner.
2. Installation of Air Return Duct
• Use rivet to connect the air return duct on the air return
inlet of the indoor unit, then connect the other end with the air return blind as gure shown.
3.Thermal Insulation of Duct
• Air-sending duct and air return duct shall be thermally
insulated. First stick the gluey nail on the duct, then attach the heat preservation cotton with a layer of tinfoil paper and use the gluey nail cap to x. Finally use the tinfoil adhesive tape to seal the connected part. As gure shown.
51
Installing the Suspension Screw
Wooden Structure
Orig Inal Concrete Slad Steel Reinforcement Structure
New Concrete Lab
Use M8 or M10 suspension screws (4, prepared in the eld) (When the suspension screw height exceeds 0.9m, M10 size is theonly choice). These screws shall be installed as follows with space adapting to air conditioner overall dimensions according tothe original building structures.
A square wood shall be supported by the beams and then set the suspension screws.
To set with embedded parts,foundation bolts etc.
Use hole hinge, hole plunger or hole bolt Use steel angle or new support steel angle directly
Hanging of the indoor unit
Pipe Material
Allowable Pipe Length and Drop
Supplementary Refrigerant
• Fasten the nut on the suspens on screw and then hang the suspension screw in the T slot of the suspension part
of the unit.
• Aided with a level meter, adjust level of the unit within 5mm
CAUTION
• In installation,if there is refrigerant gas leakage, pleasetake ventilation measures immediately.The refrigerant gas
will generate poisonous gas upon contacting re.
• After installation, please verify that there is no refrigerant leakage. The leaked refrigerant gas will produce
poisonous gas when meeting re source such as heater and furnace etc.
Model Gas Side Liquid Side
AD25S2SS1FA AD35S2SS1FA AD25S2SS2FA AD35S2SS2FA
φ9.52 φ6.35
AD50S2SS1FA AD50S2SS2FA φ12.7 φ6.35 AD71S2SS1FA AD71S2SS2FA φ15.88 φ9.52
Phosphorus deoxidized copper seamless pipe (TP2M) for air conditioner.
These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.
The refrigerant supplementation shall be as specied in the installation instructions attached with the outdoor unit. The adding procedure shall be aided with a measuring meter for a specied amount of supplemented refrigerant.
52
Note:
Connection of Refrigerant Pipe
Creating Vacuum
Open All Valves
Gas Leakage Detection
Insulation Treatment
Over lling or underilling of refrigerant will cause compressor fault. The amount of the added refrigerant shall be as specied in the instructions.
Connecting Installing Torque (N-m)
φ6.35 11.8 (1.2 kgf-m) φ9.52 24.5 (2.5 kgf-m) φ12.7 49.0 (5.0 kgf-m)
φ15.88 78.4 (8.0 kgf-m)
Conduct ared connection work to connect all refrigerant pipes.
• The connection of indoor unit pipes must use
double spanners.
• The installing torque shall be as given in the
following table.
• Wall thick ness of connection pipe≥0.8mm
With a vacuum pump, create vacuum from the stop valve of the outdoor unit. Emptying with refrigerant sealed in the outdoor unit is absolutely forbidden.
Open all the valves on the outdoor unit.
Check with a leakage detector or soap water if there is gas leakage at the pipe connections and bonnets.
Conduct insulation treatment on both the gas side and liquid side of pipes respectively. During cooling operation, both the liquid and gas sides are cold and thus shall be insulated so as to avoid dew generation.
• The insulating material at gas side shall be resistant to a temperature above 120°C
• The indoor unit pipe connection part shall be insulated.
53
In order to drain water normally, the drain pipe shall be processed as specied in the installation manual and shall be thermal insulated to avoid dew generation. Improper hose connection may cause indoor water leakage.
Requirements
Pipe and Insulation Material
• The indoor drain pipe shall be thermal insulated.
• The connection part between the drain pipe and the indoor
unit shall be insulated so as to prevent dew generation.
• The drain pipe shall be slant downwards (greater than
1/100). The middle part shall not be of stype elbow, otherwise abnormal sound will be produced.
• The horizontal length of the drain pipe shall be less than
20m. In case of long pipe, supports shall be provided every
1.5-2m to prevent wavy form.
• Central piping shall be laid out according to the right gure.
• Take care not to apply external force onto the drain pipe
connection part.
• For unit with water pump drain pipeuse hard PVC general
purpose pipe VP which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used for connection of the drain socket and drain hose (accessory).
Pipe Rigid PVC Pipe VP20 mm (Internal Diameter)
Insulation Foamed PE with Thickness Above 7 mm
CAUTlON
54
Hose
Drain Conrmation
Precautions for Electrical Wiring
Wiring Connection
Drain pipe size: (3/4) PVC pipe
The hose is used for adjusting the off-center and angle of the rigid PVC pipe.
• Directly stretch the hose to install without making any deformation.
• The soft end of the hose must be fastened with a hose clamp.
• Please apply the hose on horizontal part Insulation treatment.
• Wrap the hose and its clamp up to the indoor unit without any clearance with insulating material, as shown in the
gure.
During trial run, check that there is no leakage at the pipe connection part during water draining even in winter.
WARNING
Danger of Bodily Injury or Death
Turn off electric power at circuit breaker or power source before making any electric connections. Ground connections must be completed before making line voltage connections.
• Electrical wiring work should be conducted only by authorized personnel.
• Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with
insulated grip on the ends of the wires.
• Use copper conductor only.
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals. The specication of power cable is HO5RN-F3G 4.0mm
2
.
The specication of cable between indoor unit to outdoor unit is HO5RN-F4G 2.5mm2.
55
- The installation of pipe-work shall be kept to a minimum.
- Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that
space is smaller than Amin (2m2).
- Compliance with national gas regulations shall be observed.
- Mechanical connections shall be accessible for maintenance purposes.
- The minimum oor area of the room: 2m2.
- The maximum refrigerant charge amount: 1.7 kg.
- Information for handling, installation, cleaning, servicing and disposal of refrigerant.
- WARNING: Keep any required ventilation openings clear of obstruction.
- Notice: Servicing shall be performed only as recommended by the manufacturer.
Unventilated Areas
- WARNING: The appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specied.
- WARNING: The appliance shall be stored in a room without continuously operating open ames (e.g.an operating
gas appliance) and ignition sources (e.g.an operating electric heater).
Qualication of Workers
- Specic information about the required qualication of the working personnel for maintenance, service and repair
operations.
- WARNING: Every working procedure that affects safety means shall only be carried out by competent persons
Examples for such working procedures are:
- Breaking into the refrigerating circuit.
- Opening of sealed components
- Opening of ventilated enclosures.
Information on Servicing
- Prior to beginning work on systems, safety checks are necessary to ensure that the risk of ignition is minimized.
- Work shall be undertaken under a controlled procedure so as to minimized the risk of ammable gas or vapor
being present while the work is being performed.
- Work in conned spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the
conditions within the area have been made safe by control of ammable material.
Checking for Presence of Refrigerant
- The area shall be checked with an appropriate refrigerant detector prior to and during work. The leak detection
equipment should be suitable for use with all applicable refrigerants, i.e.non-sparking, adequately sealed or intrinsically safe.
Presence of Fire Extinguisher
- If any hot work is to be conducted, appropriate re extinguishing equipment shall be available to hand. Have a dry
powder or CO
2
re extinguisher adjacent to the charging area.
No Ignition Sources
- All possible ignition sources, including cigarette smoking, should be kept sufciently far away from the site of
installation, repairing, removing and disposal. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no ammable hazards or ignition risks. “No Smoking” signs shall be displayed.
Ventilated Area
- Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting
any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperseany released refrigerant and preferably expel it externally into the atmosphere.
56
Checks to the Refrigeration Equipment
- Where electrical components are being changed, they shall be t for the purpose and to the correct specication.
At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s technical department for assistance.
The Following Checks Shall be Applied to Installations
- The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
- The ventilation machinery and outlets are operating adequately and are not obstructed;
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of
refrigerant;
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be
corrected;
- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
Checks to Electrical Devices
- Repair and maintenance to electrical components shall include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
- Initial safety checks shall include:
• That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
• That no live electrical components and wiring are exposed while charging, recovering or purging the system;
• That there is continuity of earth bonding.
Repairs to Sealed Components
- During repairs to sealed components, all electrical supplies shall be disconnected prior to any removal of
sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
- Ensure that by working on electrical components, the casing is not altered in such a way that the level of
protection is affected, including damage to cables, excessive number of connections, terminals not made to original specication, damage to seals, incorrect tting of glands, etc.
- Ensure that the apparatus is mounted securely.
- Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose
of preventing the ingress of ammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specications.
Repair to Intrinsically Safe Components
- Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed
the permissible voltage and current permitted for the equipment in use.
- Intrinsically safe components are the only types that can be worked on while live in the presence of a ammable
atmosphere.
- Replace components only with parts specied by the manufacturer. Other parts may result in the ignition of
refrigerant in the atmosphere from a leak.
57
Cabling
- Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other
adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
Detection of Flammable Refrigerants Removal and Evacuation
- The refrigerant charge shall be recovered into the correct recovery cylinders and the system shall be “ushed”
with OFN to render the unit safe. This process may need to be repeated several times.
- Compressed air or oxygen shall not be used for purging refrigerant systems.
- Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to ll until the working
pressure is achieved, then venting to atmosphere, and nally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the nal OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
- The vacuum pump is not close to any ignition sources and that ventilation is available.
Charging Procedures
- Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines
shall be as short as possible to minimise the amount of refrigerant contained in them.
- Cylinders shall be kept upright.
- Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to overll the refrigeration system.
- Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be
leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
Decommissioning
- Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and
all its detail.
- Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to
re-use of reclaimed refrigerant.
- Electrical power must be available before the task is commenced.
- Become familiar with the equipment and its operation.
- Isolate system electrically.
- Before attempting the procedure, ensure that:
• Mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• All personal protective equipment is available and being used correctly;
• The recovery process is supervised at all times by a competent person;
• Recovery equipment and cylinders conform to the appropriate standards.
58
- Pump down refrigerant system, if possible.
- If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
- Make sure that cylinder is situated on the scales before recovery takes place.
- Start the recovery machine and operate in accordance with manufacturer's instructions.
- Do not overll cylinders. (No more than 80% volume liquid charge).
- Do not exceed the maximum working pressure of the cylinder, even temporarily.
- When the cylinders have been lled correctly and the process completed, make sure that the cylinders and the
equipment are removed from site promptly and all isolation valves on the equipment are closed off.
- Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and
checked.
Labelling
- Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall
be dated and signed.
- Ensure that there are labels on the equipment stating the equipment contains ammable refrigerant.
Recovery
- When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are
employed.
- Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be
used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).
- Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty
recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
- The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is
at hand and shall be suitable for the recovery of all appropriate refrigerants.
- A set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with
leak- free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
- The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the
relevant waste transfer note arranged.
- Do not mix refrigerants in recovery units and especially not in cylinders.
- If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable
level to make certain that ammable refrigerant does not remain within the lubricant.
- The evacuation process shall be carried out prior to returning the compressor to the suppliers.
- Only electric heating to the compressor body shall be employed to accelerate this process.
59
Part 4 Indoor Units -Medium Pressure Slim Duct Type
2. Dimension..............................................................................................................................................................71
60
1.
Specication
Item Model AD35S2SM3FA
Function —— Cooling Heating
Capacity W 3500 4000
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*1
Speed (H-M-L) r/min 900/800/700/650
Fan Motor Output/Input Power W 110/120
Air-Flows (H-M-L) m³/h 840/720/600/450
External Static Pressure pa
25(Default)/37/50/70/90/
100/110/120/130/150
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/¢7.0
Row —— 2
Total Area 0.11
Temp.Scope °C 2.0-7.0
Dimension (LxWxH)
External mmxmmxmm 700/700/248
Package mmxmmxmm 950/900/340
Drainage Pipe (Material,I.D/O.D) mm PVC 21/25
Control Type(Remote/Wired)
Wired YR-E17 (O) or
Remote YR-HBS01 (O)
Fresh Air Hole Dimension mm
123
Electricity Heater kW None
Noise Level (H-M-L)
Sound Power Level dB(A) 55
Sound Pressure Level dB(A) 41/35/28/26
Weight (Net/Shipping) kg/kg 27/31
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27°C DB/19°CWB, indoor temperature (Heating): 20°C DB Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
61
Item Model AD50S2SM1FA
Function —— Cooling Heating
Capacity W 5000 6000
Sensible heat ratio W 0.73 /
Dehumidifying capacity 10-³xm³/h 1.8
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed(H-M-L) r/min 900/820/770/720
Fan motor output/input power W 45/70
Air-ows (H-M-L) m³/h 1080/900/780/660
External static pressure Pa
25/37/50/70/90/
100/110/120/130/150
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area /
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 957/655/250
Package mmxmmxmm 1170/860/340
Drainage pipe (Material,I.D/O.D) mm PVC 25/29
Control type(Remote/Wired) Wired YR-E17(O) or Remote YR-HBS01(O)
Fresh air hole dimension mm 145
Electricity heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 57
Sound pressure level dB(A) 37/34/32/29
Weight(Net/Shipping) kg/kg 26/33
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ12.7(1/2)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
62
Item Model AD50S2SM3FA
Function —— Cooling Heating
Capacity W 5000 6000
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h 1.0
Indoor unit
Power supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed(H-M-L) r/min 750/650/550/500
Fan motor output/input power W 140/160
Air-ows (H-M-L) m³/h 1020/900/780/550
External static pressure Pa
25(default)/37/50/70/90/
100/110/120/130/150
Heat exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row —— 2
Total area /
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 1100/700/248
Package mmxmmxmm 1270/860/340
Drainage pipe (Material,I.D/O.D) mm PVC 21/25
Control type(Remote/Wired) Wired YR-E17(O) or Remote YR-HBS01(O)
Fresh air hole dimension mm 123
Electricity heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 56
Sound pressure level dB(A) 43/37/30/28
Weight(Net/Shipping) kg/kg 35/39
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ6.35(1/4)
Gas mm Φ12.7(1/2)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter.
63
Item Model AD71S2SM1FA
Function cooling heating
Capacity KW 7.1(2.0~8.2) 8.0(2.5~8.5)
Sensible heat ratio 0.74 /
Total power input KW 2.15(0.6~2.6) 2.16(0.6~2.6)
Max. power input W 3000 3000
EER or COP W/W 3.30 3.71
Dehumidifying capacity 10
-
³×m³/h 2.5
Power cable H05RN-F 4G 6.0mm2
Power source N, V, Hz 1PH, 220-240V~, 50/60Hz
Running /Max.Running current A / A 9.7(2.3-12)/16 9.8(2.3-12)/16
Start Current A 3
Indoor unit
Unit model (color) AD71S2SM1FA
Fan
Type × Number Centrifugal*2
Speed(H-M-L) r/min 1130/950/820/780
Fan motor output/ input power W 85/111
Air-ow(H-M-L) m³/h 1440/1140/900/800
External static pressure Pa 25/37//50/70/90/100/110/120/130/150
Heat
exchanger
Type / Diameter mm Inner grooved pipe/φ7.0
Row 3
Total Area 7.668
Dimension
External(L*W*H) mm×mm×mm 957/655/250
Package(L*W*H) mm×mm×mm 1170/860/340
Drainage pipe (Material, I.D./O.D.) mm PVC 25/29 Controller
(O-Optional,S-Standard)
Wired YR-E16(O)/YR-E17
Fresh air hole dimension mm None
Electricity heater kW None
Sound power Noise level (H-M-L) dB(A) 58
Sound pressure Noise level (H-M-L) dB(A) 42/38/35
Pipe
Liquid Pipe(mm) 9.52 Gas Pipe(mm) 15.88 Connecting method Flared
Weight (Net / Shipping) kg / kg 31.2/36.8
Norminal condition: indoor temperature (Cooling): 27°C DB/19°C WB, indoor temperature (Heating): 20°C DB Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
64
Item Model AD71S2SM3FA/1UH071N1ERG
Function Cooling Heating Capacity kW 7.1(2.0~9.0) 8(2.0~10.0) Sensible heat ratio 0.72 / Total power input kW 2.03(0.4~4.0) 2.0(0.4~4.0) Max. power input W 4000 4000 EER or COP W/W 3.5(B) 4(C) Dehumidifying capacity 10
-3×m3
/h 2.4 Power cable / Power source N, V, Hz 1PH, 220-240V~, 50/60Hz Running/Max. Running current A/A
8.8(2.0-17.5)/17.5 8.0(2.0-17.5)/17.5
Start current A 0.52
Circuit breaker A 5 5
Indoor unit
Unit model (color) AD71S2SM3FA
Fan
Type×Number CENTRIFUGALX2 Speed (H-M-L) r/min 950/850/750/700 (37Pa) Fan motor output/ input power kW 0.228 Air-ow (H-M-L) kW 0.160
External static pressure m
3
/h
1440/1260/1100/900(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat exchanger
Type/Diameter mm Inner grooved pipe/φ7.0 Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1100*700*248
Package (L×W×H) mm×mm×mm 1290/840/320
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YRHBS(O) Fresh air hole dimension mm 123 Electricity heater kW 0 Sound power Noise level (H-M-L) dB (A) 58 Sound pressure Noise level (H-M-L) dB (A) 42/38/35 Weight (Net / Shipping) kg / kg 31/37
Piping
Refrigerant
Type / Charge
g
R410A/2500
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
50
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.
65
Item Model AD90S2SM3FA/1UH090N1ERG
Function Cooling Heating Capacity kW 8.5(2.5~10) 9.5(2.5~11) Sensible heat ratio 0.72 / Total power input kW 2.50(0.5~4.4) 2.50(0.5~4.4) Max. power input W 4400 4400 EER or COP W/W 3.4(B) 3.8(C) Dehumidifying capacity 10
-3×m3
/h 2.5 Power cable / Power source N, V, Hz 1PH, 220-240V~, 50/60Hz Running/Max. Running current A/A
11.1(2.3-19.2)/19.2 11.1(2.3-19.2)/19.2
Start current A 0.56
Circuit breaker A 5 5
Indoor unit
Unit model (color) AD90S2SM3FA
Fan
Type×Number CENTRIFUGALX2 Speed (H-M-L) r/min 1050/980/920/860(37Pa) Fan motor output/ input power kW 0.260 Air-ow (H-M-L) kW 0.180
External static pressure m³/h
1440/1260/1100/900(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat exchanger
Type/Diameter mm Inner grooved pipe/φ7.0 Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1100*700*248
Package (L×W×H) mm×mm×mm 1290/840/320
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YRHBS(O) Fresh air hole dimension mm 123 Electricity heater kW 0 Sound power noise level (H-M-L) dB (A) 60 Sound pressure noise level (H-M-L) dB (A) 44/40/37 Weight (Net / Shipping) kg / kg 38/45
Piping
Refrigerant
Type / Charge
g
R410A/2500
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
50
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.
66
Item Model AD105S2SM3FA/1UH105N1ERG
Function Cooling Heating Capacity kW 10(2.5~11) 10.4(2.5~12.0) Sensible heat ratio 0.72 / Total power input kW 2.93(0.5~4.5) 2.8(0.5~4.5) Max. power input W 5000.00 5000.00 EER or COP W/W 3.31(B) 3.71(C) Dehumidifying capacity 10
-3×m3
/h 3.2 Power cable / Power source N, V, Hz 1PH, 220-240V~, 50/60Hz Running/Max. Running current A/A
13.3(2.3-19.0)/21.0 13.1(2.3-19.0)/21.0
Start current A 0.52
Circuit breaker A 5 5
Indoor unit
Unit model (color) AD105S2SM3FA
Fan
Type×Number CENTRIFUGALX3 Speed (H-M-L) r/min 900/840/780/750(37Pa) Fan motor output/ input power kW 0.260
Air-ow (H-M-L) kW 0.180
External static pressure m³/h
2000/1740/1380/1280(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat exchanger
Type/Diameter mm Inner grooved pipe/φ7.0 Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1500*700*248
Package (L×W×H) mm×mm×mm 1710/870/330
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YRHBS(O) Fresh air hole dimension mm 123 Electricity heater kW 0 Sound power noise level (H-M-L) dB (A) 60 Sound pressure noise level (H-M-L) dB (A) 44/40/37 Weight (Net / Shipping) kg / kg 46/55
Piping
Refrigerant
Type / Charge
g
R410A/2500
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
50
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.
67
Item Model AD125S2SM3FA/1UH125P1ERG
Function Cooling Heating Capacity kW 12.5(3.5~15.0) 14(4~18.0) Sensible heat ratio 0.74 Total power input kW 3.66(1.0-6.5) 3.78(1.0-6.5) Max. power input W 6500 6500 EER or COP W/W 3.31(A) 3.70(A) Dehumidifying capacity 10
-3×m3
/h 4.9 Power cable / Power source N, V, Hz 1PH, 220-240V~, 50/60Hz Running/Max. Running current A/A
17.0(8.7-30.0)/30A 17.2(8.7-30.0)/30A Start current A / Circuit breaker A
Indoor unit
Unit model (color) AD125S2SM3FA
Fan
Type×Number CENTRIFUGALX3 Speed (H-M-L) r/min 1070/960/880/850 Fan motor output/ input power kW 0.272 Air-ow (H-M-L) kW 0.190
External static pressure m³/h
2250/1960/1680/1500(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat exchanger
Type/Diameter mm Inner grooved pipe/φ7.0 Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1500*700*248
Package (L×W×H) mm×mm×mm 1710/870/330
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YR-HBS01(O) Fresh air hole dimension mm 123 Electricity heater kW 0 Sound power noise level (H-M-L) dB (A) 65 Sound pressure noise level (H-M-L) dB (A) 45/42/37 Weight (Net / Shipping) kg / kg 52/62
Piping
Refrigerant
Type / Charge
g
R410A/3700
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
75
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.
68
Item Model AD125S2SM3FA/1UH125P1ERK
Function Cooling Heating Capacity kW 12.5(3.5~15.0) 14(4~18.0) Sensible heat ratio 0.74 Total power input kW 3.66(1.0-6.5) 3.78(1.0-6.5) Max. power input W 6500 6500 EER or COP W/W 3.31(A) 3.70(A) Dehumidifying capacity 10
-3×m3
/h 4.9 Power cable / Power source N, V, Hz 3N~380-415V,50/60Hz Running/Max. Running current A/A
6.5(2.9-10.0)/11.0 6.7(2.9-10.0)/11.0 Start current A / Circuit breaker A
Indoor unit
Unit model (color) AD125S2SM3FA
Fan
Type×Number CENTRIFUGALX3 Speed (H-M-L) r/min 1070/960/880/850 Fan motor output/ input power kW 0.272 Air-ow (H-M-L) kW 0.190
External static pressure m³/h
2250/1960/1680/1500(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat exchanger
Type/Diameter mm Inner grooved pipe/φ7.0 Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1500*700*248
Package (L×W×H) mm×mm×mm 1710/870/330
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YR-HBS01(O) Fresh air hole dimension mm 123 Electricity heater kW 0 Sound power noise level (H-M-L) dB (A) 65 Sound pressure noise level (H-M-L) dB (A) 45/42/37 Weight (Net / Shipping) kg / kg 52/62
Piping
Refrigerant
Type / Charge
g
R410A/3700
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
75
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.
69
Item Model AD140S2SM3FA/1UH140P1ERG
Function Cooling Heating Capacity kW 13.4(3.5~15.0) 15.5(4~19.0) Sensible heat ratio 0.74 Total power input kW 4.05(1.0-6.5) 4.18(1.0-6.5) Max. power input W 6500 6500 EER or COP W/W 3.31(A) 3.70(A) Dehumidifying capacity 10
-3×m3
/h 4.9 Power cable / Power source N, V, Hz 1PH, 220-240V~, 50/60Hz Running/Max. Running current A/A
18.0(8.7-30.0)/32A 18.5(8.7-30.0)/32A Start current A / Circuit breaker A
Indoor unit
Unit model (color) AD140S2SM3FA
Fan
Type×Number CENTRIFUGALX3 Speed (H-M-L) r/min 1180/1080/990/930 Fan motor output/ input power kW 0.285 Air-ow (H-M-L) kW 0.200
External static pressure m
3
/h
2500/2160/1780/1500(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat exchanger
Type/Diameter mm Inner grooved pipe/φ7.0 Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1500*700*248
Package (L×W×H) mm×mm×mm 1710/870/330
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YR-HBS01(O) Fresh air hole dimension mm 123 Electricity heater kW 0 Sound power noise level (H-M-L) dB (A) 66 Sound pressure noise level (H-M-L) dB (A) 46/43/38 Weight (Net / Shipping) kg / kg 52/62
Piping
Refrigerant
Type / Charge
g
R410A/3700
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
75
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.
70
Item Model AD140S2SM3FA/1UH140P1ERK
Function Cooling Heating Capacity kW 13.4(3.5~15.0) 15.5(4~19.0) Sensible heat ratio 0.74 Total power input kW 4.05(1.0-6.5) 4.18(1.0-6.5) Max. power input W 6500 6500 EER or COP W/W 3.31(A) 3.70(A) Dehumidifying capacity 10
-3×m3
/h 4.9 Power cable / Power source N, V, Hz 3N~380-415V,50/60Hz Running/Max. Running current A/A
7.0(2.9-11.0)/11A 7.3(2.9-11.0)/11A Start current A / Circuit breaker A
Indoor unit
Unit model (color) AD140S2SM3FA
Fan
Type×Number CENTRIFUGALX3 Speed (H-M-L) r/min 1180/1080/990/930 Fan motor output/ input power kW 0.285 Air-ow (H-M-L) kW 0.200
External static pressure m
3
/h
2500/2160/1780/1500(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat exchanger
Type/Diameter mm Inner grooved pipe/φ7.0 Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1500*700*248
Package (L×W×H) mm×mm×mm 1710/870/330
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YR-HBS01(O) Fresh air hole dimension mm 123 Electricity heater kW 0 Sound power noise level (H-M-L) dB (A) 66 Sound pressure noise level (H-M-L) dB (A) 46/43/38 Weight (Net / Shipping) kg / kg 52/62
Piping
Refrigerant
Type / Charge
g
R410A/3700
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
75
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.
71
2. Dimension
AB35S2SM3FA
700
760
805
592
620.5
287.1
141.3 186
768
738
700
593
166
467
120
91
130
225
185
106
11
294
33
53
76
47
578
238
72
957
990
1050
595.5
655
720
250
148
57
57
57
103
797
Note: The cushion pasted in the bottom plate isn't included in the thickness data.
AD50S2SM1FA AD71S2SM1FA
73
AD50S2SM3FA
74
AD71S2SM3FA AD90S2SM3FA
123
700
165
992
248
165
128
158
10095
620
1162
1100
992
978
238
75
?123
238
700
619
165
1378
1562
1500
1392
248
9995
128
158
AD105S2SM3FA AD125S2SM3FA AD140S2SM3FA
76
3. Wiring Diagram
Y/G:YELLOW/GREEN
NOTE:
1.DASHED PARTS ARE OPTIONAL.
2.
USER SHOULD NOT SET SW01 AND
SW03 WITHOUT GUIDENCE.
3.WHEN ONE WIRED CONTROLLER CONTROL MULTIPLE INDOOR UNIT,
IT CAN CONNECT ANOTHER INDOOR UNIT BY CN22 OR CN22-1.
WHEN TWO WIRD CONTROLLERS CONTROL ONE INDOOR UNIT,
THE WIRED CONTROLLER NEED CONNECT WITH CN22 AND CN22-1.
TEMP.
SENSOR
ROOM
SENSOR
PIPING
TEMP.
ROOMCARD
ROTOM NAF CD
SW03
FUSE
WIRED
CONTROLLER
FLOAT
SWITCH
WIFI
MODULE
PUMP
TO OUT
DOOR UNIT
2
1
3
Y/G
M
12345678
ON
M
B A
C
B
A
C
OFF
0150527034K
2
1
3
N L S
B A C
SW01
12345678
ON
OFF
FRESH AIR MOTOR
(SW01-6 select OFF) /
EXTERNAL ALARM OUTPUT
(SW01-6 select ON)
( Contact rating_230VAC,3A)
M
CN21
Heater_L
CH4
Heater_N
CH2
CN5
CN4
CN34
CN16
CH1
SW01-1
SW01-2
SW01-3
OFF
SW01-4
SW01-5
SW01-6
SW01-7
SW01-8
MODEL
OFF
AD105S2SM3/4FA
OFF
OFF
OFF
ON
ON
OFF
CN13
CN6
CN41
CN22
CN22-1
4.SW03-5
->SW03-08 ARE USED FOR
ADDRESS SETTING ON THE
SITUATION OF ONE WIRED CONTROLLER CONTROL MORE THAN
ONE INDOOR UNIT.
5.REFER TO SERVICE MANUL TO GET MUCH MORE DETAILS
ABOUT THE STATIC PRESSURE LEVEL SETTING.
CN1
AD50S2SM3/4FA
SW03-1 SW03-2 SW03-3 SW03-4 SW03-5 SW03-6 SW03-7
SW03-8
OFF OFF OFF OFF OFF OFF OFF
FOR ALL
DUCTED MODEL
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
AD71S2SM3/4FA
AD90S2SM3/4FA
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
(WITHOUT
DIGITAL
DISPALY)
INFRARED
REMOTE
RECEIVER
AD35S2SM3/4FA
ON
ON
OFF
OFF
OFF
ON ONONON
Y/G
AD35S2SM3FA
77
AD50S2SM1FA AD71S2SM1FA
Y/G:YELLOW/GREEN
NOTE:
1.DASHED PARTS ARE OPTIONAL.
2.SW03-4 IS AT ON POSITION,DO NOT CHANGE
THE SETTINGS OF SWITCHS WITHOUT GUIDANCE.
3.WHEN ONE WIRED CONTROLLER CONTROL MULTIPLE INDOOR UNIT,
IT CAN CONNECT ANOTHER INDOOR UNIT BY CN22 OR CN22-1.
WHEN TWO WIRD CONTROLLERS CONTROL ONE INDOOR UNIT,
THE WIRED CONTROLLER NEED CONNECT WITH CN22 AND CN22-1.
TEMP.
SENSOR
ROOM
SENSOR
PIPING
TEMP.
ROOMCARD
R O T O M N A F C D
SW03
FUSE
WIRED
CONTROLLER
FLOAT
SWITCH
WIFI
MODULE
PUMP
TO OUT DOOR
2
1
3
Y/G
M
12345678
ON
REMOTE RECEIVER
M
B
A
C
B
A
C
OFF
0150523302
2
1
3
N L S
B A C
SW01
12345678
ON
OFF
FRESH AIR MOTOR
(SW01-6 select OFF) /
EXTERNAL ALARM OUTPUT
(SW01-6 select ON)
( Contact rating_230VAC,3A)
M
CN21
Heater_L
CH4
Heater_N
CH2
CN5
CN4
CN34
CN16
CH1
SW01-1
SW01-2
SW01-3
ON
SW01-4
SW01-5
SW01-6
SW01-7
SW01-8
MODEL
OFF
AM24LP2VHA
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ADH071M3ERG
OFF
OFF
ON
CN13
CN6
CN41
CN22
CN22-1
4.SW03-5
->SW03-08 IS USED FOR
ADDRESS SETTING ON THE
SITUATION OF ONE WIRED CONTROLLER CONTROL MORE THAN
ONE INDOOR UNIT.
5.REFER TO SERVICE MANUL TO GET MUCH MORE DETAILS
ABOUT THE STATIC PRESSURE LEVEL SELECTION.
CN1
AD71S2SM1FA
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF OFF
ON
AD50S2SM1FA
SW03-1
SW03-2
SW03-3
FOR ALL DUCTED
MODEL
SW03-4 SW03-5 SW03-6
SW03-7
SW03-8
OFF OFF OFF OFF OFF OFF OFF ON
78
AD71S2SM3FA AD90S2SM3FA AD105S2SM3FA
Y/G:YELLOW/GREEN
NOTE:
1.DASHED PARTS ARE OPTIONAL.
2.
USER SHOULD NOT SET SW01 AND
SW03 WITHOUT GUIDENCE.
3.WHEN ONE WIRED CONTROLLER CONTROL MULTIPLE INDOOR UNIT,
IT CAN CONNECT ANOTHER INDOOR UNIT BY CN22 OR CN22-1.
WHEN TWO WIRD CONTROLLERS CONTROL ONE INDOOR UNIT,
THE WIRED CONTROLLER NEED CONNECT WITH CN22 AND CN22-1.
TEMP.
SENSOR
ROOM
SENSOR
PIPING
TEMP.
ROOMCARD
ROTOM NAF CD
SW03
FUSE
WIRED
CONTROLLER
FLOAT
SWITCH
WIFI
MODULE
PUMP
TO OUT
DOOR UNIT
2
1
3
Y/G
M
12345678
ON
M
B A
C
B
A
C
OFF
0150527034K
2
1
3
N L S
B A C
SW01
12345678
ON
OFF
FRESH AIR MOTOR
(SW01-6 select OFF) /
EXTERNAL ALARM OUTPUT
(SW01-6 select ON)
( Contact rating_230VAC,3A)
M
CN21
Heater_L
CH4
Heater_N
CH2
CN5
CN4
CN34
CN16
CH1
SW01-1
SW01-2
SW01-3
OFF
SW01-4
SW01-5
SW01-6
SW01-7
SW01-8
MODEL
OFF
AD105S2SM3/4FA
OFF
OFF
OFF
ON
ON
OFF
CN13
CN6
CN41
CN22
CN22-1
4.SW03-5
->SW03-08 ARE USED FOR
ADDRESS SETTING ON THE
SITUATION OF ONE WIRED CONTROLLER CONTROL MORE THAN
ONE INDOOR UNIT.
5.REFER TO SERVICE MANUL TO GET MUCH MORE DETAILS
ABOUT THE STATIC PRESSURE LEVEL SETTING.
CN1
AD50S2SM3/4FA
SW03-1 SW03-2 SW03-3 SW03-4 SW03-5 SW03-6 SW03-7
SW03-8
OFF OFF OFF OFF OFF OFF OFF
FOR ALL
DUCTED MODEL
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
AD71S2SM3/4FA
AD90S2SM3/4FA
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
(WITHOUT
DIGITAL
DISPALY)
INFRARED
REMOTE
RECEIVER
AD35S2SM3/4FA
ON
ON
OFF
OFF
OFF
ON ONONON
Y/G
79
AD125S2SM3FA AD140S2SM3FA
BLK:black BLU:blue
GR:grey
ORG:orange
PNK:pink RD:red
WHT:white YL:yellow
Y/G:
yellow/green
FLOAT
SWITCH
CN5
TRANSFORMER
PUMP
CN9
CN8
REMOTE CENTRAL
ADAPTOR
YCJ-A002
TEMP.
SENSOR
ROOM
SENSOR
PIPING
TEMP.
CN3
CN29
CN18
CN13
CN19
T3.15A/250VAC
FUSE
WIRED
CONTROLLER
ROOM CARD
CH3(L)
CH4(N)
CH5
12345678
ON
OFF
SW1
ON
OFF
1234
SW2
~
2 1
3
WHT
Y/G
CN1
A
B
C
A B
C
REMOTE
RECEIVER
INFRARED
CN4
WiFi
MODULE
GND
S
5V
CN6
CN7
GND
S
5V
M
FAN MOTOR
DRIVER
MODULE
MAIN CONTROL
BOARD
DC FAN
MOTOR
U
V
W
RD
WHT
BLK
CN609
CN604
P601
(ACL)
P602(ACN)
Reactor
CN603
HU
HV
HW
VCC
GND
YL
BLU
ORG
PNK
GR
WHT
RD
BLK
RELAY
FOR HE-
ATER(12
V CONT-
ROL SIDE
To outdoor unit
Note:
1.Dashed parts are op-
tional.
2Once out of factorty
do not change the DIP
switches without
technical guidence
3.SW2 is used for
address setting on the
situation of one wired
controller control more
than one indoor unit.
4.Use wired controller to
select appropriate exter-
nal static pressure level.
5.Refer to service
manual to get more
information about the
static pressure level
select or DIP switch
SW1, SW2 function
definations
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
MODEL
CN20
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
AD125S2SM3(4)FA
0150517885A
M
FRELAY FOR
FRESH AIR
MOTOR
(CN7 Contact
rating-230
VAC,3A) /
E.A.0
AD140S2SM3(4)FA
80
4. Airow and Static Pressure Chart
600
700
800
900
1000
1100
1200
150Pa 130Pa 120Pa 110Pa 100Pa 90Pa 70Pa 50Pa 37Pa 25Pa
air flow m3/h
static pressure (Pa)
AIR FLOW AND STATIC PRESSURE CHART
S-H
H
M
L
S
AD50S2SM1FA
AD71S2SM1FA
600
700
800
900
1000
1100
1200
1300
1400
1500
150Pa 130Pa 120Pa 110Pa 100Pa 90Pa 70Pa 50Pa 37Pa 25Pa
air flow m3/h
static pressure (Pa)
AIRFLOW AND STATIC PRESSURE CHART
H
M
L
S
81
500
600
700
800
900
1000
1100
25 37 50 70 90 100 110 120 130 150
Air flow m
3
/h
Static pressure (Pa)
AD50S2SM3FA air flow and static pressure chart
High
Med
Low
Quiet
350
450
550
650
750
850
950
25 37 50 70 90 100 110 120 130 150
Air flow m
3
/h
Static pressure (Pa)
AD35S2SM3FA air flow and static pressure chart
High
Med
Low
Quiet
82
600
800
1000
1200
1400
1600
25 37 50 70 90 100 110 120 130 150
Static Pressure(Pa)
Airflow and Static Pressure Chart -----AD71S2SM3FA
High
Med
Low
Quiet
800
900
1000
1100
1200
1300
1400
1500
1600
25 37 50 70 90 100 1 10 120 130 150
Static Pressure(Pa)
Airflow and Static Pressure Chart -----AD90S2SM3FA
High
Med
Low
Quiet
83
1000
1200
1400
1600
1800
2000
2200
2400
2600
25 37 50 70 90 1 00 110 120 130 150
Static Pressure(Pa)
Airflow and Static Pressure Chart -----AD125S2SM3FA
High
Med
Low
Quiet
500
700
900
1100
1300
1500
1700
1900
2100
2300
25 37 50 70 90 100 110 1 20 130 15 0
Static Pressure(Pa)
Airflow and Static Pressure Chart -----AD105S2SM3FA
High
Med
Low
Quiet
84
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
25 37 50 70 90 100 110 120 130 150
Static Pressure(Pa)
Airflow and Static Pressure Chart -----AD140S2SM3FA
High
Med
Low
Quiet
85
For AD50S2SM1FA AD71S2SM1FA Installation procedure
The machine is adaptive in following situation
1. Applicable ambient temperature range:
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualied person.
3. If the fuse on the indoor PC board is broken please change it with the type of T 6.3A /250VAC (For series 24,28,36,48).
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be: H05RN-F 3G 4.0mm
2
.
The connecting cable should be: H05RN-F 4G 2.0mm2. All the cables shall have got the European authentication certicate. During installation, when the connecting cables break off, it must be assured that the grouding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.For AD50S2SM1FA AD71S2SM1FA, we can get the 10 different ESP through adjust wired controller YR-E17,please refer below:
Adjsutmenmt etchobdywirecdontrolle YR-E17 In th state of ON and non screen saving state, press Fan+Set keys for 5s to enter static pressure grade adjustment state with static pressure icon ashing and current static pressure grade statically displaying. Press key ↑↓to change static pressure grade, then press set key to conrm. Details please refer to wired controller operation & installation manual. Adjustment method by infrared remote controller+infrared receiver RE-02: step a:set the infrared remote controller at condition: Fan mode, Fan speed high step b: then aim the remote controller at the infrared remote receiver RE­02, press health button 4+N times (1≤N≤10,integer)within 12 seconds, then the receiver will keep N+1 times, the static pressure level N is been set successfully. Note: For infrared remote controller YR-HBS01, need press ON/OFF button make the controller's at OFF status rst, then open the button cover press fresh button will enter fan mode interface.
Stactic pressure
grade
1 2 3 4 5 6 7 8 9 10
Stactic pressure 25pa 37pa 50pa 70pa 90pa 100pa 110pa 120pa 130pa 150pa
Cooling
Indoor temperature
max.DB/WB
min.DB/WB
32/23°C 18/14°C
Outdoor temperature
max.DB/WB
min.DB/WB
46/26°C
10/6°C
Heating
Indoor temperature
max.DB/WB
min.DB/WB
27°C 15°C
Outdoor temperature
max.DB/WB
min.DB/WB
24/18°C
-15°C
AD50S2SM1FA AD71S2SM1FA
5. Instalaltion
86
NOTE
All wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to your local distributor.
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.
Preparation of indoor unit
Before or during the installation of the unit, assemble necessary optional panel etc. depending on the specic type.
Select places for installation satisfying following conditions and at the same time obtain the consent on the part of your client user.
a.Places where chilled or heated air circulates freely. When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases, suggest your client users to install air circulators. b.Places where perfect drainage can be prepared and sufcient drainage. c. Places free from air disturbances to the suction port and blowout hole of the indoor unit, places where the re alarm may not malfunction or short-circuit. d.Places with the environmental dew-point temperature is lower than 28 C and the relative humidity is less than 80 %. (When installing at a place under a high humidity environment, pay sufcient attention to the prevention of dewing such as thermal insulation of the unit. ) e.Ceiling height shall have the following height.
Avoid installation and use at those places listed below.
a.Places exposed to oil splashes or steam (e.g. kitchens and machine plants).
Installation and use at such places incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin parts. b.Places where corrosive gas (such as sulfurous acid gas) or inammable gas (thinner, gasoline etc.) in generated or remains. Installation and use at such places cause corrosion in the heat exchanger and damage in molded synthetic resin parts.
c.Places adjacent to equipment generating electromagnetic waves or high-frequency waves such as in hospitals.
Generated noise may cause malfunctioning of the controller.
Model Liquid side Gas side
AD50S2SM1FA φ6.35mm φ12.7mm AD71S2SM1FA φ9.52mm φ15.88mm
Pipe size
AD50S2SM1FA AD71S2SM1FA
Combination with silent panel 366mm
50mm
Obstacle
Installation space
100mm 100mm
87
1. Preparation for suspending the unit a. Size of hole at ceiling and position of hanging bolts
<Combination with silent panel >
b.Hanger bolts installation
Use care of the piping direction when the unit is installed.
2.Installation of indoor unit
Fix the indoor unit to the hanger bolts. If required it is possible to suspend the unit to the beam etc. Directly by use of the bolts without using the hanger bolts.
Note
When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging bracket.
Adjusting to the levelness
(a) Adjust the out-of levelness using a level or by the following method. Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below. (b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the oat switch may occur.
Tap selection on blower unit
(When the high performance lter is used.) Taps of blower unit are set at the standard selection at the shipping from factory. Where the static pressure is raised by employing such option as the high performance lter, etc., change the connection of connectors provided at the ank of control box as shown below.
Dimensions
Model
A(mm) B(mm) C(mm) D(mm) E(mm) F(mm)
AD50S2S M1FA AD71S2SM1FA 983 1433 1493 595 740 800
AD50S2SM1FA AD71S2SM1FA
88
Drain Piping
(a) Drain piping should always be in a down hill grade (1/50-1/100) and avoid riding across an elevation or making
traps.
(b) When connecting the drain pipe to unit pay suffcient attention not to apply excess force to the piping on the unit side. Also x the piping at a point as close as possible to the unit. (c) For unit without water pump, please refer to the digram and select drain pipe size according to drain opening inner diameter size. The drain pipe shall be slant downwards (greater than 1/100). The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, supports shall be provided every 1.5-2m to prevent wavy form. Central piping shall be laid out according to the right gure. Take care not to apply external force onto the drain pipe connection part. (d) For unit with water pump drain pipeuse hard PVC general purpose pipe VP which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used for connection of the drain socket and drain hose (accessory). (e) When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch Use VP-30(11/4") or thicker pipe for this purpose
.
(f) The hard PVC pipe put indoor side should be heat insulated. Do not ever provide an air vent. (g) The height of the drain head can be elevated up to a point 500 mm above the ceiling, and when an obstacle exists in the ceiling space, elevate the piping to avoid the obstacle using an elbow or corresponding gadget. When doing this, if the stretch for the needed height is higher than 500mm, the back-ow quantity of drain at the event of interruption of the operation gets too much and it may cause overow at the drain pan. Therefore, make the height of the drain pipe within the distance given in the sketch below. (h) Avoid positioning the drain piping outlet at a place where generation of odor may be stimulated. Do not lead the drain piping direct into a sewer from where sulfur gas may generate.
Unit model The size of drain opening
AD50S2SM1FA AD71S2SM1FA φ21mm
89
Drainage Test
(1)
Conduct a drainage test after completion of the electrical work.
(2)
During the trial, make sure that drain ows properly through the piping
and that no water leaks from connections.
(3)
In case of a new building, conduct the test before it is furnished with the
ceiling.
(4)
Be sure to conduct this test even when the unit is installed in the
heating season.
Proce dures
(a)
Supply about 1000 cc of water to the unit through the air outlet using a
feed water pump.
(b)
Check the drain while cooling operation. Before the electrical work has not been completed, connect a convex joint in the drain pipe connection to provide a water inlet. Then, check if water leaks from the piping system and that drain ows through the drain pipe normally.
Installation work for air outlet ducts
Calculate the draft and external static pressure and select the length, shape and blowout.
• Blowout duct
• 2-spot, 3-spot and 4-spot with φ200 type duct are the standard specications. Note (1) Shield the central blowout hole for 2-spot. (2) Shield the blowout hole around the center or 3-spot.
• Limit the difference in length between spots at less than 2:1.
• Reduce the length of duct as much as possible.
• Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)
• Use a band. etc. to connect the main unit and the blowout duct ange.
• Conduct the duct installation work before nishing the ceiling.
Connection of suction, exhaust ducts a.Fresh air inlet
• Inlet can be selected from the side or rear faces depending on the working conditions.
• Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted. (Side inlet cannot be used.)
b.Exhaust (Make sure to use also the suction.)
• Use the side exhaust port.
90
DANGER OF BODILY INJURY OR DEATH
• TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS.
• GROUND CONN
ECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
Precautions for electrical wiring
Electrical wiring work should be conducted only by authorized personnel. Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires. Use copper conductor only.
Selection of size of power supply and interconnecting wires
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)
The specication of power cable is HO5RN-F3G 4.0mm
2
The specication of cable between indoor unit to outdoor unit is HO5RN-F4G 2.5mm
2
POWER SUPPLY & INDOOR-OUTDOOR CONNECTION:
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by outdoor unit terminal blocks.
WIRED CONTROLLER & INDOOR PCB CONNECTION (on for one wiring type):
Note: When do the wired controller & indoor PCB wiring work for model AD50/71S2SM1FA,do not connect
the shielded wired to the unit’s shell,do not parallel wiring with strong electric lines within 0.3 meters, please keep strong lines and the signal lines separately.
Item
Model
Phase
Circuit breaker Power source
wire size
(minimum)
(mm
2
)
Earth leakage breaker
Switch breaker(A)
Overcurrent
protector rated
capacity
Switch
breaker(A)
Leak
current(mA)
AD50S2SM1FA AD71S2SM1FA
1 40 26 4.0 40 30
WARNING
.
INDOOR UNIT PCB
WIRED
CONTROLLER
CN22 CON1
A B C
A B C
91
The Machineis Adaptive in Following Situation
Safety Precautions
1. Applicable ambient temperature range:
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualied person.
3. If the fuse on the indoor PC board is broken please change it with the type of T5.0/250V (For series AD35/50/71S2SM3/4FA)
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be: H05RN-F 3G 4.0mm
2
; The connecting cable should be: H05RN-F 4G 2.0mm
2
All the cables shall have got the European authentication certicate. During installation, when the connecting cables break off, it must be assured that the grouding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.For AD35S2SM3FA/AD35S2SM4FA/AD50S2SM3FA/AD50S2SM4FA/AD71S2SM3FA, we can get the 10 different ESP through adjust wired controller YR-E17, please refer below:
Stactic Pressure
Grade
1 2 3 4 5 6 7 8 9 10
Stactic Pressure 25Pa 37Pa 50Pa 70Pa 90Pa 100Pa 110Pa 120Pa 130Pa 150Pa
Adjsutment metchod bywired controller YR-E17: In the state of ON and non screen saving state, press Fan+Set keys for 5s to enter static pressure grade adjustmentstate with static pressure icon ashing and current staticpressure grade statically displaying. Press key↑↓ to changestatic pressure grade, then press Set key to conrm. Details please refer to wired controller operation & installation manual. Adjsutment metchod by Infrared remote controller+Infrared receiver RE-02: Step a: set the Infrared remote controller at condition: FAN mode, fan speed high Step b: then aim the remote controller at the infrared remote receiver RE-02, press HEALTH button 4+N times (1≤N≤10, integer) within 12 seconds, then the receiver will beep N+1 times, the static pressure level N is been set successfully. Note: For Infrared remote controller YR-HBS01, need press ON/OFF button make the controller’s at OFF status rst, then open the button cover press FRESH button will enter FAN mode interface.
Cooling
Indoor Temperature
Max. DB/WB
Min. DB/WB
32/23°C 18/14°C
Outdoor Temperature
Max. DB/WB
Min. DB/WB
46/26°C
10/6°C
Heating
Indoor Temperature
Max. DB/WB
Min. DB/WB
27°C 15°C
Outdoor Temperature
Max. DB/WB
Min. DB/WB
24/18°C
15°C
AD35S2SM3FA AD50S2SM3FA AD71S2SM3FA
92
Air outlet frame
Electrical components Case
Drain pan Evaporator
Drain opening
AD35S2SM3FA AD35S2SM4FA AD50S2SM3FA AD50S2SM4FA AD71S2SM3FA AD71S2SM4FA
Installation Manual For Wire Controller
5. Wiring connections of wire controller:
6. Communication wiring:
There are three methods to connection wire controller and the indoor units: A. One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wire controller and the master unit (the indoor unit connected with wire controller directly), the others connect with the master unit through 2 pieces of polar wire. B. One wire controller controls one indoor unit, and the indoor unit connects with the wire controller through 3 pieces of polar wire. C. Two wired controllers control one indoor unit. The wire controller connected with indoor unit is called master one, the other is called slave one. Master wire controller and indoor unit; master and slave wire controllers are all connected through 3 pieces of polar wire.
The wire controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white 2-yellow 3-red) is connected with the terminal A, B, C of wire controller respectively. The communication wiring is 5 meter long; If the actual length is more than it, please distribute wiring according to below table:
One side of the shielded sheet of communication wire must be earthed.
Communication Wiring Length (m) Dimensions of Wiring
< 100 0.3mm
2
x3-Core Shielded Wire
≥100 and <200 0.5mm
2
x3-Core Shielded Wire
≥200 and <300 0.75mm
2
x3-Core Shielded Wire
≥300 and <400 1.25mm
2
x3-Core Shielded Wire
≥400 and <600 2mm
2
x3-Core Shielded Wire
93
Installation Procedure
Note:
WARNING:
All wiring of this installation must comply with national, state and local regulations. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to your local distributor.
Be sure to read these instructions carefully before beginning installation. Failure to follow these instructions could cause serious injury or death, equipment malfunction and/or property damage.
Preparation of indoor unit
Before or during the installation of the unit, assemble necessary optional panel etc. depending on the specic type.
Select places for installation satisfying following conditions and at the same time obtain the consent on the part of your client user.
a. Places where chilled or heated air circulates freely. When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases, suggest your client users to install air circulators. b. Places where perfect drainage can be prepared and sufcient drainage. c. Places free from air disturbances to the suction port and blowout hole of the indoor unit, places where the re alarm may not malfunction or short-circuit. d. Places with the environmental dew-point temperature is lower than 28 and the relative humidity is less than 80 %. (When installing at a place under a high humidity environment, pay sufcient attention to the prevention of dewing such as thermal insulation of the unit.) e. Ceiling height shall have the following height.
AD35S2SM3FA AD35S2SM4FA AD50S2SM3FA AD50S2SM4FA AD71S2SM3FA AD71S2SM4FA
Combination With Silent Panel 366mm
Avoid installation and use at those places listed below.
a. Places exposed to oil splashes or steam (e.g. kitchens and machine plants). Installation and use at such places incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin
parts.
b. Places where corrosive gas (Such as sulfurous acid gas) or inammable gas (Thinner, gasoline etc.) in generated or remains. Installation and use at such places cause corrosion in the heat exchanger and damage in molded synthetic resin parts. c. Places adjacent to equipment generating electromagnetic waves or high-frequency waves such as in hospitals. Generated noise may cause malfunctioning of the controller.
Pipe size
Model Liquid Side Gas Side
AD35S2SM3FA AD35S2SM4FA
ø
6.35mm
ø
9.52mm
AD50S2SM3FA AD50S2SM4FA
ø
6.35mm
ø
12.7mm
AD71S2SM3FA AD71S2SM4FA
ø
9.52mm
ø
15.88mm
Installation s
100mm 100mm
Obstacle
50mm
pace
94
1. Preparation for Suspending the Unit
a. Size of hole at ceiling and position of hanging bolts
<Combination with Silent Panel>
AD35S2SM3FA AD35S2SM4FA AD50S2SM3FA AD50S2SM4FA AD71S2SM3FA AD71S2SM4FA
Dimensions Model
A (mm) B (mm) C (mm) D (mm) E (mm) F (mm)
AD35S2SM3FA AD35S2SM4FA 762 1212 1272 620 765 825 AD50S2SM3FA AD50S2SM4FA
AD71S2SM3FA AD71S2SM4FA
1162 1612 1672 620 765 825
b. Hanger bolts installation Use care of the piping direction when the unit is installed.
2. Installation of Indoor Unit
Fix the indoor unit to the hanger bolts. If required it is possible to suspend the unit to the beam etc. Directly by use of the bolts without using the hanger bolts.
Adjusting to the levelness (a) Adjust the out-of levelness using a level or by the following method. Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below. (b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the oat switch may occur.
Tap selection on blower unit (When the high performance lter is used.) Taps of blower unit are set at the standard selection at the shipping from factory. Where the static pressure is raised by employing such option as the high performance lter, etc. Change the connection of connectors provided at the ank of control box as shown below.
Note:
Hanging bolt position
Pipe connection
side
Hanging bolt position
Ceiling hole size
F
Panel dimensions
Ceiling~panel wrap dimensions
Hole-in anchor Hole-in plug
Insert
Concrete
Hanging bolt M10
Hanging bolt
M10 nut
M10 washer
Main unit
M10 spring washer
Piping side Supply water
Water level
0~5mm
(0~0.2)
Bring the piping side slightly lower
Standard tap (at shipping)
White
Blue Blue Blue
Blue
Red Red Red Red
Red
Moter side
Moter side
Conector white
Conector white
white
white white
white
Black
Yellow Yellow Yellow
Control box side
High speed tap
Ceiling~panel
wrap dimensions
E
D 70
75
Ceiling hole size
Panel dimensions
C
B
A
150
300
30
30
95
Drain Piping
Drain piping should always be in a downhill grade (1/50-1/100) and avoid riding across an elevation or making
traps.
(b). When connecting the drain pipe to unit pay suffcient attentionnot to apply excess force to the piping on the unit side. Also x the piping at a point as close as possible to the unit. (c). For unit without water pump, please refer to the digram and select drain pipe size according to drain opening inner diameter size. The drain pipe shall be slant downwards (Greater than 1/100). The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, supports shall be provided every 1.5-2m to prevent wavy form. Central piping shall be laid out according to the right gure. Take care not to apply external force onto the drain pipe connection part. (d). For unit with water pump drain pipeuse hard PVC general purpose pipe VP which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used for connection of the drain socket and drain hose (Accessory). (e). When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch Use VP-30(11/4) or thicker pipe for this purpose (f). The hard PVC pipe put indoor side should be heat insulated. Do not ever provide an air vent. (g). The height of the drain head can be elevated up to a point 500mm above the ceiling, and when an obstacle exists in the ceiling space, elevate the piping to avoid the obstacle using an elbow or corresponding gadget. When doing this, if the stretch for the needed height is higher than 500 mm, the back-ow quantity of drain at the event of interruption of the operation gets too much and it may cause overow at the drain pan. Therefore, make the height of the drain pipe within the distance given in the sketch below. (h). Avoid positioning the drain piping outlet at a place where generation of odor may be stimulated. Do not lead the drain piping direct into a sewer from where sulfur gas may generate.
Unit Model The Size of Drain Opening
AD35S2SM3FA AD35S2SM4FA AD50S2SM3FA AD50S2SM4FA AD71S2SM3FA AD71S2SM4FA
ø25mm
96
Drainage Test
(1) Conduct a drainage test after completion of the electrical work. (2) During the trial, make sure that drain ows properly through the piping and that no water leaks from connections. (3) In case of a new building, conduct the test before it is furnished with the ceiling. (4) Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
(a) Supply about 1000 cc of water to the unit through the air outlet using a feed water pump. (b) Check the drain while cooling operation. Before the electrical work has not been completed, connect a convex joint in the drain pipe connect on to provide a water inlet. Then, check if water leaks from the piping system and that drain ows through the drain pipe normally.
Installation work for air outlet ducts
A. Blowout duct
• 2-spot, 3-spot and 4-spot with ø 200 type duct are the standard specications.
Note:
(1) Shield the central blowout hole for 2-spot. (2) Shield the blowout hole around the center for 3-spot.
• Limit the difference in length between spots at less than 2:1.
• Reduce the length of duct as much as possible.
• Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)
• Use a band. etc. to connect the main unit and the blowout duct ange.
• Conduct the duct installation work before nishing the
ceiling.
Calculate the draft and external static pressure and select the length, shape and blowout.
Connection of Suction, Exhaust Ducts
a.Fresh air inlet
• Inlet can be selected from the side or rear faces depending on the working conditions.
• Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted. (Side inlet cannot be used.)
b.Exhaust (Make sure to use also the suction.) Use the side exhaust port.
97
WARNING
Danger of bodily injury or death
• Turn off electric power at circuit breaker or power source before making any electric connections.
• Ground connections must be completed before making line voltage connections.
Precautions for electrical wiring
• Electrical wiring work should be conducted only by authorized personnel.
• Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.
• Use copper conductor only.
Selection of size of power supply and interconnecting wires Select wire sizes and circuit protection from table below. (This table shows 20m length wires with less than 2% voltage drop.)
Item
Model
Phase
Circuit breaker
Power Source
Wire Size
(Minimum)
(mm2)
Earth Leakage Breaker
Switch Breaker
(A)
Overcurrent
Protector
Rated
Capacity (A)
Switch
Breaker (A)
Leak
Current
(mA)
AD35S2SM3FA AD35S2SM4FA AD50S2SM3FA AD50S2SM4FA AD71S2SM3FA AD71S2SM4FA
1 40 26 4.0 40 30
Power supply & indoor-outdoor connection:
Wired controller & Indoor PCB connection (One for one wiring type):
Note: When do the wired controller & indoor PCB wiring work for model AD50/71S2SM1FA, do not connect the shielded wired to the unit’s shell, do not parallel wiring with strong electric lines within 0.3 meters, please keep strong lines and the signal lines separately.
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by outdoor unit terminal blocks.
.
INDOOR UNIT PCB
CN22
WIRED
CONTROLLER
CON1
A B
C
A B C
Loading...